You are on page 1of 4

PROJET TOPPING DE CONDENSAT -- SKIKDA

SC1
INSTRUMENT DATA SHEET FOR
PH ANALYZER
DOCUMENT NO. : SC1-200-DS-IN-0004 Rev. 1 Sheet 1 of 4

INSTRUMENT DATA SHEET FOR


PH ANALYZER

1 21-09-2007 Issue for Purchase

0 08-02-2007 Issue for Design 李理想 皮宇 皮宇 陈怡

B 23-01-2007 Issue for Review 李理想 皮宇 皮宇 陈怡

A 13-12-2006 Issue for Review 王萌萌 李理想 皮宇 雷晓虹 皮宇 马强 陈怡

REV. DATE DESCRIPTION PREPARED CHECKED APPROVED


SC No.: SC1
INSTRUMENT DATA SHEET FOR Doc. No.: SC1-200-DS-IN-0004
PH ANALYZER Unit No.: 200
P.O. No.:
Client: SONATRACH Sheet: 2 OF 4
Project: PROJET TOPPING DE CONDENSAT -- SKIKDA Rev.: 1
Site: SKIKDA Date: 21-09-2007

NOTES:
(1) ※ INFORMATION TO BE SUPPLIED OR CONFIRMED BY VENDOR.
(2) TRANSMITTER WILL BE MOUNTED ON 2" STANCHION OR LOCAL RACK BUT CIRCUIT BETWEEN SENSOR AND
TRANSMITTER SHALL BE DESIGNED TO MEET HAZARDOUS AREA CLASSIFICATION SPECIFIED.
(3) SYSTEM CONFIGURATION TO BE RECOMMENDED BY VENDOR.
(4) SENSOR
THE ELECTROCHEMICAL PH CELL SHALL BE PROVIDED AND CHEMICALLY RESISTANT MATERIALS OF
CONSTRUCTION SHALL BE CONSIDERED.
SENSOR SHALL BE OF FLOW THROUGH TYPE WITH 1 1/2" FLANGED CONNECTION AND RETRACTABLE TYPE.
ISOLATION VALVE SHALL BE PROVIDED. IT MAY INCLUDE AUTOMATIC TEMPERATURE COMPENSATOR, IF REQUIRED.
(5) TRANSMITTER
THE TRANSMITTER SHALL BE MOUNTED ON 2" STANCHION OR LOCAL RACK WITH ALL REQUIRED DEVICES
INCLUDING SAMPLING SYSTEM, ETC. IT SHALL BE OF 2 WIRED SYSTEM (4-20mA, SMART/HART PROTOCOL).
ACCURACY SHALL BE LESS THAN 2.0% OF MEASURING RANGE AND REPEATABILITY SHALL BE LESS THAN
0.25% OF FULL SCALE. INTEGRATED DIGITAL TYPE OF LOCAL INDICATOR SHALL BE FURNISHED.
(6) SAMPLING SYSTEM
VENDOR SHALL MOUNT REQUIRED ACCESSORIES FOR SAMPLING AND SENSOR, ETC. ON EXPOSED LOCAL
RACK THAT IS SELF MOUNTING TYPE, IF REQUIRED.
VENDOR SHALL SPECIFY THE UTILITY REQUIREMENT IN QUOTATION, IF ANY.
VENDOR SHALL FABRICATE HIS SAMPLE HANDLING SYSTEM ON HIS SHOP.
(7) SYSTEM CABLE
VENDOR SHALL PROVIDE 10m OF SPECIAL CABLE FOR FROM SENSOR-TO TRANSMITTER TRANSMISSION. IT
SHALL BE FABRICATED ON HIS SHOP ON THE LOCAL RACK, IF REQUIRED.
(8) ENCLOSURE OF ALL ELECTRICAL DEVICES SHALL BE SUITABLE FOR AREA CLASSIFICATION SHOWN ON
DATA SHEET.
(9) IMMERSION LENGTH TO BE SPECIFIED DEPENDING ON LINE SIZE SO THAT REPRESENTATIVE SAMPLE IS AVAILABLE.
(10) AUTOMATIC SENSOR CLEANER SHALL BE SPECIFIED.
(11) COMPATIBILITY OF BARRIERS SHALL BE ASCERTAINED WITH VENDOR.
(12) CALIBRATION FREQUENCY TO BE CONFIRMED BY VENDOR BASED ON SYSTEM DRIFT.
BUFFER SOLUTION QUANTITY SHALL BE PROVIDED ACCORDINGLY FOR AT LEAST ONE YEAR.
(13) BODY AND WETTED PARTS MATERIALS SHALL BE SUITABLE FOR THE SERVICE AND DESIGN CONDITIONS.
SC No.: SC1
INSTRUMENT DATA SHEET FOR Doc. No.: SC1-200-DS-IN-0004
PH ANALYZER Unit No.: 200
P.O. No.:
Client: SONATRACH Sheet: 3 OF 4
Project: PROJET TOPPING DE CONDENSAT -- SKIKDA Rev.: 1
Site: SKIKDA Date: 21-09-2007

GENERAL
1 TAG NO. 200-AT2201
2 QUANTITY P&ID NO. ONE SC1-200-DW-PR-1113
3 SERVICE CAUSTIC SLUDGE TO 200-V-505
4 LINE NO. 1 1/2"-200-CSL-5013-1D2
5 LINE SIZE LINE SCHEDULE 1 1/2" SCH80
6 PIPE MATERIAL CLASS 1D2 (ASTM F1545 A106 GR.B-PTFE-LINED SMLS PER ASME B36.10M)
7 AREA CLASSIFICATION (IEC) ZONE 2, GROUP IIB, T4
SENSOR
※8 SENSOR TYPE FLOW-THROUGH
※9 CONNECTION & RATING (ASME B16.5) ANSI 1" 150# RF
※10 IMMERSION LENGTH (MM) 120
※11 BODY MATERIAL Glass
※12 COVER MATERIAL Plastic
13 WORKING RANGE 0~14 PH
※14 TYPE OF CLEANING N/A
※15 OPTIONS OPTIONAL CONTROL UNIT N/A
※16 TEMP. COMPENSATION AUTO
17 ENCLOSURE (CERTIFICATION) IP68 (EEX iaⅡC)
TRANSMITTER
18 TYPE (MS/CM) INDICATION, TRANSMITTER
※19 MOUNTING RACK
20 RANGE 0~14 PH
21 OUTPUT SIGNAL 4~20 mA HART
※22 POWER SUPPLY 24VDC
23 ELECTRICAL CONNECTION 1/2" NPT
24 ENCLOSURE (CERTIFICATION) IP67 (EEX iaⅡC)
25
26
27
ACCESSORIES
28 REMOTE INDICATOR NO
※29 JUNCTION BOX NO
※30 MOUNTING BRACKET YES
※31 SPECIAL TOOL NO
※32 CALIBRATION SET NO
※33 BUFFER SOLUTION YES
※34 SPECIAL CABLE YES
※35 SAMPLE COOLER & REDUCTION PRESSURE NO
36
SPARE PARTS
37 SEE REQUISITION REQUIREMENT
38
PROCESS CONDITIONS
39 FLUID STATE CAUSTIC SLUDGE LIQUID
40 UNIT NOR DESIGN
41 INLET PRESSURE KG/CM²G 1.5 0.5
42 TEMPERATURE DEG C 40 65
43 VISCOSITY cP 0.804
44 OPERATING SPECIFIC GRAVITY 1.046
45
46
MANUFACTURER
※47 MANUFACTURER ENDRESS+HAUSER
※48 MODEL NO. CPS11D-7BA2G,CM42-MGA001EAF00,CYK10-G101,CPA240-21BC110
NOTES:
SC No.: SC1
INSTRUMENT DATA SHEET FOR Doc. No.: SC1-200-DS-IN-0004
PH ANALYZER Unit No.: 200
P.O. No.:
Client: SONATRACH Sheet: 4 OF 4
Project: PROJET TOPPING DE CONDENSAT -- SKIKDA Rev.: 1
Site: SKIKDA Date: 21-09-2007

GENERAL
1 TAG NO. 200-AT2202
2 QUANTITY P&ID NO. ONE SC1-200-DW-PR-1114
3 SERVICE CAUSTIC SLUDGE TO 200-V-506A
4 LINE NO. 1 1/2"-200-TWW-5001-1A8
5 LINE SIZE LINE SCHEDULE 1 1/2" SCH160
6 PIPE MATERIAL CLASS 1A8 (ASTM A106 GR.B SMLS PE PER ASME B36.10M)
7 AREA CLASSIFICATION (IEC) ZONE 2, GROUP IIB, T4
SENSOR
※8 SENSOR TYPE FLOW-THROUGH
※9 CONNECTION & RATING (ASME B16.5) ANSI 1" 150# RF
※10 IMMERSION LENGTH (MM) 120
※11 BODY MATERIAL Glass
※12 COVER MATERIAL Plastic
13 WORKING RANGE 0~14 PH
※14 TYPE OF CLEANING N/A
※15 OPTIONS OPTIONAL CONTROL UNIT N/A
※16 TEMP. COMPENSATION AUTO
17 ENCLOSURE (CERTIFICATION) IP68 (EEX iaⅡC)
TRANSMITTER
※18 TYPE (MS/CM) INDICATION, TRANSMITTER
※19 MOUNTING RACK
20 RANGE 0~14 PH
21 OUTPUT SIGNAL 4~20 mA HART
※22 POWER SUPPLY 24VDC
23 ELECTRICAL CONNECTION 1/2" NPT
24 ENCLOSURE (CERTIFICATION) IP67 (EEX iaⅡC)
25
26
27
ACCESSORIES
※28 REMOTE INDICATOR NO
※29 JUNCTION BOX NO
※30 MOUNTING BRACKET YES
※31 SPECIAL TOOL NO
※32 CALIBRATION SET NO
※33 BUFFER SOLUTION YES
※34 SPECIAL CABLE YES
※35 SAMPLE COOLER & REDUCTION PRESSURE NO
36
SPARE PARTS
37 SEE REQUISITION REQUIREMENT
38
PROCESS CONDITIONS
39 FLUID STATE CAUSTIC SLUDGE LIQUID
40 UNIT NOR DESIGN
41 PRESSURE KG/CM²G 1.5 0.5
42 TEMPERATURE DEG C 40 65
43 VISCOSITY cP 0.804
44 OPERATING SPECIFIC GRAVITY 1.046
45
46
MANUFACTURER
※47 MANUFACTURER ENDRESS+HAUSER
※48 MODEL NO. CPS11D-7BA2G,CM42-MGA001EAF00,CYK10-G101,CPA240-21AC110
NOTES:

You might also like