Installation Instructions: Warning Warning
Installation Instructions: Warning Warning
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
See NOTES
NOTES:
Service clearance of 30 in. must be maintained on one of the sides
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
adjacent to the control box.
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
Clearance to one of the other three sides must be 36 in.
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
Clearance to one of the remaining two sides may be 12 in. and the
See See
NOTES final side may be 6 in..
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
NOTES
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
A clearance of 24 in. must be maintained
between two units.
ÍÍÍÍÍÍÍÍÍÍÍÍÍ Control
ÍÍÍÍÍÍÍÍÍÍÍÍÍ
See NOTES 48 in. clearance required on top of unit.
Box
ÍÍÍÍÍÍÍÍÍÍÍÍÍ FIGURE 1
LIQUID LINE
CONNECTION
C
ELECTRICAL INLETS
A
SUCTION LINE
CONNECTION
4-1/2” 4-3/4”
(108) (121)
B
TOP VIEW
SIDE VIEW
Model Number A B C
XP14-018-230 31 (787)
XP14-024-230 39 (991)
30-1/2 (775) 35 (889)
XP14-030-230 39 (991)
XP14-036-230 35 (889)
XP14-042-230 39 (991)
XP14-048-230 39 (991) 35-1/2 (902) 39-1/2 (1003)
XP14-060-230 45 (1143)
7-3/4 8-3/4
(197) 4-1/2 3-3/4
J (222)
(114) (95)
Page 2
IMPORTANT ! ELEVATED SLAB MOUNTING USING FEET
EXTENDERS
Exhaust vents from dryers, water heaters and
furnaces should be directed away from the outdoor Use additional 2” SCH 40 male
2” (50.8MM) SCH 40 threaded adapters which can
unit. Prolonged exposure to exhaust gases and the FEMALE THREADED
be threaded into the female
chemicals contained within them may cause ADAPTER
threaded adapters to make
condensation to form on the steel cabinet and other additional adjustments to the
metal components of the outdoor unit. This will level of the unit.
diminish unit performance and longevity.
2” (50.8MM)
SCH 40 MALE
PLACEMENT THREADED
ADAPTER
Install unit away from windows.
BASE
LEG DETAIL
MOUNTING
SLAB
! IMPORTANT !
Unit Stabilizer Bracket Use
GROUND LEVEL
(field-provided):
Always use stabilizers when unit is raised
FIGURE 3 above the factory height.
(Elevated units could become unstable in
gusty wind conditions.)
CAUTION Stabilizers may be used on any unit installed
on unstable and uneven surfaces.
Before attempting to perform any service or mainte
nance, turn the electrical power to unit OFF at discon
nect switch. FIGURE 5
Page 3
XP14 SERIES
STEP 2 -- REFRIGERANT PIPING -- Flush
ing Existing Line Set & Indoor Coil
WARNING
When using a high pressure gas such as
Flush the existing line set per the following instruc nitrogen to pressurize a refrigeration or air
tions. For more information, refer to the Installation conditioning system, use a regulator that
and Service Procedures manual available on Dave can control the pressure down to 1 or 2
Net. CAUTION - DO NOT attempt to flush and re-use ex psig (6.9 to 13.8 kPa).
isting line sets or indoor coil when the system con
tains contaminants (i.e., compressor burn out).
NOTE - When installing refrigerant lines longer than 50
feet, refer to the Refrigerant Piping Design and Fabrication
Guidelines manual available on DaveNet (Corp. 9351-L9),
WARNING
or contact the Technical Support Department Product Ap Refrigerant can be harmful if it is inhaled. Refrigerant
plication group for assistance. must be used and recovered responsibly.
Failure to follow this warning may result in personal injury
NOTE - For new or replacement line set installation, refer or death.
to Service and Application Note - Corp. 9112-L4 (C-91-4).
TABLE 1
REFRIGERANT LINE SET — INCHES (MM)
Valve Field
Connections
Recommended Line Set WARNING
Model
Liquid Vapor Liquid Vapor Fire, Explosion and Personal Safety Haz
L15 Line Sets
Line Line Line Line ard. Failure to follow this warning could re
-018 sult in damage, personal injury or death.
3/8 in. 3/4 in. 3/8 in. 3/4 in. L15-41 — 15 ft. -
-024 (10 (19 (10 (19 50 ft. (4.6 m - 15 Never use oxygen to pressurize or purge
mm) mm) mm) mm) m) refrigeration lines. Oxygen, when exposed
-030
-036 to a spark or open flame, can cause fire
3/8 in. 7/8 in. 3/8 in. 7/8 in. L15-65 — 15 ft. -
-042 (10 (22 (10 (22 50 ft. (4.6 m - 15 and/or an explosion, that could result in
-048
mm) mm) mm) mm) m) property damage, personal injury or death.
3/8 in. 1-1/8 3/8 in. 1-1/8
-060 (10 in. (29 (10 in. (29 Field Fabricated
mm) mm) mm) mm)
NOTE — Some applications may required a field provided 7/8” to
1-1/8” adapter
WARNING
Polyol ester (POE) oils used with HFC-410A
IMPORTANT ! refrigerant absorb moisture very quickly. It is very
important that the refrigerant system be kept closed
If this unit is being matched with an approved line as much as possible. DO NOT remove line set caps
set or indoor unit coil that was previously charged or service valve stub caps until you are ready to make
with mineral oil, or if it is being matched with a coil connections.
which was manufactured before January of 1999,
the coil and line set must be flushed prior to installa
tion. Take care to empty all existing traps. Polyol es
ter (POE) oils are used in Lennox units charged with IMPORTANT !
HFC-410A refrigerant. Residual mineral oil can act
Some scroll compressors have an internal vacuum
as an insulator, preventing proper heat transfer. It
protector that will unload scrolls when suction pres
can also clog the expansion device and reduce sys sure goes below 20 psig. A hissing sound will be
tem performance and capacity. heard when the compressor is running unloaded.
Failure to properly flush the system per this instruc Protector will reset when low pressure in system is
tion and the detailed Installation and Service Proce raised above 40 psig. DO NOT REPLACE COM
dures manual will void the warranty. PRESSOR.
Page 4
STEP 2 -- REFRIGERANT PIPING -- Removing Existing Indoor Metering Device
1A
TYPICAL EXISTING FIXED ORIFICE
REMOVAL PROCEDURE
(UNCASED COIL SHOWN)
OR
1B TYPICAL EXISTING EXPANSION VALVE REMOVAL
PROCEDURE (UNCASED COIL SHOWN)
BRASS NUT
TEFLON®
RING SENSING
LINE
DISTRIBUTOR
ASSEMBLY DISTRIBUTOR EQUALIZER
ASSEMBLY LINE
REMOVE AND DISCARD
WHITE TEFLON® SEAL
(IF PRESENT) LIQUID LINE ASSEMBLY
(INCLUDES STRAINER) LIQUID LINE
ASSEMBLY WITH
BRASS NUT
A. On fully cased coils, remove the coil access and plumbing panels.
B. Remove any shipping clamps from the liquid line and distributor as
sembly. MALE EQUALIZER
LINE FITTING VAPOR
C. Using two wrenches, disconnect liquid line from liquid line orifice hous LIQUID
SENSING BULB LINE
ing. Take care not to twist or damage distributor tubes during this pro LINE
cess.
A. On fully cased coils, remove the coil access and plumbing panels.
D. Remove and discard fixed orifice, valve stem assembly (if present)
and Teflon® washer as illustrated above. B. Remove any shipping clamps from the liquid line and distributor
assembly.
E. Use a field-provided fitting to temporarily reconnect the liquid line to the
indoor unit's liquid line orifice housing. C. Disconnect the equalizer line from the check expansion valve
equalizer line fitting on the vapor line.
2
D. Remove the vapor line sensing bulb.
CONNECT GAUGES AND EQUIPMENT FOR
FLUSHING PROCEDURE E. Disconnect the liquid line from the check expansion valve at the
liquid line assembly.
CYLINDER CONTAINING
CLEAN HCFC-22 TO BE GAUGE F. Disconnect the check expansion valve from the liquid line orifice
USED FOR FLUSHING MANIFOLD housing. Take care not to twist or damage distributor tubes during
(Positioned to deliver liquid this process.
A refrigerant)
G. Remove and discard check expansion valve and the two Teflon®
1 LOW HIGH rings.
H. Use a field-provided fitting to temporarily reconnect the liquid line to
VAPOR LINE NEW
SERVICE VALVE OUTDOOR the indoor unit's liquid line orifice housing.
UNIT
EXISTING
INDOOR
UNIT B
OPENED CLOSED
3 FLUSHING LINE SET
The line set and indoor unit coil must be flushed with at least the same
amount of clean refrigerant that previously charged the system. Check
the charge in the flushing cylinder before proceeding.
LIQUID LINE SERVICE
VALVE A. Set the recovery machine for liquid recovery and start the recovery
RECOVERY machine. Open the gauge set valves to allow the recovery
CYLINDER TANK machine to pull a vacuum on the existing system line set and indoor
RETURN unit B
coil.
C
VAPOR
LIQUID
FIGURE 6
Page 5
XP14 SERIES
STEP 2 -- REFRIGERANT PIPING -- Brazing Procedures
3 ATTACH THE MANIFOLD GAUGE SET FOR BRAZING LIQUID AND SUCTION / VAPOR LINE SERVICE
VALVES
Flow regulated nitrogen (at 1 to 2 psig) through the low-side refrigeration gauge set into the liquid line service port valve, and out of the suction /
vapor line service port valve.
A. Connect gauge set low pressure side to
liquid line service valve (service port). USE REGULATOR TO FLOW
LOW HIGH NITROGEN AT 1 TO 2 PSIG.
B. Connect gauge set center port to bottle of
nitrogen with regulator.
C. Remove core from valve in suction / vapor
line service port to allow nitrogen to escape. ATTACH
GAUGES
INDOOR OUTDOOR
UNIT UNIT
NITROGEN
LIQUID LINE LIQUID LINE SERVICE
VALVE
A WHEN BRAZING LINE SET TO
SERVICE VALVES, POINT FLAME
AWAY FROM SERVICE VALVE.
FIGURE 7
CAUTION WARNING
Brazing alloys and flux contain materials which are
hazardous to your health. Danger of fire. Bleeding the refrigerant
Avoid breathing vapors or fumes from brazing charge from only the high side may result
operations. Perform operations only in well-ventilated in pressurization of the low side shell and
areas. suction tubing. Application of a brazing
torch to a pressurized system may result
Wear gloves and protective goggles or face shield to
in ignition of the refrigerant and oil
protect against burns.
mixture. Check the high and low
Wash hands with soap and water after handling brazing pressures before applying heat.
alloys and flux.
Page 6
4 WRAP SERVICE VALVES
To help protect service valve seals during brazing, wrap water-saturated cloths around service valve bodies and copper tube stubs. Use
additional water-saturated cloths underneath the valve body to protect the base paint.
5 FLOW NITROGEN
Flow regulated nitrogen (at 1 to 2 psig) through the refrigeration gauge set into the valve stem port connection on the liquid service valve and
out of the suction / vapor valve stem port. See steps 3A, 3B and 3C on manifold gauge set connections.
WARNING
SUCTION / VAPOR LINE
FIRE, PERSONAL INJURY, OR PROPERTY DAMAGE SERVICE VALVE
may result if you do not wrap a water-saturated cloth around
both liquid and suction line service valve bodies and copper
tube stub while brazing the line set! The braze, when
complete, must be quenched with water to absorb any
residual heat.
Do not open service valves until refrigerant lines and WHEN BRAZING LINE SET TO
indoor coil have been leak-tested and evacuated. Refer SERVICE VALVES, POINT FLAME
to Installation and Service Procedures manual found on AWAY FROM SERVICE VALVE.
DAVENET.
FIGURE 7 (CONTINUED)
Page 7
XP14 SERIES
STEP 3 -- INSTALLING INDOOR EXPANSION VALVE
This outdoor unit is designed for use in systems that include an check/expansion valve metering device. See the XP14
Product Specifications bulletin (EHB) for approved check/expansion valve kit match-ups and application information. The
check/expansion valve can be installed internal or external to the indoor coil. In applications where an uncased coil is being
installed in a field-provided plenum, install the check/expansion valve in a manner that will provide access for future field
service of the check expansion valve. Refer to below illustration for reference during installation of check/expansion valve.
INDOOR EXPANSION VALVE INSTALLATION C. Install one of the provided Teflon® rings around the 1/2 Turn
TWO PIECE stubbed end of the check expansion valve and lightly
PATCH PLATE (Uncased Coil Shown) lubricate the connector threads and expose surface of 11 12 1
(UNCASED the Teflon® ring with refrigerant oil. 10 2
STUB
D. Attach the stubbed end of the check expansion valve to 9 3
COIL ONLY) LIQUID LINE
END CHECK
ORIFICE 4
HOUSING EXPANSION the liquid line orifice housing. Finger tighten and use an 8 7 5
DISTRIBUTOR VALVE appropriately sized wrench to turn an additional 1/2 turn 6
TUBES clockwise as illustrated in the figure above, or tighten to
TEFLON®
RING 20 ft-lb.
E. Place the remaining Teflon® washer around the other
end of the check expansion valve. Lightly lubricate
connector threads and expose surface of the Teflon®
TEFLON®
RING
SENSING ring with refrigerant oil.
LINE
F. Attach the liquid line assembly to the check expansion
valve. Finger tighten and use an appropriately sized
DISTRIBUTOR EQUALIZER wrench to turn an additional 1/2 turn clockwise as
ASSEMBLY LINE illustrated in the figure above or tighten to 20 ft-lb.
LIQUID LINE
ASSEMBLY WITH SENSING BULB INSTALLATION
BRASS NUT
FIGURE 8
Page 8
STEP 4 -- LEAK TEST AND EVACUATION
LOW HIGH
OUTDOOR UNIT
B A
TO VAPOR
SERVICE VALVE
NOTE - Position
canister to deliver
liquid refrigerant.
NITROGEN HFC-410A
1 A Connect the high pressure hose of an HFC-410A manifold gauge set to the vapor valve service port.
NOTE — Normally, the high pressure hose is connected to the liquid line port. However, connecting it
to the vapor port better protects the manifold gauge set from high pressure damage.
B With both manifold valves closed, connect the cylinder of HFC-410A refrigerant to the center port of
the manifold gauge set.
NOTE — Later in the procedure, the HFC-410A container will be replaced by the nitrogen container.
FIGURE 9
Page 9
XP14 SERIES
STEP 4 -- LEAK TEST AND EVACUATION (Continued)
EVACUATION
3
A
CONNECT GAUGE SET
NOTE — Remove cores from service valves (if not already done).
Connect low side of manifold gauge set with
LOW HIGH
HFC-410A
B
VACUUM PUMP
TO LIQUID LINE
SERVICE VALVE
4 A
B
EVACUATE THE SYSTEM
NOTE — During the early stages of evacuation, it is desirable to close the manifold gauge valve at least once. A rapid rise in pressure indicates a
relatively large leak. If this occurs, repeat the leak testing procedure.
NOTE — The term absolute pressure means the total actual pressure above absolute zero within a given volume or system. Absolute pressure
in a vacuum is equal to atmospheric pressure minus vacuum pressure.
C When the absolute pressure reaches 23,000 microns (29.01 inches of mercury),
perform the following: WARNING !
S Close manifold gauge valves.
S Close valve on vacuum pump. Possible equipment damage.
S Turn off vacuum pump. Avoid deep vacuum operation. Do not use
S Disconnect manifold gauge center port hose from vacuum pump. compressors to evacuate a system.
S Attach manifold center port hose to a nitrogen cylinder with pressure Extremely low vacuum can cause internal
regulator set to 150 psig (1034 kPa) and purge the hose. arcing and compressor failure. Damage
S Open manifold gauge valves to break the vacuum in the line set and indoor caused by deep vacuum operation will
unit. void warranty.
S Close manifold gauge valves.
D Shut off the nitrogen cylinder and remove the manifold gauge hose from the cylinder. Open the manifold gauge valves to release the nitrogen
from the line set and indoor unit.
E Reconnect the manifold gauge to the vacuum pump, turn the pump on, and continue to evacuate the line set and indoor unit until the absolute
pressure does not rise above 500 microns (29.9 inches of mercury) within a 20-minute period after shutting off the vacuum pump and closing
the manifold gauge valves.
F When the absolute pressure requirement above has been met, disconnect the manifold hose from the vacuum pump and connect it to a
cylinder of HFC-410A positioned to deliver liquid refrigerant. Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line
set and indoor unit.
G Perform the following:
S Close manifold gauge valves.
S Shut off HFC-410A cylinder. 1/6 TURN
S Reinstall service valve cores by removing manifold hose from service valve. Quickly install cores with core
tool while maintaining a positive system pressure. 12 1
11
S Replace stem caps and finger tighten them, then tighten an additional one-sixth (1/6) of a turn as illustrated. 10 2
9 3
8 4
7 5
6
FIGURE 10
Page 10
STEP 5 -- ELECTRICAL -- Circuit Sizing and Wire Routing
In the U.S.A., wiring must conform with current local codes
and the current National Electric Code (NEC). In Canada,
IMPORTANT !
wiring must conform with current local codes and the current If unit is equipped with a crankcase heater, it should
Canadian Electrical Code (CEC). be energized 24 hours before unit start-up to pre
Refer to the furnace or air handler installation instructions vent compressor damage as a result of slugging.
for additional wiring application diagrams and refer to unit
nameplate for minimum circuit ampacity and maximum
overcurrent protection size.
24VAC TRANSFORMER
CAUTION
Use the transformer provided with the furnace or air han Electrostatic discharge can affect
dler for low‐voltage control power (24VAC - 40 VA mini electronic components. Take care
mum) during unit installation and service to
protect the unit's electronic controls.
WARNING ELECTROSTATIC
DISCHARGE
Precautions will help to avoid control
exposure to electrostatic discharge by
Electric Shock Hazard. Can cause injury (ESD)
Precautions and putting the unit, the control and the
or death. Unit must be grounded in Procedures technician at the same electrostatic
accordance with national and local
codes. potential. Touch hand and all tools on an
unpainted unit surface before
Line voltage is present at all components
performing any service procedure to
when unit is not in operation on units with
neutralize electrostatic charge.
single‐pole contactors. Disconnect all
remote electric power supplies before
opening access panel. Unit may have
multiple power supplies.
1
SIZE CIRCUIT AND INSTALL DISCONNECT
SWITCH
Refer to the unit nameplate for minimum circuit ampacity, and
maximum fuse or circuit breaker (HACR per NEC). Install power
2 INSTALL THERMOSTAT
Install room thermostat (ordered separately) on an inside wall
approximately in the center of the conditioned area and 5 feet
(1.5m) from the floor. It should not be installed on an outside wall
or where it can be affected by sunlight or drafts.
wiring and properly sized disconnect switch.
MAIN FUSE
BOX/BREAKER
PANEL THERMOSTAT
DISCONNECT
SWITCH
5 FEET
(1.5M)
NOTE — Units are approved for use only with copper conductors. NOTE — 24VAC, Class II circuit connections are made in the control
Ground unit at disconnect switch or connect to an earth ground. panel.
FIGURE 11
Page 11
XP14 SERIES
3 Unit Low Voltage Wiring HIGH VOLTAGE FIELD WIRING
FACTORY WIRING
LOW VOLTAGE (24V) FIELD WIRING
YELLOW
B Run 24VAC control wires through wire tie.
C Make 24VAC control wire connections using field provided wire
nuts.
BLACK
D Tighten wire tie to security 24V control wiring.
NOTE - FOR PROPER VOLTAGES, SELECT THERMOSTAT WIRE (CONTROL WIRES)
GAUGE PER TABLE ABOVE.
NOTE - WIRE TIE PROVIDES LOW VOLTAGE WIRE STRAIN RELIEF AND MAINTAINS
SEPARATION OF FIELD-INSTALLED LOW AND HIGH VOLTAGE CIRCUITS.
NOTE - DO NOT BUNDLE ANY EXCESS 24VAC CONTROL WIRES INSIDE CONTROL
BOX.
CUTOUT WITH
A GROMMET
FIGURE 12
24V POWER R R R
24V POWER 24V POWER
R R R
24V POWER C C C
COMMON COMMON
EMERGENCY
C C C
COMMON COMMON HEAT RELAY
W1 W1 W1 E OUTDOOR
1ST‐STAGE 1ST‐STAGE EMERGENCY
AUXILIARY AUXILIARY HEAT THERMOSTAT
HEAT W2 HEAT
W3 W1 W1 W1
1ST‐STAGE 1ST‐STAGE
AUXILIARY W2 AUXILIARY
HEAT HEAT
G G W3
INDOOR BLOWER
G G
O O INDOOR BLOWER
REVERSING VALVE
O O
Y1 Y1 REVERSING VALVE
COMPRESSOR
(SOME CONNECTIONS MAY NOT APPLY. REFER Y1 Y1
COMPRESSOR
TO SPECIFIC THERMOSTAT AND INDOOR UNIT.)
(SOME CONNECTIONS MAY NOT APPLY. REFER TO
SPECIFIC THERMOSTAT AND INDOOR UNIT.)
FIGURE 13
Page 12
Charging S If the timing selector jumper is missing, the defrost
control defaults to a 90-minute defrost interval.
The XP14 unit is factory-charged with enough HFC-410A Compressor Delay (P5)
refrigerant to accommodate a 15-foot length of refrigerant
The defrost control has a field-selectable function to re
piping. Charge should be checked and adjusted using the
duce occasional sounds that may occur while the unit is
tables provided on the charging procedure sticker on the
cycling in and out of the defrost mode.
unit access panel. Detailed information is given in the
XP14 Installation and Service Procedures manual, which The compressor will be cycled off for 30 seconds going in
is available on DaveNet. and out of the defrost mode when the compressor delay
jumper is installed.
Defrost System NOTE — The 30‐second compressor feature is ignored
The defrost system includes a defrost thermostat (S6) and when jumpering the TEST pins.
a defrost control (CMC1). Time Delay
DEFROST CONTROL (CMC1) The timed‐off delay is five minutes long. The delay helps to
protect the compressor from short‐cycling in case the pow
This defrost control includes the combined functions of a
er to the unit is interrupted or a pressure switch opens. The
time/temperature defrost control, defrost relay, time delay,
delay is bypassed by placing the timer select jumper
diagnostic LEDs, and a terminal strip for field wiring con
across the TEST pins for 0.5 seconds.
nections.
Test Mode
DEFROST CONTROL (CMC1) The TEST mode is activated by removing the jumper on
the defrost termination pins (30, 60 or 90) and placing the
DEFROST TIMING jumper on the TEST pins after 24VAC is applied to the con
PINS (P1)
trol. The low pressure input is ignored in TEST mode.
TEST
PINS
DIAGNOSTIC
IMPORTANT
LEDS
The TEST pins are ignored and the TEST function is
COMPRESSOR
DELAY PINS locked out:
REVERSING
VALVE
S If the jumper is applied on the TEST pin before
24V TERMINAL 24VAC is applied to the control.
STRIP
S87 CONNECTIONS S If there is a jumper on the 30 or 60 minute defrost ter
LOW PRESSURE
SERVICE LIGHT
mination pins.
SWITCH
CONNECTIONS
DEFROST Bypass-Anti-Short Cycle Delay
THERMOSTAT (S6)
The Y1 input must be active ON, the high pressure switch
S4 must be closed or a jumper must be installed on the high
HIGH PRESSURE pressure terminals of the control.
SWITCH
Initiate a Force Defrost
The Y1 input must be active ON, the high pressure switch
FIGURE 14 must be closed or a jumper must be installed on the high
The defrost control provides automatic switching from nor pressure terminals of the control, the defrost thermostat
mal heating operation to defrost mode and back. When the must be closed or a jumper must be placed across the DF
defrost thermostat is closed, the control accumulates com terminals on the control and the O terminals must not have
pressor run time at 30, 60 or 90 minute field adjustable in 24VAC (no power to reversing valve) before control will
tervals. When the selected compressor run time interval is enter into a force defrost.
reached, the defrost relay is energized and defrost begins. Test Mode Sequence
Defrost Control Timing Pins (P1) Using the defrost termination pin, short the TEST pins for
Each timing pin selection provides a different accumu a period of two seconds:
lated compressor run time period for one defrost cycle. S Clear timed lockout / or pressure switch lockout func
This time period must occur before a defrost cycle is initi tion.
ated. The defrost interval can be adjusted to 30 (T1), 60 S Enter defrost mode
(T2), or 90 (T3) minutes (see figure 14). The maximum
defrost period is 14 minutes and cannot be adjusted. After entering force defrost, if the jumper is removed be
fore 5 seconds has elapsed, the unit will remain in forced
NOTE — Defrost control part number is listed near the P1 defrost mode until defrost thermostat opens or terminated
timing pins. on maximum defrost time (14 minutes). If the jumper is not
S Factory default is 90 minutes. removed, once 5 seconds has elapsed (7 seconds total),
Page 13
XP14 SERIES
the unit will terminate defrost and return to heat mode. The Defrost Control Diagnostic LEDs
TEST mode will then be lockedout and no further TEST The defrost board uses two LEDs for diagnostics. The
mode operation will be executed until the jumper on the LEDs flash a specific sequence according to the condition.
TEST pins is removed and reapplied to the applicable de
TABLE 2
frost termination pins.
DEFROST CONTROL (CMC1) DIAGNOSTIC LEDS
Mode Green LED (DS2) Red LED (DS1)
IMPORTANT No power to con
trol
OFF OFF
NOTE - After testing has been completed, properly re Normal operation /
position test jumper across desired timing pins. Simultaneous Slow FLASH
power to control
Anti‐short cycle
Alternating Slow FLASH
Service Light Connection lockout
The defrost control includes terminal connections for a ser High pressure Slow FLASH OFF
vice light which provides a signal that activates the room switch fault
thermostat service light during periods of inefficient opera High pressure ON OFF
tion. switch lockout
Customer Address
Indoor Unit Model Serial
Outdoor Unit Model Serial
Notes:
START UP CHECKS
Refrigerant Type:
System Refrigerant Charge (Refer to manufacturer's information on unit or installation instructions for required
subcooling and approach temperatures.)
Subcooling: A — B = SUBCOOLING
Saturated Condensing Temperature (A)
minus Liquid Line Temperature (B)
Approach: A — B = APPROACH
Liquid Line Temperature (A)
minus Outdoor Air Temperature (B)
Indoor Coil Temperature Drop (18 to 22°F) A — B = COIL TEMP DROP
Return Air Temperature (A)
minus Supply Air Temperature (B)
Page 14
Homeowners Information S The indoor evaporator coil is equipped with a drain pan
to collect condensate formed as your system removes
humidity from the inside air. Have your dealer show
CAUTION you the location of the drain line and how to check for
obstructions. (This would also apply to an auxiliary
Before attempting to perform any service or mainte drain, if installed.)
nance, turn the electrical power to unit OFF at discon Thermostat Operation
nect switch. See the ComfortSense® 7000 thermostat homeowner
Cleaning of the outdoor unit's coil should be performed by manual for instructions on how to operate your thermostat.
a licensed professional service technician (or equivalent). Heat Pump Operation
Contact your dealer and set up a schedule (preferably Your new Lennox heat pump has several characteristics
twice a year, but at least once a year) to inspect and ser that you should be aware of:
vice your outdoor unit. The following maintenance may be S Heat pumps satisfy heating demand by delivering
performed by the homeowner.
large amounts of warm air into the living space. This
is quite different from gas‐ or oil‐fired furnaces or an
IMPORTANT ! electric furnace which deliver lower volumes of consid
Sprinklers and soaker hoses should not be installed erably hotter air to heat the space.
where they could cause prolonged exposure to the S Do not be alarmed if you notice frost on the outdoor coil
outdoor unit by treated water. Prolonged exposure in the winter months. Frost develops on the outdoor
of the unit to treated water (i.e., sprinkler systems, coil during the heating cycle when temperatures are
soakers, waste water, etc.) will corrode the surface below 45F (7C). An electronic control activates a de
of steel and aluminum parts, diminish performance frost cycle lasting 5 to 15 minutes at preset intervals
and affect longevity of the unit. to clear the outdoor coil of the frost.
S During the defrost cycle, you may notice steam rising
Outdoor Coil from the outdoor unit. This is a normal occurrence.
The outdoor unit must be properly maintained to ensure its The thermostat may engage auxiliary heat during the
proper operation. defrost cycle to satisfy a heating demand; however,
S Please contact your dealer to schedule proper inspec the unit will return to normal operation at the conclu
tion and maintenance for your equipment. sion of the defrost cycle.
S Make sure no obstructions restrict airflow to the outdoor Extended Power Outage
unit. The heat pump is equipped with a compressor crankcase
S Grass clippings, leaves, or shrubs crowding the unit can heater which protects the compressor from refrigerant
cause the unit to work harder and use more energy. slugging during cold weather operation.
S Keep shrubbery trimmed away from the unit and periodi If power to your unit has been interrupted for several hours
cally check for debris which collects around the unit. or more, set the room thermostat selector to the EMER
GENCY HEAT setting to obtain temporary heat without the
S Keep snow level below the louvered panels to ensure risk of serious damage to the heat pump.
proper performance.
In EMERGENCY HEAT mode, all heating demand is satis
Routine Maintenance fied by auxiliary heat; heat pump operation is locked out.
In order to ensure peak performance, your system must be After a six‐hour compressor crankcase warm‐up period,
properly maintained. Clogged filters and blocked airflow the thermostat can be switched to the HEAT setting and
prevent your unit from operating at its most efficient level. normal heat pump operation may resume.
NOTE — The filter and all access panels must be in place Preservice Check
any time the unit is in operation. If you are unsure about the If your system fails to operate, check the following before
filter required for your system, call your Lennox dealer for calling for service:
assistance. S Verify room thermostat settings are correct.
S Ask your Lennox dealer to show you where your indoor S Verify that all electrical disconnect switches are ON.
unit's filter is located. It will be either at the indoor unit
(installed internal or external to the cabinet) or behind S Check for any blown fuses or tripped circuit breakers.
a return air grille in the wall or ceiling. Check the filter S Verify unit access panels are in place.
monthly and clean or replace it as needed. S Verify air filter is clean.
S Disposable filters should be replaced with a filter of the S If service is needed, locate and write down the unit
same type and size. model number and have it handy before calling.
Page 15
XP14 SERIES