Figure 1 is the column application plan at the base of an 8 story
building, showing the loads at serviceability limit state. It is required to
found this building on a pile foundation. Using the pile catalogue, carry
out sufficient calculation to establish the pile layout and quantity of
reinforcing steels required in the pile caps using concrete C25/30 and
grade 460 steel.
Figure 1: Load Application Plan @ Base of Building
Pile
diameter 400 500 600 750
(mm)
Safe
working 806 1343 1668 2452
load (kN)
Column Al (Typical for A3, E1 & E3)
select a suitable pile type from the pile catalogue.Assuming, we want to use two piles for this columns, we can
determine the pile type required by dividing the loads on the column
at serviceability by the number of piles required, which is 2, and then
select a suitable pile type from the pile catalogue.
Assuming, we want to use two piles for this columns, we can
determine the pile type required by dividing the loads on the column
at serviceability by the number of piles required, which is 2, and then
select a suitable pile type from the pile catalogue.__ load(un factored)
il
no of pile 5
— 904 465 _ 6g4 shiv < 806K
We can adopt, two 400mm diameter piles
Figure 2: Pile-cap (Type 1)
Geometry of the pile-cap
Try an overall depth h=1000mm with an average effective depth of
900mm, the spacing between piles 3 x 400 = 1200mm, and assuming
an overhang of 150mm from the piles both ways, length of pile cap
=1200+(400/2)+(400/2)+150+150= 1900mm. Width of pile cap = 400
+150 +150 =700mm. The layout of the pile cap is shown es figure 2
Agoul
IS WE WalIL WW Use WWE piles 11 uns Lulu!
is, WE Lal
determine the pile type required by dividing the loads on the column
at serviceability by the number of piles required, which is 2, and then
select a suitable pile type from the pile catalogue.Nuis = 1.354, + 1.5Q, = 1.35(904) + 1.5(465)
= 1917.9kN
self weight of pile cap
=1.7x 08x 1x 25
= 33.25kN
N =1917.9+ 33.25 = 1951kN
Tension Reinforcement
pa Nt _ 1951 x (1200/2)
—_______ = 65 iN
2 ~~ 2x 900 (50.33kN
T 650.33 x 10°
= 1625.01mm?
O87Fx 0.87 x 460 owen
‘The total area of reinforcement required in both direction Acreq = 2X
1625.01 =3250.5mm?
Assuming, we want to use two piles for this columns, we can
determine the pile type required by dividing the loads on the column
at serviceability by the number of piles required, which is 2, and then
select a suitable pile type from the pile catalogue.Try 18T16—100mm (As.prov = 3618mm”)
Verify Minimum Area of Stee!
Asmin = 0. pole hd > 0.0013bd
vk
2/3
fem = 0.3f%,) = 0.3 x 25°? = 2.56MPa
0.26 x 28, yo00 x 900 >
0.0013 x 1900 x 900
=2474.5mm? < As grow Ok
Shear Verification
1951
Via = 970k
a = ue ~ “ — (400 +150) + oK = 280mm
a 280
Ved = VS = 976--—_ = 151.8kN
ee VG Bx 900) |
Viric = 0.12k (L00pf4)!/*bd > 0.035k2/* 4/ Fudd
=. | 208 [200 are
k= 14a 1+¥ 500 147 <2
Ap 3618
= Fa ~ To00% 900 ~ °-00%
Varde = 0.12 - 1.47(100 x 0.0021 x 25)"*bd
> 0.085 x 1.4773 - ¥25bd
524.3kN > (Vea =151.8kN) ok
select a suitable pile type from the pile catalogue.Pile spacing has being deliberately chosen at exactly 3 times the pile
diameter to avoid further punching checks except at the column face
Atthe column face:
Nea < Vramar
2(1- 38) fara
25
_ 2 Vos .
0.2 ( 5) 25 x (4 x 400) - 900
VRamar =
=6480kN > (2
=1951kN) ok
@
Having provided the longitudinal reinforcement required in the pile
caps, an additional layer of steel is usually provided on the surface of
the pile cap, often known as the “anti-burst steel”. This is provided
based on the minimum area of steel. The pile themselves are designed
as axially loaded “stocky “columns, in many instances would only
require minimum area of steel.
Thank You!
Assuming, we want to use two piles for this columns, we can
determine the pile type required by dividing the loads on the column
at serviceability by the number of piles required, which is 2, and then
select a suitable pile type from the pile catalogue.