Professional Documents
Culture Documents
Bess Sangali - NGCP Zamboanga Fiber Optic Line Test Report
Bess Sangali - NGCP Zamboanga Fiber Optic Line Test Report
A. VISUAL INSPECTION
Inspection Points ok
Fiber Optic Cable ok
OPGW ok
ODF ok
B. SPLICING LOSS
SPLICING LOSS VALUE (dB)
BUFFER FIBER NO. COLOR Remarks
Location A: BESS ODF Location B: NGCP ZAMBOANGA ODF
1 BLUE 0.01 0.01 Passed
2 ORANGE 0.00 0.00 Passed
3 GREEN 0.00 0.00 Passed
4 BROWN 0.00 0.00 Passed
5 SLATE 0.00 0.01 Passed
6 WHITE 0.01 0.00 Passed
BLUE
7 RED 0.00 0.00 Passed
8 BLACK 0.00 0.00 Passed
9 YELLOW 0.00 0.00 Passed
10 VIOLET 0.00 0.00 Passed
11 PINK 0.00 0.01 Passed
12 AQUA 0.01 0.00 Passed
13 BLUE 0.00 0.00 Passed
14 ORANGE 0.00 0.01 Passed
15 GREEN 0.00 0.00 Passed
16 BROWN 0.00 0.00 Passed
17 SLATE 0.00 0.00 Passed
18 WHITE 0.00 0.00 Passed
ORANGE
19 RED 0.00 0.00 Passed
20 BLACK 0.00 0.00 Passed
21 YELLOW 0.00 0.00 Passed
22 VIOLET 0.01 0.00 Passed
23 PINK 0.00 0.00 Passed
24 AQUA 0.00 0.00 Passed
25 BLUE 0.00 0.00 Passed
26 ORANGE 0.01 0.00 Passed
27 GREEN 0.00 0.00 Passed
28 BROWN 0.00 0.00 Passed
29 SLATE 0.00 0.00 Passed
30 WHITE 0.01 0.00 Passed
GREEN 0.01 0.00
31 RED Passed
32 BLACK 0.00 0.00 Passed
33 YELLOW 0.00 0.00 Passed
34 VIOLET 0.00 0.00 Passed
35 PINK 0.01 0.00 Passed
36 AQUA 0.00 0.00 Passed
Splicing Loss should be less than 0.03dB (In reference to ANSI/NETA ATS 2013 page 192 connectors and splices shall be installed in accordance with industry
Acceptance Criteria:
standards. (7.25.1.2))
Test Instrument: Fujikura FSM 90S+ Model / Serial No. YVT4DJ7KJP81DKNJ Calibration Due: 25-Aug-24
TESTING AND COMMISSIONING
FIBER OPTIC CABLE TEST REPORT
Attenuation result must be less than or equal to 0.4 dB/km (In reference to ANSI/NETA ATS 2013 page 192 that the Attenuation loss measurement shall be in
Acceptance Criteria:
accordance with manufacturer's recommendation when no local site specifications are available.)
Note: The Attenuation Test Result is still acceptable given the line is less than 1 km affecting the result depending on the distance of the FO Line.
Test Instrument: AFL /OFL 280-103 UPC Model / Serial No. 2E30PW6808 Calibration Due: 05-Dec-23
TESTING AND COMMISSIONING
FIBER OPTIC CABLE TEST REPORT
Remarks: ____________________________________________________________________
Splicing Loss Result and Power Loss Test are within acceptance criteria
Attenuation Test is still acceptable thru the measured distance of the line.
____________________________________________________________________
The continuity of the cores have been confirmed through Visual Fault Locator.
The attenuation test result of fiber ranging 536 meters which includes
Note 1: ____________________________________________________________________
cable attenuation, insertion loss, and splice loss.
____________________________________________________________________
Tested by: Checked by: Witnessed by: Noted by: