You are on page 1of 3

TESTING AND COMMISSIONING

FIBER OPTIC CABLE TEST REPORT

F-PMS/CTC-39 Rev 0, 12-Aug-2021

Company Client NATIONAL GRID CORPORATION OF THE PHILIPPINES


PLANT/SUBSTATION BESS SANGALI - NGCP ZAMBOANGA SUBSTATION
Location SANGALI, ZAMBOANGA CITY
Test Date NOVEMBER 03-11, 2023
FIBER OPTIC DATA
Manufacturer Ambient Temperature 30 deg. C
Type SINGLEMODE Length 536 meters
Wavelength 1310 nm Pulse 100 ns

A. VISUAL INSPECTION
Inspection Points ok
Fiber Optic Cable ok
OPGW ok
ODF ok

B. SPLICING LOSS
SPLICING LOSS VALUE (dB)
BUFFER FIBER NO. COLOR Remarks
Location A: BESS ODF Location B: NGCP ZAMBOANGA ODF
1 BLUE 0.01 0.01 Passed
2 ORANGE 0.00 0.00 Passed
3 GREEN 0.00 0.00 Passed
4 BROWN 0.00 0.00 Passed
5 SLATE 0.00 0.01 Passed
6 WHITE 0.01 0.00 Passed
BLUE
7 RED 0.00 0.00 Passed
8 BLACK 0.00 0.00 Passed
9 YELLOW 0.00 0.00 Passed
10 VIOLET 0.00 0.00 Passed
11 PINK 0.00 0.01 Passed
12 AQUA 0.01 0.00 Passed
13 BLUE 0.00 0.00 Passed
14 ORANGE 0.00 0.01 Passed
15 GREEN 0.00 0.00 Passed
16 BROWN 0.00 0.00 Passed
17 SLATE 0.00 0.00 Passed
18 WHITE 0.00 0.00 Passed
ORANGE
19 RED 0.00 0.00 Passed
20 BLACK 0.00 0.00 Passed
21 YELLOW 0.00 0.00 Passed
22 VIOLET 0.01 0.00 Passed
23 PINK 0.00 0.00 Passed
24 AQUA 0.00 0.00 Passed
25 BLUE 0.00 0.00 Passed
26 ORANGE 0.01 0.00 Passed
27 GREEN 0.00 0.00 Passed
28 BROWN 0.00 0.00 Passed
29 SLATE 0.00 0.00 Passed
30 WHITE 0.01 0.00 Passed
GREEN 0.01 0.00
31 RED Passed
32 BLACK 0.00 0.00 Passed
33 YELLOW 0.00 0.00 Passed
34 VIOLET 0.00 0.00 Passed
35 PINK 0.01 0.00 Passed
36 AQUA 0.00 0.00 Passed
Splicing Loss should be less than 0.03dB (In reference to ANSI/NETA ATS 2013 page 192 connectors and splices shall be installed in accordance with industry
Acceptance Criteria:
standards. (7.25.1.2))
Test Instrument: Fujikura FSM 90S+ Model / Serial No. YVT4DJ7KJP81DKNJ Calibration Due: 25-Aug-24
TESTING AND COMMISSIONING
FIBER OPTIC CABLE TEST REPORT

F-PMS/CTC-39 Rev 0, 12-Aug-2021

C. ATTENUATION TEST FOR (1310 nm)


Buffer Fiber No. Fiber Wavelength Loss, dB Length, km Attenuation, dB/km for reference
1 BLUE 1310nm 1.293 0.535 2.416 for reference
2 ORANGE 1310nm 1.072 0.536 1.999 for reference
3 GREEN 1310nm 0.985 0.535 1.841 for reference
4 BROWN 1310nm 0.877 0.536 1.636 for reference
5 SLATE 1310nm 1.12 0.536 2.089 for reference
6 WHITE 1310nm 3.009 0.536 5.612 for reference
BLUE
7 RED 1310nm 2.351 0.536 4.385 for reference
8 BLACK 1310nm 2.184 0.536 4.074 for reference
9 YELLOW 1310nm 2.293 0.534 4.293 for reference
10 VIOLET 1310nm 2.15 0.535 4.018 for reference
11 PINK 1310nm 2.614 0.534 4.894 for reference
12 AQUA 1310nm 2.127 0.536 3.967 for reference
13 BLUE 1310nm 2.069 0.534 3.874 for reference
14 ORANGE 1310nm 2.402 0.534 4.497 for reference
15 GREEN 1310nm 2.888 0.535 5.397 for reference
16 BROWN 1310nm 2.049 0.535 3.829 for reference
17 SLATE 1310nm 2.296 0.533 4.307 for reference
18 WHITE 1310nm 2.263 0.535 4.229 for reference
ORANGE
19 RED 1310nm 2.363 0.535 4.416 for reference
20 BLACK 1310nm 2.603 0.535 4.864 for reference
21 YELLOW 1310nm 2.427 0.535 4.535 for reference
22 VIOLET 1310nm 2.063 0.535 3.855 for reference
23 PINK 1310nm 2.556 0.535 4.776 for reference
24 AQUA 1310nm 2.403 0.535 4.491 for reference
25 BLUE 1310nm 2.552 0.535 4.769 for reference
26 ORANGE 1310nm 2.543 0.535 4.752 for reference
27 GREEN 1310nm 2.224 0.535 4.156 for reference
28 BROWN 1310nm 2.016 0.535 3.767 for reference
29 SLATE 1310nm 2.299 0.535 4.296 for reference
30 WHITE 1310nm 2.117 0.535 3.956 for reference
GREEN
31 RED 1310nm 2.865 0.534 5.364 for reference
32 BLACK 1310nm 1.791 0.534 3.353 for reference
33 YELLOW 1310nm 1.995 0.534 3.735 for reference
34 VIOLET 1310nm 2.478 0.534 4.640 for reference
35 PINK 1310nm 2.06 0.534 3.857 for reference
36 AQUA 1310nm 1.941 0.534 3.634 for reference

Attenuation result must be less than or equal to 0.4 dB/km (In reference to ANSI/NETA ATS 2013 page 192 that the Attenuation loss measurement shall be in
Acceptance Criteria:
accordance with manufacturer's recommendation when no local site specifications are available.)
Note: The Attenuation Test Result is still acceptable given the line is less than 1 km affecting the result depending on the distance of the FO Line.
Test Instrument: AFL /OFL 280-103 UPC Model / Serial No. 2E30PW6808 Calibration Due: 05-Dec-23
TESTING AND COMMISSIONING
FIBER OPTIC CABLE TEST REPORT

F-PMS/CTC-39 Rev 0, 12-Aug-2021


D. POWER LOSS
INJECTED VALUE (dBm) TX POWER (dBm) MEASURED VALUE (dBm)
BUFFER FIBER NO. COLOR Remarks
P = P1-P2 P1 P2
1 BLUE 4.1 -6.44 -10.54 Passed
2 ORANGE -2.21 -6.44 -4.23 Passed
3 GREEN 3.49 -6.44 -9.93 Passed
4 BROWN 0.38 -6.44 -6.82 Passed
5 SLATE -0.04 -6.44 -6.4 Passed
6 WHITE 3.89 -6.44 -10.33 Passed
BLUE
7 RED -1.5 -6.44 -4.94 Passed
8 BLACK -1 -6.44 -5.44 Passed
9 YELLOW 4.54 -6.44 -10.98 Passed
10 VIOLET -0.06 -6.44 -6.38 Passed
11 PINK 8.72 -6.44 -15.16 Passed
12 AQUA -2.65 -6.44 -3.79 Passed
13 BLUE -4.17 -6.44 -2.27 Passed
14 ORANGE -4.17 -6.44 -2.27 Passed
15 GREEN -4.04 -6.44 -2.40 Passed
16 BROWN -4.04 -6.44 -2.4 Passed
17 SLATE -4.08 -6.44 -2.36 Passed
18 WHITE -3.95 -6.44 -2.49 Passed
ORANGE
19 RED -2.59 -6.44 -3.85 Passed
20 BLACK -3.87 -6.44 -2.57 Passed
21 YELLOW -4.04 -6.44 -2.4 Passed
22 VIOLET -4.25 -6.44 -2.19 Passed
23 PINK -4.08 -6.44 -2.36 Passed
24 AQUA -3.91 -6.44 -2.53 Passed
25 BLUE -2.65 -6.44 -3.79 Passed
26 ORANGE -2.21 -6.44 -4.23 Passed
27 GREEN -3.78 -6.44 -2.66 Passed
28 BROWN -4.12 -6.44 -2.32 Passed
29 SLATE -3.45 -6.44 -2.99 Passed
30 WHITE -2.7 -6.44 -3.74 Passed
GREEN
31 RED -2.47 -6.44 -3.97 Passed
32 BLACK -2.93 -6.44 -3.51 Passed
33 YELLOW -3.45 -6.44 -2.99 Passed
34 VIOLET -1.78 -6.44 -4.66 Passed
35 PINK -2.82 -6.44 -3.62 Passed
36 AQUA -3.4 -6.44 -3.04 Passed
Power loss should not be greater than -30 dB (In reference to ANSI/NETA ATS 2013 page 192 that the attenuation loss measurement shall be in accordance with
Acceptance Criteria:
manufacturer's recommendation when no local site specifications are available.)
Test Instrument: AFL /OFL 280-103 UPC Model / Serial No. 2E30PW6808 Calibration Due: 05-Dec-23

Remarks: ____________________________________________________________________
Splicing Loss Result and Power Loss Test are within acceptance criteria
Attenuation Test is still acceptable thru the measured distance of the line.
____________________________________________________________________
The continuity of the cores have been confirmed through Visual Fault Locator.
The attenuation test result of fiber ranging 536 meters which includes
Note 1: ____________________________________________________________________
cable attenuation, insertion loss, and splice loss.
____________________________________________________________________
Tested by: Checked by: Witnessed by: Noted by:

EV CALUAG / DA EBREO RM CUNANAN / JCB IGNACIO MANUEL CHILAGAN JR. JS FERNANDO


MBI/Test Technician MIESCOR- Team Lead Client Representative - NGCP NTD-MSO MIESCOR/ QC-Electrical

R.J. BAUTISTA / J.G. TANCIONGCO JOSEPH CORTEZ PORTIA O. OBIAS


MBI Team Lead/ QC Engineer Client Representative - NGCP NTD-MSO MIESCOR/Project Manager

You might also like