Professional Documents
Culture Documents
Fire Disel Pump Manual Controllers - 20231125 - 0001
Fire Disel Pump Manual Controllers - 20231125 - 0001
.,
$MST&LS&? iC MAruffiffi ffiAML}&fl. TMffi
.r.:iliili+$\ri!r$:""''
a ##ffi,w
a8w 8 ffi
rg WMffi
,*=*,KffiW Nri
-t
E' '_
.::::::::i;*fiiN
l: **N4#d #& M s
vffi&Ki Nrl
='Y=Y=ffiotw
!t 'rl
&
w
$. frrntrm#u*mtimm
@ X. $r:mftmfrf;mt&*m
W 3. Mmnrc il:*mtu$^ffiffi
& 4. h{mrxm
e
ffi
\gl ffi. &$m$^m,ms
d@M
%# ffi. ffimrx$$p*xrmti*ro
M
ffiffi Y. ffimmtmry
ffi m. ffi*rwfrme
ffi
W { ffi. Lmmgffiffi#*
ffi.
ffie
$$. Tmmhr:i*mt ffi#ffi1$$]t#r:t*
GPDV2-Manual-EN v2.2.1.0
1
IVlethods of Starting/Stopping........ 6
lnstallation ..7
FCC Regulations and Radio Standards Specification (RSS) Rutes ..7
Location...... ...7
Mounting ...8
Storage....... ..,8
.,'8
Water Connections ...8
Electrical Wiring .................... ...8
Electrical Con nections ...8
Energy Consumption.................. ...9
lncoming Power Connections ...9
Circuit protection o
Alarms .32
Chargers and Batteries ................. .33
Starter Configuration .................. .34
Sensor Selection .34
.36
3
a. -]
4
#m
ffimtredrumtfr*m ffi
Diesel engine fire pump controllers are designed to automatically start a diesel engine driven fire pump upon
detection of a pressure drop in the fire protection system. A diesel engine fire pump controller provides automatic
& manual starting and stopping. An automatic start is controlled by a pressure transducer or by remote automatic
devices such as a deluge valve. A manual start is controlled by remote manual button or by controller pushbutton.
The automatic shutdown option provides a 30-minute automatic stop after automatic start once all starting causes
have returned to normal. The diesel engine fire pump controller includes two battery chargers to ensure the
engine batteries are continuously charged.
METHODS OF STARTING
AUTOMATIC START
The controller will start automatically on low pressure detection by the pressure sensor when the pressure drops
below the cut-in threshold.
I\,4ANUAL START
The engine can be started by pressing the CRANK 1 or and/or CRANK 2 push button, regardless of the system
pressure, when the Main Selector switch is in the HAND position. The Fuel Solenoid Valve will open as soon as a
CRANK button is pressed and will remain in this state.
SEQUENTIAL START
ln case of a multiple pump application, it may be necessary to delay the starting of each motor when there is a
water pressure drop to prevent simultaneous starting of all motors.
WEEKLY START
The engine can be started (and stopped) automatically at the preprogrammed time
TEST START
The motor can be starled manually by pressing the run test button
E
METHODS OF STOPPING
MANUAL STOP
Manual stop is done by pressing the STOP push button. Note that pressing the stop push button will stop the
engine only if all starting causes have disappeared.
AUTOMATIC STOP
The automatic stop is possible only after an automatic start and this function has been activated. When this
function is Enabled, the motor is automatically stopped 30 minutes (adjustable) after the restoration of the
pressure (above the cut-out threshold) given that no other run cause is present.
EMERGENCY STOP
The emergency stop is always possible in any running condition and is done by positioning the main selector
-switch to the OFF position.
)
t
tnstaBHmtx*n
'.::= This equipment has been tested a.: : c ::'nply with the limits for a Class A digital device' pursuant :c
,
:.1 '5 of the FCC Rules. These limits ar: - - -e::c provide reasonable protection agarnst harmfulcan inter{ere^:e
rad a:e
,', -e r the equipment is operated in a com- = :r-, ronment. This equipment generates, uses, and .
-a: o frequency energy and, if not installe: = - -*.,a: n accordance with the instruction manual, may cause
to cause 'z'*- -
ha'-'-
-:erference to radio communications. Ope-' - -,= equipment in a residential area is likely
-::rference in which case the user will be -=: -?: :3 correct the interference at his own expense'
the -se- s
3:anges or modifications not expressly a:: :: :, the party responsible for compliance could void
-
Location
Thecontrollershallbelocatedascloseas:':--:::otheengine/motoritcontrolsandshallbewithinsg
engine/motor. The controller shall be locate: : " : -=ected such that it will not be damaged by water esca
Dump or pump connections. Current carryr.: :=:: :f the controller shall be not less than 12
in (305 rrr^
'cor level.
-7
rt
Working clearances around controller shall comply with NFPA 70, National Electrical Code,
Article .1 10 or C22.1,
Canadian Electrical Code, Article 26.302 or otherlocal codes.
The controller is suitable for use in locations subject to a moderate degree of moisture,
such as a damp basement.
The pump room ambient temperature shall be between 39'F (4'C) and 104'F (40'C)
1if a temperature option is
included, see the rating labelfor maximum temperature)
The standard controller enclosure is rated NEMA 2. lt is the installer's responsibility to insure
that either the
standard enclosure meets the ambient conditions or that an enclosure wiih an appiopriate rating
has been
provided. Controllers must be installed inside a building and they are not designed
for outside environment The
paint color may change if the controller is exposed to ultraviolet rays for a lonj period
of time.
Mounting
The fire pump controller shall be mounted in a substantial manner on a single incombustible
supporting structure.
Wall mounted controllers shall be attached to the structure or wall using all-four (4) mounting
ears provided on the
eontroller with hardware designed to support the weight of the controlle-=r at a rreight not
less-than 12 in (305 mm)
above floor level. Floor mounted controllers shall be ittacheo to the floor using ail holes provided
on the mounting
feet with hardware designed to support the weight of the controller. The .orniing teet piovije
(305 mm) clearance for current carrying parts- For seismic applications, the mounting
th";";"r;;;; 1; i.
arrangement should be rigid
wall and base only. The structural engineer of record on the project shall be ,".pon.i-ibl" forinchorage
details.
Storage
lf the controller is not installed and energized immediately, Tornatech recommend following
the instructions from the
chapter 3 of the NEMA tCS 15 standard.
Electrical Wiring
The electrrcal wiring between the power source and the diesel engine fire pump controller
shall meet the NFpA 20,
Chapter 12.3.5.1, 12.3.5'2 and 12.2.5.3, NFPA 70 National Electrical Code Articte 695 or C22.1
Canadran Etectricat
Code, Section 32-200 or other local codes.
8
!.
Energy Consumption
Model / State
12OVAC 22Ol24OVAC VDC Output
12VDC / @ No charge
1.0A 1.0A
12VDC/@ Full chargex
6A
13.8V
4A
24VDC / @ No charge
1.0A 0.5A
24VDCl@ Full chargexx
9A
27.6V
6A
Circuit protection
CB'1 protects battery charger 1 and C82 protects battery charger 2. C83 protects the control circuit from battery 1
and C84 protects the control circuit from battery 2
Always follow this procedure when connecting or disconnecting the controller: Connect both batteries before
connecting the AC power. Disconnect the AC power before disconnecting the batteries.
I
Terminal Strip Descriptions
si
:
'{:r, !'il q
s.--j :{...1, ,.Li.,r .. (Dry Contact Only: Voltage Free):
G: Low Fuel Level (NO)
r ;',i :r ., i
V: Belloutput
l!:J
/:'a
Lis i*i W: Test Solenoid Valve
i:tt:'t'1
I i.'i
t1
i.l
X:Analog inputs
Al'1 : Discharge Pressure transducer
iti
z"i: ! l.-.1
llrii Al2: Optional additional Discharge Pressure transducer
ti
i.....i
Al3: Analog lnput sensor (depending on the options)
ti
t:: :]
[:l Al4: Analog lnput sensor (depending on the options)
1:::l Al5: Analog lnput sensor (depending on the options)
Y:AC monitoring
Z: CANBUS: UP to ViZiTouch, DOWN to Exp. lO board
AA: Factory reserved power connections
10
_i
M $erri #
Fh"lge
?'"419 *I,:i*
1:)afr1a A,erp
Ii.{ax Pref;s
f$$G Ftr*
The rating label is the most important label. lt must be read carefully to ensure the compatibility between the
controller and the installation.
a;
:
.-i
'i
]
a
t
***d
H{-#.*e
al
'1
ri.l.:.
I
',{
,l
1t ='
:
\:
c
Verify that the controller is installed securely to the wall, or on the mounting stand (optional). Verify the Main
Selector Switch is in the "OFF" position. This selector switch is also called the "HOA' and can be placed in 3
positions: "H" Hand/lVlanual, "O" OFF. 'A" Automatic.
11
J\n'l
1",1]1, tr*r l] q)
*slstt
KT N]
t.tti
d.q ffi N ffi
ffiW N\\}
$:t ,i.,:,
o*d r-r[ fl
rl I J Iir.-?
r a {a
Open the controller's door and verify that the disconnect switch and all circuit breakers are in the "OFF" position
Verify and/or install the proper water connections for the water input and the drain. They must be securely installed
and tightened. Refer to the silkscreen markings on the plastic cover.
12
!. J
.$jL:)
l !!'::-'i:i''
fv t.
, -'"-- 1
-...:
i:"i
)
**d
'rr Tf'?3
13
*s&
Once the controller has booted up, the "First Start Up" page appears. Press "User Login" and enter a valid
authorization code. Once logged in, press "power,,.
Chrg,1
0.68
Float 13-74 V
Chrg.2
FIoat 13,76 V
The "Power" page will automatically validate the power if no alarm is detected and if the power meets the
requirements. Note: The power validation timer might not appear if all is adequate immediately.
To continue to next step, press " <First Starl Up ".
14
1
iffil.. :
i rffifi s-&t=x $lr- * .ffi
\::
*.-R"-.. i l
-dji..u*.,..,.
s'
: ,..ffi,
iiffii -,,'
"HAND" posltion'
press "Engine First startup" and turn the Main Selector switch to the
engine
has been officiaily commissioned (by an authorized
Note: Before starting the engine, verify that the engine properly'
,"p[."nt"tr" o. ,u'*i.l Oe"aterl and itrat the exhaust pipe is connected
"skip engine varidation step". This selection will be
Note: you can choose to skip this step compretery by serecting
recorded in the logs.
-Pressononeorbothofthegreencrankbuttonstostarttheengine.
e<I
lso E!
I1fi I
1+0 i":1i
151
PSI
t*rtem
15
Press "Pressure".
- Verify that the pressure reading on the screen matches with the calibrated pressure gauge installed
on the
sensing line.
- Choose the desired units of measurement for pressure reading.
- Adjust, if required. the range of the digital pressure gauge at Max. pres.
- lnsert the Cut-Out and Cut-ln pressure values of the fire pump.
- lnsert, if so desired, the cut-out and cut-ln pressure values of the jockey pump.
Note: The jockey pump Cut-Out and Cut-ln values must be set at the jockey pump controller itself. lnserting
these
values at the Fire Pump controller is only for pressure recording data purposes.
Go back to the controller start-up page and press the "Other Configuration" button. Enter the time and date. Select
the "Automatic shutdown" and the duration the pump will keep running after the automatic stop if an automatic stop
is desired. Select the frequency at which the periodic test will occur, t[e day of the week, the hour and the duration
of the test. Also, enter the duration of the Manual Run Test.
16
Mc,m*
f,.her*r:, "l
*t mr
i.:f,*r{*f J
From the "Home" page, verify that the displayed values are correct'
#*ld
*
H*"#s,
preferred
Turn the
,,lVlain
Selector Switch" to the "AUTO" position to activate the "Automatic" mode. This is the
position and from now on, the "Main Selector Switch" should always remain in that position.
17
.\
MK
The "First Start up" is now completed. The controller is fully installed and configured
18
MTm$m'ru ffimmturtr$
The ViZiTouch
::
.:i
a
I
. tt .i: .11
.i
::::::<
l
:
i :: : Y iK
r :
I i 'i.r
:
B il L
Warninq
After 2 years of service, the Vizitouch battery may become less efficient and could lose the time after a shutdown.
Alarm Bell
The alarm bell is activated under default faulty conditions stated by the NFPA20 standard.
Any of these conditions will energize the alarm bell but may be silenced, except in some cases, by pressing on the
the 'Silence bell" button on the Alarms page. When silenced, the alarm bell restarts ringing if a new fault occurs or if
the alarm conditions remain unchanged after 24 hours. The alarm bell automatically stops ringing if alarm
conditions are not present anymore.
Note: Other optional or user defined conditions can also activate the bell and can be configured by the user. See
section 5 and verify drawings affixed inside the cabinet for more details.
First Setup
The First Setup must be done prior to using the controller. Completing the First Setup is the only way to access the
homepage and enable the automatic mode of the controller.
'19
ViZiTouch: Manual Rebooting Method
ti required, here is the procedure to manually reboot the ViZiTouch:
1- Turn OFF all disconnecting means to de-energize the ViZiTouch. The ViZiTouch's screen should turn black
2- Press the stop button or wait until the ViZiTouch's LED extinguishes.
3- Wait 10 seconds.
4- Turn ON all disconnecting means.
lL
20
I L
t-{mffire
{ii-t.*l
|ffii
L :1...jL..J.
u,lilt*+r l
/"nrLLiL
2 [i9
#qtn
.'
3
*nar$ry :
4 ,1-.-'.....t
L::=:J
ijir\ .
5
6 '!1r lr
The home page displays all controller statuses and important values of the controller. This includes all voltages,
currents, pressure, engine state and status, as well as all timers and cranking sequences.
A- Navigation bar: Pressing this icon will open a navigation menu on the left side of the screen:
1- Go to Home page
2- Go to Alarms page
3- Go to Configuration page
4- Go to History page
5- Go to Service page
6- Go to Download Manuals page
7- Select Controller Language
C- Displays the date, time and ambiant temperature. Press on the temperature display to chose the temperature
unit.
D- Battery chargers I and 2'. The state of each charger is displayed by changing the color of the charger icon:
21
I
I
# Gslor'of the box Liuhtnino color Status
,l
Green Green Normalactivities (bellow 2 amps)
2 Green Yellow Charging (above 2 amps)
3 Red Red Failure
4 Grey Grev No AC voltaqe
E- Alternative current status: Red when there is a failure and green otherwise.
F- Ammeter: Displays the actual current between the charger and the battery in amps.
G- The battery: The battery will be red if it is in failure and green otherwise. The data shows the actual voltage of
the battery and the charger in volts.
H- Starter contactor: Grey when non active (open) and green when they are activated (closed) during a crank.
l- Starter state window: This window only appears during a cranking cycle. The counter inside indicates the step
timer, ranging from 15 to 0 seconds. As there are two cranking modes, "waiting for crank" and "cranking", two
symbols will alternate: a gear during cranking mode and an hourglass during the waiting mode.
J- The starter gear: Grey when non active and green when activated during cranking.
K- The diesel engine: lt will be grey if the engine is stopped, green if an "Engine Run" signal is detected and red if a
'Fail to start" occurred, after 6 unsuccessful cranking attempts. lnside the engine two major alarms are represented;
the "low oil pressure" alarm and the "engine high temperature" alarm. These alarms will stop the engine only if it is
running in test mode. When active, the appropriate alarm symbolwillturn red.
L- Fuel solenoid valve: This valve controls the flow of fuel to the engine. When the fuel solenoid is activated, the
valve will be horizontal, green and the yellow representation of the fuel will flow through the entire pipe. When the
"Stop Solenoid valve" is activated, the valve will rotate vertically, become red and the yellow representation of the
fuel will stop at the valve, indicating that the fuel does not flow through anymore.
M- Motor starting or stopping cause: A message box will indicate the reason why the motor is running. Possible
choices include, but are not limited to:
Local: (Optional) This start cause is triggered if the engine is locally started directly from its own control panel and
the option is Enabled.
Manual: The controller receives a manual crank request from one or both of the manual crank membrane buttons
while the selector switch is the "HAND" position.
Flow: Automatic motor starting is activated by a signal in the FLOW/ZONE START/STOP input.
High zone: Automatic motor starting is activated by a signal in the FLOWZONE START/STOP input.
22
Run test. Automatic motor starling is
activated by the run test pushbutton'
R-Controllertype.DrsplaysifthecontrollerisanAutomaticorNon-Automatictype.
S-Shutdownmode:DisplaysiftheshutdownonthiscontrollerisAutomaticorManual.
,?
i
ry
ffi
&#mr$ffis Wffi
Alarms (Menu)
*h.,10*fiJq.==..-*1 : ll L
* bh "1i#+
rflnltr
i$l$t]$i(l$ ,41,l 1,16==dne$# {**v sll turyure {fi6",U8f,Sf
This page displays the list of currently active and occurred alarms. Alarms with adjustable parameters can be set in
the Config > Advanced > Alarms pages (see section 6)
An alarm is called ACTIVE when its triggering condition is still valid.
An alarm is called OCCURRED when its triggering condition has been active, but is no longer true.
Alarms representing serious concerns will have a red triangle with an exclamation point in the center at the end of
the alarm message.
Alarms representing simple warnings will have a yellow triangle with an exclamation point in the center at the end of
the alarm message.
Pressing on the Bell Test button will ring the bell for three seconds.
To silence the bell, press the ALARM button or it will silence itself after the expiration of a factory set time
Pressing on the RESET button will reset OCCURRED alarms only.
Common Alarms. A common alarm is an alarm that is activated when one or more of a certain type of condttions
are active. There are 3 common alarm:
Engine Trouble. Activated when one or more of these conditions are active
- High Coolant Temperature (5)
[ngine Low Coolant Temperature (312)
- Engine Low Oil Pressure (4)
- Engine Failto Start
- Engine Failwhen Running
- Engine Overspeed- (3)
24
:!
Pump Room Trouble. Activated when one or more of these conditions are active
- Fuel Tank Leak
- Low Fuel Level
- High Fuel Level
- AC Failure
- Low Pump Room Temperature
- Low Suction Pressure
- Water Reservoir Low
- Water Reservoir Empty
CTRL Trouble: lmportant: this relay is normally energized when the controller is in normal condition. The relay is
de-energized when controller trouble is detected (fail safe). Activated when one or more of these conditions are
active .
- DC Failure: Monitor the DC power from the batteries and activates if both batteries fail.
- Battery 1-2 Fatl. Monitors the status of batteries and activates on a failure. This occurs when the battery is
disconnected, is of the wrong type or is unable to be recharged.
- Service Required: Activates when service is due for the controller. This occurs when the date set in the service
page has passed, or if no service has ever been done.
- Weak Battery 1-2: Activates if the battery voltage falls below the weak battery factory set point
- Loss of Continuity 1-2: Activates if the engine start contactors are disconnected from the controller.
- Weekly Test Cut-ln Not Reached Activates if the Cut-ln is not reached during a manual or a weekly run test. At
the end of the 20s timer, if the Cut-ln is not reached, the test may still be successful at starting the engine if the
pressure has dropped by at least 5 PSl.
- Check Weekly Test Solenoid: Activates if the pressure does not drop a minimum of 5 PSI during the manual run
test or the weekly test. lndicates a failure with the Test Solenoid Valve.
25
1 - Pressure Transducer fault detected: Occurs if the pressure reading is out of its normal range. Additionnally, if an
optional dual pressure sensor is installed, it will be activated if the two pressure transducers show different
readings. Fufther investigation is advised to determine what caused the different readings. Note that the controller
will always choose the lowest pressure reading to determine the actual system pressure.
- Overpressure: Activates if the analog readout of the discharge pressure goes higher than the overpressure set
:r:int in the alarm page.
- Underpressure: Activates if the analog readout of the discharge pressure goes lower than the "Under Pressure"
set point in the alarm page.
- Low Suction Pressure. Activates if the analog readout of the suction pressure is Enabled and goes lower than the
low suction pressure set point in the alarm page.
- Water Reservoir Low: Activates if the "Water Reservoir Low" contact input (lN3) is triggered or if the analog
readout of the water reservoir is Enabled and is lower than the water reservoir low set point in the alarm page.
- Fuel Tank Leak: Activates if the "Fuel Tank Leak" contact input (lNa) is triggered.
- Low Fuel Level: Activates if the "Low Fuel Level" contact input (lNl) is triggered or if the analog readout of the fuel
level is Enabled and goes lower than the low fuel level set point alarm.
- High Fuel Level: Activates if the "High Fuel Level" contact input (lN5) is triggered or if the analog readout of the
fuel level is Enabled and goes higherthan the high fuel levelset pointalarm.
- Engine FailWhen Running:Activates if the "Engine Run" signal is lost while the engine is running. The engine will
try to start the cranking sequence once again if the starting causes are not back to normal.
- Engine Fail to Start: Activates if the engine fail to start after the complete 6 attempts crank sequence. The engine
willturn red.
- ECIVI Selector Switch in Alternate Position: Activates if the specific 'ECM' (Electronic Control tModule) input (301)
is triggered on the engine connector strip.
- ECM Warning: Activates if the specific "ECM' input (303) is triggered on the engine connector strip.
- ECtvl Fault: Activates if the specific'ECtVI' input (304) is triggered on the engine connector strip.
- FIM: Activates if the specific FIM (Fuel lnjection Malfunction) input (302) is triggered on the engine connector strip
- PLD Low Suction Pressure:Activates if the specific PLD (Pressure Limiting Device) input (305) is triggered on the
engine connector strip.
- High Raw Water Level: Activates if the specific input is (310) triggered on the engine connector strip.
- Low Raw Water Flow: Activates if the specific input (31 1) is triggered on the engine connector strip.
- Engine High Temperature: Activates if the specific "High Temp" input (5) is triggered on the engine connector strip
and the engine is running. A 3 hour timer will start when the engine stops, and if the condition is still present, the
alarm will be activated. This alarm will stop the engine only if triggered during a manual run test or a weekly test.
- Engine Low Temperature: Activates if the specific "Low Temp" input (312) is triggered on the engine connector
strip.
- Engine Low Oil Pressure: Activates if the specific "Low Oil Pressure" input (4) is triggered on the engine connector
r:trip and the engine is running. This alarm will stop the engine only if triggered during a manual run test or a weekly
test.
lo
I
- Engine Overspeed*: Activates if the specific "Overspeed" input (3) is triggered on the engine connector strip and
the engine is running. This alarm will immediately stop the engine and cannot be reset by using the reset button on
the alarm page. The alarm must be reset on the engine itself and the controller must be turned OFF and ON with
the HOA selector switch to complete the reset procedure for this alarm.
- Battery'1-2 Overvoltage: Activates if the voltage of the specific battery is higher than the specified overvoltage set
point
- Water Reservoir High: Activates if the optional "Water Reservoir High" contact input is triggered or if the analog
readout of the water level is Enabled and goes higher than the "High Water Level" set pointllarm page"
- lO Exp Comm Error: Activates if communication with the Expansion lO board could not be established for 15
seconds.
- Pump on demand. Activates when the pressure is below the cut-in set-point on an automatic pressure actuated
controller.
- Engine Run:Activates when the input "Engine Run" (2) is active on the engine strip of the lO card.
- Invalid Cut-ln: Activates when the Cut-ln value is not acceptable. (0 or higher than the Cut-Out).
27
ffimmffrpuxnmt*mr-t
Config
Config (Menu)
#t'.s*rre
fit
, Pressure tr"a*sdr:cer i S{drxh
:llv4.r..::::)]1rjl1:::7s::..lrrs"'(:llr'1
ri i 1q
I nLrSAa'r
i
r
i.. ...i.......,,,,.....-.-",,,:)
ffid$ 1,4c.
# ,{q#,}= rc
** l,&*rsi{x'
User Login:
that only basic settings can be
The padlock icon indicates the current authorization level. A locked padlock indicates
additional settings. An unlocked padlock
changed. press on the padlock to enter an authorization code to uniock
showing an authorization number indicates that some settings are
unlocked. Press on the padlock again when you
have concluded your oput"iion to logout and to save any changes made in the configuration'
Pressure:
of the page'
The main pressure parameters can be set inside the box at the top
mH20'
- Pressure reading: Can be selected as PSl, kPa, bar, FoH' or
- lnput Device: CJn be selected as Pressure transducer 1 or 2
- Maximum Pressure: can be set between the cut-out value and 9999.
Pressure value. (The cut-out should be set
- cut-out: can be set between the cut-ln value and the Maximum
before the Cut-ln).
- Cut-ln: Can be set below the Cut-Out value
Periodic Test:
"every other week" or "monthly". The day of the week' the time of
The periodic Test can be selected as "weekly",
day for the test and the test Duration can also be specified in
this box.
Automatic Shutdown:
pump after the demand dissapears. A timer between 1
lf enabled, the Automatic Shutdown will automaticly stop the
and 1440 minutes can be selected.
28
Advanced:
Go to the advanced configuration pages
NumPad Page
l.aiit,::l)t:tl
Run Test
1....:;-!1,.1
141::.::: j=
-,r','W)i,.W
ii:,
;.rr,,,.t =;iff;jjffiffi
l
ffi ,.,r,,-', ";)!ifiii,,
".
-J.IO p{ !16r,, p
Sun. Mon. Tues, Wrd. Thur" Ffi. Sat.
-t3
*:.t afr ffi ":11
,::,;*: , B 4 #
,1
ct ,X*.
:
1* 1# ,14
15 t6 lfl 19 2[
1l "t,,
2I ?3 ,a W zs #
is ffi :Ir x t ;$ a
Anierics, i',1cntreal
select the Year by pressing inside the year box and enter the value,
or.use the left and right arrows to simply
decrement or increment the value. Likewise, select the month o/ piessing
on the month box and select the value
from the list shown, or use the left and right arrows to cycle throigh
the choices.
once set, press on the proper day to select the actual day, if difiJrent.
The time is set by pressing the two square
boxes under the clock; the left seti the hours and the righi sets
the minutes. press the upoate button to commit the
29
a
,a
LT).;ffiK,ilij :#i.
'.\ A
NN
30
Other KeyPads
The Keypad is activated every time the user presses on a grey rectangle box with white text representing a text that
can be set. The "X" button allows the user to cancel editing the value. The back arrow erases the last entered
generate a
character. Simply click the "OK" button once the value is set. This type of text field is mostly used to
digital text indication for a custom alarm input.
$n {ifilMi \
e4 *un F
{3i4ift{i3.1.A.e-
i.id$.{$$rx
t}artuql$k
l;$yJatq! 6?r€{$'iw*$
xnt<:&m&,$.,*qfter* il{i
$NA?ffi
'' eaaiflks.fra,,'a,{#
m.ratpw_d(, 6p.ffi}-
e **B
\:
This page is the portalto allthe advanced configuration parameters of the ViZiTouch. Pressing on a tab will redirect
to the corresponding page.
31
*
&C r*ili{6&
ffi
: ***ter$ fr f,;ii*,,r
t s*ii:
R f**tr -
.*t#}tr6'rir{lt
tlt**i ii,.
h
::r.,1ffi.i$rti:=L ifi
Most alarms are not configurable in the field, but some are with the appropriate password level. lf it's configurable,
the checkboxes will be in white. Otherwise the checkboxes will be grey. Also, the two last fields: Value Usage and
Analog Value are not always visible.
15**ft::TS#l
E{X**er{:
*laaisu
#${{:x{e,fu&{:*E? lr
@lqr-.l!.,}$ ramm
+:
,I#i#r-.&# x #.
nmarossr@A.fu*ry W l.w{,:
Start Test: The alarm can be tested using this button. This test will only announce the chosen alarm. lt will activate
the bell if the alarm is audible and will activate any output relays associated with this alarm. The test will not activate
other common alarms or other components. To stop the testing, press the "Stop Test" button.
Alarm: Makes this signal an alarm (red display). Otherwise, it will be a warning (yellow display).
Audible: Check this box to make the bell ring while this alarm is active.
e.
Silence Duration. Set the time this Alarm will remain silenced
Annunciate when occurred: Check this box to keep activated any associated relay even when this alarm has
occurred.
Acknowledgeable: Check this box to make the alarm acknowledgeable. lf an alarm is ackowledged, the bell will be
silenced and the alarm lO board Output will stop being active. To acknowledge an alarm, go to the alarm list page
and press the blue "Active" status on the right of the alarm. The "Active" status should change to "Acknowledge".
Timer On: lt is the time delay between the triggering of the condition and the activation of the alarm.
Timer Off: lt is the time delay between the stopping of the condition and the deactivation of the alarm.
Analog Value Usage: lt is used to describe the activation range of the alarm. "Lower Than", "Higher Than" and
"Between" can be selected. The corresponding value has to be entered.
Text: This field can be used to change the name of the alarm that will be displayed while this alarm is active. Note
that changing the factory set name of an alarm will disable any translation of this alarm to different languages.
Hysteresis: ln the "Analogue Value Usage" field, it is possible to chose "Hysteresis Low Setpoint" and "Hysteresis
High Setpoint". Both Analog Low Value and High Value needs to be selected for this mode to be effective. For the
"Hysteresis Low Setpoint", the alarm will be trigger if the chosen signal goes below the "Low Setpoint" and will be
reset when the signal rise above the "High Setpoint". For the "Hysteresis High Setpoint", the alarm will be trigger if
the chosen signal goes above the "High Setpoint" and will be reset when the signal falls below the "Low Setpoint".
X.q*mk mea{#ry a v
t${le&, f?a${ * 4#
X *xx,,.E*:lfuree 1q t6
xx 15 : #:
{
{-}aan;+r Srmrt geiltstft T*xt }llitrvd 1lt
na
This page is used to adjust some features of the batteries and chargers.
Charger 1-2 reference voltage: This is the normal voltage of the chargers in float mode and serves as a reference to
trigger the "charger fail" alarm.
Weak battery '1 -2: Under this voltage, the batteries are considered weak. The alarm "weak battery" is then
activated.
Battery 1-2 overvoltage: Overthis voltage, the batteries are considered in overvoltage. The alarm "battery
overvoltage" is then activated.
Battery missing count before alarm: This is the number of "battery missing" test that needs to be failed before the
"battery failed" alarm is triggered.
33
Charger boost health monitor enable: lf checked, this feature will enable the monitoring of the chargers boost
health
Charger boost health test interval: This is the minimum interval between two charger boost tests.
Charger boost detection threshold: This is the minimum value the voltage has to raise during a boost test for the
test to be consider as a success.
t6ef,ww
tx
8{st: *l}'s' {3&i*w
{.e}**i&s $t6.i?$
This page displays information on the charger configuration. lf more than one starter is installed, it will be possible
to choose which starter will be activated first.
nw{p-.t*,** rs
$,*$#.,..,..,*ry-
W
e*xllp..*ifla [$ b
efl $4*{l ; &e{/{B{$
{asn&#Br $]r*!:etffiBt:X'
lmportant Notice!
Every analog sensor cable used for this controller should be shielded. The shield has to be grounded on the motor
34
its warranty'
side. Not complying to these recommendations may affect the controller good functioning and void
Five analog sensors, an AC voltage sensor, two battery current sensors and two battery voltage
sensors can b.e
to the Pressure Transducer. The other Analog
catibrated 6y accessing this pagelThe Analog lnput 1 is dedicated
lnput depends on the controller options.
**:tri&rxtb*
*l**-r*n{ue
W,,,i;',
A@"c.*
,/lii:isr'
: :: Senssr value
W*.
l. ll t:::::.a::aaiil I :!ii:ii:::-i i :lLll,ril::::::::::3iiii
=
Sensor v*lu*
13r1.:{*.tr-*: ir.dhi.
Every sensor, except the AC Voltage can be calibrated the same way. The Signal destination, the Unit type,
the
Unrt the lVin and Max values are vlriables that are set in factory but the calibration can be made in the field'
There are three ways of calibrating a sensor that can be chosen in the windows below "Sensor value".
-Sensor value: Connect an external measurement tool that is already calibrated (like a Manometer to calibrate a
pressure sensor). Bring the system to calibrate to a low point. While looking at the measurement tool, press the
read button (the button-with i circular arrow). The value that was displayed on the measurement tool when the read
button was pressed needs to be enter in the "Low" window below the Desired value. Repeat these steps with a high
value. Then press compute. For the PTl, only a high value is required'
-Theorical voltage: Use a graphic of the theorical sensor's voltage response (usually given in the datasheet of the
sensor). Enter a low point (value, voltage) and a high point. Then press compute.
For better results, use two points that are far apart, but in the normal range of the sensor.
fr lq$t fiU
$ffi'r,,.'r, + :-fti$*
For the pressure transducer PT1, the low point (zero) is automatically acquired during first power up. lt can be re-
acquired by pressing the blue round arrow. The high point needs to be entered in order to calibrate the sensor.
{};#j**i er*tr?Arll %
Plesi }:fim{llnma 3
tli*del{:it{.41 ilBs
{?irmiit {*ril,:l{lfr 4f
mies@* isffi"5BS
,r.i#l*:#rd- fri
,$i#li{lrs fl{&i$. *
I
s}i*seX flar*{ flunt*c.t*s" t p
This page is used to choose the logic of the signals that will activate the Outputs on the lO board and to test those
Outputs.
'&la*x I i:*t,sffi
The first box from the top is used to change the name of the output. For the output's logic, a combination
of 5 digital
and can be inverted by pressing the
inputs can be selected. Each input can be an alarm or a signal from a list
A logical ANo or oR can combine the chosen inputs and the exit
NO/NC contact symbol at the left of the screen.
can also be inveried by pressing the NO/NC contact symbol at the right of the screen.
pressing the "Test" button, at the bottom of the screen, will change the state of the output for one second' Note:
activating some outputs may cause the motor to start.
{{n # -.3:*;*r:$*,,,i
{,*sh} 3.3,?,}}r
This page is used to update the controller software. A USB key or a network connection with the software update
is
needed
37
F
- *H $rux*1ili*; fi .,,$
t' x#ilx**,**;trJlG
\/ l-* *u*r* ncrroteel r-sttr*iier
, u **#l =*$
LJi{H1t\i
at*l*Wi.*eu,tfi ix
': iF
This page is used to visualize the program version, the serial number and the model of the controller.
Some parameters can be changed on this page, but be careful, modifying a parameterwillchange the basic
operation of the controller. Afterurards the controller may no longer respeit the NFpA standard.
- Automatic Controller: Enable automatic starting causes.
- Pressure Actuated Controller: Enable the automatic controller to start following a pressure
drop.
It is possible to reload a past configuration by pressing the "reload configuration" button. Dates ,'*,,
with an are
settings following a "Service".
Do not change a parameter on this page without previously consulting a Tornatech representant.
*rr,aM*#i*#
$. Sts tix
'4iffi,i@ #ryffiffi,
,#llllgir}m:${rlls f{&rri{ed
$.fi"*fufu *r:'Mywir$.
a_***]
:l:1: r*lw{dC *x &l*{is$r*xt*{:
This page is used to configure the Lockout input and the lnterlock output parameters. To be active those options
need to be assigned to an lnput or an Output on the lO board.
#f3:,$!#
Wn'n,,*N&,
ve*.wiw\
litt.zw& ffi
ira#i#_ffis*
kttr#:Sl#,fi
:::.11f-r,X,,Sry W
U:fj}r'$1#*
'f#.3::{la:L{a#4,,*
This page is for vizualisation purpose only. lt allow the user to verify which signal is mapped on which controller's
input
6iffT&ticX?S$i'ffi
*1eg*l {-xs:d
L&xm;&r*'l {.*r*:'1
]lxrg.ryIi&rqe--{fu&:.4
fisma,r$@
Lg+3{,Eg
r*
This page is used to visualize the ViZitouch and the lO Card registers by pressing on the blue arrows on the right of
the screen Expansion Cards can also be installed via this page.
39
T
rl*tlrx*ii*
,xs t1}i,l&',$,11,{:)l
I? fx*.,. lt4&*ss.*}.:l
rmmSf 1*',"16*.{i":lt1.}
$is$l{ s*ts:l*Fi{ilffi
Airy)iy,
This page displays the lP address, the Subnet Mask, the Default Gateway and the DNS1 -2-3 of the controller. All
those parameter can be changed manually by checking the box on the upper left corner. To apply the change,
press on the blue arrow in the bottom right corner.
40
4
[*imtmry
History (Menu) History
.t* I'l@t&*!r rE?C
{:$em**
t
#p
{.1s{i,er C_}*lTcE
hx$q:{$,{{}ars
k
{4rurp{:larxee {:
g{*tiSJii.1i p
tfuws$kn Bd
This page is used to access all data related to events, statistics, pressure history, power logs and the downloading
of this information via one of the two USB ports.
-Events: This button leads to the "Events" page, which displays the events from the most recent 500 logs. Each
event log contains the date and time of occurrence as well as a brief description of the event.
-Pressure/Power Curves: This button leads to the "Pressure Curves" / "Power Curves" page accordingly, which
displays all relevant pressure/power information from the most recent 500 logs.
-Saved Logs. This button leads to a page where past logs can be viewed.
-Statistics: This button leads to the "Statistics" page, which leads to "All Time Statistics", "First Service Statistics"
and "Last Service Statistics" pages.
-Download: This button leads to the "Download" page, which allows the user to download information, including the
user manual, drawings, logs, statistics and configuration.
41
Events Page History > Events
m-a+**s ffi
S{S,S5, r 1$i3},,i*$. ,@-.sl*ifirllli
Fnil wtldt-l friUxlir6t.-ffifl8,8@
ffi
ffi
ryj&
The Events Page shows the events from the last 500 logs which occurred in chronological order. The first column is
the date, the second one is the time of occurrence and the third column is the "Event message". To obtain a log that
is clder than thoses events, visit the "Saved Logs".
[:] frt in
f k
\ {
lgl Ennlre Rln
2J16.10.-ri
l5:15:24 16:16:14
On this page, a graphic of the "System Pressure", the "Cut-in", the "Cut-Out", the main pump "Engine Run" and the
"Jockey Pump Run" through time can be viewed. By pressing on the screen, the caption will disappear or will be
.Xisplayed. The time scale can be changed by pressing the time span desired on top of the screen (from '1 minute to
2 weeks). The blue arrows on both sides of the graphic are used to navigate through time. The blue button in the
bottom left corner leads to the table used to generate this graph.
42
L*1.,
t ^r4l
.*,
r$ttrlsssr IO: I}H :zE'fsi Q::H[ {.sS,
Pressing
This table allows viewing of the exact values used to generate the Pressure Curves with the precise time.
the blue button on the top left corner will return to the graph page.
1m tlrlr ;\rr ltr lr aii .!i1 5i i] !;lh til :d :Jc 4lJ 5d l'l tlv :'k
4 h
?o16.10.31 2016.10-31
16;15:?4 16116:24
"Battery 2
On this page, a graphic of the "Battery 1 Voltage', the "Battery 2 Voltage", the "Battery 1 Current" and the
orwill be displayed. The
Current';ttrrougritime can be viewed. By press-ing on the screen, the caption will disappear
the screen (from '1 minute to 2 weeks). The
time scale can be changed by pressingit'le time ipan desired on top of
blue arrows on both sidls of itre graprric are used to navigate through time. The blue button in the bottom
left corner
leads to the table used to generate this graph.
I i
ldiIsi{6 .#ti+
II3
13S
S.i.r-r
{!34
it 03A
o,i a
w
This table allows viewing of the exact values used to generate the Power Curves with the precise time press the
blue button on the top left corner to return to the graph page
l{t 1ft*x*,8{1:&.
k4p.20n6,ffi.tsv :-t=+
|oqx;*sr*,*d,,ffir
tuw";*st&dgr;@
h*F,;$W$4"nss
@'i.*x*"d*,u*"
This page is used to access all past log files. Each log file is a CSV file containing the time, the date, the Cut-in, the
Cut-out, the system pressure, the batteryvoltages and currents, the engine run signal, the jockeypump run signal
and the log event message. Each file can contain up to '1 MB of data. The month and year is integrated in the iifle.
At the beginning of each month, a new CSV file is created. Each time a CSV file is full, a new one is created with an
incremented number in the title. Press on the file to consult this content.
44
rt
+
:
2016.11,01
I
4t$frsEf.
20[dl{,[,u:. i*:1rfo
'?flt$:I,n-*l
&,{st}&gn fi:8...*{.-Wl,t,NW..i.#.
?alfrl{st ,r. IrISrlS
701A-11{11 lIr13.!1t", E$*trf Srd ll$llnF{ loFE
2! f:11ts1 :lla {sr
Is1{r1*$} 12.1]r.ro
fsla.11,01 t1:1:ri1i
'?0t6itr1iS'l u,j:I*jre;:B#S fltldtillt Fr::
The logs are arranged chronologically. To select the displayed data, press on the filter icon in the top center of the
screen
v Lvtrt{E
t' ::::}:{*!',:,,+.i*
Biltf*ry'I g*iAass
:: ::::::j]
3:
-.";-:
. ..-.-
. b; -- J/..^-
qrffi_{qr{.rJ@t{e#*
$.11:$g:aciBnrli
1*:-l*<@*q:$r}t..............::ffii$
From this page, the selected values will be displayed. Press on "Log File" at the top left of the screen to go back to
the logs table.
45
Statistic History > Statistics
This page leads to 3 other Statistics pages: "All Time Statistics", "First Service Statistics" and "Last Service
Statistics".
rtti ut I t: --:
tri $sw HHrHuis
*fsa
W 2S1*,{f.}1.1d:15:tl
$nTirne, O.2t:ffi:??
46
i
First Service Statistics Histo > Statistics > First Service Statistics
t: *'='=, .= ;.tr;st*tist s: l.
.t
-
t: r:::- "::i
,= #l*r!r* $s6silii .:0rt6rflfstrli|l{i..-l3:Z?,,: ?ry.
SIl'finre [-23:0$:S
Sfi.:T-l$rB s.ffii$fll14
f.l5rt:Sounl 12
inirlisl i {$-7ps
This page allows the user to view the "First setup statistics". The parameters are:
From:
- Since: Date of the first setup
- On Time: Time the controller spent On, in DAYS-HOURS:MINUTES-SECONDS
Engine:
- On Time. Time the engine spent On, in DAYS-HOURS:MtNUTES-SECONDS
- Start Count: Number of times the engine has started
- Last Started on. Last time the engine started
Pressure:
- [Vlinimum: Smallest pressure value
- [Vinimum Occurred On: Date the smallest value happened
- Maximum: Biggest pressure value
- lVlaximum Occurred On: Date the biggest value happened
- Average. Average pressure since first start-up
Temperature
- [\4inimum: Smallest temperature value
- IVinimum Occurred On: Date the smallest value happened
- IVlaximum: Biggest temperature value
- I\4aximum Occurred On: Date the biggest value happened
- Average: Average temperature since first start-up
Jockey Pump Running
- on Time: Time the Jockey Pump spent on, in DAys-HoURS:MINUTES-SECONDS
- Start Count: Number of times the Jockey Pump has started
- Last Started On: Last time the Jockey Pump started
47
Last Service Statistics cs > Last Service Statistics
${@}
8Ur tr2
P&Y&*iitr#
*rtuiHffi rrlgi?EI
This page allows the user to view the "Last Setup Statistics". The parameters are the same as the
ones from the
"First Setup Statistics" page but from the "Last Service
4B
ffimrw$*m
Service
r !r: iiili liI iilS r i: rfll lilst{ln: E$$iuk{} Iltig -.e-=#., , L *lB
Seat':** *#fi*
\d:
'tit
l-i"# Sirtpr l"
rJ ,i,
3*ch*y', fr xm11 fl qt$*l
The Live View" page is where the user can grant or refuse the remote access demands'
,,Nameplate lnformation" page contains all the information found on the nameplate.
The
The Jockey Pump Cut-Out and Cut-ln can be set on this page'
49
ffimwst*mm# M$mmu"sm$m
Pressing on the question mark will redirect to the download page. A pdf version of the manual can be
downloaded
on an USB device.
50
!
kmn6{.,teffie ffi
E4
ffiffi
?mmh n *m$ fr ffimmu$ $ryTmroflm ffiffi
How to Test:
Charger 1 Fail
Unpower the charger 1 by putting the circuit breaker in the off position.
Charger 2 Fail
Unpower the charger 2 by putting the circuit breaker in the off position.
DC Failure
Switch Circuit Breaker 3 (C83) and Circuit Breaker 4 (CB4) in Off position or disconnect #6
and #g engine wires (See
drawing for more details).
AC Failure
Make sure both batteries are connected and all circuit breakers are in the oN position. switch
the disconnect switch
to "OFF" position.
cl
High Water Level
Put a jumper between High Water Level input and ground (See drawing for more details)
Failto Start
Disconnect #1, #9, #10 and #12 engine wires (See drawing for more details). Start the cranking sequence (Example
Remove Remote Automatic Start jumper). Wait until the cranking sequence ends.
Overspeed
lf your engrne has an overspeed switch, switch it to the ON position. lf not, disconnect #3 engine wire (See drawing
for more details) and put a jumper between #3 and #6. (Note: You don't need to start the engine to activate this
alarm.)
Battery 1 Failure
Disconnect #6 engine wire (See drawing for more details)
Battery 2 Failure
Disconnect #8 engine wire (See drawing for more details).
Weak Battery 1
You need to be logged in to modify these settings. Go to Config>Advanced>Alarms>WeakBattery'1. Change the
Weak Battery 1 setpoint to the maximum allowable.
Weak Battery 2
You need to be logged in to modify these settings. Go to Config>Advanced>Alarms>WeakBattery2. Change the
Weak Battery2 setpoint to the maximum allowable.
Battery 1 Overvoltage
You need to be logged in to modify these settings. Go to Config>Advanced> Alarms>BatterylOvervoltage. Change
the Overvoltage Battery 1 setpoint to the minimum allowable.
53
it
Battery 2 Overvoltage
You need to be logged in to modify these settings. Go to Config>Advanced> Alarms>Battery2Overvoltage. Change
the Overvoltage Battery 2 setpoint to the minimum allowable.
Loss of Continuity 1
Disconnect #9 engine wire (See drawing for more details). Wait 1-2 minutes.
Loss of Continuity 2
Disconnect #10 engine wire (See drawing for more details). Wait 1 -2 minutes
Underpressure
'i'cu need to be logged in to modify these settings. Go to Config>Advanced> Alarms>Underpressure. Change the
Underpressure setpoint to the maximum allowable.
Overpressure
You need to be logged in to modify these settings. Go to Config>Advanced> Alarms>Overpressure. Change the
Overpressure setpoint to the minimum allowable.
Engine Trouble
To activate this common alarm, at least one of the following alarms must be active: Fail to start, Overspeed,
ElectronicControlModule SelectorSwitch inAlternate Position (301), Fuellnjection Malfunction (302), Electronic
Control Module Warning (303), Electronic Control Module Fault (304), Low Engine Temperature (3'12), Low Oil
Pressure, High Engine Temperature, Battery 1 Failure, Battery 2 Failure, Loss of Continuity 1, Loss of Continuity 2.
Overpressure or Low Pneumatic Pressure
WT Cl Not Reached
You need to be logged in to modify these settings. Go to the Config page. Change Cut-ln to 0. Press Run Test button
{Yellow button of the membrane). Wait until the test ends.
Flow Start
Put a jumper between the Flow Start input and ground (See drawing for more details)
Cooling No Flow
Put a jumper between the Cooling No Flow input and ground (See drawing for more details)
Flow Meter On
Put a jumper between the Flow Meter On input and ground (See drawing for more details)
54
i
Pump on Demand
Open the pressure line to simulate a pressure drop. The engine will start and the Pump On Demand warning will
appear.
lnvalid Cut-ln
You need to be logged in to modify these settings. Go to the Config page. Change the Cut-ln to 0. (Note: The engine
will start.)
55
q
1
Patents
CCIu'rit# Title Grant- N<r
CA ica activator for 2741881
US Mechanical activator for r us839978882
CA ical activator for electrical contactor 165512
CA Mechanical activator for electrical contactor 1 6551 4
US Mechanical activator D803794
US activator for electrical contactor Patent pendinq
EP Mechanical activator electrical contactor 002955393-0001 /2
AE Mechan ical activator for electrical contactor Patent pending
AE Mecha activator for electrical contactor Patent pendinq
CA Fire ital 163254
US Fi d ital interface D770313
AE Fire interface Patent pending
EP Fire pump diqital interface 002937250-0001
CA and method for failure in a sensor of a fire Patent pending
US and for failure of a re ina Patent pending
56
n
Note Th IS d oc u ment shou td be an indication of whether or n ot th e instal lation and general condition
of the equ ipment IS adeq uate for a field acceptance test. This document S h ould a lso a id the ind ivid u a
respo nst bl e for executing the fi eld acceptance test to decide whether or not to carry out the field acceptance
test of the u ment.
lnstallation Check List: YES NO
Ve rify h at the namep ate voltages of the Fire P ump Controller corresponds with the AC
1
VO e a'VA able an d the DC of th in
Visual tn spection fo an v damage to the exte rio of the Fire P UM p Controller, Make S ure
2
the en clos ure Iarm bell selector switch m em b ran and are not
Verify th at the F tre P UM p Controller h been nsta led with tn sight of the pump and
3
A ne or m otor.
Verify that the Fire Pump Controller has been installed not less lhan 12 inches from the
4
floor of the mechanical room.
Verify that al electrical CO nnections to th e Fi re Pu mp Cont ro ller a re d one usrn g lqu id
5
condu it an d conn ectors
with th A Fi re Pu m p Cont ro ler doo op e n, visually nspect for any d n chi ps, di rt or
6 foreig n o bjects n the bottom of the encl osu re, oose WI res, broke n com ponents and
electrician workmans
Verify that th e correct AC voltage S suppl ed to the contro ller by tak ing voltage
7
readi at the L & N 2 or L & L2 term inals
Ve rify hat the termi na con nectio NS between the F re Pu mp Co ntroller nd he engine
I 1 to 1 2 a nd 301 303 305 1 J 1 31 are done.
Ve rify hat rin s to term nals #6, #8 (batteri es) an d #1 (g ro un d) are of the appropriate
9
au srze See la bel in side co ntroller.
10 roundi of the Fire Pum Controller
lnitial Power-U Check List: YES NO
1 that the selector switch is in the ition
with the F re Pu mp Co ntroller door open, turn to "oN' he ci rCU it brea kers C B3 an d
2
cB4 D C then C B and C 82 then S 1 Th is is nt.
Close the Fire P um p Control ler door rify on th e ViZiTo uch Homepag e that the
3
co rrect batte
Place the selector switch in the " HAND" position. Verify that no alarms are displayed
4 on
the screen.
Place the selector switch in the "AUTO" position. Verify that no alarms are displayed
5 on
the screen.
M a n ua I a nd A utomatic Start Chec k List:
YES NO
1 Place the selector switch in the "Hand" ition.
Verify the starting of the engine by pressing th e "Battery # 1 Manual Crank" membrane
2
button.
3 the eb the SC I ector switch to t he o FF' osition
Verify the starting of the engine by pressing the "B attery # 2 Manual Crank" membrane
4
button.
5 the ine the selector switch to t he o FF' osition
Set he C ut-Out and Cut-l n setti ng q by fol lowi ng the Vizt-l ouch docum entation You
6 need to be logged rn to mod itv these setting S, Verify the automatic start by d ropp ng the
re below the Cut-l n sett
Stop the n s ine by p resstn g the "Stop p ush button Note Th eng tne wi nly stop if
7
he ressure is above the Cut-O ut settin
57
)
Company:
Date:
Witnessed By:
Comments:
58
t f
Note: This d ocument is the Tornatech official Field Acceptance Test report which follows the latest NFPA 20
requirements of article 14.2.6 Controller Acceptance Test pertinent to diesel engine driven fire pump
controllers. Tornatech strongly recommends that a pre-field acceptance verification (Tornatech document
GPD-PREFAT-001-E Pre-Field Acceptance Test Check List) be completed before this official field acceptance
test.
Complete this first section if it was not completed du ring the Pre-Field Acceptance test
Manual and Automatic Start Check List YES NO
1 Place the selector switch in the "Hand" position
Verify the stafting of the engine by pressing the "Battery # 1 Manual Crank"
2
membrane button
3 Stop the engine by placing the selector switch to the "OFF" position.
Verify the starting of the engine by pressing the "Battery # 2 tVlanual Crank"
4
membrane button.
5 Stop the engine by placing the selector switch to the "OFF" position.
Set the Cut-Out and Cut-ln settings by following the ViZiT ouch documentation. You
6 need to be logged in to modify these setting ;s. Verify the automatic start by dropping
the system pressure below the Cut-ln settint g
Stop the engine by pressing the "Stop" pushbutton. Note: The engine will only stop
7
if the system prqssure is above the Cut-Out setting.
#1 YES NO
1 3 manual starts
2 3 automatic starts
3 1 RUN TEST start
4 1 remote/deluge valve start
5 Start and Run the engine at full lpeqd after 1 crank cycle
Battery # 2 YES NO
1 3 manual starts
2 3 automatic starts
J 1 RUN TEST start
4 1 Lemote/deluge valve start
5 Start and Run the ine at full s after 1 crank le
Visual/Audible Alarm Verification YES NO
Battery failure:
- on the terminal strip, disconnect wire #6 for battery1. wait for the alarm, then
reconnect the wire.
- on the terminal strip, disconnect wire #8 for battery2. wait for the alarm, then
1 reconnect the wire.
- Audible and visual alarm will appear for battery failure and controller trouble.
Note: it is important to return the wires back to their original place and reset the
alarms in order to continue the tests.
the engine will not shutdown. To shutdown, turn the selector switch to the oFF
position.
- lf the engine was started automatically, a visual and audible alarm will be present
and the engine will not shutdown. To shutdown, turn the selector switch to the OFF
position.
- Note: Please remove the jumpers and reset the alarm in order to continue to the
next simulation.
Engine Overspeed:
- Staft the engine either manually or automatically.
- with the engine running, place a jumper between terminals 6 & 3 or simulate
overspeed from the engine.
- An audible and visual alarm will be present and the engine will shutdown whether
5
it was started manually or automatically.
Note: Please remove jumpers and reset the alarm in order to continue to next
simulation.
Note: The speed switch must be reset on the engine itself.
Cut-ln Pressure:
60
Weekly Test Enabled?
Ala rm nections:
Selector in OFF or HAN D connected?
_
Yes No
Engine Run connected?
_Yes _ No
Engine Trouble connected? Yes No
lnstallation address:
Company:
Date:
Witnessed By:
Company:
61
W
'vfl
r
I
I
tr ,.^^^^- - -
--i, WFE r1:" ,
Name:
Adress
) Phone
raK.
)
cl€c(-4-<q({(q€-e-q(se-R-<sps\s\B\\\\\\\\\ssR=.S-_
Product
Model .
DIESEL ENGINE FIRE PUMP CONTROLLER
cPD-12-220
I
f
Serial Nuncei' WD1 143364
Ou'oroleci 1A07Mg
@
12VDC Negative Ground IVodel.GPD
Wiring schematic Built to the latest edition of the NFPA 20 standa D 1 143364-51
\ tsl
1N
N ------o N
208-240Vac
50-60 Hz
-j- 1L
F1
C82
>\
BC1
Charger 1
BC2
Charger 2
14
L -- LL'
LN
E
CB1
E ;i! >-. 13
\-*-*-P^6-
Fg ! g-6 Po Pna Eqa
d:IO ndo
oo 6 r'\ o
6 q o;a 6 d-N d*,^ do.
o O-" o= -
-!L
EB A-
o oo ON a9
o:
8
d 65 o i5 d= i--
o o o ooo
F
o
Fo F
o ;;;
tsFF
To l/O Diesel
Board
V[,lBl
UP
(P.2 i D4)
(VfZt" :ro,v=aan1,/ )
@ : lluo
tt-/t
L
J14 J4 J5
Selector Switch
OFF
H --t--
'+-
JI 30
AUTO
31
l
iesel Engine Fire Pump Controller DRAWING No.
@
12VDC Negative Ground lModel:GPD NUMBER
Wiring schematic Built to the latest edition of the NFPA 20 D 1143364-51
@
P-
SV1
O: O:
,9g
Sens ng
o o
dC >-' >..
F [_-
=o
o:
O- o-
o: c84
(P.1 I F7) CB3
t, T_- -t
VMBl
15 16 17 18 / tg zo zt zz\
62 11 11 82
=
', 1l
+< +< +< +a I +a r
@ -tr, ft B
I : ti t, i, n I r, lr
N
J50 J24 J16 J14 J15 J17 J1B J44 i4 J 106 J1A7 J105
r
a,/
L
I
L. t-
I I I I I I I ll
I l l I I l I ll
A6
I
I
I
I
I
I
I
i
a ?t l 6 6 6 6 ,t- 6 (;) (;,r (:)A o) I 1 f
@ €,
l III
(, GJ (s)
,r--
I
.s-.a.
1
I
I l
."""k
I I
(\9 I
I
I
o&
,l
.1."'""J ,s o'
I I
,r.
.b-6e' ,"d" ouooo ^t""- €"""- L L L L_ s"'"e *" ""P
"-c d3
4rs- od 6 3 6
"t" .a
oY I !
;" .s ""-
as 9
a
i e\'
a9-
6 a,'$
=
p
. .It-
': 2020 rrite.r k.. r .lhr,-:.,.d Ii i d:ai,-! ro ri r.mriil::.".ei I o:p ilej r': ,a,? r: ah prr:.r.rT.n;r.i h. 14
L1p!.Sht
.J
.-
+
I
P.3
NUMBEF
Terminals diagram Built to the latest edition of the NFPA 20 standard D 1 143364-51
No mallv Cloled
l/O D esel Board
50 60Hz
N >---- - o
S1 L-.rc-
Normally opened f
ore* i" a", i NO
ararm I
L{liG-- ,J1
E
.a
closes to
Nomally Clos-"d
NC
l TB1
I 9l Water ReseNo r LDw
LT__
T
E
t Normally opened f opens to dlam 1
NO
c
I
to al6rm I
I closes I NC
Engine Connections L
L Normally opened
Closes to activale
NO
L _t J
C
All w r ng beMeen the contoller dnd d eset eng ie :,ha I he stranded ( NFPtr!l ,ri NC
TB2
r lkrrr,,,1,, r,)l ,r. lrl rn4 305 310,
Wrtrr.lt)rlwFir1. )rLiLie,,il!1,!)Ll
ill 3l;.1' I | |lrrnr.lliLr//l|AWLi,r;frrr rr| Network Connections Clos€d
NO
,ie,r,n,l, I l. 1r l(l r,,n,,l nl l(rAll r,(,: [ ,l r r],. p (rAWi i i,r fr r rrt l Slrielded Female Connector RJ.15
Normallv Opened ,
NO
Closes lo alam
Closed f _l
.l
Wrn{tr,tu(,,,rr:{r1irl[,r,r](l,,fqrr.(l.rrrni,il; lt ll r.rlo\l llrAl) fLr,lb(i Lo.ated on lrain Board Normally C
,i1,a rLl,,l ,,rr(l , /,rl ,,i..!rl n! lo L,li,f,.u opens ro alam I
I\/odbus TCP/lP HOA in OFF/HAN
Normally opeoed f
NA
NO
/C D esel Board
Normally Clos6d
Closes io 6lam 1
!t{t s!1elold, f C
lo J104 opens to alarm I NC
t, J104
NO
J1A4 { c
NC
oil Eng ie Trcube
(1t--
^
Low Pressure
J104 NO
{ C
er-
a H sh Engine Temperature
J104 NC
@!e{"r1 Jl04 NO
( 8.1 JIA4 t C
NC
Sta I Conta.tor Pump Room Trouble
(",r
- - l
J104 Normally
Closes to
op€ned l
dam I
NO
AStad Contaclor 2
Normally Closed T
C
Ground
\'t------
- -- 11 J104
/, \Cround 11 J104
lr2f-1---:
-
Fn.rdrTc to SrDn 5.len.ri
ffi,ro+
a Fleotror c Corflol VodLl€ S€l€ctor Sw.tct 1 Alt€aals 006 tion
i:l----------
("r--------------
G Eleckohic Conkol Modul6 Warning
t
a Elecl.o. c Lorlrol Module tarill .E
\-)
@)DrDrow 305 g
g
@ 310
g-r----------
6 Low RBw WatEr Flow
311
a Engino TsmpoBturu
Low
trt---------
I l
-1
P.4
T
lalalt4
BC1
@
.ffi
ffi
BC2
F1
[760]
17a")
2A-7 te t7341
DB1
W
SS1
Etr
@
lnternal Layout
. ilil Des qnaton
BC1-BC2
cBl C82
B-y,'p cg3-c84
3+r DE]
ENC]
Sens. Line
1/2 " F.NPT
tsl
Drain 3/8 'F.NPT
svl
VMBl
3-112'
1t'13
e-/"'
t I
I I
( L _l
lffil
Paint: Textured Red RAL 3002 - Seismic l\,4ounting to be Rigid Wall Only.
L ,.1
it
-Wiffi.{s
i\ilg"l!:;::"'''* '
Ul oiiel
ltring
!T!&?A 4rtr?t-4016'
:in i.3
VALUE$
1
A(tivati0m I
1 WeeAilr le3t Requir&d
: Br{er! i irririrq I Ca*lih(n No fbw
41$81 3 ?,^llt\y 2!ii,iit!t: &1t)8? 3 Esgids Fail Wh€fr Fiueni*g
4 flhnr66.1 i:ii;!r,: 4 Euqifis Fail to Sk{1
S Charg{x'? ir;i,:rr€ 5 lim8ine t]v€rsFsad (]]
$ fngine lfr,!,t.: 6 lJo Sigeel Eoa.d tdmmsn;iation Less
7 Prlrp Rn!!:r !il; ,. , fO Expan$iofr l C*mmu6ic$fioi Lsss
I tloEtoiler'i i ,, tj,l € li$ Lnpansion ? Coilthruniciticn La$*
I serlrr:.. Re!r1iir?l B liQ flxpansioo ] CanuuunicaljDn Lus$
1a *"ak Ba1rty \ 1g ,J8 Expafisisfl $ r:smmunicttjrfr Loss
11 lt€il Fert.r'. : '{, }i* Alatm Communistiin i o.s
12 i.*.. tt arrnair)i... l.r1tr.toi 1l 'lI Lop Aftiliqni Temperah,re ilntarflal $snsgr)
1
j, f-;]\s s1 i:.jrt;rijit atr,i,).1*r Sl
13 EnghrB Rri6
14 l'!ial,y 'i?st i:!:1.,. r.:i r;rried n4 CANEUS Cotcetunjcalior SysieJr Failuru
Silerrid lln Dar!*nd
EINARY I YlraterRescrvsirlaw
: Prien{nrlir i4 I ir.::r'i Z $la&r {€sesoir Efipl!
I A.tb.ilrl" g\e.:.. 4i004 3 Ytater Ressrveir lligh
I F\jl/ar1* f ali 1. :..I - 4 Flov freter Of
5 ii.li *!irin,arl 5 FuDl }ank Lent
ti APSAiI GsIrrr :':'i:il
S Low Frel La{el
7 (J',ti\pteat*r
i Hiqh Fu{"j Lsvel
I Underprri.rr! {l ElecXronir Conlro' Module in A,lsymete FesitiDn
$LodsurJirif -. - I Frel i*jeflion Mal{uh6ti6n
10 Eff(idB &ligh T€nlpsratrB
I n Ergiffe [-*w felrip€ratur€
1: Bnli*r.". 2 Slr.i,ri:.: l? Ef,EinF Elecilonic Conkol,fodtr!€ 11,;rnihE
1X *igli Lrttoittl 1.,-:-.:i::e itnternni Se. :.1 'i3 Engine Eleclrsnic aoillrol frlodule Fa!:t
14 6s$ine Low oii Fresssr+
Va,ve Ope.
a:illtn ! 1 UiarAl6ml 1 fiY 'n UserAlnm J?
I Ura{ A.1affi 1. 2 UserAl6m 1t
4t{{i* ] Urqi i,lamt 3 4!04{ 3 UserAiam 19
4 3$erAldrst 4 4 l]*r Alam 28
5 Us€r Alaffi S 5 N,A
6 U$a[ A{a.fi 6 6NA
7 User AlarNn ? 7 N.A
d UlEr Aiaml I EHA
$ Liser Alaffil I g H{h Rm t4r.ter Temperaturu
1* UserAiam l0 ,O PL]O Low Sqctia, Pressilre
11 Llr* Alant 11 ,1 LffllydEulic Press{re
1? *s€rAlenB lt 12 IO Exp?ffiion 5 cotrhtrflicarisil Los$
'i: *ser Aleffi '1.:
J3 lio Expensisn 6 Comm{sirat,on { Dss
14 Us€rilam J4 l4 YO Expafision ? {"0mmun;cdio4 Loss
ia uSeI aiam t5 15 lio
Jt:*-j,f,a:ii
Rf 2
'1*A*t*
Batert
VALUNS
LttS
NA 4?t10 NA
,,loRD 42t11 NdA
YAIUE$
lYu1fll42Clt
v&l.r.tEs
I I
ffi wffiww&Kr:ffir-
P&ffiYffi LfiS?
w.ffi": pffi-ss-*#s#1$4SS-.f
&*ferer"l** : part*
$pK...
Fart mr*mhsr
r*uit. *r*a\{^*r
eB3-C#4
4 ,l
ffiatte,t-g *f"la rgen h*srd ts0.!-mffi2 B*wL*vsss{
w tz.t i r"l*e*W
VNfiB,!
t I
H&_mTCIR01s$
?.ra**du**r PT,i 1
G$ffisfri"{0**s
tf* ffi*ard 1 ,,
*ffi.1
f;I-ffiTffiffitrffi3#
vaXv* t I ,I
$v{ $*a-GffiAossr ,l
*hmrg*r fe;;**w x
2
4 4
l4:j
.l . -_.
A*H*ri*ms
Tr:rn*l**h 1n*. {H*ad fiff i**}- L*v*{, $*ei:**, **ria**
Iql.: + 1St4 334 *$33
T*{l{r**: + i fi** }$3 $*i.}S
ilur*pc
T*rncl**h ilur*pe SpffiL - !Vovr*, $*lEi*m
T*1.: + 32 {8} }0 84 4il fil
l'{iddl* tmst
T*rrretmh fXf, - Suhai- U*ited &r*h [r"*]r*t*s
Tei.: + $?1t#)q 8S7 SS15
Asia
Tornatech Pte Ltd. - $ingapnre
Tel.: + EE 57SS $114
T*1.: + S1$?g$ 7*?}
a\
i
-11
WYffiffiru tuTxtffi
i ! "l r!1- li- il
-
$*