Professional Documents
Culture Documents
CB78OlCB784
hstdlation and Operating Instructions
The Cleaver-Brooks CB78O/CB784 is a microprocessor
based integrated burner control for automatically fired
gas, oil, or combinationfuel single burner applications. The
CB780 consists of a Relay Module and Keyboard Display
Module. The CB784 consistsof the Relay Module only. The
Keyboard Display Module is optional with the CB784. Sub-
base, AmpliJier,and Purge Card are required to complete the
system. Options include Personal Computer Inte~ace,Control
Bus, Remote Display Mounting, First-Out Expanded Annun-
ciator and Combustion System Managment software.
The CB78O/CB784 is programmed to provide a level of
safety, functional capability
and features beyond the capacity
of conventional controls.
Functions provided by the CB780KB784 include auto-
matic burner sequencing, .flame supervision, system status
CB-7803
CB780/CB784
SPECIFICATIONS
Specifications
ELECTRICAL
RATINGS,
Table
see 1: Dissipation:
Power
Voltage and Frequency: 120 Vac (+lo/-15%), 50 or CB780/CB784: 1OW maximum.
60 HZ (+I- 10%)~. Module:
Display 3W maximum.
KeyboardDisplayModule: 13 Vdc peak full wave Maximum Total Connected Load: 2000 VA.
(+20/-15%).
rectified
Fusing: Total Connected Load: 20A maximum, type
FRN or equivalent.
CB-7803 2
CB780/CB784
SPECIFICATIONS
ENVIRONMENTAL
WEIGHT: RATINGS:
Temperature:
Ambient
CB780/CB784: 1 pound unpacked.
10 ounces,
Operating: -40°F
140°F.
Keyboard
ounces,
unpacked.
Display
to
Module:
4
Storage: -40°F to 150°F.
Humidity: 85% RH continuous, noncondensing. IMPORTANT: Flame Detection System available for use
Vibration: 0.5G environment. with CB78O/CB784. To select your Plug-in Flame
DIMENSIONS: Refer to Figs. 1 and-2. Signal Ampl@er and matching Flame Detector, see
Table 2.
II I I
Failure
Part Response
Type Color Self-checking Time Number
Infrared Red No 833-2722 3 sec. Gas, oil, Infrared 817-1742
coalfiel (Lead Sulfide)
Type part
Number
833-2723' Gas, oil, Infrared
Dynamic Auto-Check coal (Lead Sulfide)
Self-check Check
I I I I
Peeper)
aThe 817-1743 Flame Detector should be used only on burners that cycle on-off at least once every twenty-four hours. Appliances with
burners that remain on for twenty-four hours continuously or longer should use the 8 17-1121 Flame Detector with the 833-2741 Amplifier
as the ultraviolet flame detection system.
Circuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute during burner operation
and shuts down the burner if the detection system fails.
Circuitry tests the flame signal amplifier 12 times a minute during burner operation and shuts down the burner if the amplifier fails.
JIlV9AO.AF.
No.
APPROVAL
Report
approved,
Mutual
Factory
BODIES:
Underwriters
Laboratories Inc. listed, File
No.
MP268,
IRIacceptable.
Communications
Federal
MCCZ.
No.
Guide
Commission,
Part 15,Class B-
Canadian
Standards
Association
certified,
LR9S329-3.
Emissions.
3 CB-7803
CCB780lCB784
SPECIFICATIONS
Fig. 1-Mounting dimensions of CB780/CB784 Relay Module and 833-2725 Subbase, in inches (mm)
I I
0 ALARM l
5-1/4 (133) I
5 (127) c
CB-7803 4
CB780/CB784
SPECIFICATIONS
-1
(102) 4
3-1/2 (89)
detector.
2-3/4
I
-LCOLLAR WITH 1/2-14 NPSM M7419
INTERNALTHREADS
817-1743
7
I HEATBL7K
CELL MOUNT
1-5/8 (41)
1- 1 -1/16 (27) +
FLEXIBLE CONDUIT
BUSHING WITH NPSM INTERNAL
MAGNIFYING LENS COLLAR, 3/4-14 NPSM THREADS
INTERNAL THREADS Ml9EPA
81 7-1 742
833-2727
(Standard with CB780, optional with CB784)
817-1121
5 CB-7803
PRINCIPALTECHNICALFEATURES
CB-7803 6
CB780/CB784
SAFETYPROVISIONS
Safety Provisions
INTERNAL HARDWARESTATUS MONITORING DYNAMIC SELF-CHECK SAFETY CIRCUIT
The CB780KB784 checks the purge card for correct The microcomputer tests itself and related hardware
parity to prevent purge timingshifts and circuitry failures. It while atthe same timethe safety relay system tests
the micro-
also analyzes the integrity of the configuration jumpers and computer operation. If amicrocomputerorsafety relay
internal hardware.ThePOWERLED blinks everyfour failure occurs and does not allow proper execution of the
seconds, signifying an internal hardware check. self-checkroutine, safety shutdown will occur andall safety
critical loads will be de-energized.
CLOSED LOOP LOGIC TEST
The test verifies the integrity of all safety critical loads, EXPANDED SAFE-STARTCHECK
terminals 8, 9, 10 and 21. If the loads are not energized The conventionalsafe-startcheck, which prevents burner
properly; i.e., the main valve terminal is powered during start-up ifflame is indicated at start-up, is expanded to
PREPURGE, the CB780KB784 will lockout on safety shut- include a flamesignal check during STANDBY, preigni-
a
down. The CB780KB784 must react to input changes but tion interlock check, aninterlock check, and a safety
critical
avoid the occurrence of nuisance shutdown events. Signal load check.
conditioning is applied to line voltage inputs to verify proper
operation in the presence of normal electricalline noise such HIGH FIRE PURGE ANDLOW FIRE START
as transient high voltage spikes orshortperiodsof line SWITCH TESTS
dropout.Signal conditioningis tolerant of synchronous noise High Fire Purge Switch Testexamines the Purge Posi-
(line noise eventsthat occur at the same time during each line tion Interlock Switch atthe moment the firing rate motor is
cycle). commanded to the high fire position. If the switch is by-
passed, welded or otherwise closed prematurely, the system
DYNAMIC AUTO-CHECK will automatically add 30 secondsto allow additional drive
DynamicAuto-Check circuitry tests the flame signal time for the firing rate motor to reach or near the open
amplifier during burner operation shuts
and down the CB780/ position before starting the purge timing; otherwise, purge
CB784 if the flame amplifier fails. timing starts when the High Fire Switch is closed. This
switch will also cause a hold (four minutes, fifteen seconds)
DYNAMIC FLAMEAMPLIFIER AND SHUTTER condition when the switch is open before purge or opens
CHECK during purge. The CB780KB784 will lockout and annunci-
Self-checking circuitry tests
all electroniccomponents in ate an alarm ifthe switch fails to close within the hold time
the flame detection system andamplifier 10 to 12 times per period.
minute and shuts down the CB780KB784 if the detection Low Fire Start Switch Testexamines the Low Fire Start
system fails. Switch at the moment PREPURGE is completed. If the
switch is bypassed, welded or otherwise prematurelyclosed,
DYNAMIC INPUT CHECK the system automatically adds 30 seconds to allow the firing
All system inputcircuits are examined to verify that the rate motor additional time to reach or nearthe low fire start
CB780KB784 is capable of recognizing the true status of position before ignition trials; otherwise, ignition trials start
external controls, limits and interlocks.If anyinput fails this after the Low Fire Switch closes. The test also is used to prove
test, a safety shutdown occurs andthe fault is annunciated. that the firing rate motor is at low fire position throughout
the ignition trial period. This switch will also cause a hold
DYNAMIC SAFETY RELAY TEST (four minutes, fifteen seconds) condition the if switch opens
Checks the ability ofthe dynamic safetyrelay contacts to after purging is complete. The CB780KB784 will lockout
open andclose. It also verifies that the safety critical loads, and annunciate an alarm theifswitch fails to close within the
terminals 8,9,10and 21, can be de-energized, asrequired,by hold timeperiod.
the Dynamic Self-check logic.
7 CB-7803
CB780/CB784
SAFETYPROVISIONS
CB-7803 8
CB780/CB784
INSTALLATION
Installation
9 CB-7803
CB780/CB784
INSTALLATION
Fig. 6-Internal block diagram of the CB780KB784 (see Figs.7,8,9, or 10 for detailed wiring instructions).
L1
(HOT)
L2
CONFIGURATION
FLAME SIGNAL
STATUSLEDs
R PRE-IGNITION
INTERLOCK
LOCKOUT
w
PILOT
3K1
ALARM
RS485
t INDICATES FEEDBACKSENSING
TO RELAY STATUS FEEDBACK
AND LINE VOLT INPUTS
DDL
COMMUNICATIONS
-FIELD WIRING
RESET INTERNAL WIRING
CB-7803 10
CB780/CB784
WIRING
Wiring
1. a. For proper subbasewiring, refer to Fig. 7. important. Be aware that modules on the closest
b. For proper remote wiring of the Keyboard Dis- and farthest end of the daisy chain configuration
play Module, refer to Fig. 8, 9 or 10 or to the string requirea 120 ohm (1/4 watt minimum) resis-
Specifications for the Keyboard Display Module, tor termination across terminals1 and 2 of electri-
Communication Interface Base Unit or Control cal connectors, for connections over 100 feet, see
Bus. Fig. 8 , 9 and 10.
2. Disconnect the power supply from the main discon- Remote Reset-Use no. 22AWGor greater
nect beforebeginning installation toprevent electrical twisted pair wire, insulated for low voltage; see
shock and equipment damage. Morethan one disconnect Fig. 8,9 and 10.
may be involved. Communication Interface ControlBus Module-
3. All wiring must comply with all applicable electrical For communications purposes, use an unshielded
codes, ordinances and regulations. Wiring, where required, 22 AWG 2-wire twisted cable if the leadwire run
must comply with NEC, Class1 (Line Voltage) wiring. and noise conditions permit or use a Belden 8771
4. Recommended wire size and type: shieldedcable orequivalent.TheKeyboard
a. All Line Voltageterminals use no. 14 or 16 cop- Display Module,Control Bus(for remote mount-
per conductor (9OOC or higher) 600 volt insula- ing or communications) or Communication Inter-
tion wire (wire size must be coordinated with fuse face ControlBus Module must be wiredin a daisy
protection). For high temperature installations, chainconfiguration, (l(a)-l(a),2@)-2@),3(c)-3(c)).
use wireselected for a temperaturerating above The order of interconnection of all the devices
the maximum operating temperature. All leadwires listed aboveisnotimportant.Beaware that
should be moisture resistant. modules on the closest and farthest end of the
b. KeyboardDisplay Module-For communica- daisy chain configuration string require a 120
tions purposes, use an unshielded 22 AWG 2-wire ohm (1/4 watt minimum) resistor termination
twistedcableandonewire for groundif the across terminals1 and 2of the electrical connec-
leadwire run and noise conditions permit; how- tors, for connections over 100 feet, see Fig. 8,9
ever, some installations may need up to five wires, and 10.
three for communications and two for remote reset Use the recommended wire size for the 13 Vdc
(in eithera single cable or separate cablesfor com- full wave rectified transformer power input of
munications or remotereset) or useBelden 8771 no. 18 AWG wire insulatedfor voltages and tem-
shielded cable or equivalent. The Keyboard Dis- peratures encountered in the application. Sug-
play Module, Control Bus (for remote mounting or gested wire types include TTW(60C), THW(75C)
communications)orCommunication Interface and THHN(90C).
ControlBus Module must be wired in a daisy chain 5. Recommended grounding practices:
configuration, (l(a)-l(a),2(b)-2(b), 3(c)-3(c)).The a. The earth ground provides for a connection be-
order of interconnection of all the devices listed tween the subbase and the control panel of the equip-
above is not important. Be awarethat moduleson ment. The earth ground wire must be capable of
the closest and farthest end of the daisy chain conducting the current to blow the 20A fuse (or
configuration string require a 120 ohm (1/4 watt breaker) in event of an internal short circuit.The
minimum) resistor termination across terminals CB780/CB784needs a lowimpedanceground
1 and 2 of the electrical connectors, for connec- connection to the equipmentframewhich,in
tions over 100 feet, see Fig. 8,9 and 10. turn, needs a low impedance connection to earth
c. Control Bus-For communicationspurposes, ground. For a ground path to be low impedance
use an unshielded 22 AWG 2-wire twisted cable at RF frequencies, the connectionmust be made
if the leadwire run and noise conditions permit; with minimum length conductors that have a
however, some installations may need up to five maximum surface area. Wide straps or brackets
wires, three for communications and two for re- are preferred rather than leadwires. Be careful to
motereset(ineither a single cable or separate ensure thatmechanically tightenedjoints along
cables) or use a Belden 8771 shielded cable or the ground path, suchas pipe or conduitthreads
equivalent. The Keyboard Display Module, Con- or surfaces held together with fasteners, are free
trol Bus (for remote mounting or communications) of nonconductivecoatingsand are protected
or Communication Interface ControlBus Module against corrosion on mating surfaces.
mustbewired in a daisy chain configuration, b. KeyboardDisplayModule,ControlBus, or
(l(a)-l(a), 2(b)-2(b),3(c)-3(c)). Theorderofinter- Communication Interface ControlBus Module-
connection of all the devices listed above is not
11 CB-7803
CB780/CB784
WIRING
The shield, if used, should be connected to the 2. Do not route Remote Reset wires in conduit
signal ground terminal 3(c) provided as ofpart the with line voltage circuits.
CB780/CB784deviceControlBusconnection.
Connect the shield at both ends to earth ground. NOTE: A 13 Vdc power supply must be used any time more
c.CB780/CB784-Each CB780KB784 willhave than one Keyboard Display Module is used.
an earth ground terminal that must be grounded to
the metal control panel with wire as short as prac- 7. Maximum wire lengths:
tical. Each ground wire must be of capable
carrying a. CB780KB784 leadwires-The maximum length
a fault current equal to the rating of the protec- of leadwire is300 feet to terminal inputs (Control,
tive fuse (20A).A number 14 copper conductor Preignition Interlock,RunningLockout Interlock,
is adequate, but widestraps or brackets are pre- High Fire Switch and Low Fire Switch).
ferred rather than leadwires. b. Flame Detectorleadwires-The maximum flame
6. Recommended wire routing: sensor leadwire length is limited by the flame
a. Flame detector leadwires: signal strength.
1. Do not run high voltageignition transformer c. Remote Reset leadwires-The maximum length
wires in the same conduit with the flamedetec- of wire is 1000 feet toa Remote Reset pushbutton.
tion wiring. d. Control Bus-The maximum Control Bus cable
2. Do not route scanner wiresin conduit with line length depends onthe number of system modules
voltage circuits. connected, the noise conditions and the cable used.
3. Enclose scanner wires without armor cable in The maximum length of all interconnecting wire
metal cable or conduit. is 1000 feet.
4. Follow directionsin flame detector Instructions. 8. Make sure loads do not exceed the terminal ratings.
b. Control Bus: Refer to the label onthe CB780KB784 or to the ratingsin
1. Do not run high voltage ignition transformer Specifications; see Table1.
wires in the same conduit orclose proximity 9. Check the power supply circuit. The voltage and fre-
with the Control Buswiring. quency tolerance must matchthose of the CB780KB784.A
2. Do not route Control Bus inwires conduit with line separate power supply circuit may be required for the
voltage circuits. CB78O/CB784. Add the required disconnect means and
c.KeyboardDisplayModule (VFD): Because the overload protection.
VFD is powered from alow voltage, energy lim- 10. Check all wiring circuits and complete the Static
ited source, it can be mounted outside of a control Checkout, see Table 8, before installing the CB780KB784
panel if it is protected from mechanical damage. on the subbase.
d. Remote Reset: 11. Install all electrical connectors.
1.Donotrunhighvoltageignitiontransformer 12. Restore power tothe panel.
wires in the same conduit with the Remote Reset
wiring.
CB-7803 12
CB780/CB784
WIRING
r
I
I
I
I
I I MODULATE I
I
I BURNER MOTOR
I (BLOWER)
I
I
I
I
BURNER
CONTROLLER/LIMITS
LOCKOUT INTERLOCKS
(INC. AIR FLOW SWITCH)
1
I
I 10 SEC. INTERRUPTED
PILOT/IGNITION PURGE SWITCH
I
I
I
5 SECOND IGNITION
I 15 SEC.
INTERRUPTED
ERMINATION)
I PILOT VALVE
-
I 'I
I 817-1742 L1
A- - INFRARED
(LEAD SULFIDE) (HOTA
L2
I FLAME DETECTOR
I
I
OR
- I I
t
b
I
---I
YELLOW 817-1121
ULTRAVIOLET
FLAME DETECTOR
BLUE- J
2ND STAGE
FUEL VALVE
(OPTIONAL)
13 CB-7803
CB780/CB784
WIRING
Fig. 8-Wiring the Keyboard Display Module with Fig. 9-Wiring multiple Keyboard DisplayModules.
Communication Interface ControlBus Module.
833-2727 KEYBOARD DISPLAY MODULE
833-2727 KEYBOARD DISPLAY MODULE (MOUNTED ON CB 780/CB 784)
(MOUNTED ON CB 780/CB784)
I
MOMENTARY
MOMENTARY PUSH B U T O N
PUSH B U T O N
SWITCH
833-2734
COMMUNICATIONS
INTERFACE
CONTROLBUS
I I
833-2727 REMOTE KEYBOARD DISPLAY MODULE
Fig. 10-Wiring the Control Bus with remote Keyboard Display Module.
1
120 OHM
P P
RESISTOR
120 OHM
RESISTOR
I I
833-2727 REMOTE KEYBOARD DISPLAY MODULE
CB-7803 14
CB780/CB784
ASSEMBLY
Assembly
MOUNTING CB780KB784
Fig. 1l-Electrical panel installation.
NOTE: For installation dimensions, seeFig. 1.
15 CB-7803
CB780/CB784
ASSEMBLY
MODULE (VFD)
Fig. 12-Purge Card installation. 1. The Keyboard Display Module (VFD) can be mounted
either on the face of a panel door or on other remote locations;
see Fig. 15.
2. When mountingthe Keyboard Display Module the on
face of a door panel, closely follow these instructions:
a. Select the location on the door panelfor flush mount-
ing. Pay attention to the insertion dimension
of the two
Keyboard Display Module screws, two interlocking
earsand the twoplug-inconnectorstoallow for
sufficient clearance, 1/4 inch minimum inwardfrom
the surfaceof the door panel.
b. Use the Keyboard Display Module asa template; see
Fig. 28. Mark the two screw locations, two interlock-
ing ear locations and two plug-in connector locations.
Drill the pilot holesfor the mounting screws. Provide
for two holes on the door panel for the interlocking
ears and plug-in connector holes.
c. Mount the Keyboard Display Module securing the
two no. 4 screws.
REMOTE MOUNTING OF KEYBOARD DISPLAY Proper flame detector installationis the basis of a safe and
reliable flame safeguard installation. Refer to the instruc-
tions packed with the flame detector and the equipment
manufacturer instructions; see Fig. 17.
Keep theflame signal leadwires as short as possible from
the flame detector to the wiring subbase. Capacitance in-
creases with leadwire length, reducing the signal strength.
The maximum permissible leadwire length depends on the
type of flame detector, leadwire and conduit.The ultimate
limiting factor in the flame detector leadwire is the flame
signal; see Table9.
CB-7803 16
ASSEMBLY
G
-
ULTRAVIOLET (817-1743)
A-22
BLUE
YELLOW
WHITE
L2 WHITE I
L, BLACK
L2 BLACK
17 CB-7803
CB780/CB784
OPERATION
Operation
SEQUENCE OF OPERATION The Lockout Interlock or Running Interlock inputs
The CB780/CB784 has the following operating sequence, (interlockcircuitincluding Airflow Switch) must close
see Fig. 18 and Table4. by ten seconds into PREPURGE; otherwise, a safety
shutdown occurs.
INITIATE After the firing rate motor reaches the PREPURGE
The CB780/CB784enters the INITIATE sequence when rate position and PREPURGE timing is completed, the
the Relay Moduleis powered. The CB780/CB784 canalso firing rate motor willdrive to the low fire position.
enter the INITIATE sequenceif the Relay Moduleverifies When the firing rate motor reaches lowfire position,
voltage fluctuations of +1O/- 15% or frequencyfluctuations the Low Fire Switch,terminal 18, inputmust be
of +/-lo% during any part of the operating sequence. The energized beforeentering the Ignition Trial state.
INITIATE sequencelasts for ten seconds unlessthe voltage
or frequencytolerances are not met. When the tolerances are IGNITION TRIALS
notmet,aholdconditionwill be initiated andwill be a PilotFlameEstablish-
displayed on the VFD for at least five seconds. When the ing Period (PFEP): Fault History
tolerances are met, the INITIATE sequence will restart. If 1. Withthefiring
the condition is not corrected and the hold condition exists rate motor at the low fire position:
for four minutes,the CB780/CB784 willlockout. Causes for a. The pilot valve and the ignition transformer,
hold conditionsin the INITIATE sequence: terminals 8, 10 and 21, are energized. The
a. AC line dropout is detected. CB780/CB784 has afifteen second interrupted
b. AC line frequency error caused by using 60 Hz
a device pilot valve, terminal 21 and a ten secondinter-
on a50 Hz line, or vice versa. rupted pilot valvehgnition, terminal 8.
c. AC line noise that can prevent asufficient reading of b. During PFEEthe Low Fire Switch must remain
the line voltage inputs. closed. If it opens, a safety shutdown occurs.
[y]
d. Brownouts caused by a lowline voltage. c. ThePreignitionInterlockinputisignored
The INITIATE sequence throughout the Ignition Trial state.
also delays the burner motor 2. Flame mustbe proven bythe end of the four or ten
starterfrom being energized $ Diagnostic Info second PFEPto allow the sequence tocontinue. If
andde-energizedfroman flame is not proven by the end of PFEP, a safety
intermittent AC line input or control input. shutdown occurs.
[ T I
3. With flame proven,the ignition, terminal 10, is de-
STANDBY energized for early spark termination.
The CB780/CB784 is b.MainFlameEstablish-
+Total Cycles
ready to start an operating ing Period (MFEP): 3 FlameSignal 2.7V
sequence whenthe operat- 1. The CB78O/CB784
ing control determines acall for heat is present. The burner hasa selectable ten second or fifteen second
switch, limits,operating controland all microcomputer moni- MFEP. Afterthe Ignition Trials, and withthe pres-
tored circuits must be in the correct state for the CB780/ ence of flame, the main fuel valve, terminal 9, is
CB784 to continueinto the PREPURGE sequence. powered. If a flameoutoccurs, the CB780/CB784
will lockout within 3 seconds.
NORMAL START-UP
PREPURGE $ TotalHours 396 RUN
The CB780KB784 pro- 1. A ten second stabilizationperiod occurs atthe begin-
vides a PREPURGE timing ning of the RUN period.
selectable from 30 seconds to 2-1/2 minutes with power 2. The firing rate motor releases to modulation.
applied andthe CB780/CB784 operatingcontrol indicating 3. The CB780/CB784is now in RUN andwill remain in
a call for heat: RUN until the controllerinput, terminal 6 , opens, indicating
a.Running Interlocks, Preignition Interlocks, Burner that the demand is satisfied or alimit has opened.
Switch, Run/Test Switch, Lockout Interlocks and all
microcomputer monitoredcircuits must be inthe cor- POSTPURGE
rect operating state. TheCB780KB784pro-
b. The blower motor output, terminal 5 , is powered to
start the PREPURGE sequence. The firing rate motor
vides a fifteensecond
POST-PURGE following +
Expanded Annun. b
is driven to the high fire position. The PREPURGE the completion of the RUN
timing does not begin until the Lockout Interlock period. The blower motor output is powered to drive all
String and HighFire Switch are both closed. products of combustion and any unburned fuel from the
c. The Preignition Interlock input must remain closed
throughout PREPURGE;otherwise, safety shutdown
occurs.
CB-7803 18
CB780/CB784
OPERATION
LED
DISPLAY
BURNER
OPERATING
CONTROLS
AND
INTERLOCKS
FLAME
SIGNAL
FIRING
RATE
MOTOR
19 CB-7803
OPERATION
message will replace a selectable message to support the available. The CB780/CB784 LEDs provide positive visual
sequence status information.
It will also replacea selectable indication of the program sequence: POWER, PILOT,
message after 60 seconds if it or a lockoutmessage is FLAME, MAIN andALARM.
CB-7803 20
OPERATION
KEYBOARD FUNCTIONS arrow (:), which is located in the lower leftposition of the
The keyboard contains four pushbuttons and each has second line of the display, represents the SCROLL Down-
separate functions (SCROLL-Down, SCROLL-Up, MODE Up pushbuttons. The SCROLL Down-Up pushbuttons )(:
and Change-Level). The MODE and Change-Level push- can be pressed to display selectablemessages one at a time or
buttons, when pressed together, provide a SAVE function. held downto scroll through the selectablemessages at a rate
1. SCROLL Down-Up pushbuttons(:), see Fig. 20. of two per second. When the last item of the selectable
TheSCROLLDown-Uppushbuttons )(: are used to message is viewed, the display wraps around and displays
scroll through the selectable messages. The double-headed the first selectable message again.
BURNER CONTROL
M7401
21 CB-7803
CB780/CB784
OPERATION
I1 I 1\/II 11 I 1\/II
I I /
///
rn+
SCROLL
SCROLL
4-p 4-p
m-sAvE-m
MODE MODE
J P 2
M7402
Q-SAVE-nm m; m-sAvE4-p-m
SCROLL SCROLL
MODE 4-p MODE
4
J 1 3
/ \ M7403
3 1
n represents a numberedvalue.
T represents the terminal number. M7404
CB-7803 22
CB780/CB784
OPERATION
:(second-line-msg)< LH1
:Fault Cycle
:Fault Hours
:Fault Code LH2
:*fault -message*< LH2
"sequence-message< LH2
A
:(second-line-msg)< LH2
:Fault Cycle
:Fault Hours
:Fault Code LH3
:*fault -message*< LH3
"sequence-message< LH3
A
:(second-line-msg)< LH3
:Fault Cycle
:Fault Hours
:Fault Code LH4
:*fault -message*< LH4
"sequence-message< LH4
A
:(second-line-msg)< LH4
:Fault Cycle
:Fault Hours
:Fault Code LH5
:*fault -message*< LH5
"sequence-message< LH5
A
:(second-line-msg)< LH5
:Fault Cycle
:Fault Hours
:Fault Code LH6
:*fault -message*< LH6
"sequence-message< LH6
A
:(second-line-msg)< LH6
:Diagnostic Info-
:Device RM78nnx < LDI
:Device Suffix nnnn < LDI
:Run/Test Sw. RUNorTEST < LDI
Coperating Control (Opercontrol) T6 ONor OFF < LDI
:Interlock T7 ONor OFF < LDI
:Pilot Valve T8 ONor OFF < LDI
:Main Valve T9 ONor OFF < LDI
:Ignition T10 ONor OFF < LDI
CLowFire Sw T18 ONor OFF < LDI
CHighFireSw T19 ONor OFF < LDI
:Preignition Interlock (PreIgn ILK) T20 ONor OFF < LDI
:Pilot VdveDirst Stage Oilvalve (Valv/Start,V25) T21 ONor OFF < LDI
:Jumper 1 INTACT or CLIPPED < LDI
:Jumper 2 INTACT or CLIPPED < LDI
:Jumper 3 INTACT or CLIPPED < LDI
:Amplifier Type (Amp Type) NORMAL or AMP-CHECK or SHUTTER LDI
:Flame Response 0.8s or 3s < LDI
:Purge Time mm:ss < LDI
:Manufacturing Code (Mfg Code) nnnn < LDI
:Software Revision (SW Rev.) nnndnnnn < LDI
:Expanded Annun.- (see Table 5)
:Remote Command NONE/HOLD/HFLF
23 CB-7803
CB780/CB784
OPERATION
RUN/TEST SWITCH FUNCTIONS to be made. This activates a fifteen second flameout timer
The Run/Test Switch is located on the top side of the that permits pilot flame adjustment without nuisance safety
CB780KB784; see Fig. 19.The Run/Test Switch allows the shutdowns. The Run/Test Switch will be ignored during
burner sequenceto be altered as follows: PFEP for the CB780KB784 if terminals 8 and 9 or 9 and 21
1. In Prepurge Drive To High Fire Position,the Run/Test are jumpered.
Switch, when placed in the TEST position, will hold in 5. During RUN,the Run/Test Switch, when place din the
PREPURGE with the firing rate motor in the High Fire TEST position, will drive the firing rate motor to the Low
position. Fire position.
2. In the measured PREPURGE sequence,the Run/Test
Switch, when placed in the TEST position, will cause the NOTE: WhenCB780/CB784isswitchedtotheTESTmode,
PREPURGE timingto stop. Thefiring rate motor will be in it will stop and hold atthe next Run/Test Switch point in
the High Fire position. the operatingsequence. Make sure that the Ruflest
3. In Prepurge Driveto Low Fire position, the Run/Test Switch is in the RUNposition before leaving the installa-
Switch, when placed in the TEST position, will hold the tion.
burner sequencein PREPURGE withthe firing rate motor in
the Low Fire position. SELECTABLE SITE-CONFIGURABLEJUMPERS
4. In PFEP, the Run/Test Switch, when placed in the The CB780KB784 hastwo site-configurable jumper
TEST position, will stop the timer during the first eight options; see Fig. 24andTable 7. The site-configurable
seconds when aten second PFEP is selected or during the jumpers shouldbe clipped withside cutters and the resistors
first three seconds when a four second PFEP is selected, removed fromthe Relay Module.
allowing pilot-turn-downtest and other burner adjustments
CB-7803 24
OPERATION STATICCHECKOUT
n
JUMPER OPTIONS. Fig. 24-Selectable site-configurable jumpers.
Jumper SELECTABLE CONFIGURATION JUMPERS
Number Description Intact Clipped
J RUN/TEST SWITCH
JR1 Pilot Flame 10 Seconds 4 Seconds
Establishing
Period (PFEP)
JR3 Enabled
Start-up Disabled
Interlock Check
NOTE: For allstandard installations, these jumpers
should be left intact, unless otherwise indicated on
wiring diagram.
Static Checkout
/"/, CAUTION
1. Use extreme care while testing the system.Line
EQUIPMENT RECOMMENDED
1. Voltmeter (20 kohm/volt minimum sensitivity) set on
the 0-300 Vac scale.
2. Two jumper wires; no. 14 wire, insulated, 12 inches
voltage is present on most terminal connections [304.8 mm] long with insulated alligator clips at both ends.
when poweris on.
2.Openthemasterswitchbeforeinstallingor
removing a jumperon the subbase. GENERAL INSTRUCTIONS
3. Before continuing to the next test, be sure to 1. Perform all applicable tests listedin Static Checkout,
remove testjumper(s) used in the previous test. Table 8, in the order listed.
4. Replace all limits and interlocks that are not 2. Make sure all manualfuel shutoffvalve(s) are closed.
operating properly. Do not bypass limits and 3. Raise the setpoint of the operating controller to simu-
interlocks. late a call for heat.
5. Close all manual fuel shutoff valve(s) before 4. For each test, open the master switch and install the
starting these tests. jumper wire(s) betweenthe subbase wiring terminals listed
in the Test Jumpers column.
5. Close the master switch before observing operation.
After checking all wiring, perform this checkout before 6. Read the voltage between the subbase wiring termi-
installing the CB780KB784 on the subbase. These tests nals listedin the Voltmeter column.
verify the Wiring Subbase is wired correctly, andthe exter- 7. If there is no voltage or the operation is abnormal,
nal controllers, limits, interlocks, actuators, valves, trans- check the circuits and external devices as described inthe
formers, motors and other devices are operating properly. last column.
8. Check all wiring for correct connections, tight termi-
NOTE: Do not performa dielectric test with theCB780KB784 nal screws, correct wire, and proper wiring techniques. Re-
installed. Internal surge protectors will break down and place all damaged or incorrectly sized wires.
conduct a current. This could cause the CB780KB784 to 9. Replace faulty controllers, limits, interlocks, actuators,
fail the dielectric test or possibly destroy the internal valves, transformers, motors and other devices as required.
lightning and high current protection. 10. Ensure normal operation is obtained for each required
test before continuingthe checkout.
11. After completing each test, be sure to remove the
test jumper(s).
25 CB-7803
CB780/CB784
STATIC CHECKOUT
A WARNING
Make sureall manual fuel shutoff valves are closed.
IMPORTANT: Low fuelpressure limits, ifused, could be open. Bypass themwith jumpersfor the remaining Static
Tests (if restaired).
None 4-L2 Line voltage at terminal 4. 1. Master switch.
2. Power connected to the master
switch.
3.Overloadprotection (fuse, circuit
breaker, etc.) has not opened the
power line.
2 None 5-L2 Line voltage at terminal 6. 1. Limits.
2. Burner controller.
3 None 20-L2 Line voltage at terminal 20. 1. Preignition interlocks.
4 4-5 7-L2 1. Burner motor (fan or blower) starts. 1. Burnermotor circuit.
2. Line voltage at terminal 7 within a. Manual switch of burner motor.
10 seconds. b. Burner motor power supply,
overload protection, and starter.
c. Burnermotor.
2. Running or Lockout Interlocks
(including Airflow Switch).
5 4-10 Ignition spark (if ignition transformer is 1. Watch for spark or listen for buzz.
connected to terminal 10). a Ignition electrodes are clean.
- b. Ignition transformer is okay.
6 4-8 1, Ignition spark (if ignition transformer is 1. Watch for spark or listen for buzz.
connected to terminal 8). a Ignition electrodes are clean.
2. Automatic pilot valve opens (if con- b. Ignition transformer is okay.
nected to terminal 8). 2. Listen for click or feel head of valve
NOTE: Refer to wiring diagram of system for activation.
being tested. a Actuatorifused.
- b. Pilot valve.
7 4-21 Same as test no. 6 for connections to terminal 8. Same as test no. 6. If using direct spark
If using direct spark ignition, check the first ignition, check the first stage fuelvalve(s)
- stage fuelvalve(s) instead of pilot valve. isntead of the pilot valve.
8 4-9 Automatic main fuel valve(s) open. If using 1. Listen for and observe operation of
direct spark ignition with intermittent pilot on the main fuel valve(s) and actuator(s).
terminal 21, check the optional second stage 2. Valve(s) and actuator(s).
fuel valve, if used.
9 4-3 Alarm (if used) turns on. 1. Alarm.
10. 4-5 and 18-L2 Firing rate motor drives open; zero volts at 1. Low Fire Start Switch.
12-13 terminal 18 after motor starts driving open. 2. Firing rate motor and transformer.
11 4-5 and 18-L2 Firing rate motor drives closed; linevoltage at 1. Low Fire Start switch.
14-13 terminal 18 after motor is in Low Fireposition. 2. Firing rate motor and transformer.
12
4-5 and 19-L2 Firing rate motor drives open; linevoltage at 1. High Fire Purge Switch.
- 12-13 terminal 19 after motor is in High Fire position. 2. Firing rate motor and transformer.
13 4-5 and 19-L2 Firing rate motor drives closed; zero volts at 1. Low Fire Start Switch.
14-13 terminal 19 after m otor starts driving closed. 2. Firing rate motor and transformer.
-
(Continued)
CB-7803 26
STATICCHECKOUT CHECKOUT
A WARNING
Make sure all manual fuel shutoff valves are closed.
Checkout
/
A WARNING
9 \
IMPORTANT:
1. If the system fails topeg?orm properly, note the fault
code, fault message, equipmentstatus, and sequence
Do not allow fuel to accumulatein the combus- time on the display. Refer to the Troubleshooting sec-
tionchamber. If fuelisallowedtoenterthe tion of the CB780KB784 Operation and Maintenance
chamber for longer than a few seconds without Manual, Manual Number 750-166.
igniting, an explosive mixture could result. It is 2. Repeat ALL required Checkout tests after all adjust-
recommended that you limit the trial for pilot to ments are made.ALL tests must be satisfied with the
ten seconds, andlimit the attempt to light the main flame detector(s) inits FINAL position.
burner to two seconds from the time the fuel has
reached the burner nozzle. In any case, do not EQUIPMENT RECOMMENDED
exceed the nominal lightoff time specified by the Volt-ohmmeter (20 kohrdvolt minimum sensitivity) with:
equipment manufacturer; close the manual fuel 0-300Vac capability.
shutoff valve(s) if the flameis not burning at the 0-6000 ohm capability.
end of the specified time. 0-10 Vdc capability.
A CAUTION
/ - \
27 CB-7803
CB780/CB784
CHECKOUT
Flame signal withhotcombustion chamber-all 7. Power is connected to the system disconnect switch,
installations. (master switch).
Safety shutdown tests-all installations. 8. Lockout is reset (pushin reset button) onlyif the Relay
See Figs. 1 and 2 for location of component parts and Module is powered; see Figs.1 and 2.
Fig. 7 or wiring subbase specifications for terminal locations. 9. R u f l e s t Switch is in RUN position.
10. System is in the STANDBY condition. STANDBY
PRELIMINARY INSPECTION message is viewable in the VFD.
Performthefollowinginspectionstoavoidcommon 11. All limits and interlocks are reset.
problems. Make certain that:
1. Wiring connections are correct and all terminal screws FLAME SIGNAL MEASUREMENT
are tight. (TABLE 9 AND FIG. 26)
2. Flame detector(s) is clean, and installed and positioned Measure the flame signal at the appropriate times as
properly. Consult the applicable instructions. defined in the following Checkout tests. Read the flame
3. Correct combination of amplifier and flame detec- signal in volts dc at the flame amplifier test jacks + and
tor(s) is used. See Table 2in the Specifications section. (Com) or atthe Keyboard Display Module.
4. Plug-in amplifier and purge card are securely in place. 1. Use 1M ohm/volt meter with 0ato 10 Vdc capability.
5. Burner is completely installed and ready tofire; con- 2. Set the 1M ohm/volt meter to the0 to 10 Vdc range.
sultequipmentmanufacturerinstructions.Fuellinesare 3. Insert the positive (red) probe into the +jack of the
purged of air. flame amplifier. Insert the negative (black) probe into the
6. Combustion chamber and flues are clear of fuel and (Com) jack of the flame amplifier; see Fig. 26.
fuel vapor. 4. Allow a few seconds for the meter reading to stabilize.
817-1743 ,
5.0 Vdc at 1M ohdvolt meter 833-2724
a This minimum or stronger signal shouldbeeasily obtainedifthe detectoris correctly installed and positioned to properly sense
the flame. This voltaged must be obtained before completing checkout.
The flamesignal amplifier circuitry istested one-half second every five seconds during burner operation and shuts the down
burner if the amplifier fails (all installations).
This flame amplifieris Auto-Checktype.
CB-7803 28
CB780/CB784
CHECKOUT
3. For all optical detectors, clean the detector viewing g. Afteracontinuous sparkis obtained,openthemaster
window and inside of the sight pipe as applicable. switch and add a jumper on the subbase from
4. With the burner running, check temperature at the de- terminal 4(Ll)to the pilot terminal8 or 21. Recon-
tector. If it exceeds the detector maximum rated temperature: nect the leadwire from the pilot valve if it was
Add a heat block to stop conducted heat traveling disconnected in step b.
up the sight pipe. h. Close the master switch to energize boththe igni-
Add a shield or screen to reflect radiated heat. tion transformer andthe pilot valve.
Add cooling (refer to sight pipe ventilation in the i. If the pilot does notignite and if the ignition spark
detector Instructions). is still continuous, adjust the pressure regulator until
5. Make sure theflame adjustment is not too lean. a pilotis established.
6. Make surethe detector is properly sightingthe flame. j. When the pilot ignites properly and stays ignited,
7. If necessary, resight or repositionthe detector. open the master switch and removethe jumper(s)
from terminals4-8,4-10 and 4-21of the subbase.
INITIAL LIGHTOFF CHECK FOR PROVED k. Check for adequate bleedingof the fuel line.
PILOT 1. Reinstall the CB780KB784 on the subbase, close
Perform this check on all installations that use a pilot. It the master switch, and then return to step 4.
should immediately followthe preliminary inspection. 7. When pilot ignites, measure the flame signal. If the
pilot flame signal is unsteady or approaching the 1.25 Vdc
NOTE: Low fuel pressure limits, if used, could be open.If minimumvalue,adjust the pilot flame sizeordetector
so, bypass themwith jumpers duringthis check. sighting to provide a maximum and steady flame signal.
8. Recyclethe system to recheck lightoff and flame pilot
1. Open the master switch. signal.
2. Make sure that the manual main fuel shutoff valve(s) 9. Whenthe MAIN IGN periodis displayed onthe VFD,
is closed. Open the manual pilot shutoff valve. If the pilot makesuretheautomaticmainfuelvalve is open;then
takeoff is downstream from the manual main fuel shutoff smoothly open the manual main fuel shutoff valve(s) and
valve(s), very slightly open the manual main valve to supply watch for main burnerflame ignition. When the main burner
pilot gas flow. Make sure the main fuel is shut off just up- flame is established, proceed to step15.
stream fromthe burner inlet, or disconnect power from the 10. If the main burner flame is not established within
automatic mainfuel valve(s). ten seconds, close the manual main fuel shutoff valve(s).
3. Close the master switch and start the system with a 11. Recycle the system to recheck the lightoff and pilot
call for heat by raisingthe set pointof the operating control- flame signal.
ler; see Fig. 19 or CB780KB784 sequence. The program 12. Smoothly open the manual fuel shutoff valve(s) and
should startthe ten second INITIATE sequence. try lightoff again. (The first reattempt may have been re-
4. Let the sequence advance through PREPURGE. When quired to purge the lines and bring sufficient fuel to the
the PILOT IGN status is displayed on the Keyboard Display burner.)
Module, ignition spark should occur and the pilot should 13. If the main burner flame is not established within
light. If the pilot ignites,the FLAME LED will be energized. five seconds or the normal lightoff time specified by the
Proceed to step7. equipment manufacturer, close the manual main fuel shutoff
5. If the pilot flame is not established in ten seconds, safety
valves(s). Check all burner adjustments.
shutdown occurs. Let the sequence complete its cycle. Consult 14. If the main burner flame is not established after two
the equipment operating manual for further information. attempts:
6. Push the reset pushbutton, and let the system recycle a. Check for improper pilot size.
once. If the pilot still does not ignite, make the following b. Check for excess combustion air at low fire.
ignition/pilot adjustments: c. Check for adequate lowfire fuel flow.
a. Open master switch and remove the CB780KB784 d. Check for proper gas supply pressure.
from the subbase. e. Check for proper valve operation.
b. On the subbase, temporarilyjumper terminal 4 to f. Check for proper pilot flame positioning.
ignition terminals8,lO or 21; refer to the appropri- 15.Repeatsteps 10 through14toestablishthemain
ate wiring diagram to determine the proper termi- burner flame; then proceed to step 16.
nal. Disconnect the leadwire the to pilot valveif it 16. With the sequence in RUN, make burner adjustments
is connected tothe same terminal. for flame stability and Btu input rating.
c. Close the master switch to energize onlythe igni- 17. Shut downthe system by opening the burner switch or
tion transformer. by lowering the set point of the operating controller. Make
d. If the ignition spark is not strong and continuous, sure the main flame goes out. There be a may
delay due to gas
open the master switch and adjust the ignition trappedbetweenthevalve(s)andburner.Makesureall
electrode spark gap setting to the manufacturer automatic fuel valve(s) close.
recommendations.
e. Make sure the ignition electrodes are clean.
f. Close the master switch and observethe spark.
29 CB-7803
CB780/CB784
CHECKOUT
18. Restart the system by closingthe burner switch and/or 12. Wait about three minutes. Close the master switch,
raising the set pointof the operating controller. Observe that open the manualfuel shutoff valve(s), and try to lightoffthe
the pilot is established during PILOT IGN and the main burner again. The first attempt may have been required to
burner flame is established during MAIN IGN within the purge the lines and bring sufficient fuel the to burner.
normal lightoff time. 13. If the first stage burner flame is not established within
19. Measure the flame signal. Continue to check for the ten seconds, close the manual fuel shutoff valve(s), and open
proper signal, see Table9, through the RUN period. Check the master switch.
the signal at both High and Low Firing Rate positions and 14. If necessary, repeat steps 11through 13to establishthe
while modulating. first stage burner flame. Then proceed to step 15.
20. Run the burner through another sequence, observing 15. When the first stage burner flame is established, the
the flame signal for: sequence will advance to RUN. Make burner adjustments
a. Pilot flame alone @SI). for flame stability and input rating. If a second stageis used,
b. Pilot and main flame together. proceed to step 18.
c. Main flame alone (unless monitoring an intermit- 16. Shut downthe system by opening the burner switch or
tent pilot). Also observe the time ittakes to light the by lowering the set point of the operating controller. Make
mainflame. Ignition of mainflame shouldbe smooth. sure the burner flame goes out and all automatic fuel valve(s)
21.Makesureallreadingsare in the requiredranges close.
before proceeding. 17. If used, remove the bypass jumpers from the low fuel
22. Return the system to normal operation. pressure limit and subbase.
18. If a second stageis used, make sure the automatic sec-
NOTE: After completing these tests, open the master switch ond stage fuel valve(s) has opened. Check the lightoff as
and remove all test jumpers from the subbase terminals, follows (otherwise proceed to step19):
limitskontrols or switches. a. Open the manual second stagefuel valve(s).
b. Restart the system by raising the set point of the
INITIAL LIGHTOFF CHECK FOR DIRECT operating controller.
SPARK IGNITION c. When the first stage burner flame isestablished,
This check applies to gas and oil burners not a pilot.
using watch for the automatic second stage fuel valve(s)
It should immediately follow the preliminary inspection. to open. Observe that the second stage lights off
Referto the appropriatesampleblockdiagram of field properly.
wiring for the ignition transformer and fuel valve(s) hookup. d. Make burner adjustments for flame stability and
input rating.
NOTE: Lowfuelpressurelimits, ifused, couldbeopen. If so, e. Shut down the system by lowering the set point of
bypass them with jumpers during this check. theoperatingcontroller.Makesure the burner
flame goesoutandallautomaticfuelvalve(s)
1. Open the master switch. close.
2. Complete the normal ready-to-fire checkout of the f. Proceed to step 19.
fuel supply and equipment as recommended bythe equip- 19. Restart the system by closingthe burner switch and/or
ment manufacturer. raising the set point of the operating controller. Observe that
3. Close all manual main fuel shutoff valve(s). Check the burner flame is established during PILOT IGN, within the
that the automatic fuel valve(s) are closed. Make sure is fuel normal lightoff time specified by the equipment manufacturer.
not enteringthe combustion chamber. 20. Measure the flame signal. Continue to check for the
4. Closethe master switch and start the system withacall proper signal, see Table9, through the RUN period. Check
for heat by raising the setpoint of the operating controller, the signal at both high and low firing rate positions and while
see Fig.18 for CB780KB784 sequencing. The program modulating. Any pulsating or unsteady readings will require
sequence should start the ten second INITIATE sequence. further attention.
5. Let the sequence advance through PREPURGE. Igni- 21.Makesureallreadingsare in the requiredranges
tion spark should occur after PREPURGE period. Listenfor before proceeding.
the clickof the first stage fuel solenoid valve(s).
6. Let the program sequence complete its cycle. NOTE: Upon completing these tests, open the master
7. Open the manual fuel shutoff valve(s). switch and remove all test jumpers from the subbase
8. Push the reset button and recycle the program se- terminals, limitdcontrols or switches.
quence through PREPURGE.
9. When PILOT IGN status is displayed, watch thatthe 22. Return the system to normal operation.
first stage burner flame is established. If it is established,
proceed to step 15. PILOT TURNDOWN TEST (ALL INSTALLATIONS
10. If the first stage burnerflame is not established within USING A PILOT)
ten seconds, close the manual fuel shutoff valve(s), and open Perform this check on all installations usethat
apilot. The
the master switch after POSTPURGE is completed. purpose of this testis to verify that the main burner can be lit
11. Check all burner adjustments. by the smallestpilot flame thatwillhold in the flame
CB-7803 30
CB780/CB784
CHECKOUT
31 CB-7803
CB780/CB784
CHECKOUT
HOT REFRACTORYSATURATION TEST aware thatit must also properly sight the flame. For an infrared
(ALL INFRARED DETECTORS) detector, try lengthening the sight pipe or decreasing the pipe
Test to make certain that radiation from hot refractory size (diameter). For details, refer to the detector Instructions
does not maskthe flickering radiationof the flame itself. and the equipment Operating Manual. Continue adjustments
Start the burner and monitor the flame signal duringthe until hot refractory hold-in is eliminated.
warmup period.A decrease in signal strength as the refrac-
tory heats up indicates hot refractory saturation.If saturation ULTRAVIOLET SENSOR, IGNITIONSPARK RE-
is extreme, the flame signal will drop below 1.25Vdc andthe SPONSE TEST (ALL ULTRAVIOLET DETECTORS)
system will shut down as though a flame failure occurred. Test to make certain the that
ignition sparkis not actuating
If hot refractory saturationoccurs, the condition must be the FLAME LED.
corrected. Add an orifice plate in front of the cell to restrict 1. Close the pilot and main burner manualfuel shut-off
the viewing area, lengthen the sight pipeor decrease the pipe valve(s).
size (diameter). Continue adjustments until hot refractory 2. Start the burner and usethe R u f l e s t Switch to stop
saturation is eliminated. the sequencein the PILOT IGN period. Ignition spark should
occur, butthe flame signal should not be more 0.5 thanVdc.
HOT REFRACTORYHOLD-IN TEST 3.If the flame signal is higher than 0.5 Vdc and the
(ALL INFRARED DETECTORS) FLAME LED does come on, consultthe equipment operat-
Test to make certain hot refractory will not delay the ing manual and resight the detector farther out from the
flame detection system response to a flameout. This condi- spark, or away from possible reflection. Itbemay necessary
tion can delay responseflame to failure and also can prevent to construct a barrier to block the ignition spark from the
a system restart as long as hot refractory is detected. detector view. Continue adjustments untilthe flame signal
Infrared (lead sulfide) detectors can respond to infrared due to ignition spark is less than0.5 Vdc.
rays emitted by a hot refractory, even when the refractory has
visibly ceased to glow. Infrared radiation from a hot refrac-RESPONSE TO OTHER ULTRAVIOLET
tory is steady, but radiation from a flame has a flickering SOURCES
characteristic. The infrared detection system responds only Some sources of artificial light, such as incandescent or
to flickering infrared radiation;it can reject a steady signal fluorescent bulbs, mercury sodium vapor lamps and day-
from hot refractory. The refractory steady signal be canmade light, produce small amountsof ultraviolet radiation. Under
to fluctuateif it is reflected, bent or blocked by smoke or fuel certain conditions, an ultraviolet detector will respond to
mist within the combustion chamber.Be careful when ap- these sources asif it is sensing a flame. To check for proper
plying an infrared system to verify its response flame only.
to detector operation, check the Flame Failure Response Time
To check infrared (lead sulfide) detectors for hot refrac- (FFRT) and conduct Safety Shutdown Tests under all oper-
tory hold-in, operate the burner until the refractory reaches ating conditions.
its maximum temperature. If the installation has a multi-fuel
burner, burn the heavier fuel that is most likely to reflect, FLAME SIGNAL WITH HOT COMBUSTION
bend or obscurethe hot refractory steady infrared radiation. CHAMBER (ALL INSTALLATIONS)
When the maximum refractory temperature is reached, close With all initial start-up tests and burner adjustments com-
all manualfuel shutoff valve(s),or openthe electrical circuits pleted, operate the burner until the combustion chamberis at
of all automatic fuel valve(s). Visually observe when the the maximum expected temperature. Observe the equipment
burner flame or FLAME LED goes out. If this takes more manufacturer warm-up instructions. Recycle the burner un-
thanthreeseconds, the infrareddetector is sensinghot der these hot conditions and measure the flame signal. Check
refractory. Immediately terminate the firing cycle. (Lower thepilotalone, the mainburner flame alone,andboth
the set point to the operating controller, or set the Burner together (unless monitoring only the main burner flame
Switch to OFF. Do not open the master switch.) when using DSI). Check the signal at both High and Low
Firing Rate positions and while modulating, if applicable.
NOTE: Some burners continue to purge oil lines between theCheck the FFRT of the Flame Amplifier. Lowerthe set
valve(s) and nozzle(s) even thoughthe fuel valve(s) are point of the operating controller and observe the ittime takes
closed. Terminating the firing cycle (instead of opening for the burner flame to go out. This should be within 3 sec-
the master switch) will allow purging the combustion onds maximum.
chamber. This will reduce a buildup of fuel vapors in the If the flame signal is too low or unsteady, checkflame the
combustion chamber caused by oil line purging. detector temperature. Relocatethe detector if the tempera-
tureis too high. If necessary, realign the sighting to the obtain
If the detector is sensing hot refractory, the condition must proper signal and response time. If the response timeis still
be corrected. Add an orifice plate in front of the cell to restrict too slow, replacethe Plug-in Flame Signal Amplifier. If the
the viewing area of the detector. If this does not correct the detector is relocated or resighted, or the amplifieris replaced,
problem, resight the detector at a cooler, more distantofpart repeat all required Checkout tests.
the combustion chamber. While resighting the detector, be
CB-7803 32
CB780/CB784
CHECKOUT
33 CB-7803
CB780/CB784
TROUBLESHOOTING
Troubleshooting
CB780KB784 SYSTEM DIAGNOSTICS Diagnostic Information Index
Troubleshootingcontrolsystemequipmentfailures is The CB780KB784monitors input/output terminals and
made easier with the CB780KB784 self-diagnostics and can displaythe status of the terminal at the VFD (example:
first-out annunciation. In addition to an isolated spst alarm Pilot Valve T8 ON<). SeeTable 5 for a complete terminal
relay (audible annunciation), the CB780KB784 provides description and number. The display will show the actual
visual annunciation by displayinga fault code and fault or status of the terminal. If voltage is detected atthe terminal,
hold message at the Keyboard Display Module2 row by ON is displayed, butif no voltageis detected atthe terminal,
20 column VFD. The CB780KB784 provides118 diag- OFF is displayed; see Table5.
nostic messages for troubleshooting the system (see the
CB780KB784 Operating andMaintenanceManual, Manual Historical Information Index
Number 750-166). The CB780KB784 has nonvolitile memory that allows
Self-diagnostics of the CB780KB784 enables it to detect the Relay Module to retain Historical Information for the six
and annunciate both external and internal system problems. most recent lockouts. Each of the six lockout files retains
the
Internal faults and external faults such as interlock failures, cycle whenthe fault occurred, the hour of operation whenthe
flame failures andfalse flame signals are annunciated the by fault occurred,a fault code, a fault message and burner status
CB780KB784, which energizesthe ALARM LED or visu- when the fault occurred; see Table 4.
ally displayed atthe Keyboard Display Module VFD.
The VFD displaysa sequence status message indicating: IMPORTANT: The CB780 will not operate withouta Key-
STANDBY, PREPURGE, PILOT IGN,MAIN IGN, RUN board Display Module or a Control Bus installed.
and POSTPURGE. The selectable messages also provide
visual indicationof current status and historical statusof the SERVICE NOTE: If the Keyboard Display Module VFD
equipment such as: Flame Signal,Total Cycles, Total Hours, is scrambled, remove and reinstall the Keyboard Display
Fault History, Diagnostic Information and Expanded An- Module, and reset the CB780KB784 Relay Module.
nunciator terminal status (if used). With this information,
most problems can be diagnosed without extensive trial andSERVICE NOTE Reset CB780KB784 by pressing the
error testing. reset pushbutton on the CB780KB784, or pressing a
Table 4 provides the sequence and status hold messages. remote reset pushbutton wired through the Keyboard
Table 10 provides a summary of all CB780KB784 fault Display Module or Control Bus.A power-up reset will
messages and fault codes. In addition, Diagnostic Informa- cause an electrical reset of the CB780KB784, but will not
tion and History Data are available to in assist
troubleshoot- reset a lockout condition.
ing the CB780KB784, see Table6.
The CB780KB784 provides diagnostic information to SERVICE NOTE: Use the access slots on the sides of the
aid the service mechanic in obtaining information when Wiring Subbase to check the terminal voltage of the
troubleshootingthe system, see Tables 4,5,6 and 10. Informa- CB780KB784.
tion available the
in Diagnostic Information includes Device
Type,Device Suffix, SoftwareRevision,Manufacturing SERVICE NOTE: Maximum ambient operating tempera-
Code,Flame Amplifier Type, Flame Failure Response Time, ture of an 817-1121flame sensor, Series1through 6 will
Selectable Jumper Configuration Status, Run/Test Switch be reduced to125°Fbecause of the duty cycle operation
Status and Terminal Status. of the CB780KB784 Relay Module.
CB-7803 34
CB780/CB784
TROUBLESHOOTING
TABLE 10-HOLD AND FAULT MESSAGE SUMMARY,
35 CB-7803
CB780/CB784
TROUBLESHOOTING
U u M5082A
Cleave rooks
Printed in U S A .