TUF Ultra-sonic Flowmeter

Typical Application:Large-diameter pipes and places where it


Is inconvenient to install pipeline or plug-in structural meters.

1. General TUF Ultra-sonic Flowmeter


The TUF series ultra-sonic flowmeter is based on the
liquid, and the variation of its propagation time is
principle of low voltage, multi-pulse time difference,
proportional to the flow velocity of the liquid, and
high-precision and super-stable dual-balance signal
when the flow rate is zero, the two sensors, the time
differential transmitting and differential receiving digital
required to transmit and receive sound waves is
detection technology is used to measure the smooth and
exactly the same (unique, practically measurable
counter-current acoustic transmission time, and the
zero-flow Technique) ; when the medium flows, the
velocity is calculated according to the time difference. It
time required to transmit sound waves in the
has the advantages of good stability, small zero drift,
countercurrent direction is greater than that in the
high measuring accuracy, wide range ratio and strong
current direction. The expression for the relations:
anti-interference.
The slight change in the propagation time of the
ultrasonic beam in the liquid is due to the flow of the

Where: V: medium flow rate


θ : angle between sound beam and liquid
flow direction
M: the number of linear propagation times
of sound beam in liquid
D: Inner diameter of pipe
Tup: the propagation time of sound beam in
the positive direction
Tdown: the propagation time of sound beam
in the reverse direction
△T:Tup-Tdown

99
TUF Ultra-sonic Flowmeter

Portable ultra-sonic flowmeter TUF-2000P


•High-precision measurement: linearity is better than
0.5%, repeatability is better than 0.2% and
measurement accuracy is better than 1%;
•Non-contact measurement: the magnetic ultrasonic
flowmeter sensor can be adsorbed on the outer wall of
the pipeline to complete the flow measurement;

•Wide measuring range: different types of sensors can

be used to measure the flow of pipes with diameters of

DN15-DN 6000mm;
•Chinese and English menus are available.
•Charging power: built-in large-capacity hydrogen
rechargeable battery, which can work for more than 20
hours;;
•The inside places the printer.
•The inside places the data recorder.

Standard Model Model Illustration Quantity Description


Volume:225*180*67MM
Host TUF-2000P 1 Working temperature:-20~60℃,Measuring
accuracy±1%
Magnetic, Volume:64*35*32mm,Working
Medium Sensor TM-1 2 temperature:-40~90℃,Measuring Range:
DN50-DN700mm
Length: 5 M,it is used for connecting the ultrasonic
Ultrasonic Special Signal Cable 2
flowmeter host and the sensor
Length: 3 M,Used to charge the ultrasonic flowmeter or
Power Cord 1
use the alternating current for long time measurement
Thermal Printing Paper 2 Length: 30 M
Weight:110g,Used for ultrasonic signal propagation
Ultrasonic Coupling Agent 1
between ultrasonic sensor and pipe wall
Length: 3 M,Maximum Pull:100kg,For magnetic duct
Tensioner 2
strapping sensors.
Length: 3 M,Used to measure the pipe circumference or
Tape Measure 1
the installation distance between two probes.

Instructions 1

Volume: 456*335*133mm,Suitable for harsh


Aluminum Alloy Protection Box 1
environment such as field and underground.

100
Optional Sensor Illustration Description Measuring Range Temperature Range
Small External Bonded Sensor Magnetism DN50-DN100mm -40~90℃

Medium External Bonded Sensor Magnetism DN50-DN700mm -40~90℃

Large External Bonded Sensor Magnetism DN300-DN6000mm -40~90℃

Small High Temperature Sensor DN15-DN100mm -40~160℃

Medium High Temperature Sensor DN50-DN700mm -40~160℃


Measurement
Other Accessories Illustration Description Measuring Range
Accuracy
±1%H±0.1mm
Ultrasonic Thickness Gage Precision Measurement 1.2~225.0mm H is the thickness of the
measured object.
It is suitable for the occasion where the measuring
Lengthening Signal Cable Length: 10mx2
pipeline is far away from the host.
It is suitable for fixing sensors with pipe diameters
Extended Tensioner Length: 6mx2
exceeding 1000mm.
Thermal Printing Paper Length: 30m

Specifications
Item Performance Parameter
Host 2x20 dot matrix backlight LCD,working temperature: -20~60℃;
24-column character miniature thermal printer
4x4+2 type keyboard; Data interface RS-232
Sensor Type TS-1 standard, applicable pipe diameter: DN15-100mm fluid temperature ≤90℃
Type TM-1 standard, applicable pipe diameter: DN50-700mm, fluid temperature ≤ 90℃
Type TL-1 standard,applicable pipe diameter: DN300-DN6000mm fluid temperature
≤90℃
Measuring Medium Water, seawater, industrial sewage, acid-base liquid, various oils and other liquids that
can conduct sound waves.
Velocity Range 0~±30m/s
Measurement Accuracy >±1%
Working Power Ni-MH battery can work continuously for more than 20 hours or 220VAC with a
tolerance of
±15%
power consumption 2W
Charge Intelligent charging, direct access to AC220V, automatic stop when charging is
completed, and the indicator turns green
Weight NW. 2.0
Remarks Equipped with high-strength protective box, it can be used in harsh environment such as
field and underground.

Encoding Rules of Portable Ultra-sonic Flowmeter

Type TS-1 standard eg: TUF-2000P


TUF-2000P Type TM-1 standard Note: Portable ultrasonic flowmeter, standard configuration
Type TL-1 standard Small sensor TS-1

101
TUF Ultra-sonic Flowmeter

Handheld Ultra-sonic Flowmeter TUF-2000H


● High-precision measurement: linearity 0.5%,
repeatability 0.2%, and accuracy up to ±1%.
●The volume is 210x90x30mm and the weight is 0.5kg;
● Non-contact measurement: the magnetic ultrasonic
flowmeter sensor can be adsorbed on the outer wall of the
pipeline to
complete the flow measurement.
●Wide measuring range: different sensors can be used to
measure the flow of pipes with diameters of
DN15-DN6000mm.
● Charging power supply: Built-in large-capacity Ni-MH
rechargeable battery can support the flowmeter to work
continuously for more than 12 hours;
●Large LCD display: It can display the cumulative flow,
instantaneous flow, flow rate, working state, etc. at the
same time;
●The built-in data recorder has a space of 24 kbytes and
can store 2000 lines of measurement data.

Standard Model Model Illustration Quantity Description


Volume:210*90*30mm
Host TUF-2000H 1 Working temperature:-20~60℃,Measuring
accuracy±1%
Magnetic, Volume:64*35*32mm,Working
Medium Sensor TM-1 2 temperature:-40~90℃,Measuring Range:
DN50-DN700mm
Ultrasonic Special Signal Length: 5m Used for connecting the ultrasonic
2
Cable flowmeter host and the sensor
Data Line 1 Length: 1m Used to export data to a computer.

Power Cord 1 Length: 1m Used for charging

Weight:110g,Used for ultrasonic signal propagation


Ultrasonic Coupling Agent 1
between ultrasonic sensor and pipe wall
Length: 3m,Maximum Pull:100kg
Tensioner 2
For magnetic duct strapping sensors.
Length: 3m,Used to measure the pipe circumference
Tape Measure 1
or the installation distance between two probes.

Instructions 1

Aluminum Alloy Protection


1 Volume: 415*315*100mm
Box

102
Optional Sensor Model Illustration Description Measuring Range Temperature Range
Small External Bonded
TS-1 Magnetism DN50-DN100mm -40~90℃
Sensor
Medium External Bonded
TM-1 Magnetism DN50-DN700mm -40~90℃
Sensor

Large External Bonded


TL-1 Magnetism DN300-DN6000mm -40~90℃
Sensor
Small High Temperature
HTS-1 DN15-DN100mm -40~160℃
Sensor
Medium High Temperature
HTM-1 DN50-DN700mm -40~160℃
Sensor
Other Accessories Illustration Description Measuring Range Measurement Accuracy
±1%H±0.1mm
Precision
Ultrasonic Thickness Gage TT100 1.2~225.0mm H is the thickness of the measured
Measurement
object
Lengthening Signal Cable Length: It is suitable for the occasion where the measuring pipeline is
10mx2 far away from the host.
Extended Tensioner Length: It is suitable for fixing sensors with pipe diameters exceeding
6mx2 1000mm.
Specifications
Item Performance Parameters
linearity 0.5%
Repeatability 0.2%
Accuracy +1 % of indicating value, flow rate>0.2m/s
Response Time 0-999s
Velocity Range + 32m/s
Measuring Diameter DN15-DN6000mm
Unit of Measure Meters, feet, cubic meters, liters, cubic feet, gallons etc.
Accumulator 7-bit positive, negative and net accumulator
Type of liquid All kinds of single uniform liquids capable of conducting sound waves
Security The setting value is locked
Display 4x8 Chinese or 4x16English
Communication RS232, baud rate 75-57600,compatible with Fuji ultrasonic flowmeter and other products as required by users
interface
Sensor M1 standard, or there are four other options.
Sensor Power The standard is 5mx2, it can also be lengthened to10mx2
Power 3 AAA built-in Ni-H batteries, 12-hour continuous operation, AC100-240V adapters
Data Recorder Built-in data recorder can record 2000 lines of data.
Manual Accumulator 7 bits, press the key to start calibration.
Shell Material Fire retarding ABS
Shell Size 200x90x30 mm
Host Weight 500g(1.2 lbs)includes batteries
Encoding Rules of Portable Ultra-sonic Flowmeter
— 1.Type TS-1 standard eg: TUF-2000H1
TUF-2000H —— 2.Type TM-1 standard Note: Portable ultrasonic flowmeter, standard components
— 3.Type TL-1 standard Another optional small sensor TS-1

103
TUF Ultra-sonic Flowmeter

Fixed Ultrasonic Flowmeter TUF-2000B


TUF-2000F Basic TUF-2000B
•Volume 120x40x25mm
•High-precision measurement: linearity is better than •Lowest price, only with flow
0.5%, repeatability is better than 0.2%, and measurement measurement function.
•IP68, waterproof with full glue filling.
accuracy is better than± 1%;
•It can realize local measurement,
•Wide measuring range: different model of sensors can be secondary remote transmission display,
used to measure the flow of DN15-DN6000mm pipeline; parameter setting and networking
•High-Protection Grade:Up to IP68, and can be immersed measurement.

in water for 2m;


•Comprising an magnetism meter for easy operations; Functional TUF-2000F On the basis of basic functions, the following
functions are added:
•Multiple display: including primary meter and secondary
•IP68, it can work 2 meters underwater.
meter;
•3 channels of 4-20mA analog inputs
•Long transmission distance and fast networking: RS-485 •2channels of 3-wire PT-100 resistance
is used to connect the communication between the primary signal input
•Isolated RS232/RS485 output, 2 isolated
meter and the secondary meter. The transmission distance
OCT outputs
•1 isolated 4-20mA output (passive)

Structure diagram of fixed ultrasonic flowmeter


Optional secondary meter (used for single point
measurement, remote transmission display and parameter Wall mounted TUF-2000FB
setting) ・Used for wall mounting
•Size:178 X 165x55mm
RS485 bus communication
(the distance can reach more than 1000m) Panel mounted TUF-2000FS
・Used for meter panel installation
24V power supply •Hole Size: 152mmx76mm
EXA TYPE TUF-2000FD
•Explosive-proof Grade DIIBT4
•Size:285x265x90mm

Networking Measurement Diagram


RS485 bus communicationcan reach 1000 meters.
(the distance can reach more than 1000m)
24V Power Supply

Note: The flowmeter uses 4-core cable for


power supply and communication.
(Red: 24V+; Black: 24V-; White: 458+;
Green: 485-)

104
TUF ultra-sonic flowmeter

Optional sensor of fixed ultrasonic flowmeter TUF-2000B TUF-2000F

Feature Basic Type Functional Type

External Clamp Type


•Safe without interruption of flow and loss of pressure•accuracy ± 1%
•Easy to install and maintain
•Lowest price, independent of measuring diameter

Immersible Type
•Safe without interruption of flow and loss of pressure-accuracy ± 1%
•Users need to be trained, using a special hole opener to self-installation
•The price is high, independent of measuring diameter
•Good reception and stable long-term operation
Standard Segment Type
•The installation needs to break the pipe, no pressure loss •accuracy±0.5%
•Maintenance needs to be cut off, and users can install it by themselves.
•The larger the measuring diameter, the higher the price

.
• High accuracy, good reception signal, long-term operation stability

Optional Flow Sensor


Different sensors can be selected according to different fluid, pipeline conditions and installation methods.

Type Illustration
Illustration Standard Model Diameter Temp Range Dimensions
Standard
TS-2 DN15-DN100 -30~90°C 45 x 25 x 32mm
Small type

Standard Standard
TM-1 DN50-DN700 -30~90°C 64x39x44mm
Holding type Medium type

Standard Large
TL-1 DN300-DN6000 -30~90°C 97x 54 x 53mm
type

Hi-temp Small
TS-2-HT DN15-DN100 -30~160°C 45x 25 x 32mm
type
High
Hi-temp
temperature TM-1-HT DN50-DN700 -30~160°C 64 x39 x 44mm
Medium type
Holding type
Hi-temp Large
TL-1-HT DN300-DN6000 -30~160°C 97x54x53mm
type

N-type TC-1 DN80-DN6000 -30~160°C 190x80x55mm


Immersible
type Lengthening
TC-2 DN80-DN6000 -30~160°C 335 x 80 x 55mm
type

304 Stainless Steel


π-segment type G3 DN15-DN25 -30~160°C See the
threaded connection
specification
Standard Carbon steel
G2 DN32-DN40 -30~160°C sheet of
Segment type segment type threaded connection
segment
Standard Carbon steel sensor for
G1 DN50-DN6000 -30~160°C
segment type flanged connection specifications

105
TUF Ultra-sonic Flowmeter
Fixed ultrasonic flowmeter TUF-2000S
•High-precision measurement: linearity is better Schematic diagram
than 0.5%, repeatability is better than 0.2%, and
measurement accuracy is better than 1%;
•Wide measuring range: different model of sensors
can be used to measure the flow of
DN15-DN6000mm pipeline;
•Chinese and English menus are available;
•Strong reliability: the measurement accuracy,
service life and reliability of the low-voltage
multi-pulse transmitting circuit are greatly
improved;
•Strong anti-interference ability: double-balanced
signal difference is used to distribute transmitting
and receiving circuits, effectively resisting strong
interference sources such as frequency converters,
TV towers and high voltage lines;
•Powerful memory function: automatic memory of
accumulated flow in the first 64 days, the first 64
months and the first 5 years, automatic memory of
the time and flow of the first 64 calls and power
outages, and automatic memory of the working state
of the flowmeter in the first 64 days.

Optional Flow Sensor


Meter Installation
Illustration Type Model Temp Range Accuracy
Range Requirements
Three-wire
PT100 Holding No need to cut
CT-1 ≥DN50 -40~160°C
temperature off the flow
sensor
Three-wire
PT100
Need to cut off
Immersible TCT-1 ≥DN50 -40~160°C
the flow
temperature
sensor 100℃±0.8℃
Three-wire Temperature
PT100 installed difference after
under pressure accurate
No need to cut matching is ≤
and PCT-1 ≥DN50 -40~160°C
off the flow 0.1℃
Immersibleed
temperature
sensor
Small diameter
three-wire
PT100 Need to cut off
SCT-1 <DN50 -40~160°C
Immersibleed the flow
into temperature
sensor

106
RL Ultra-sonic Heat Meter

The flow regulating valve is upstream The flow regulating valve is downstream