You are on page 1of 12

Heating Line Product Guide 435.

0
Ignition Controls Section
Product Bulletin G67
Issue Date 1098

G67 Intermittent Pilot Ignition Controls

The G67 Intermittent Pilot Ignition


(IPI) Control is used to
automatically light a pilot burner
and energize the main burner
gas valve of a heating system in
response to the thermostat’s call
for heat. When the heating load is
satisfied, the thermostat opens
and the G67 de-energizes the
pilot and main burner gas valves.
The G67 can be used with
equipment with a maximum firing
rate of 117 kW (400,000 Btu/hr)
Any application over 117 kW
(400,000 Btu/hr) must be
approved in advance by the Figure 1: G67 Intermittent Pilot Figure 2: EC Approved G67EG
Johnson Controls Application Ignition Control Intermittent Pilot Ignition Control
Engineering Department.

Features and Benefits


❑ Energy Efficient Allows pilot gas to be on only during the run
cycle

❑ High Energy Spark Promotes consistent dependable pilot lighting

❑ Compact Size Provides limited space applications

❑ Solid State Components Provides long life

❑ Quick Response to Loss of Provides rapid closure of main valve


Pilot Flame (0.8 second maximum)

❑ G67EG Approved Worldwide Broadens applications to include global markets

© 1998 Johnson Controls, Inc. 1


Code No. LIT-4350400 www.johnsoncontrols.com
A pplication S equence of Operation
The G67 ignition control may only be used for Figure 3 illustrates the sequence of operation for the
two types of applications: G67.
• well ventilated or outdoor applications On a call for heat from the system thermostat, the G67
ignition control simultaneously opens the pilot valve
• power vent or induced draft application
and supplies a continuous spark to the pilot burner’s
The G67 is suitable for operation over a temperature electrode. When the pilot burner gas ignites, the pilot
range of -40 to 66°C (-40 to 150°F). Consideration flame sensor detects the pilot flame and signals the
must be given to the temperature of the surface on G67 to energize the main gas valve and discontinue
which the G67 is mounted. the spark. The main gas valve will not be energized
until the flame sensor detects the presence of the pilot
Use the G67B( ) only on rooftop, excess air, and power
flame.
vented gas burning equipment.
If the pilot flame goes out (with the thermostat still
When using the G67, the appliance or equipment must
calling for heat), the G67 will de-energize the main gas
be approved by a recognized testing agency in
valve and provide a continuous spark at the pilot
accordance with the applicable American National
burner’s electrode. When the pilot flame is re-ignited
Standards. See Specifications section. No other
and detected by the pilot flame sensor, the main gas
application is permissible.
valve is energized and the spark is shut off. The G67
The G67 solid-state ignition control lights a pilot burner ignition control de-energizes the pilot gas valve and
by a spark. Pilot gas is ignited and burns during each main burner gas valve when the thermostat stops
run cycle (intermittent pilot). Main burner and pilot gas calling for heat.
are extinguished during the Off cycle. All applications
must use a redundant main gas valve.
The main gas valve will not open until the pilot flame M ounting
has been proven by the sensing circuit. Should a loss Choose a location that provides the shortest, direct
of flame occur, the main valve closes and the spark cable route to the spark electrode, flame sensor
recurs within 0.8 seconds. assembly. Easy access to the terminals is desired for
wiring and servicing. The G67 may be mounted in any
position.
O perating Mode Definitions For G67A and G67B, refer to Figures 4 through 6 for
The following definitions describe operating conditions: wiring schematics/diagrams and Figure 7 for mounting
dimensions. For G67EG, refer to Figures 8 and 9 for
Trial for Ignition--Period during which the pilot valve
wiring schematic/diagram and Figure 10 for mounting
and spark are activated attempting to ignite gas at the
dimensions.
main burner.
Run--Main gas valve remains energized and the spark
is turned off after successful ignition.
Flameout--Loss of proven flame. Should a flameout
occur, the main valve closes and the spark recurs
within 0.8 seconds.

2 G67 Intermittent Pilot Ignition Controls Product Bulletin


Start Thermostat
Call for Heat

Flame Yes
Present?

No

Trial for
Ignition

Pilot
Flame
No Sensed?

Yes

Energize
Main Valve

Run

Yes De-energize
Flameout?
Main Valve

No

Yes Thermostat
Calling for
Heat?

No

De-energize Control
Pilot and Main Valves.

End

Figure 3: Sequence of Operation

G67 Intermittent Pilot Ignition Control Product Bulletin 3


Therm ostat
H igh Lim its
R W in this Line
O nly Internal W iring
E xte rn a l W irin g
6

R Flam e
24 V A C Q1 R3 S ensor
Input 1
R2
R1
Q 3
S park S ensing
C ircuit C ircuit 4
GR MV PV
GR
P ilot GR
B urner
G round GR 5
Jum per

Figure 4: Wiring Schematic for G67 Self-Checking Control

Th erm o stat

W R Y
H ig h Lim its
in th is L in e
O nly

24 P o w er
VA C S u pp ly
MV PV
P ilo t
B u rne r
Jum pe r G ro un d
5 G ro un d
Term ina ls

1 6 2 4 3
Flam e
S e nsor

H ig h Vo lta ge
C a ble

P o w er is w ired directly to R (C o m m o n) on th e
th erm o stat an d Te rm ina l 6 o n th e G 6 7.

Figure 5: Wiring Diagram for G67A( )

4 G67 Intermittent Pilot Ignition Controls Product Bulletin


Therm o stat

: 5 <

H igh Lim its


in this L ine
On ly

24 P ow er
VA C S upply
MV PV
P ilot
B urner
Ju m per Grou nd
5 Grou nd
Te rm inals
1 2 4 3

Y 75
Flam e
S ensor

H igh Voltage
C able

P ow er is w ired directly to R (C om m on) on the therm osta t.


Term inals 1 and 2 on th e G 67 are tied together intern ally.

Figure 6: Wiring Diagram for G67B( )

8 .89
0 .35

S p ark Te rm ina l
fo r R a ja h C on ne ctor
6 7.5 6
2 .66 Tw o H o le s fo r
2 2.6
0 .89 M ou ntin g S cre w s

4 .11
5 0.8
0 .16 2
2 .00 6 .35 Q uick C on ne ct
0 .25 Term in a ls

11 5 1 04 .9
4 .53 4 .13

2 2.3
0 .88

56 5 5.6
2 .21 5 .33 2 .19 5 .58
0 .21 0 .22

Figure 7: G67(A and B) Mounting Dimensions, mm (in.)

G67 Intermittent Pilot Ignition Control Product Bulletin 5


High Limits in Internal Wiring
this Line Only External Wiring

6
Thermostat

R W 2
Flame
24VAC K1a K2c K2 Sensor
Input 1
K2b
K2a
K1 3
7 Spark
Circuit Sensing
Circuit 4

MV PV Spark
Chassis Gap

7
Burner
Ground
5
Jumper

Figure 8: Wiring Schematic for G67EG Self-Checking Control

Pilot Burner/ Flame


Spark Igniter Sensor

Main Burner
Ground
Pilot Gas
Supply

CHASSIS
5

24V 7 Transformer
COM
THS 2
MV PV
M.V. 3 Limits in
Thermostat
Line Only Power
P.V. 1 Thermostat Supply
24V 6
SENSE 4

G67EG
Ignition Control

Figure 9: Wiring Diagram for G67EG

6 G67 Intermittent Pilot Ignition Controls Product Bulletin


7 .87 5 6.3 8
0 .31 2 .22

5 7.9 1
2 .28

6 .35 S p ad e Te rm in als
0 .25

7 7.7 2
3 .06

3 3.7 8
1 .33
5 .58
0 .22

1 9.5 5
0 .77

1 07 .95 11 6
4 .25 11 9.3 8
4 .57 4 .70

Tw o H ole s
4 .1 fo r N o . 8 M ach in e
0 .16 2 o r N o . 6 S h ee t M e tal
M ou ntin g S cre w s

5 .58 6 6.8 5 0.8


0 .22 2 .63 2 .00

Figure 10: G67EG Mounting Dimensions, mm (in.)

G67 Intermittent Pilot Ignition Control Product Bulletin 7


O rdering Information
G 67 _ _ - _ _
Customer-specific Requirements

1st Other 2nd


Letter Trial Time Features Letter Voltage
A Non-100% Lockout Self Checking G 24V 60 Hz

B Non-100% Lockout Non-Self Checking


E Non-100% Lockout Self Checking/EC Approval

The presence of a particular construction in this information does not guarantee its availability.
Consult Johnson Controls for available constructions.

8 G67 Intermittent Pilot Ignition Controls Product Bulletin


Notes

G67 Intermittent Pilot Ignition Control Product Bulletin 9


Notes

10 G67 Intermittent Pilot Ignition Controls Product Bulletin


Notes

G67 Intermittent Pilot Ignition Control Product Bulletin 11


S pecifications
Product G67 Non-100% Lockout Intermittent Pilot Ignition Control
Ignition Type Indirect
Ignition Source High voltage spark, capacitive discharge
Maximum High Voltage 1,220 mm (48 in.) recommended
Cable Length
Flame Detection Means Flame rectification
Flame Detection Types Remote sensing
Minimum Flame Current 0.2 microampere
Flame Failure Response 0.8 second, maximum
Time
Spark Gap 2.5 mm (0.1 in.) nominal
Ignition Trial Time Infinite
Power Requirements
Control 24 VAC, 50/60 Hz, nominal
Operation Current 0.15A nominal + valves
Contact Ratings
Main Valve 2A continuous, 5A inrush
Pilot Valve 2A continuous, 5A inrush
Ambient Operating and -40 to 66°C (-40 to 150°F)
Storage Temperature
Humidity 95% RH non-condensing
Types of Gas Natural, Liquefied Petroleum (LP), manufactured, mixed, or LP gas-air mixture may be used in a
well-vented or outdoor application.
Packaging Bulk pack supplied to original equipment manufacturer (individual pack options).
Bulk Pack Quantity 50
Bulk Pack Weight 12 kg (27 lb)
Agency Listing IAS (AGA, CGA) Certificate Number C2154020
EN/EC Type Examination Certificate Number 115687 (G67EG only)
Specification Standards ANSI Standard Z21.20
CSA C22.2-No. 199
EN 298 (G67EG only)
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from
misapplication or misuse of its products.

Refer to the G67 Series Technical Bulletins (LIT-121190 and LIT-121191) for necessary information on the installation, use, and servicing of this
product.

Controls Group www.johnsoncontrols.com


507 E. Michigan Street FAN 435.0
P.O. Box 423 Heating Line Product Guide
Milwaukee, WI 53201 Printed in U.S.A

12 G67 Intermittent Pilot Ignition Controls Product Bulletin