You are on page 1of 4

Power Factor Testing in Transformer Condition

Assessment - Is There a Better Way?


Alex Rojas, Member, IEEE

localized insulation resistance. Conversely, when utilizing


Abstract- Condition assessment of transformer core-coil as- AC, gradients are distributed according to another
sembly, at the factory or in the field, includes one fundamental material/geometric property - namely capacitance.
test: insulation Power Factor (also known as Dissipation Factor or The second method, an AC test, was typically referred to
Tan Delta). Although this test can be performed with decades old
technology, users have voiced their need for safer, faster, and more as the measurement of "Capacitance and Power Factor"
portable test devices. This need calls for a review of what makes (C&PF) in North America and as "Capacitance and
older test equipment operate at higher voltages and currents. The Dissipation Factor" (C&DF) in Europe. To this date,
geometric and material properties examined when performing specialists argue about the value of each test, DC vs. AC,
such tests is discussed. Why the need for higher test voltages when which provides more information, and which is more useful in
measuring insulation power factor: is it interference mitigation
or true material condition assessment? Modern high-power elec- forecasting the life of electrical insulation.
troniks and microprocessor controllers offer alternative methods At the factory, fully assembled transformers are tested for
for packaging test instruments while maintaining accuracy, and compliance to previously determined performance levels.
improving safety, speed and convenience.
Most end-users refer to domestic or internationally accepted
standards/guides (i.e. ANSI, IEC, NMX, etc.) to communicate
Index Terms -- AC Test, Capacitance, Dielectric, Dissipation their specific factory test requirements and performance
Factor, Field Test, IGBT, Insulation, Power Factor, Noise,
Transformer. levels. In defining tests for medium/large power transformers,
many users make exceptions to standard test levels and
procedures in order to fit their custom design requirements.
I. INTRODUCTION Once in the field, acceptance tests are performed prior to
D emand for methods and instrumentation to determine the putting the power transformer into service. These are
condition of insulating components, assembled into principally done to determine if damage in shipping has
power apparatus, came with the vast expansion of electrical occurred and to confirm proper reassembly of some
power systems during the first half of the twentieth century. components taken out for shipping. Another very valuable
Insulation failures prompted the industry to develop and product of initial field testing is that base line results will
implement maintenance programs. The electrical industry was provide the best yardstick for determining the transformer's
on a steep learning curve and system voltage such as 110 kV future condition. Further, this initial assessment is being
were considered very high at that time [1]. As it is today, early conducted under field conditions and using similar test
testing methods and instruments were meant to assess the equipment that will be utilized in subsequent testing.
condition of the insulation system at the time of testing. Numerous field test protocols are observed in determining
Further efforts were made to predict the service life of the condition of the material and geometry in the transformer
equipment based on collected data. However, electricity was a dielectric and conductive (electrode) components. Test
relatively new field at that time and long term deterioration of programs include all or part of the following: winding and
insulation was less well understood. bushing power factor, leakage reactance, winding turns ratio,
Chronologically, DC insulation test instruments were winding resistance, core excitation current, core loss and
employed first. Then and now, test sets measured insulation excitation power factor, core ground, Sweep Frequency
resistance in MEGOHMS and were/are typically conducted at Response Analysis, and more.
higher voltage levels on equipment that was designed to The remainder of this document focuses on arguably the
operate at higher potentials. One marked difference versus most widely performed transformer condition assessment field
subsequent AC test methods is that voltage stress is distributed test: Capacitance and Power Factor (C&PF).
distinctively. When applying a DC voltage across the
terminals of the equipment under evaluation gradients
developing within its assembly are distributed according to the

Alex Rojas is with Megger, Dallas, TX 75237 USA (e-mail:


alex.rojasamegger.com).
1-4244-0288-3/06/$20.00 (©2006 IEEE
2

II. TEST SPECIMEN PROPERTIES ammeter. The power factor definition in equation (1) applies
C&PF testing of electrical insulation has been embraced by equally in power delivery to electric loads, as it does to
many in the insulation field as it provides information on the insulation systems. However, optimum operating points are at
dielectric constant of the insulating materials as well as the opposite positions. When designing/operating power delivery
dielectric losses. The dielectric constant is an intrinsic material systems, we strive for maintaining the PF closest to unity.
property that influences the capacitance between two Whereas, when designing/operating insulation systems we
electrodes at different potential. In turn, the capacitance target a number closest to zero.
influences the voltage gradient distribution within assembly Figure 2 helps visualize the current vector which develops
components. Uneven concentration of high voltage gradients from applying the above described test voltage V. The current
in the insulation, typically measured in kV/mm, contributes to taken by an ideal capacitor (no losses, Ir = 0) is purely
increased dielectric power loss where the gradient is higher. capacitive, thus leading the voltage by 900 (0 = 900). In
In turn, higher power loss heats the insulation. Localized hot practice, no insulation is perfect but has a certain amount of
spots may develop which start deteriorating the insulation that loss, and the total current I leads the voltage by a phase angle
would eventually lead to dielectric failure. 0 (0< 900). Some find it more convenient to use the dielectric-
For example, one of the byproducts of insulation loss angle 6, where 6 = (900 - 0). For low power factor
decomposition is water. As water content in the insulation insulation Ic and I are approximately the same magnitude
increases, so does its power loss (Watts). The detection and since the loss component Ir is very small.
removal of moisture from equipment is very important, as the Basic trigonometry yields the following relationships:
presence of moisture causes the insulation to deteriorate faster.
As a transformer with a 2.5% moisture content ages ten times Power Factor = cos 0 Ir (2)
faster than the transformer at 0.25% moisture, it is imperative I
to detect and rectify such a situation [1]. and the dissipation factor is defined as:
In practical terms, a C&PF test instrument sees a two
winding transformer as if it were a three terminal capacitor Dissipation Factor = tan 5 Ir (3)
illustrated in figure 1. The "H" electrode represents all HV Ic
conducting components (three windings tied together in three-
phase equipment). Likewise, the "L" electrode represents all
LV conducting components. The transformer tank, typically
grounded, is represented by the electrode "G". Z

mI
W

I 0

Fig. 2. Test Current Components


I

Power factor is particularly recommended for detecting


moisture and other loss-producing contaminants in
Fig. 1. Transformer Without Tertiary Windings transformer windings and bushings. Some argue that the
power-factor test is more revealing than the DC insulation-
In the simplest terms, power factor expresses the ratio of
resistance test when there is a high-loss dielectric in series (as
values obtained from applying AC voltage across any in a transformer winding surrounded by oil), and is less
capacitor equivalent component illustrated above: influenced by surface leakage components. Other users have
Power Factor Watts absorbed in insulation reported cases where high-power-factor readings indicated
Applied Voltage x Charging Current moisture in the windings, while the oil dielectric tests were up
to standard [2].
Therefore, it is not surprising that early instirument Oil-paper insulation systems exhibit flat capacitance and
configurations for conducting this test were made up of a set loss curve with respect to test voltage. Thus, measurements at
of the following components: wattmeter, voltmeter and voltages lower than rated could be readily used to represent
3

the insulation characteristics at rated voltage. Dry-type noise ratio. Some went even further to device test sequences
insulation, however, exhibits an increase in power factor where 1OkV is applied at frequencies other than the
values within 2.5 kV and 10 kV. Motors, generators or fundamental 60 or 50 Hz. One of these methods initially
smaller transformers with dry assemblies, have been typically applies test voltage at lower than power frequency; to
tested at several voltages in order to determine the tip-up for overcome the frequency bias, a second test is performed at
the insulation. Such tip-up may be at 100%, 50% and 25% of higher than power frequency. The test result is the average of
the phase-to-phase voltage, or 100%, 50% and 25% of rated both. Still another approach uses a modulated test voltage,
phase voltage. avoiding the power frequency by producing test voltage with
two frequency components - one above and another below the
III. TEST INSTRUMENTATION AND TECHNIQUES power frequency.
Realizing the benefits of C&PF testing, field test Today, a classic application for lower test voltage power
instrumentation and techniques operating at lower voltages factor test instruments is in the drying-out process at
were devised. Early on, a test voltage of 2.5 kV was used. The manufacturing operations. The transformer is heated under
selection of such test voltage was justified by two criteria: partial vacuum conditions to vaporize and remove moisture
* It was sufficiently high to provide an acceptable signal- from the insulating material (see figure 3). Outputting a test
to-noise ratio in (then) typical field applications. voltage of approximately 28 Volts the instrument is connected
* The typical insulation to be tested was an oil-paper to the transformer during this process. The power factor of
assembly. core and coil assembly drops as the paper dries out (typically
Traced back to 1915, the classical instrument circuit from 30% to 0.5%). The power factor reading from the
configuration for performing C&PF testing is the Schering instrument is used to determine when to terminate the process.
Bridge with a null detector. Today, it continues to be Proper insulation condition monitoring is accomplished
manufactured by various companies, but due to operating without complicating the process to make provisions for high
limitations; it is primarily used in standards and test voltage testing.
laboratories. A notable variation from the basic configuration
is the "Inverted Schering Bridge" which was cleverly
packaged for commercialization using the capacitance
between the grounded case and the bridge assembly as the
reference capacitor.
The next worthy happening was the invention of the
"transformer ratio arm bridge" (TRAB). This circuit measures
capacitance (C) and dissipation factor (DF). The bridge is
useful only at one frequency and its readout is equivalent to
the series connected RC circuit. The loss (W) needs to be
calculated from F, C & DF.
The latter end of the twentieth century brought with it
important developments in analog as well as digital
measurement technologies. These technologies made it
possible for a variety of test set configurations to be realized. Fig. 3. Core & Coil Assembly at Dry-Out Chamber
One such a configuration is the combination of a bridge circuit
with readout of the residual value. Another configuration is
that of a voltmeter-ammeter-wattmeter (VAW) using digital V. NEW INSTRUMENT DESIGN ALTERNATIVES
and DSP technology. Such technology has been very Since the driver for utilizing higher test voltages is to
effective especially when combined with test frequencies attenuate the effect of conducted and emitted noise; future
other than the power frequency. work should focus on identifying contemporary noise
canceling techniques. The industry would benefit from novel
IV. TEST VOLTAGE EVOLUTION approaches to filter-out interference encountered in the field
As the electric power transmission and distribution industry (i.e. high voltage substations, manufacturing sites, etc.).
evolved it increased system operating voltages to transmit Traditional tools of harmonic analysis and cancellation
more power. Operators managed to keep line losses as low as techniques are generally based on Fast Fourier Transforms
possible by keeping line currents at acceptable levels, while (FFT) which assume that only harmonics are present and the
transmitting larger amounts of power at higher voltages. This periodicity intervals are fixed. However, periodicity intervals
new field test environment brought on a new challenge to test in the presence of interharmonics are variable and very long
instrumentation manufacturers: immunity to electrostatic [5]. New signal analysis methods are being proposed to take
interference. Consequently, the 2.5 kV test level was this characteristic into account.
increased to 10 kV in order to provide an acceptable signal-to- Those instrument users wanting to test at higher voltages
4

may benefit from power electronics that would readily and VII. REFERENCES
reliably control the magnitudes of their test voltage, current, [1] Oleh Iwanusiw, "Capacitance and Power Factor testing of Electrical
and frequency. Along with the rapid evolution of digital Insulation", Application Note, August 2005.
signal processors (DSP) the power industry has seen an [2] US Bureau of Reclamation, "Testing Solid Insulation of Electrical
Equipment", Volume 3-1, 2000
evolution in high power switching devices that these DSP [3] Katsumi Satoh and Masanori Yamamoto, "The Present State of the Art
devices would control. High-power semiconductors have in High-Power Semiconductor Devices", Proceedings of the IEEE, Vol.
evolved from early thyristors, to gate turn off thyristors 89, No. 6, June 2001.
(GTOs), gate commutated turn off thyristors (GCTs), and [4] Sibylle Dieckerhoff, Steffen Bernet, "Power Loss-Oriented Evaluation
of High Voltage IGBTs and Multilevel Converters in Transformerless
more recently high/low voltage insulated gate bipolar Traction Applications", IEEE Transactions on Power Electronics,pp.
transistors (IGBTs) [3]. For example, High-voltage IGBT 1328-1336, Vol. 20, No. 6, November 2005
semiconductor technology has matured and been embraced by [5] Z. Leonowicz, T. Lobos, and Jacek Rezmer, "Advanced Spectrum
Estimation Methods for Signal Analysis in Power Electronics," IEEE
most in the electric power network industry and many in the Transaction on Industrial Electronics, pp. 514-519, Vol. 50, No. 3, June
traction business [4]. Single-unit commercially available 2003
voltage classes include 3.3 kV, 4.5 kV and 6.5 kV [6] Oleh Iwanusiw, "Measuring Transformer Winding Resistance",
Application Note, May 2001.
components. Such offering provides test instrument power
electronics designers with new alternatives to package high-
voltage power supplies. Potential savings in assembly weight, VIII. BIOGRAPHY
size and cost are very real. Future work would involve Alex Rojas is a Senior Applications Engineer at
identifying the best technology for packaging into portable Megger. He supports internal and external
test instruments. customers in the use of test instrumentation for
condition assessment of substation and distribution
equipment. He joined Megger in 2004 from Beacon
VI. CONCLUSIONS Power Corporation where he was Applications
Engineering Group Leader (manager) contributing
Capacitance and power factor testing of transformers has in the development and application of power quality
been an integral part of condition assessment at the factory solutions for the utility and distributed generation
and in the field for many decades. As electric grid voltages markets. From 1996 until 2001 he was an R&D
increased, conducted and radiated noise in measurement consulting engineer at ABB's US technology center in Raleigh, North
Carolina. At ABB he led projects ranging from applied research through
environments has posed a challenge for obtaining stable design and manufacturing implementation of new power distribution
readings. Capacitance and power factor measurements in equipment. His projects included long-term R&D assignments in Europe and
paper-oil insulation systems are independent of applied product launches throughout South/Central America. Prior to this role, he
served five years as design engineer at an ABB transformer design and
voltage in the 28V and lOkV range. The implementation of manufacturing facility which later became Waukesha Electric Systems. In
alternative noise-reduction techniques and modern high-power Waukesha he was responsible for the electrical, electromechanical, and
electronics offer promising packaging improvements. The thermal design; as well as test program definition of oil-filled power
transformers. Mr. Rojas has an MSEE with highest honors from Michigan
continued implementation of these technologies, along with Technological University (thesis topic: Dielectric Breakdown in Board/Oil
evolving test methods, will lead to the improved safety, speed Interfaces), and a BSEE from The Ohio State University. Mr. Rojas is a
and convenience of test instruments. member of NETA and IEEE. Email: alex.rojasC&meggencom

You might also like