You are on page 1of 11

This article has been accepted for inclusion in a future issue of this journal.

Content is final as presented, with the exception of pagination.

Arc Flash in the National


Electrical Code
DO ARTICLES 240.87 AND 240.67 ACHIEVE THEIR INTENT AND GOALS?

XXXXX

By Marcelo E. Valdes, Steve Hinton, and The NaTioNa l elecTr ica l code (Nec) h as
Francisco Martinez included requirements for arc-flash-related labeling for
several code cycles [1]. increasingly rigorous requirements
for specific arc-flash-related protection attempt to reduce
any arc-flash hazards to which personnel may be exposed.
Digital Object Identifier 10.1109/MIAS.2018.2868354
They may be exposed to arc-flash hazards during planned
Date of publication: 5 November 2018 energized work or accidentally at any time. The risk-control

2 IEEE Industry Applications Magazine œ J A N U A RY / F E B R U A RY 2 0 1 9 1077-2618/19©2019IEEE


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

mechanisms added to the Nec in recent times include


additional signage requirements and two articles that Table 1. NEC 240.87
intend to reduce arc-flash hazard by decreasing clearing
For Circuit Breakers, One of the Following Means Shall Be
time for circuits rated 1,200 a or greater whether pro- Provided:
tected by circuit breakers or fuses. This article discusses
these recent protection requirements and their intent and 1) ZSI
potential practical effects as well as how to ensure that 2) Differential relaying
the protection this language seeks to provide is included
3) ERMS with local status indicator
in the electrical power distribution system.
4) Energy-reducing active arc-flash mitigation system
Overview of Clearing Time Methods 5) An instantaneous trip setting that is less than the available
currently, National Fire Protection association (NFPa) 70, arcing current
the 2017 Nec [1], has two sections addressing required
6) An instantaneous override that is less than the available
minimum arc-energy reduction for low-voltage fuses and arcing current
circuit breakers rated 1,200 a and higher. For fuses, sec-
tion 240.67 takes effect 1 January 2020. section 240.87 is 7) An approved equivalent means
in effect now for circuit breakers. Both sections require
documentation available to those authorized to design,
install, operate, or inspect the installation as to the loca- Table 2. NEC 240.67
tion of the circuit breaker or fuse. Both sections offer
methods to reduce clearing time (for implied arc-flash A Fuse Shall Have a Clearing Time of 0.07 s or Lower at the
reduction) and are shown in Tables 1 and 2. Available Arcing Current, or One of the Following Shall Be
Provided:
These methods can be used to reduce clearing time,
but they are all very different solutions. how does a 1) Differential relaying
designer know if the specified method provides the 2) ERMS with local status indicator
desired reduction of arc-flash incident energy (ei)? The
methods described may be divided into two categories: 3) Energy-reducing active arc-flash mitigation system
1) those methods that expressly list what is needed to 4) An approved equivalent means
ensure that the protection threshold will sense the
expected available arcing current
2) those methods that imply such needs but do not 5) administrative controls
expressly state them. 6) personal protective equipment (PPe).
This is an important distinction because adding a The first three methods do not require any specific
mechanism to reduce clearing time does not ensure its action, understanding, or comprehension on the part of
effectiveness unless the added protection operates when the personnel benefiting from the control measure as
needed (i.e., at the full range of expected arcing current they are automatic or by default. however, the second
in the protected circuit). To comply with the intent of the three do require active personnel participation, compre-
code, the ability for the control measures to operate at hension, skill, or training. That makes the second set of
the expected available arcing current is the key operat- measures fallible and subject to human error. hence, any
ing parameter that must be determined, regardless if it is hazard control measure in the upper half of the list is
stated in the Nec. To implement one of the stated mecha- considered more robust or better than those in the sec-
nisms without knowing if it will work may comply with ond half.
the letter of the code but not with its intent. in addition, a The first control measure, elimination, refers to any
robust and reliable solution will use a lower threshold due measure that fully eliminates the hazard. The second,
to the potential variability of the arcing current. substitution, refers to any measure that substitutes less in
lieu of a more hazardous situation. The third, engineered
How to Categorize and Evaluate Solutions controls, is any kind of automated system that, when
NFPa 70e-2015 [2] describes the hierarchy of risk-control operational, provides an automatic reduction of the haz-
methods specified in american National standards insti- ard on a continuous basis without any interaction from
tute (aNsi)/american industrial hygiene association Z10 the regularly exposed personnel or anyone acting on their
[3], Occupational Health and Safety Management Systems. behalf. it is important to note that engineered controls
The hierarchy lists the following six risk-control measures: tend to require maintenance and possibly adjustment to
1) elimination ensure they operate as expected during the useful life of
2) substitution the equipment.
3) engineered controls The fourth category, awareness, includes all methods
4) awareness to instruct, advise, warn, or impart skills to operating

J A N U A RY / F E B R U A RY 2 0 1 9 œ IEEE Industry Applications Magazine 3


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

personnel so they can reduce their risk. in this category serving utility or the end user. higher fault current will
are warning signs, job site meetings, training, and so on. cause higher incident energy for fixed clearing times pro-
administrative controls, the fifth category, include steps portional to available fault current. lower arcing current
or actions personnel can do prior to exposure to a hazard can result in protection operating more slowly and higher
to lower their risk. Turning a switch on or off, positioning incident energy due to the increased operating time of the
a lever, and ensuring the status of a device or apparatus protective device.
prior to the task would fall under this category. The last The third parameter in arcing current calculations is
category, PPe, entails a person wearing PPe to minimize the equipment bus/conductor gap. The arc current must
the negative effects of any unintentional event that may sustain itself across the gap. ieee 1584-2002 provides
occur during exposure. a table of typical gaps for various equipment types (see
This article will refer to this hierarchy of risk-control Table 3).
methods to explain the measures in the Nec articles. Most arc-flash studies use a combination of these
values. in equipment, however, different values could
Arcing Current: How Low Is Low Enough? be found, both larger and smaller, and this provides an
ieee 1584-2002, IEEE Guide for Performing Arc Flash additional source of variation in arcing current calcula-
Hazard Calculations [4], and ieee 1584.1 provide formu- tions. The 100–85% range defined in ieee 1584-2002 for
las and methods for calculating arc-flash currents to deter- arcing current only attempts to account for the variance in
mine arc-flash incident energy and arc-flash boundaries. the experimental data from the arc-flash research prior to
The formulas are used to calculate a value referred to as 2002. all other potential sources of variance are not con-
100% arcing current and another at 85% of the first value. sidered in the current ieee model.
The calculations are based on three factors used as vari- sources of arcing current variance may include but are
ables within the equations: not limited to
● system voltage (nominal) ● the chaotic nature of an electrical arcing fault

● available three-phase short circuit current ● variable system topology and varying short circuit cur-

● equipment bus/conductor gap. rent


The first parameter, system voltage, is easily deter- ● incorrect assumptions regarding conductor impedances

mined. The second is often estimated at preliminary ● conservative utility high-fault-current assumptions

phases of a project design. and even in the later stages ● conservative fault study methods by power systems

of a project, the short circuit current value may depend engineers


on several assumptions, switching or operating scenarios, ● incorrect measurements of system conductors

and worst-case tolerances. For the short circuit evaluation ● incorrect assumptions about regenerating sources

of equipment, power system engineers performing short ● a variance in source voltage due to system loading

circuit calculations purposely drive any potential error ● incorrect assumptions about bus/conductor gap or arc

toward higher values because that is conservative from environment (i.e., size of equipment enclosure or com-
an equipment-rating perspective. ensuring properly rated partment).
equipment, per Nec 110.16, involves calculating maxi- These sources of variance and others can yield arc-
mum short circuit fault current and evaluating it against ing current that is slightly higher or lower than expected.
the withstand and interrupting ratings of the electrical slightly higher current can yield proportionately higher
distribution and protection equipment. conservatism arc-flash incident energy, but slightly lower arcing cur-
from the equipment ratings perspective is not necessar- rent can yield significantly higher incident energy if the
ily appropriate from an arc-flash calculation perspective. protection reacts more slowly because it does not sense
For arc-flash calculations, it is important to have the cor- the arcing fault as expected. The more sensitive protection
rect value of fault current. it is best to have the expected is, the more robust it may be considered, which means
range of fault current available because it may vary during it is more likely to operate for the actual arc fault cur-
the day due to different topologies used, either by the rent. ieee 1584.1 [4] instructs that, to calculate arc flash,
consideration should be made for overly conservative
source fault current and whether motors are turned on
Table 3. A portion of IEEE 1584 Table 4, from p. 12
or off. it important to note that ieee 1584 is undergoing
System Typical Gap Between revision, and the revised version will include additional
Voltage (kV) Equipment Type Conductors (mm) sources of variance both in arcing current and incident
0.208-1 Open air 10–40 energy. When the new model becomes available, the
reader is encouraged to consider it within the context of
Switchgear 32 this article.
MCC and panels 25 Figures 1 and 2 show the ieee 1584-2002 calculated
85% arcing current as a percentage of short circuit cur-
Cable 13
rent for various gap assumptions. Table 2 in ieee 1584

4 IEEE Industry Applications Magazine œ J A N U A RY / F E B R U A RY 2 0 1 9


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

lists typical bus gaps for different equipment classes. For the line side of the main device [5]. But when the main
low-voltage switchgear, the commonly used value is 32 device is fed from a utility-owned transformer, options
mm. For switchboard and motor control centers (Mccs), are limited. Generally, it is best to isolate the main device
the typical value suggested is 25 mm, and most engineers to minimize 1) exposure when energized work is being
performing studies use this value in switchboards and performed on the load side of the main device and 2) the
Mccs. Most moderately sized commercial and industrial possibility of an arcing fault on the load side (location 2 in
power systems tend to operate with available short circuit Figure 3) propagating to the line side.
currents between 30 and 50 ka. a conservative assump-
tion (i.e., biasing toward a low arcing current value) for Solution Types
arcing current could be approximately 40% for 480-V The hazard controls listed in the Nec articles are either
systems and 20% for 208-V systems. however, it is best to engineered or administrative controls per the hierarchy
have a study done for short circuit, protective device coor- identified in NFPa 70e [2] and aNsi Z10 [3]. The energy-
dination, and arc-flash so the values for arcing current can reducing maintenance switch is an administrative control.
be used to determine protective device settings. The other measures are engineered controls.

Arcing Current Where?


The last question regarding arcing current is where is
the arc? For a main circuit breaker, the arcing current 50%
may be the bus protected by the main circuit breaker. in 13 mm, 85%
25 mm, 85%
most cases, the entire bus is considered to have the same 40% 32 mm, 85%
arc-flash incident energy value. however, for a feeder in Ia as % Ibf 40 mm, 85%
a switchboard, the arcing current could be at the circuit
breaker’s load-side terminals (location 3 in Figure 3) or 30%
at the far end of the feeder conductor (location 4 in Fig-
ure 3). That downstream arcing current (location 4) is 20%
probably much lower due to the conductor impedance.
it is also possible that the load-side equipment is more
10%
likely to be serviced while energized than the overcur-
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105
rent protection’s secondary terminals (location 3) if it is
Ibf (kA)
distribution equipment feeding multiple loads. hence, the
protection should consider the lower-arcing current at the
far end of the conductors. FIGURE 2. A plot of 85% arcing current (I a) as the percentage of
available bolted fault current (I bf) for a 208-V system, per the IEEE
another concern is the arc-flash current at the line
1584-2002 model.
side of main devices (location 1 in Figure 3). When the
main device is fed from a source such as a substation
transformer within the owner’s system, there are several
measures that can be taken to provide protection for
Source

70%
1 Switchboard
60%
2,000 A
2
Ia as % Ibf

50%

40% 1,200 A 1,200 A


3
13 mm, 85%
30% 25 mm, 85%
32 mm, 85%
40 mm, 85%
20% 4
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
105

Load
Ibf (kA)

FIGURE 1. A plot of 85% arcing current (I a) as the percentage of


available bolted fault current (I bf) for a 480-V system, per the IEEE FIGURE 3. Possible arcing fault locations relative to overcurrent
1584-2002 model. protection in equipment.

J A N U A RY / F E B R U A RY 2 0 1 9 œ IEEE Industry Applications Magazine 5


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

Engineered Controls especially true if the designer is not taking advantage of


modern instantaneous selective coordination methods
Instantaneous Overcurrent Function and recently introduced by manufacturers into the Ul and
Override Function Below Estimated Arcing Current National electrical Manufacturers association markets
in North america, circuit breakers are listed under two [9]–[11].
industry standards:
● Underwriters laboratory (Ul) 489, Molded-Case Circuit Zone-Selective Interlocking
Breakers, Molded-Case Switches, and Circuit-Breaker Zone-selective interlocking (Zsi) is commonly avail-
Enclosures [6] able from all circuit breaker manufacturers. in all cases,
● Ul 1066, Standard for Low-Voltage AC and DC Power enabling the feature allows circuit breakers at the sec-
Circuit Breakers Used in Enclosures [7] ond and higher tier to operate faster than if they did not
The molded-case class may also be divided into implement Zsi. however, the lowest-tier devices will not
traditional molded-case circuit breakers (MccBs; see operate any faster. regardless if Zsi is implemented, it is
ieee 3004.5 [8, p. 2]) and insulated-case circuit break- required that the protection thresholds be set sufficiently
ers (iccBs; see ieee 3004.5 [8, p. 2]). MccBs always sensitive enough to detect the expected arcing current for
have instantaneous protection. For some larger MccBs, the entire protection zone.
manufacturers may state instantaneous protection may Zsi is a way to improve clearing time without sacri-
be turned off, but an instantaneous override will always ficing system selectivity. Manufacturers may implement
be present at a relative low multiple of the frame size, Zsi in different ways so the actual capabilities may vary,
typically not higher than 15 times the frame size. low- but the basic principles are consistent. Figure 4 shows
voltage power circuit breakers (lVPcBs; see ieee 3004.5 a simple Zsi scheme. The basic premise is that lower-
[8, p. 2]) may have a high range of adjustability in their and upper-tier devices detect the same fault current; the
instantaneous function, maybe more than 15 times the lower-tier device (fault location 2 in Figure 4) simultane-
sensor rating. Most lVPcBs will allow the adjustable ously initiates its protection logic, sending a signal to
instantaneous protection to be turned off. however, many the upper-tier device indicating that it is in the process
will have a fixed override that cannot be turned off. some of asserting a trip and protecting. The upper-tier device
will not have an override; hence, when the user-adjustable receives the signal (also known as a restraint signal) and
instantaneous function is turned off, no instantaneous shifts its timing from unrestrained (in-zone protection) to
protection is present. iccBs share MccB and lVPcB restrained (backup protection). depending on the device,
characteristics but always implement an adjustable instan- the restrained protection may be adjustable by the user,
taneous protection or override or both. whereas the unrestrained protection is automatic, or
regardless of the type of circuit breaker, it is possible both may be user adjustable. When the fault location is
that the instantaneous function could be set above the in position 1 in Figure 4, the 2,000-a main should oper-
available arcing current, resulting in higher clearing times, ate its protection at the faster unrestrained timing point
especially in smaller, weaker, or lower voltage systems since no restraint signal was received. The Zsi scheme
and when circuit breakers are larger. in terms of device improves the protection provided by the main with the
selectivity expectations for the system, if lVPcBs are used assistance of the Zsi function in the 1,200-a feeders.
within multiple coordination tiers, then it is more likely however, the protection provided by the 1,200-a feeders
that there will be a desire to set instantaneous protection is not improved, even though the devices are part of a Zsi
to a high (insensitive) level or to disable it. This will be scheme. The 1,200-a feeders may meet the letter of the
code text but not its intent.
Modern Zsi offers significant enhancements for pro-
tection [12]. Zsi implementations in advanced trip unit
Switchboard systems may provide various ways to test the Zsi system,
2,000 A Main
which has traditionally been a concern when installing
Restraint such systems. When installing a Zsi system, it is impor-
Fault 1 Signal tant to verify that it is wired correctly and signals are
Current
getting to the correct devices. Generally, if the wiring is
damaged upstream, devices will revert to the unrestrained
1,200-A Feeder
timing and, hence, protect well, but selectivity may be
1,200-A Feeder
compromised.
2
Bus Differential Protection
Bus differential protection works on the simple concept
FIGURE 4. A simple three-circuit breaker ZSI scheme with two 1,200- known as Kirchhoff’s current law. simply stated, for this
A feeders providing a restrain signal to a single 2,000-A main. application, it means that all of the measured currents into

6 IEEE Industry Applications Magazine œ J A N U A RY / F E B R U A RY 2 0 1 9


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

a bus must balance the measured currents leaving it. any code-defined requirements for this function, there are no
imbalance in current, above the programmed threshold, performance requirements, just that they must be provid-
must be a fault. in a differential protection scheme, the dif- ed. Protection can only work as intended if it is set sensi-
ferential relay is connected to current sensors that measure tive to the available arcing current magnitude. The benefit
all of the power coming in, sources, and power going out of these switches is that they generally have a broad range
to loads. a fault below a feeder, such as fault 2 fed by the of adjustability and should be able to be adjusted to be
1,200-a feeder shown in Figure 4, has power measured sensitive enough to achieve acceptable arc-flash reduc-
going into the main bus and going through the feeder. The tion. however, a responsible party must establish what
differential relay will not sense that current as a fault. a the expected arcing current is and ensure the protection is
fault in location 1 on the bus in Figure 4 will cause power adjusted correctly. once commissioned, maintenance per-
to flow into the bus and be measured at the main circuit. sonnel should only need to enable and disable the func-
however, neither feeder is carrying the power out of the tion as prescribed in the planned task procedures.
bus, and the differential relay will sense the bus fault
and signal the main circuit breaker to open. like the Zsi Indication and Control Local to What?
scheme described previously, a differential scheme that Maintenance switches should be used with indicator lights.
includes the three circuits shown in Figure 4 will provide The code states that a local indicator must be provided,
additional protection for the main bus but not for the but the text is not specific as to what should be local. does
feeder circuits. To determine the exact zone of protection it need to be local to the overcurrent protection device
provided, the equipment drawings must be examined, (ocPd) being affected or to the remote equipment being
with the exact location of current transformers and circuit protected? Good engineering practice would dictate that it
breakers noted. again, the letter of 240.87 may be satis- should exist where the protected equipment is. however,
fied, but the intent is not. like any other protection, the the switchboard manufacturer, if not given specific direc-
threshold for operation must be below the available arcing tions to the contrary, will often include it near the ocPd
current fault expected within the target zone of protection. being controlled by the switch. Most importantly, the per-
Use of shunt trips and lockout relays can add to the total son who is relying on that protection should be aware of
clearing time, negatively impacting the arc-flash reduction. its status and what circuit or equipment is being protected.
To facility operators, it may be important to know if the
Administrative Controls protection is accidentally left on when not needed.
Within the hierarchy of hazard control measures, admin- The maintenance control switch should have test pro-
istrative controls are second to last (with last being least cedures for confirming that the circuit breaker or relay
effective). The reason for this is that they are very depen- being controlled has received the signal and processed it
dent on the behavior of the person implementing the con- correctly. These should be followed up on initial start-up
trol. For example, a person and at regular intervals afterward. This could be referred
● could forget to implement it to as positive feedback of status. The switch should be
● might not be sufficiently trained to know how to oper- lockable so it can be properly locked in the on state by
ate it maintenance personnel.
● might not be sufficiently trained to know the need to This function can temporarily compromise coordina-
operate it tion, until it is disabled. Users are often concerned about
● might not know that his or her work task could have forgetting to turn this off after a task, and an obvious
been incorrectly planned with the administrative con- indication of the status is often designed into the system.
trol accidentally omitted indications, such as tower lights evident through the elec-
● could operate the incorrect control trical room, sound alarms, and even e-mails to supervi-
● could operate it at the wrong time sory personnel, have been used to ensure a maintenance
● might not know the control could be inoperative. switch is not left on indefinitely. similar measures should
The possibility of human error will lower the value of be used to ensure that a maintenance switch is used
an administrative control, relative to fully automated solu- when needed. The manufacturer should be consulted for
tions, regardless of how effective the control is in mitigat- device implementation information because wiring and
ing the hazard. see aNsi Z10 [3] for further discussion. space requirements may vary.

Energy-Reducing Maintenance Switching What About the Arc-Flash Label?


with Local Status Indicator another consideration when relying on an energy-reduc-
ing maintenance switch to provide lower levels of arc-
Sensitive to What? flash incident energy is whether that lower level should
energy-reducing maintenance switches are offered by cir- be reflected on the NFPa 70e defined arc-flash label [2,
cuit breaker manufacturers and even by at least one manu- sec. 130.5(d), p. 28] installed on the equipment. There
facturer of fused Ul 977 listed power switches [13]. in the are many opinions about this subject. one argument is

J A N U A RY / F E B R U A RY 2 0 1 9 œ IEEE Industry Applications Magazine 7


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

that arc-flash labels should not be ambiguous or complex arc-flash mitigation system is. however, there are sev-
and should be conservative in case the reader is not fully eral possibilities should the authority having jurisdiction
aware of proper procedures or inadequately trained. (ahJ) choose to accept them. components of such sys-
tems may include
Administrative Procedures Require Qualified Personnel ● for sensing: light-sensing relays as event detectors and

and Task Planning controllers or overcurrent relays to sense arcing current


The better protection afforded by the energy-reducing ● for interruption: low-voltage circuit breakers, medium-

maintenance switch can be reflected in the data provided voltage circuit breakers, low-voltage fuses, medium-
by the arc-flash study and form part of the risk assess- voltage fuses, crowbars to divert energy and collapse
ment [2, sec. 130.5, p. 25] required to plan an energized system voltage, or combinations of these.
work task [2, sec. 130.2(a), p. 24]. The other argument arc-flash relays are usually able to directly sense the
is that the maintenance function is embedded in the light from an arc-flash event near the sensor location [14].
equipment and always available to be used, so the better These devices are fast and considered to be very good at
protection can be reflected in the arc-flash label, or a sec- sensing an arcing fault event. however, they have some
ond label, that clearly indicates the incident energy with drawbacks. They can unexpectedly operate from the light
the switch turned on or off. however, this may not be emanating from a circuit breaker interrupting a remote
the case for equipment fed by multiple sources involving fault [15]. Furthermore, they can sense within an equip-
multiple energy-reducing maintenance switches, unless ment enclosure very well but do not sense a fault at the
they are coordinated in some manner. a concern may also far end of a conductor feeding remote equipment. in some
be the improper use of an energy-reducing maintenance cases, it may be possible to prevent a nuisance operation
switch by unqualified personnel not aware of the system’s due to an interrupting circuit breaker within the enclosure
limitations. some of the limitations are the following. using Zsi restraint from the trip unit controlling the circuit
● Neither a circuit breaker nor its load is made safe using breaker [12, c, p. 1643] or via other interlocking methods.
the switch. The protection provided by the circuit overcurrent relays, aNsi 50/51 devices, may be able to
breaker may be improved, but that does not mean the provide additional protection and control over and above
circuit breaker or the load circuit is electrically safe. that provided by circuit breaker trip units in some situ-
● The arc-flash hazard at the line side of the circuit ations. one example is sensing faults on the conductors
breaker is not affected by an energy-reduction main- between the secondary of a substation transformer and
tenance setting (erMs) on that circuit breaker. Protec- the first secondary low-voltage devices. details of these
tion for the line side depends on an upstream device implementations are beyond the scope of this article, and
that may not be affected by the switch mounted in the some references on secondary substation protection are
proximity of the circuit breaker. provided in [5].
● a bus, or equipment, may have multiple sources, and, low-voltage circuit breakers and power switches can
unless the switch controls all of them, they may need be controlled from various sensing devices. When using a
to be addressed simultaneously to make sure the haz- combination of interrupting devices and external controls,
ard from each source is minimized. it is important to understand the full operation time of
● When the switch is local to the circuit breaker but the sensing, signaling, and switching devices. in many cases,
actual equipment to be worked on is remote, there are although the relay sensing may be very fast, the combina-
opportunities for mistakes (e.g., setting the switch on tion of the various delays provides for slower protection
the wrong ocPd or having the switch operated by than the integral instantaneous protection provided by
other personnel if it’s not properly locked out in the the circuit breaker. in most cases, external relays should
enabled position). only be used in special applications that warrant the com-
● The switch may be used properly, but, if the setting is plexity and cost.
not sensitive enough, arc-flash protection may not be Medium-voltage circuit breakers may be especially
improved. suitable to protect conductors and equipment fed from
● setting the normal instantaneous protection temporari- a transformer prior to the first low-voltage device. such
ly lower, and thereby using it as an erMs, may provide circuit breakers may be controlled in many ways. see the
the expected energy-reducing function. however, this references on secondary substation protection provided in
method does not provide the annunciation function [5] and [12].
that is described in the code, and, therefore, it is tech- low- and medium-voltage fuses could, potentially, be
nically not an acceptable method. accelerated by use of a crowbar to divert energy, collapse
voltage, and force the highest available fault current to
Approved Equivalent Means Solution flow through the fuses to ensure they operate in their
and Energy-Reducing Active Arc-Flash Mitigation System current-limiting range. if the current is high enough, it
The code does not clearly explain what an approved will flow for under half a cycle, and arc-flash protection
equivalent means or what an active energy-reducing can be very quick with minimal consequences. crowbars

8 IEEE Industry Applications Magazine œ J A N U A RY / F E B R U A RY 2 0 1 9


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

are shunt devices that divert current and collapse system The fuse curves an ahJ would review are incapable of
voltage by causing a minimum impedance fault some- revealing slower melting times.
where in the system. as arc-flash protection, they should ieee 1584-2002 (sect. 5.6, p. 13) includes formulas for
work very well if the arc fault is detected. however, the fuses based on testing done by the research group for one
bolted fault current may not be desirable and have seri- brand of fuses. The tests were performed primarily at 600
ous consequences to the distribution system. if such a V. The test data were used to derive several fuse formulas
mitigation system is considered, the manufacturer should that could be used in lieu of time–current curves to evalu-
be consulted to fully understand the implications of the ate arc-flash incident energy performance. The formulas
application, how the sensing will operate, and how the provide for an energy calculation based on available
energy diversion device will operate. at the time of this bolted fault current regardless of arcing gap and driving
writing, most crowbar devices seem to be one-time-use voltage. Both arcing gap and driving voltage are impor-
devices, which has implications on the ability to test tant factors affecting arcing current.
them. Because an arc-flash mitigation system is a safety Furthermore, the experiments to determine fuse
mechanism, the ability to fully confirm operation for performance also put a thin wire (trigger wire) in series
maintenance purposes is also important. with the fuse, which is a weak conductor. The trigger
wire serves as a primitive fuse. When high current is
240.67 Fusible Switches, Improving Protection passed through, both heat up and eventually melt. The
in 2017, the Nec added section 240.67, which describes trigger wire should melt first, causing an arc-flash event,
requirements similar to those found in 240.87 for switch- which is interrupted by the fuses. The current causing
es with 1,200-a or higher fuses. The requirements, as the wire to heat also causes the fuse to heat before an
defined, are not necessary to be enforced until 2020. The arcing event occurs. This could be interpreted as biasing
existence of the requirements indicates that the code- the tested fuse to operate more quickly, but no clear data
making panel perceives a potential hazard and conse- are available to identify if this is consequential.
quential risk to personnel that merit consideration. The an additional concern is that most of the test data are
2020 enforcement date seems to be an attempt to delay a at 600 V. This means the arcing current is a relatively high
solution having limited commercial availability. percentage of available short circuit fault current relative
The section allows fuse protection to be evaluated to the percent at 480 or 208 V. The ieee fuse formulas do
with the arcing current to investigate if the fuse will not provide any guidance on how to correct the formulas
protect sufficiently quickly without additional protective when applied at lower driving voltages. Figure 5 shows
measures being applied in the system. The requirement the identified fuses, 1,200 a and greater, and the pro-
is for fuses to clear in 70 ms or fewer at the estimated arc- spective fault current at which the fuse seems to reduce
ing current. The authors believe this requirement may be energy to about 8 cal per the formulas provided in ieee
insufficient for various reasons. 1584-2002.
● it forces the ahJ to evaluate complex time–current- Figure 6 shows incident energy per the ieee 1584-2002
curves. Not all ahJ have the skills to evaluate time– model for 480-/277- V, 32-mm gap at 18-in working dis-
current curves. tance at three clearing times: 0.025 s, typical for a larger
● The time–current curves provided will be for a specific slow MccB; 0.05 s, typical for a large iccB or lVPcB; and
brand and model of fuse. When a fuse melts, it could 0.07 s, the value specified as sufficient fuse performance
be replaced by one with different characteristics. a in 240.67, which allows for no additional measures to
conservative course of action would be to use enve- be taken to reduce clearing time for a fused switch. as
lope or test fuses, like fuse-to-circuit breaker series can be seen in Figure 6, the slower 0.07 s does allow a
rating tests do, so not just one manufacturer’s fuses are bit more energy, although it is lower than 8 cal up to an
considered. available 70- ka short circuit current.
● The 70-ms clearing time exceeds three cycles, and Based on the ieee 1584-2002 fuse arc-flash incident
even a three-cycle clearing time is not the best a fuse energy formulas, an attempt was made to transpose
can do. Fuses in this size range are current limiting those formulas for 480-V applications (see Table 4). Fuses
and provide best performance when operating in above 1,200 a probably need additional means to reduce
their current-limiting range. Fuses operating in their incident energy below the commonly desired level of
current-limiting range may provide the best arc-flash 8 cal/cm2. likewise, at 208 V, 1,200-a fuses would benefit
incident energy mitigation possible for any overcur- from the additional protection described in 240.67. an arc-
rent device. flash study is the best way to determine if the fuse will
● Fuse curves are drawn as single-phase devices. When provide the desired protection at the available arcing cur-
a fuse melts in one phase, the fault current in a three- rent expected.
phase balanced fault changes to a single-phase fault at Fuses can provide optimum protection if they are
87% of the original fault current, increasing the possi- operating within their current-limiting range. The cur-
bility of the second or third fuse melting more slowly. rent-limiting threshold is defined in the applicable

J A N U A RY / F E B R U A RY 2 0 1 9 œ IEEE Industry Applications Magazine 9


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

IEEE 1584-2002 Fuse Equations Table 5. The current-limiting ratio values, UL fuse
32 standard
Incident Energy cal/cm2

24 Fuse Class Ratio

16 Class RK5 65
Class RK1 30
8
Class J 30
0 Class CC 30
0 20 40 60 80 100 120
Available Bolted Fault Current (kA) Class L 30 (601–1,200 A)
L-1601-2000 L-1201-1600 L-801-1200 Class L 35 (1,201–2,000 A)
Class L 40 (2,001–4,000 A)
FIGURE 5. A fault current where the fuse limits the incident energy
to 8 cal at 600 V, transposed to 480 and 208 V.
a conservative interpretation of available data. Most
products will perform better than standard allowed
14 maximum thresholds. however, different fuse manu-
0.025 s 0.05 s
facturers and different types of fuses may be installed
12 0.07 s 1.2 Cal/Cm2
4 Cal/Cm2 8 Cal/Cm2 over time, meaning the conservative course of action is
10 to base design decisions on the worst practical scenario
Cal/cm2

8 over the life of the equipment. This also adds some


flexibility to account for other issues that may impact
6
fuse melting times.
4

2 Arc-Flash and Electrical Safety Improvements


That Do Not Address Implied Code Intent
0
Within the industry, many design decisions can be
10 20 30 40 50 60 70 80 90 100
Ibf (kA) made that have a positive impact on electrical safety
and arc-flash-hazard mitigation. designers, following
Prevention Through design principles, should consider
FIGURE 6. A graph of incident energy per IEEE 1584-2002 at an
many of these decisions and implement them as much
18-in working distance for a 32-mm arcing gap. The arc-in-a-box
formulas for three different clearing times are shown for 480/277 V, as possible in system designs. among these consider-
32 mm, and 18 in. ations may be
● high-resistance grounding, widely believed to reduce

the probability of an accidental arcing fault [16]


Table 4. An approximate prospective current ● arc-resistant equipment, which provides benefits for
value where the IEEE 1584-2002 fuse formulas personnel working or standing near fully closed equip-
predict 8-cal/cm2 incident energy at 600 V, ment; however, it does not reduce the hazard when
transposed for 480 and 208 V someone is working on live equipment with doors
open or covers removed [17]
Fuse Class kA for kA for kA for
● remote human–machine interface, diagnostics, dis-
and Range 8 cal 600 V 8 cal 480 V 8 cal 208 V
play, and so forth, a good solution that is very easy to
L, 1,601–2,000 96 120 240 implement in modern equipment and provides many
L, 1,201–1,600 41 51 103 benefits; however, it does not address live work hazard
control implied by the code
L, 801–1,200 25 31 63
● remote circuit breaker operation, a very good risk miti-

Determined Transposed Transposed gation method but does not address live work hazard
from graph by 5/4 ratio by 5/2 ratio concerns as the code attempts to do.

standard for those fuses. The ratios and thresholds are Suggested Improvements in the Code
shown in Tables 5 and 6. Fuses will provide the best
possible arc-flash protection after one fuse melts, if the Circuit Application
expected arcing current is larger than the value shown current code sections make no allowances for the applica-
in the current-limiting threshold table, which provides tion of the circuit being addressed. is the circuit a service

10 IEEE Industry Applications Magazine œ J A N U A RY / F E B R U A RY 2 0 1 9


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

entrance main, a feeder on an important distribution bus,


or a branch device feeding a single load or machine? is it Table 6. The current-limiting threshold values,
an additional device being used as a local disconnect pro- UL fuse standard
viding mostly a disconnect function rather than a critical
Class L Fuse Size (A) Current-Limiting Threshold (A)
protective function?
The extra protection mandated by code requirements 1,200 36,000
seems to address the hazard during energized work (an 1,600 56,000
energy-reducing maintenance switch is only used during
planned exposure). But a local disconnect, such as a safe- 2,000 70,000
ty switch, used in a circuit fed from a remote, similarly 3,000 120,000
sized circuit breaker and feeding a dedicated load is not
4,000 160,000
exempted from the code requirements. The extra protec-
tion is not needed twice in the same circuit.
levels than the code intended, especially when fuses can
System Voltage Considerations perform much better. This eliminates ahJs from having
additional protection requirements are necessary at 1,200 a, to confirm overly complex compliance for fuse-protected
regardless of system voltage. as stated previously, key factors circuits, and instead, a specific numerical target for arcing
in good protection are 1) having it operate for the available current versus fuse size should be provided.
arcing current and 2) the arcing current as a percentage of
the bolted fault current will vary greatly with system voltage. Unprotected Conductors
if 1,200 a is the proper limit for additional protection at 480 some systems may have conductors not adequately pro-
V, then the proper limit for 600-V installations may be 1,600 tected in the case of an arc-flash event, particularly line-
a, and for 208-V installations, it may be 600 a. side conductors for service entrance equipment or other
large equipment where the power comes from a gen-
Is the Overcurrent Protection Being Improved or Not? erator or transformer. Between the power source and the
The code is not sufficiently specific when discussing addi- first overcurrent device, there may be no protection, or
tional protection functions, such as bus differential or Zsi. the protection operates at a different voltage and is not
Those enhancements only provide a benefit if they oper- adequate for conductors. a recommended practice within
ate the overcurrent device(s) for a fault in the zone of pro- the industry is to isolate such conductors so personnel
tection and only if the protection is as fast as possible at working downstream of the local ocPd are not exposed
expected arcing current levels. in other words, the thresh- to them. it is also recommended that the space with the
old for operation of the device must meet the same crite- unprotected energized conductors be isolated such that
ria as those control methods having a threshold identified. the effluent from an arc-flash event localized downstream
it is not sufficient for a device to be installed; it must play of the local ocPd cannot cause a flashover and arc-flash
an active protection role to provide benefit. event at the primary side of the ocPd.

Arcing Current Location Conclusions


an additional concern, not addressed by the code when it To ensure that the Nec is properly enforced, local ahJs
states protection will operate at the available arcing cur- must be able to reasonably verify the requirements.
rent expected, is that there is no definition of where the ensuring that arc-flash reduction goals are achieved
arcing current is to be determined—at the terminals of requires expert knowledge in the application of these
the overcurrent device or at the far end of the protected methods described in the code. implementing a method
conductors? The far end of the conductors may be the without understanding if or how it works can create
equipment that may be worked on while energized. it a false sense of security. it is important that electrical
would be reasonable to expect this is where the improved inspectors examine coordination study documentation,
protection is desired, but that detail is not identified in the particularly because the art of circuit breaker selectivity
code text, and it should be. requires more than just confirming that device time–cur-
rent curves do not overlap. Without a high-quality short
Protection with Fuses circuit coordination study and arc-flash-hazard analysis
it is well understood that the faster the protection is at performed by a competent engineer, it is difficult to con-
the arcing current level, the better it is. Fuse performance firm that arc-flash incident energy mitigation has been
should be taken from the standards defining the fuse suitably implemented. a more practical course of action
class, and for arcing current higher than those thresh- may be requiring a competent engineering professional
olds, additional protection is not needed. For arcing cur- to provide a report indicating what methods have been
rent lower than the thresholds, additional protection is applied to the installation to ensure the devices provide a
needed. evaluations using 0.07 s can provide higher E i reasonable limited level of incident energy. This could be

J A N U A RY / F E B R U A RY 2 0 1 9 œ IEEE Industry Applications Magazine 11


This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.

given either as a calories-per-square-centimeter target or [6] Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-
Breaker Enclosures, Ul standard 489, 2016.
indicating that all devices above a certain size are operat-
[7] Standard for Low-Voltage AC and DC Power Circuit Breakers Used in
ing as quickly as they can at or below the expected mini- Enclosures, Ul standard 1066, 2012.
mum arcing current level calculated. [8] IEEE Recommended Practice for the Application of Low-Voltage Circuit
Breakers in Industrial and Commercial Power Systems, ieee standard
one last note: it is important to remember that equip-
3004.5-2014.
ment-based solutions will be sufficient only if mainte- [9] e. larsen, “a new approach to low-voltage circuit breaker short-circuit
nance is properly performed and all appropriate safe selective coordination,” in Proc. IEEE/IAS Industrial and Commercial
Power Systems Technical Conf., 2008, pp. 1–7.
work practices are followed.
[10] M. e. Valdes, s. hansen, and P. sutherland, “optimized instantaneous
protection settings: improving selectivity and arc-flash protection,” IEEE
Author Information Ind. Appl. Mag., vol. 18, no. 3, pp. 66–73, 2012.
[11] Selective Coordination of Low-Voltage Circuit Breakers, NeMa stan-
Marcelo E. Valdes (marcelo.e.valdes@ieee.org) is with
dard aBP 1-2016.
aBB, cary, North carolina. Valdes is a Fellow of the ieee. [12] M. e. Valdes and J. dougherty, “advances in protective device inter-
Steve Hinton is with schneider electric, lexington, Ken- locking for improved protection and selectivity,” IEEE Trans. Ind. Appl.,
vol. 50, no. 3, pp. 1639–1648, 2014.
tucky. Francisco Martinez is with aBB, Tampa, Florida.
[13] Standard for Fused Power-Circuit Devices, Ul standard 977, 2012.
This article first appeared as “arc Flash in the National [14] J. a. Kay, J. arvola, and l. Kumpulainen, “Protecting at the speed of
electrical code: articles 240.87, 240.67; intent and reality, light,” IEEE Ind. Appl. Mag., vol. 17, no. 3, pp. 12–18, 2011.
[15] G. roscoe, M. e. Valdes, and r. luna, “Methods for arc-flash detec-
does the code achieve its Goals? do You achieve its
tion in electrical equipment,” in Proc. Industry Applications Society 57th
Goals?” at the 2017 ias annual Meeting. This article was Annu. Petroleum and Chemical Industry Conf. (PCIC), pgs. 1–8, 2010
reviewed by the ias codes and standards committee. [16] J. P. Nelson, J. d. Billman, J. e. Bowen, and d. a. Martindale, “The
effects of system grounding, bus insulation, and probability on arc flash
hazard reduction—Part 2: Testing,” IEEE Trans. Ind. Appl., vol. 51, no. 3,
References pp. 2665–2675, 2015.
[1] National Electrical Code, NFPa 70-2017. [17] r. M. Bugaris and d. T. rollay, “arc-resistant equipment,” IEEE Ind.
[2] Standard for Electrical Safety in the Workplace, NFPa 70e-2015. Appl. Mag., vol. 17, no. 4, pp. 62–70, 2011.
[3] Occupational Health and Safety Management Systems, aNsi/aiha
standard Z10-2012.
[4] IEEE Guide for Performing Arc Flash Hazard Calculations, ieee stan-
dard 1584-2002.
[5] M. d’Mello, M. Noonan, M. Valdes, and J. Benavides, “arc flash haz-
ard reduction at incoming terminals of lV equipment,” IEEE Trans. Ind.
Appl., vol. 52, no. 1, pp. 701–711, 2016.

12 IEEE Industry Applications Magazine œ J A N U A RY / F E B R U A RY 2 0 1 9

You might also like