Professional Documents
Culture Documents
XXXXX
By Marcelo E. Valdes, Steve Hinton, and The NaTioNa l elecTr ica l code (Nec) h as
Francisco Martinez included requirements for arc-flash-related labeling for
several code cycles [1]. increasingly rigorous requirements
for specific arc-flash-related protection attempt to reduce
any arc-flash hazards to which personnel may be exposed.
Digital Object Identifier 10.1109/MIAS.2018.2868354
They may be exposed to arc-flash hazards during planned
Date of publication: 5 November 2018 energized work or accidentally at any time. The risk-control
personnel so they can reduce their risk. in this category serving utility or the end user. higher fault current will
are warning signs, job site meetings, training, and so on. cause higher incident energy for fixed clearing times pro-
administrative controls, the fifth category, include steps portional to available fault current. lower arcing current
or actions personnel can do prior to exposure to a hazard can result in protection operating more slowly and higher
to lower their risk. Turning a switch on or off, positioning incident energy due to the increased operating time of the
a lever, and ensuring the status of a device or apparatus protective device.
prior to the task would fall under this category. The last The third parameter in arcing current calculations is
category, PPe, entails a person wearing PPe to minimize the equipment bus/conductor gap. The arc current must
the negative effects of any unintentional event that may sustain itself across the gap. ieee 1584-2002 provides
occur during exposure. a table of typical gaps for various equipment types (see
This article will refer to this hierarchy of risk-control Table 3).
methods to explain the measures in the Nec articles. Most arc-flash studies use a combination of these
values. in equipment, however, different values could
Arcing Current: How Low Is Low Enough? be found, both larger and smaller, and this provides an
ieee 1584-2002, IEEE Guide for Performing Arc Flash additional source of variation in arcing current calcula-
Hazard Calculations [4], and ieee 1584.1 provide formu- tions. The 100–85% range defined in ieee 1584-2002 for
las and methods for calculating arc-flash currents to deter- arcing current only attempts to account for the variance in
mine arc-flash incident energy and arc-flash boundaries. the experimental data from the arc-flash research prior to
The formulas are used to calculate a value referred to as 2002. all other potential sources of variance are not con-
100% arcing current and another at 85% of the first value. sidered in the current ieee model.
The calculations are based on three factors used as vari- sources of arcing current variance may include but are
ables within the equations: not limited to
● system voltage (nominal) ● the chaotic nature of an electrical arcing fault
● available three-phase short circuit current ● variable system topology and varying short circuit cur-
mined. The second is often estimated at preliminary ● conservative utility high-fault-current assumptions
phases of a project design. and even in the later stages ● conservative fault study methods by power systems
and worst-case tolerances. For the short circuit evaluation ● incorrect assumptions about regenerating sources
of equipment, power system engineers performing short ● a variance in source voltage due to system loading
circuit calculations purposely drive any potential error ● incorrect assumptions about bus/conductor gap or arc
toward higher values because that is conservative from environment (i.e., size of equipment enclosure or com-
an equipment-rating perspective. ensuring properly rated partment).
equipment, per Nec 110.16, involves calculating maxi- These sources of variance and others can yield arc-
mum short circuit fault current and evaluating it against ing current that is slightly higher or lower than expected.
the withstand and interrupting ratings of the electrical slightly higher current can yield proportionately higher
distribution and protection equipment. conservatism arc-flash incident energy, but slightly lower arcing cur-
from the equipment ratings perspective is not necessar- rent can yield significantly higher incident energy if the
ily appropriate from an arc-flash calculation perspective. protection reacts more slowly because it does not sense
For arc-flash calculations, it is important to have the cor- the arcing fault as expected. The more sensitive protection
rect value of fault current. it is best to have the expected is, the more robust it may be considered, which means
range of fault current available because it may vary during it is more likely to operate for the actual arc fault cur-
the day due to different topologies used, either by the rent. ieee 1584.1 [4] instructs that, to calculate arc flash,
consideration should be made for overly conservative
source fault current and whether motors are turned on
Table 3. A portion of IEEE 1584 Table 4, from p. 12
or off. it important to note that ieee 1584 is undergoing
System Typical Gap Between revision, and the revised version will include additional
Voltage (kV) Equipment Type Conductors (mm) sources of variance both in arcing current and incident
0.208-1 Open air 10–40 energy. When the new model becomes available, the
reader is encouraged to consider it within the context of
Switchgear 32 this article.
MCC and panels 25 Figures 1 and 2 show the ieee 1584-2002 calculated
85% arcing current as a percentage of short circuit cur-
Cable 13
rent for various gap assumptions. Table 2 in ieee 1584
lists typical bus gaps for different equipment classes. For the line side of the main device [5]. But when the main
low-voltage switchgear, the commonly used value is 32 device is fed from a utility-owned transformer, options
mm. For switchboard and motor control centers (Mccs), are limited. Generally, it is best to isolate the main device
the typical value suggested is 25 mm, and most engineers to minimize 1) exposure when energized work is being
performing studies use this value in switchboards and performed on the load side of the main device and 2) the
Mccs. Most moderately sized commercial and industrial possibility of an arcing fault on the load side (location 2 in
power systems tend to operate with available short circuit Figure 3) propagating to the line side.
currents between 30 and 50 ka. a conservative assump-
tion (i.e., biasing toward a low arcing current value) for Solution Types
arcing current could be approximately 40% for 480-V The hazard controls listed in the Nec articles are either
systems and 20% for 208-V systems. however, it is best to engineered or administrative controls per the hierarchy
have a study done for short circuit, protective device coor- identified in NFPa 70e [2] and aNsi Z10 [3]. The energy-
dination, and arc-flash so the values for arcing current can reducing maintenance switch is an administrative control.
be used to determine protective device settings. The other measures are engineered controls.
70%
1 Switchboard
60%
2,000 A
2
Ia as % Ibf
50%
Load
Ibf (kA)
a bus must balance the measured currents leaving it. any code-defined requirements for this function, there are no
imbalance in current, above the programmed threshold, performance requirements, just that they must be provid-
must be a fault. in a differential protection scheme, the dif- ed. Protection can only work as intended if it is set sensi-
ferential relay is connected to current sensors that measure tive to the available arcing current magnitude. The benefit
all of the power coming in, sources, and power going out of these switches is that they generally have a broad range
to loads. a fault below a feeder, such as fault 2 fed by the of adjustability and should be able to be adjusted to be
1,200-a feeder shown in Figure 4, has power measured sensitive enough to achieve acceptable arc-flash reduc-
going into the main bus and going through the feeder. The tion. however, a responsible party must establish what
differential relay will not sense that current as a fault. a the expected arcing current is and ensure the protection is
fault in location 1 on the bus in Figure 4 will cause power adjusted correctly. once commissioned, maintenance per-
to flow into the bus and be measured at the main circuit. sonnel should only need to enable and disable the func-
however, neither feeder is carrying the power out of the tion as prescribed in the planned task procedures.
bus, and the differential relay will sense the bus fault
and signal the main circuit breaker to open. like the Zsi Indication and Control Local to What?
scheme described previously, a differential scheme that Maintenance switches should be used with indicator lights.
includes the three circuits shown in Figure 4 will provide The code states that a local indicator must be provided,
additional protection for the main bus but not for the but the text is not specific as to what should be local. does
feeder circuits. To determine the exact zone of protection it need to be local to the overcurrent protection device
provided, the equipment drawings must be examined, (ocPd) being affected or to the remote equipment being
with the exact location of current transformers and circuit protected? Good engineering practice would dictate that it
breakers noted. again, the letter of 240.87 may be satis- should exist where the protected equipment is. however,
fied, but the intent is not. like any other protection, the the switchboard manufacturer, if not given specific direc-
threshold for operation must be below the available arcing tions to the contrary, will often include it near the ocPd
current fault expected within the target zone of protection. being controlled by the switch. Most importantly, the per-
Use of shunt trips and lockout relays can add to the total son who is relying on that protection should be aware of
clearing time, negatively impacting the arc-flash reduction. its status and what circuit or equipment is being protected.
To facility operators, it may be important to know if the
Administrative Controls protection is accidentally left on when not needed.
Within the hierarchy of hazard control measures, admin- The maintenance control switch should have test pro-
istrative controls are second to last (with last being least cedures for confirming that the circuit breaker or relay
effective). The reason for this is that they are very depen- being controlled has received the signal and processed it
dent on the behavior of the person implementing the con- correctly. These should be followed up on initial start-up
trol. For example, a person and at regular intervals afterward. This could be referred
● could forget to implement it to as positive feedback of status. The switch should be
● might not be sufficiently trained to know how to oper- lockable so it can be properly locked in the on state by
ate it maintenance personnel.
● might not be sufficiently trained to know the need to This function can temporarily compromise coordina-
operate it tion, until it is disabled. Users are often concerned about
● might not know that his or her work task could have forgetting to turn this off after a task, and an obvious
been incorrectly planned with the administrative con- indication of the status is often designed into the system.
trol accidentally omitted indications, such as tower lights evident through the elec-
● could operate the incorrect control trical room, sound alarms, and even e-mails to supervi-
● could operate it at the wrong time sory personnel, have been used to ensure a maintenance
● might not know the control could be inoperative. switch is not left on indefinitely. similar measures should
The possibility of human error will lower the value of be used to ensure that a maintenance switch is used
an administrative control, relative to fully automated solu- when needed. The manufacturer should be consulted for
tions, regardless of how effective the control is in mitigat- device implementation information because wiring and
ing the hazard. see aNsi Z10 [3] for further discussion. space requirements may vary.
that arc-flash labels should not be ambiguous or complex arc-flash mitigation system is. however, there are sev-
and should be conservative in case the reader is not fully eral possibilities should the authority having jurisdiction
aware of proper procedures or inadequately trained. (ahJ) choose to accept them. components of such sys-
tems may include
Administrative Procedures Require Qualified Personnel ● for sensing: light-sensing relays as event detectors and
maintenance switch can be reflected in the data provided voltage circuit breakers, low-voltage fuses, medium-
by the arc-flash study and form part of the risk assess- voltage fuses, crowbars to divert energy and collapse
ment [2, sec. 130.5, p. 25] required to plan an energized system voltage, or combinations of these.
work task [2, sec. 130.2(a), p. 24]. The other argument arc-flash relays are usually able to directly sense the
is that the maintenance function is embedded in the light from an arc-flash event near the sensor location [14].
equipment and always available to be used, so the better These devices are fast and considered to be very good at
protection can be reflected in the arc-flash label, or a sec- sensing an arcing fault event. however, they have some
ond label, that clearly indicates the incident energy with drawbacks. They can unexpectedly operate from the light
the switch turned on or off. however, this may not be emanating from a circuit breaker interrupting a remote
the case for equipment fed by multiple sources involving fault [15]. Furthermore, they can sense within an equip-
multiple energy-reducing maintenance switches, unless ment enclosure very well but do not sense a fault at the
they are coordinated in some manner. a concern may also far end of a conductor feeding remote equipment. in some
be the improper use of an energy-reducing maintenance cases, it may be possible to prevent a nuisance operation
switch by unqualified personnel not aware of the system’s due to an interrupting circuit breaker within the enclosure
limitations. some of the limitations are the following. using Zsi restraint from the trip unit controlling the circuit
● Neither a circuit breaker nor its load is made safe using breaker [12, c, p. 1643] or via other interlocking methods.
the switch. The protection provided by the circuit overcurrent relays, aNsi 50/51 devices, may be able to
breaker may be improved, but that does not mean the provide additional protection and control over and above
circuit breaker or the load circuit is electrically safe. that provided by circuit breaker trip units in some situ-
● The arc-flash hazard at the line side of the circuit ations. one example is sensing faults on the conductors
breaker is not affected by an energy-reduction main- between the secondary of a substation transformer and
tenance setting (erMs) on that circuit breaker. Protec- the first secondary low-voltage devices. details of these
tion for the line side depends on an upstream device implementations are beyond the scope of this article, and
that may not be affected by the switch mounted in the some references on secondary substation protection are
proximity of the circuit breaker. provided in [5].
● a bus, or equipment, may have multiple sources, and, low-voltage circuit breakers and power switches can
unless the switch controls all of them, they may need be controlled from various sensing devices. When using a
to be addressed simultaneously to make sure the haz- combination of interrupting devices and external controls,
ard from each source is minimized. it is important to understand the full operation time of
● When the switch is local to the circuit breaker but the sensing, signaling, and switching devices. in many cases,
actual equipment to be worked on is remote, there are although the relay sensing may be very fast, the combina-
opportunities for mistakes (e.g., setting the switch on tion of the various delays provides for slower protection
the wrong ocPd or having the switch operated by than the integral instantaneous protection provided by
other personnel if it’s not properly locked out in the the circuit breaker. in most cases, external relays should
enabled position). only be used in special applications that warrant the com-
● The switch may be used properly, but, if the setting is plexity and cost.
not sensitive enough, arc-flash protection may not be Medium-voltage circuit breakers may be especially
improved. suitable to protect conductors and equipment fed from
● setting the normal instantaneous protection temporari- a transformer prior to the first low-voltage device. such
ly lower, and thereby using it as an erMs, may provide circuit breakers may be controlled in many ways. see the
the expected energy-reducing function. however, this references on secondary substation protection provided in
method does not provide the annunciation function [5] and [12].
that is described in the code, and, therefore, it is tech- low- and medium-voltage fuses could, potentially, be
nically not an acceptable method. accelerated by use of a crowbar to divert energy, collapse
voltage, and force the highest available fault current to
Approved Equivalent Means Solution flow through the fuses to ensure they operate in their
and Energy-Reducing Active Arc-Flash Mitigation System current-limiting range. if the current is high enough, it
The code does not clearly explain what an approved will flow for under half a cycle, and arc-flash protection
equivalent means or what an active energy-reducing can be very quick with minimal consequences. crowbars
are shunt devices that divert current and collapse system The fuse curves an ahJ would review are incapable of
voltage by causing a minimum impedance fault some- revealing slower melting times.
where in the system. as arc-flash protection, they should ieee 1584-2002 (sect. 5.6, p. 13) includes formulas for
work very well if the arc fault is detected. however, the fuses based on testing done by the research group for one
bolted fault current may not be desirable and have seri- brand of fuses. The tests were performed primarily at 600
ous consequences to the distribution system. if such a V. The test data were used to derive several fuse formulas
mitigation system is considered, the manufacturer should that could be used in lieu of time–current curves to evalu-
be consulted to fully understand the implications of the ate arc-flash incident energy performance. The formulas
application, how the sensing will operate, and how the provide for an energy calculation based on available
energy diversion device will operate. at the time of this bolted fault current regardless of arcing gap and driving
writing, most crowbar devices seem to be one-time-use voltage. Both arcing gap and driving voltage are impor-
devices, which has implications on the ability to test tant factors affecting arcing current.
them. Because an arc-flash mitigation system is a safety Furthermore, the experiments to determine fuse
mechanism, the ability to fully confirm operation for performance also put a thin wire (trigger wire) in series
maintenance purposes is also important. with the fuse, which is a weak conductor. The trigger
wire serves as a primitive fuse. When high current is
240.67 Fusible Switches, Improving Protection passed through, both heat up and eventually melt. The
in 2017, the Nec added section 240.67, which describes trigger wire should melt first, causing an arc-flash event,
requirements similar to those found in 240.87 for switch- which is interrupted by the fuses. The current causing
es with 1,200-a or higher fuses. The requirements, as the wire to heat also causes the fuse to heat before an
defined, are not necessary to be enforced until 2020. The arcing event occurs. This could be interpreted as biasing
existence of the requirements indicates that the code- the tested fuse to operate more quickly, but no clear data
making panel perceives a potential hazard and conse- are available to identify if this is consequential.
quential risk to personnel that merit consideration. The an additional concern is that most of the test data are
2020 enforcement date seems to be an attempt to delay a at 600 V. This means the arcing current is a relatively high
solution having limited commercial availability. percentage of available short circuit fault current relative
The section allows fuse protection to be evaluated to the percent at 480 or 208 V. The ieee fuse formulas do
with the arcing current to investigate if the fuse will not provide any guidance on how to correct the formulas
protect sufficiently quickly without additional protective when applied at lower driving voltages. Figure 5 shows
measures being applied in the system. The requirement the identified fuses, 1,200 a and greater, and the pro-
is for fuses to clear in 70 ms or fewer at the estimated arc- spective fault current at which the fuse seems to reduce
ing current. The authors believe this requirement may be energy to about 8 cal per the formulas provided in ieee
insufficient for various reasons. 1584-2002.
● it forces the ahJ to evaluate complex time–current- Figure 6 shows incident energy per the ieee 1584-2002
curves. Not all ahJ have the skills to evaluate time– model for 480-/277- V, 32-mm gap at 18-in working dis-
current curves. tance at three clearing times: 0.025 s, typical for a larger
● The time–current curves provided will be for a specific slow MccB; 0.05 s, typical for a large iccB or lVPcB; and
brand and model of fuse. When a fuse melts, it could 0.07 s, the value specified as sufficient fuse performance
be replaced by one with different characteristics. a in 240.67, which allows for no additional measures to
conservative course of action would be to use enve- be taken to reduce clearing time for a fused switch. as
lope or test fuses, like fuse-to-circuit breaker series can be seen in Figure 6, the slower 0.07 s does allow a
rating tests do, so not just one manufacturer’s fuses are bit more energy, although it is lower than 8 cal up to an
considered. available 70- ka short circuit current.
● The 70-ms clearing time exceeds three cycles, and Based on the ieee 1584-2002 fuse arc-flash incident
even a three-cycle clearing time is not the best a fuse energy formulas, an attempt was made to transpose
can do. Fuses in this size range are current limiting those formulas for 480-V applications (see Table 4). Fuses
and provide best performance when operating in above 1,200 a probably need additional means to reduce
their current-limiting range. Fuses operating in their incident energy below the commonly desired level of
current-limiting range may provide the best arc-flash 8 cal/cm2. likewise, at 208 V, 1,200-a fuses would benefit
incident energy mitigation possible for any overcur- from the additional protection described in 240.67. an arc-
rent device. flash study is the best way to determine if the fuse will
● Fuse curves are drawn as single-phase devices. When provide the desired protection at the available arcing cur-
a fuse melts in one phase, the fault current in a three- rent expected.
phase balanced fault changes to a single-phase fault at Fuses can provide optimum protection if they are
87% of the original fault current, increasing the possi- operating within their current-limiting range. The cur-
bility of the second or third fuse melting more slowly. rent-limiting threshold is defined in the applicable
IEEE 1584-2002 Fuse Equations Table 5. The current-limiting ratio values, UL fuse
32 standard
Incident Energy cal/cm2
16 Class RK5 65
Class RK1 30
8
Class J 30
0 Class CC 30
0 20 40 60 80 100 120
Available Bolted Fault Current (kA) Class L 30 (601–1,200 A)
L-1601-2000 L-1201-1600 L-801-1200 Class L 35 (1,201–2,000 A)
Class L 40 (2,001–4,000 A)
FIGURE 5. A fault current where the fuse limits the incident energy
to 8 cal at 600 V, transposed to 480 and 208 V.
a conservative interpretation of available data. Most
products will perform better than standard allowed
14 maximum thresholds. however, different fuse manu-
0.025 s 0.05 s
facturers and different types of fuses may be installed
12 0.07 s 1.2 Cal/Cm2
4 Cal/Cm2 8 Cal/Cm2 over time, meaning the conservative course of action is
10 to base design decisions on the worst practical scenario
Cal/cm2
Determined Transposed Transposed gation method but does not address live work hazard
from graph by 5/4 ratio by 5/2 ratio concerns as the code attempts to do.
standard for those fuses. The ratios and thresholds are Suggested Improvements in the Code
shown in Tables 5 and 6. Fuses will provide the best
possible arc-flash protection after one fuse melts, if the Circuit Application
expected arcing current is larger than the value shown current code sections make no allowances for the applica-
in the current-limiting threshold table, which provides tion of the circuit being addressed. is the circuit a service
given either as a calories-per-square-centimeter target or [6] Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-
Breaker Enclosures, Ul standard 489, 2016.
indicating that all devices above a certain size are operat-
[7] Standard for Low-Voltage AC and DC Power Circuit Breakers Used in
ing as quickly as they can at or below the expected mini- Enclosures, Ul standard 1066, 2012.
mum arcing current level calculated. [8] IEEE Recommended Practice for the Application of Low-Voltage Circuit
Breakers in Industrial and Commercial Power Systems, ieee standard
one last note: it is important to remember that equip-
3004.5-2014.
ment-based solutions will be sufficient only if mainte- [9] e. larsen, “a new approach to low-voltage circuit breaker short-circuit
nance is properly performed and all appropriate safe selective coordination,” in Proc. IEEE/IAS Industrial and Commercial
Power Systems Technical Conf., 2008, pp. 1–7.
work practices are followed.
[10] M. e. Valdes, s. hansen, and P. sutherland, “optimized instantaneous
protection settings: improving selectivity and arc-flash protection,” IEEE
Author Information Ind. Appl. Mag., vol. 18, no. 3, pp. 66–73, 2012.
[11] Selective Coordination of Low-Voltage Circuit Breakers, NeMa stan-
Marcelo E. Valdes (marcelo.e.valdes@ieee.org) is with
dard aBP 1-2016.
aBB, cary, North carolina. Valdes is a Fellow of the ieee. [12] M. e. Valdes and J. dougherty, “advances in protective device inter-
Steve Hinton is with schneider electric, lexington, Ken- locking for improved protection and selectivity,” IEEE Trans. Ind. Appl.,
vol. 50, no. 3, pp. 1639–1648, 2014.
tucky. Francisco Martinez is with aBB, Tampa, Florida.
[13] Standard for Fused Power-Circuit Devices, Ul standard 977, 2012.
This article first appeared as “arc Flash in the National [14] J. a. Kay, J. arvola, and l. Kumpulainen, “Protecting at the speed of
electrical code: articles 240.87, 240.67; intent and reality, light,” IEEE Ind. Appl. Mag., vol. 17, no. 3, pp. 12–18, 2011.
[15] G. roscoe, M. e. Valdes, and r. luna, “Methods for arc-flash detec-
does the code achieve its Goals? do You achieve its
tion in electrical equipment,” in Proc. Industry Applications Society 57th
Goals?” at the 2017 ias annual Meeting. This article was Annu. Petroleum and Chemical Industry Conf. (PCIC), pgs. 1–8, 2010
reviewed by the ias codes and standards committee. [16] J. P. Nelson, J. d. Billman, J. e. Bowen, and d. a. Martindale, “The
effects of system grounding, bus insulation, and probability on arc flash
hazard reduction—Part 2: Testing,” IEEE Trans. Ind. Appl., vol. 51, no. 3,
References pp. 2665–2675, 2015.
[1] National Electrical Code, NFPa 70-2017. [17] r. M. Bugaris and d. T. rollay, “arc-resistant equipment,” IEEE Ind.
[2] Standard for Electrical Safety in the Workplace, NFPa 70e-2015. Appl. Mag., vol. 17, no. 4, pp. 62–70, 2011.
[3] Occupational Health and Safety Management Systems, aNsi/aiha
standard Z10-2012.
[4] IEEE Guide for Performing Arc Flash Hazard Calculations, ieee stan-
dard 1584-2002.
[5] M. d’Mello, M. Noonan, M. Valdes, and J. Benavides, “arc flash haz-
ard reduction at incoming terminals of lV equipment,” IEEE Trans. Ind.
Appl., vol. 52, no. 1, pp. 701–711, 2016.