Professional Documents
Culture Documents
VRF Systems:
VRF systems offer individual zone control and flexibility, making them popular in modern buildings.
Key data points for analysis include:
Cooling Capacity:
Equation: Q_c = m_a * c_p * (T_si - T_so)
Q_c: Cooling capacity (kW)
m_a: Air mass flow rate (kg/s)
c_p: Specific heat capacity of air (kJ/kg*K)
T_si: Supply air temperature (°C)
T_so: Outdoor air temperature (°C)
Example:
Assume a VRF system needs to cool a room with 50 kg/s air flow and maintain a 20°C supply air
temperature with a 30°C outdoor temperature. The specific heat capacity of air is 1.005 kJ/kg*K.
Q_c = 50 kg/s * 1.005 kJ/kg*K * (20°C - 30°C)
Q_c = 50.25 kW
Energy Efficiency:
Equation: COP = Q_c / W_e
COP: Coefficient of performance (dimensionless)
W_e: Electrical power consumption (kW)
Example:
If the VRF system in the previous example consumes 15 kW of electricity, the COP is:
COP = 50.25 kW / 15 kW
COP = 3.35
2. Chiller Systems:
Chillers provide centralized cooling for buildings, often used in conjunction with air handling units
(AHUs). Key data points for analysis include:
Refrigeration Capacity:
Equation: Q_r = m_r * h_fg
Q_r: Refrigeration capacity (kW)
m_r: Refrigerant mass flow rate (kg/s)
h_fg: Enthalpy of refrigerant at evaporator outlet (kJ/kg)
Example:
Assume a chiller system uses R-410A refrigerant with a mass flow rate of 1 kg/s and an evaporator
outlet enthalpy of 420 kJ/kg.
Q_r = 1 kg/s * 420 kJ/kg
Q_r = 420 kW
Cooling Load:
Equation: Q_l = m_a * c_p * (T_sa - T_ra)
Q_l: Cooling load (kW)
m_a: Air mass flow rate through AHU (kg/s)
c_p: Specific heat capacity of air (kJ/kg*K)
T_sa: Supply air temperature (°C)
T_ra: Return air temperature (°C)
Example:
If the AHU in the chiller system handles 100 kg/s of air, maintains a 18°C supply air temperature,
and has a 26°C return air temperature, the cooling load is:
Q_l = 100 kg/s * 1.005 kJ/kg*K * (18°C - 26°C)
Q_l = 80.4 kW
Data Treatment Tips:
Collect accurate data: Ensure proper measurement of temperatures, flow rates, and energy
consumption for both VRF and chiller systems.
Standardize units: Use consistent units (e.g., kW, kJ/kg, kg/s) throughout your calculations
for accurate comparisons.
Consider diverse operating conditions: Analyze data under different load conditions (e.g.,
peak cooling, part-load) to understand system performance across various scenarios.
Statistical analysis: Apply statistical methods to analyze data variability and identify trends
in system performance.
VRF Systems:
1. Compressor Performance:
Volumetric efficiency: η_v = Q_c / (V_d * ΔP)
o η_v: Volumetric efficiency (dimensionless)
2. Pipe Sizing:
Pressure drop: ΔP = f * L * G^2 / (2 * D * ρ)
o ΔP: Pressure drop (kPa)
3. Control Strategies:
Setpoint temperature: T_sp = T_ra + ΔT_sp
o T_sp: Setpoint temperature (°C)
System optimization: Minimize energy consumption by adjusting setpoints, fan speeds, and
compressor operation based on real-time conditions.
4. Energy Consumption:
Annual energy consumption: E_c = Q_c * t_op / COP
o E_c: Annual energy consumption (kWh)
5. Multi-zone Analysis:
Zone cooling load: Q_zi = m_zi * c_p * (T_si - T_zi)
o Q_zi: Zone cooling load (kW)
System capacity allocation: Allocate total system capacity (Q_c) to individual zones based on
their respective cooling loads.
Chiller Systems:
1. Psychrometrics:
Dry bulb temperature: T_db: Measured temperature (°C)
Wet bulb temperature: T_wb: Temperature of a saturated air parcel in equilibrium with
water (℃)
Relative humidity: RH = 100 * (p_w / p_ws)
o RH: Relative humidity (%)