i03018293 - Control Panel
SEBU8256-03
SMCS: 7451
Illustration 54 g01726756
Illustration 55 g01736633
(1) Controller
(2) Capacitor
(3) K5 relay
https://parts.cat.com/OmmDetailsView?bookURI=ACM%2FLocal%2F589b6d31-793a-4b0c-b48c-cfaa00eadc84&controlNo=i03018293&langId=-1&serialNumber=C6T00691&storeId=22047 1/6
19/12/23, 21:48 C6.6 ENGINE - GENERATOR SET Operation & Maintenance Manuals
Illustration 56 g01413513
https://parts.cat.com/OmmDetailsView?bookURI=ACM%2FLocal%2F589b6d31-793a-4b0c-b48c-cfaa00eadc84&controlNo=i03018293&langId=-1&serialNumber=C6T00691&storeId=22047 2/6
19/12/23, 21:48 C6.6 ENGINE - GENERATOR SET Operation & Maintenance Manuals
https://parts.cat.com/OmmDetailsView?bookURI=ACM%2FLocal%2F589b6d31-793a-4b0c-b48c-cfaa00eadc84&controlNo=i03018293&langId=-1&serialNumber=C6T00691&storeId=22047 3/6
19/12/23, 21:48 C6.6 ENGINE - GENERATOR SET Operation & Maintenance Manuals
Service Menu
Accessing the Service Menu can only be accomplished by using the "JUMP" key.
Use the following procedure to access the Service Menu.
1. Press the "JUMP" key.
2. Use the Menu key for UP and the Menu key for DOWN In order to step to channel 4980.
3. Press the "SEL" key.
4. Choose the desired functions, timers, inputs or outputs by moving the cursor and pressing the "SEL" key.
Language Selection
The MCS can be configured for the following languages: English, Spanish, German and French. The language may be chosen when the
system is set up. The language may be chosen by using the "JUMP" key.
Use the following procedure to change the language.
1. Press the "JUMP" key.
2. Use the Navigation Key for UP and the Navigation Key for DOWN In order to step to channel 4231.
3. Press the "SEL" key.
4. Choose the password by using the Navigation Key for UP and the Navigation Key for DOWN and press the "SEL" key.
5. Use the Navigation Key for UP and the Navigation Key for DOWN and select the desired language.
6. Press the "SEL" key.
Note: The password must be re-entered when the display has not been used for 3 minutes.
Alarms
The following steps describe the function of the alarm.
1. An alarm occurs. The alarm light starts flashing.
2. The display automatically shows the alarm information.
3. Move the cursor to "ACK" and press the "SEL" key in order to acknowledge the alarm. Take the necessary action for the alarm.
4. The alarm will disappear when the condition that caused the alarm is no longer present.
5. Alarms that have not been acknowledged are still present if the alarm light flashes.
6. Use the navigation keys in order to step through the list of alarms.
Warnings
"WARNING BATTERY VOLTAGE" - If the control module detects voltage from the alternator that is below the setting for low voltage,
the display will show "BATTERY LOW V". The alarm indicator illuminates, and an audible alarm is activated.
"FAIL TO STOP" - If the control module determines that the signal from the engine speed sensor indicates that the engine is running
but the engine should not be running, the display will show "STOP FAIL". The alarm indicator illuminates, and an audible alarm is
activated.
"WARNING LOW OIL PRESSURE" - If the control module detects engine oil pressure that has fallen below the setting for low oil
pressure (warning), the display will show "LOW OIL PRESS". The alarm indicator illuminates, and an audible alarm is activated. This
warning is only active after the engine has exceeded the Safety On Timer.
"WARNING HIGH COOLANT TEMP" - If the control module detects engine coolant temperature that has exceeded the setting for high
coolant temperature (warning), the display will show "HIGH ENGINE TEMP". The alarm indicator illuminates, and an audible alarm is
activated. This warning is only active after the engine has exceeded the "Safety On" Timer.
"WARNING OVERSPEED" - If the engine speed exceeds the setting for engine overspeed (warning), the display will show "OVERSPEED".
The alarm indicator illuminates, and an audible alarm is activated.
https://parts.cat.com/OmmDetailsView?bookURI=ACM%2FLocal%2F589b6d31-793a-4b0c-b48c-cfaa00eadc84&controlNo=i03018293&langId=-1&serialNumber=C6T00691&storeId=22047 4/6
19/12/23, 21:48 C6.6 ENGINE - GENERATOR SET Operation & Maintenance Manuals
"WARNING GENERATOR HIGH FREQUENCY" - If the control module detects a output frequency for the generator that exceeds the
setting for high generator frequency (warning), the display will show "Hz/V FAILURE". The alarm indicator illuminates, and an audible
alarm is activated.
"WARNING GENERATOR LOW FREQUENCY" - If the control module detects a output frequency for the generator that is below the
setting for low generator frequency (warning), the display will show "Hz/V FAILURE". The alarm indicator illuminates, and an audible
alarm is activated.
"GENERATOR HIGH VOLTAGE WARNING" - If the control module detects a output voltage for the generator that exceeds the setting
for high generator voltage (warning), the display will show "OVER VOLTAGE". The alarm indicator illuminates, and an audible alarm is
activated.
"GENERATOR LOW VOLTAGE WARNING" - If the control module detects a output voltage for the generator that is less than the setting
for low generator voltage (warning), the display will show "UNDER VOLTAGE". The alarm indicator illuminates, and an audible alarm is
activated.
"LUB OIL HIGH TEMPERATURE ALARM" - If the control module detects a high lube oil temperature in excess of 120 degrees celsius for
four cylinder engines and in excess of 130 degrees celsius for six cylinder engines (warning), the display will show "LUB OIL HIGH". The
alarm indicator illuminates.
"SHUTDOWN OVERRIDE" - If the control module detects an override for engine shutdown and the switch is set to OVERRIDE, the
display will show "S/D OVERRIDE". The alarm indicator illuminates, and an audible alarm is activated.
"STARTING AIR PRESSURE LOW ALARM OPTIONAL" - If the control module detects low starting air pressure (warning), the display will
show "START AIR P LOW". The alarm indicator illuminates, and an audible alarm is activated.
"GENERATOR WINDING OR BEARING OVER TEMPERATURE ALARM OPTIONAL" - If the control module detects a generator bearing
over temperature (warning), the display will show "GEN BRG OVER TEMP". The alarm indicator illuminates, and an audible alarm is
activated.
"EXTERNAL FUEL TANK LEVEL ALARM OPTIONAL" - If the control module detects a low fuel level in an external fuel tank, the display
will show "EXT FUEL T LOW". The alarm indicator illuminates, and an audible alarm is activated.
"HIGH EXHAUST TEMPERATURE ALARM OPTIONAL" - If the control module detects a high exhaust temperature (warning), the display
will show "HIGH EXH TEMP". The alarm indicator illuminates, and an audible alarm is activated.
"HIGH PRESSURE FUEL LEAK ALARM OPTIONAL" - If the control module detects a high pressure fuel leak (warning), the display will
show "H P FUEL LEAK". The alarm indicator illuminates, and an audible alarm is activated.
"WATER IN FUEL ALARM OPTIONAL" - If the control module detects a signal for water in fuel (warning), the display will show "WATER
IN FUEL". The alarm indicator illuminates, and an audible alarm is activated.
Shutdowns
"SHUTDOWN FAIL TO START" - If the engine does not start after a preset number of attempts, the display will show "Hz/V FAILURE".
The alarm indicator will flash, and an audible alarm is activated.
"SHUTDOWN EMERGENCY STOP" - If the voltage signal at the input for the emergency stop is disconnected, the display will show "E-
STOP". The generator set will not start until the emergency stop push button has been reset. Power is removed from the fuel solenoid
and the starter solenoid. The alarm indicator will flash, and an audible alarm is activated.
"SHUTDOWN LOW OIL PRESSURE" - If the control module detects engine oil pressure that has fallen below the setting for low oil
pressure (shutdown), the display will show "LOW O P S/DOWN". The alarm indicator will flash, and an audible alarm is activated. This
warning is only active after the engine has exceeded the Safety On Timer.
"SHUTDOWN HIGH COOLANT TEMPERATURE" - If the control module detects engine coolant temperature that has exceeded the
setting for high coolant temperature (shutdown), the display will show "HET S/DOWN". The alarm indicator will flash, and an audible
alarm is activated. This warning is only active after the engine has exceeded the "Safety On" Timer.
"SHUTDOWN OVERSPEED" - If the engine speed exceeds the setting for engine overspeed (shutdown), the display will show "Hz/V
FAILURE". The alarm indicator will flash, and an audible alarm is activated.
"SHUTDOWN UNDERSPEED" - If the engine speed falls below the setting for engine underspeed (shutdown), the display will show "F/U
FAIL". The alarm indicator will flash, and an audible alarm is activated. This warning is only active after the engine has exceeded the
"Safety On" Timer.
"SHUTDOWN GENERATOR HIGH FREQUENCY" - If the control module detects a output frequency for the generator that exceeds the
setting for high generator frequency (shutdown), the display will show "Hz/V FAILURE". The alarm indicator will flash, and an audible
alarm is activated.
"SHUTDOWN GENERATOR LOW FREQUENCY" - If the control module detects a output frequency for the generator that is below the
setting for low generator frequency (shutdown), the display will show "Hz/V FAILURE". The alarm indicator will flash, and an audible
alarm is activated.
"GENERATOR HIGH VOLTAGE SHUTDOWN" - If the control module detects a output voltage for the generator that exceeds the setting
for high generator voltage (shutdown), the display will show "HIGH VOLT S/D". The alarm indicator will flash, and an audible alarm is
https://parts.cat.com/OmmDetailsView?bookURI=ACM%2FLocal%2F589b6d31-793a-4b0c-b48c-cfaa00eadc84&controlNo=i03018293&langId=-1&serialNumber=C6T00691&storeId=22047 5/6
19/12/23, 21:48 C6.6 ENGINE - GENERATOR SET Operation & Maintenance Manuals
activated.
"GENERATOR LOW VOLTAGE SHUTDOWN" - If the control module detects a output voltage for the generator that is less than the
setting for low generator voltage (shutdown), the display will show "LOW VOLT S/D". The alarm indicator will flash, and an audible
alarm is activated.
"ELECTRONIC GOVERNOR FAILURE SHUTDOWN" - If the control module detects an electronic governor failure (shutdown), the display
will show "GOV FAIL S/DOWN". The alarm indicator illuminates, and an audible alarm is activated.
https://parts.cat.com/OmmDetailsView?bookURI=ACM%2FLocal%2F589b6d31-793a-4b0c-b48c-cfaa00eadc84&controlNo=i03018293&langId=-1&serialNumber=C6T00691&storeId=22047 6/6