customers,
with a tool for excersizing different transformer setups, and test scenarios. The simulation can be used to verify the biased differential settings, the differential
and restraint metering on the relay, and the correct operation of the element, under test conditions.
Note the angles of the entered test currents for Winding 2 are shifted by 180 degrees. This shift comes from the
inversed polarity connections of the winding CTs connected to the relay terminals. From the example, the angles of W2
phA(W2) = -30 -180 = -210 degrees, phB(W2) = - 150-180 = -330, and for ph C(W2) = - 270-180 = -90 degrees
See the example below.