Transformer Differential Protection relay - Pickup ca

W in d in g a W in d in g b

Inom,CT,a: Vnom,a: Sref: Vnom,b:

800 A 66.0 kV 40.0 MVA 11.0 kV

Id>: 0.2 % I0,a filtering: Vector group ID: I0,b filtering:


Id>>: 7.0 % Star Winding? Star Winding?
Id>>>: 7.0 % Yes 1

Id> A side B side Id>> A side B side Id>>>


1Ph 0.131 0.364 1Ph 4.593 12.727 1Ph
2Ph(120⁰) 0.101 0.210 2Ph(120⁰) 3.521 7.348 2Ph(120⁰)
2Ph(180⁰) 0.087 0.182 2Ph(180⁰) 3.062 6.363 2Ph(180⁰)
3Ph 0.087 0.210 3Ph 3.062 7.348 3Ph
ay - Pickup calculation Sheet

Inom,CT,b:

2000 A

I0,b filtering:
Star Winding?
Yes

A side B side
4.593 12.727 Any comments
3.521 7.348 Baskar Palani
3.062 6.363 epillar2016@gmail.com
3.062 7.348 www.facebook.com/epillar