A. Application
• General voltage monitoring with instantaneous response
(over and undervoltage)
• Voltage monitoring where insensitive to frequency is required
(over and undervoltage).
B. Features
• processes instantaneous values and is therefore fast and
largely independent of frequency
• stores the peak value following pick-up
• no suppression of DC component
• no suppression of harmonics
• single and three-phase measurement
• maximum value detection in the three-phase mode
• adjustable lower frequency limit fmin.
I. Analogue inputs:
• voltage
IV. Measurements:
• voltage amplitude (only available if function trips).
3.5.8-1
ABB Power Automation Ltd REC 316*4 1MRB520044-Uen / Rev. D
Explanation of parameters:
ParSet 4..1
Parameter for determining in which set of parameters a par-
ticular function is active (see Section 5.11.).
Trip
defines the tripping channel activated by the tripping O/P of
the function (matrix).
Delay
Time between the function picking up and tripping.
V-Setting
Pick-up voltage setting.
f-min
defines the minimum frequency for which measurement is
required.
MaxMin
defines operation as overvoltage or undervoltage. Settings:
• MAX: overvoltage
• MIN: undervoltage.
NrOfPhases
defines whether single or three-phase measurement.
3.5.8-2
REC 316*4 1MRB520044-Uen / Rev. D ABB Power Automation Ltd
VoltageInp
defines the analogue voltage input channel.
All voltage inputs may be selected.
In the case of three-phase measurement, the first channel (R
phase) of the group of three selected must be specified.
BlockInp
Binary address used as blocking input.
F: - not blocked
T: - blocked
xx: - all binary inputs (or outputs of protection functions).
Trip
Output for signalling tripping.
Start
Output for signalling pick-up.
3.5.8-3
ABB Power Automation Ltd REC 316*4 1MRB520044-Uen / Rev. D
E. Setting instructions
Settings:
Overvoltage V-Setting
Delay Delay
Minimum frequency f-min
Over or undervoltage MaxMin
The instantaneous overvoltage function is a high-speed protec-
tion, which operates in a wide frequency range. It is intended
primarily for the following applications:
• where an overvoltage protection is required, which is largely
insensitive to frequency especially for f > fN.
The limited capacity of the v.t’s to transform low frequencies
must be taken into account for f < fN:
Input transformer units K01...K17 (REL 316*4) and K41...K47
(REC 316*4):
f
1.3UN ⋅
fN
3.5.8-4
REC 316*4 1MRB520044-Uen / Rev. D ABB Power Automation Ltd
Typical settings:
V-Setting according to application
Delay according to application
f-min 40 Hz
3.5.8-5