7UT 61** Diff.

Relay Secondary injection Test Notes


For Even Vector Group(0,2,4,6,8,10):

N.B

Transformer Data

IN

CT Data
VOLT

HV

220000

MVA

75

I Prim

Isec.

400

CTR

400

(Setting Values are shown in shaded cells)

Id

I d (Injected value)
Fault Type

Transformer
Rated Current

(set Value)

196.83

1 Phase
3 Phase

2 Phase

0.20

0.20

0.30

0.20

0.22

0.22

0.33

0.22

(With I0 elimin.) (Without I0 eliminn)

0.4
LV

66000

75

1200

1200

656.10

For Odd Vector Group(1,3,5,7,9,11):


Transformer Data

IN

Id

I d (Injected value)

CT Data
VOLT

HV

220000

MVA

38.1

Fault Type
CTR

I Prim

Isec.

200

200

Transformer
Rated Current

(set Value)

99.99

1 Phase

3 Phase

2 Phase

0.10

0.10

0.15

0.10

0.22

0.192

0.384

0.24

34.9206349206

220.5
1047.6190476191

(With I0 elimin.) (Without I0 eliminn)

0.2
LV

Where:

6300

38.1

3150

3150

3491.70