You are on page 1of 16

Passive IR Sensor PA-6810E,

360° round protection


Installation Manual

Kongsberg Maritime Part nos. 378592 (sensor)


378594 (wall mount bracket)

378596/A
December 2012 © Kongsberg Maritime AS
Document history
Document number: 378596
Rev. A December 2012 First issue.

Note
The information contained in this document remains the sole property of Kongsberg Maritime AS. No
part of this document may be copied or reproduced in any form or by any means, and the information
contained within it is not to be communicated to a third party, without the prior written consent of
Kongsberg Maritime AS.
Kongsberg Maritime AS endeavours to ensure that all information in this document is correct and fairly
stated, but does not accept liability for any errors or omissions.

Warning
The equipment to which this manual applies must only be used for the purpose for which it was
designed. Improper use or maintenance may cause damage to the equipment and/or injury to personnel.
The user must be familiar with the contents of the appropriate manuals before attempting to operate
or work on the equipment.
Kongsberg Maritime disclaims any responsibility for damage or injury caused by improper installation,
use or maintenance of the equipment.

Comments
To assist us in making improvements to the product and to this manual, we welcome comments and
constructive criticism.
e-mail: km.documentation@kongsberg.com

Kongsberg Maritime AS
www.kongsberg.com
Installation Manual

Table of contents

INTRODUCTION ................................................................ 5
SELECTING THE MOUNTING LOCATION............................. 7
TECHNICAL SPECIFICATIONS ........................................... 9
INSTALLATION PROCEDURE ........................................... 10
TEST PROCEDURE ........................................................... 12
INSTALLATION DRAWINGS............................................. 13

378596/A 3
Passive IR Sensor

4 378596/A
Introduction

Introduction

This document describes the installation of the Passive IR Sensor for the Kongsberg
Bridge Watch Monitoring System (BWMS). This sensor is used as a motion detector
by the BWMS. The main purpose is to detect movement in those areas of the vessel's
bridge that contain navigation equipment.
The sensor must be installed in sufficient numbers on the ceiling of the bridge to cover
all the look-out positions on the forward bridge and bridge wings (and not to cover any
other parts of the bridge). The sensor (or sensors) either replaces “Dead Man” reset
buttons on the bridge or is installed in addition to them.
Traditionally, if there has been no activity on the navigation operator stations and nobody
has pressed a “Dead Man” reset button for a preset time period (of between 3 and 12
minutes), then buzzers around the vessel will sound in a sequence specified according to
regulations and the vessel owners’ requirements.
On vessels where the “Dead Man” reset buttons have been replaced with motion
detectors, when movement on the bridge is detected, an alarm signal is sent to the
BWMS. (In other words, they send an alarm signal constantly to the BWMS as long as
there is movement on the bridge.) If this signal stops for a specified time period (of
between 3 and 12 minutes), the BWMS sounds the buzzers in the relevant cabins to alert
officers and crew that the bridge is not manned.
Installation of the sensors thus means that the ship's personnel no longer need to press
the “Dead Man” reset buttons every few minutes when they are not using the vessel's
controls.

378596/A 5
Passive IR Sensor

Unit features
• Super slim and compact design
• Detachable base unit with snap-in/out sensor design for easy installation
• Rotating mirror for efficient detection regardless of area setting
• Sensitivity/pulse count selectable
• NO/NC contact output

Figure 1 Parts description, Passive IR Sensor

6 378596/A
Selecting the mounting location

Selecting the mounting


location

This chapter explains the main considerations that determine the mounting location
for each sensor.
The area covered by the sensors you install must include all the look-out positions on the
forward bridge and bridge wings, and it must not include any other parts of the bridge.
The location, orientation and spacing of the sensors will be calculated by Kongsberg
project engineers to ensure that the required coverage is achieved. Before installing the
sensors, you must therefore refer to the project documentation and mount the units in
accordance with the calculations that have been performed for the vessel.
Note
Do not position the units near to any heating, ventilation or air-conditioning equipment
or outlets. Warm or cold air from these can interfere with the unit's passive infrared
system which operates by detecting variations in temperature.

378596/A 7
Passive IR Sensor

Protection area
The protection area is defined according to the installation height of the sensor, as long
as it is not limited by walls, doors, windows or other barriers.

Figure 2 Coverage and range, 360 degrees round protection, PA–6810E

Figure 3 Protection area according to height

Table 1 Protection area according to height

Height Coverage diameter


[metres] [metres]
2.0 7.0
2.6 8.8
3.0 10.0
4.0 14.0
4.9 15.2

8 378596/A
Technical specifications

Technical specifications

Table 2 Technical specifications

Model PA-6810E
Detection system Passive infrared
Coverage 360 degrees round, 15.2 m diameter max
Sensitive zone 33 pairs
Supply voltage 10.5 to 28 VDC (non-polarity)
Current consumption 25 mA max (+2 mA at L/C use)
Alarm signal Dry contact (semi-conductor), NC / NO change-over
Reset: Approx. 2 s, 24 V (AC/DC), 0.25 A (protective resistor 3.3 Ω)
Alarm memory 3 minutes flashing, 47 minutes lighting and automatically reset
Alarm LED Red: Flashing at warming up, lighting at alarm (LED disabled)
Memory LED Yellow: Flashing at memory activated, lighting at memory indication
Adjustment Horizontally: 25 deg (on mounting hole of base)
Vertically: N/A
Count change-over 1 / 2 / 3 / 4 change-over
Ambient temperature range -15 °C to +55 °C without condensation
Mounting position Indoor ceiling or wall mount with optical attachment BCW-401
Wiring connection Terminals on separate base unit
Weight 110 g
Appearance Body: ABS resin
Cover: PE resin
Accessory Tapping screw: 2 pcs
Sensor locking scres: 1 pcs

Note
The specifications are subject to change without notice.

378596/A 9
Passive IR Sensor

Installation procedure

1 Slide release lever to a direction that an arrow points to detach sensor unit from
base unit.

2 Mount the base on the ceiling with screws. Fix it so that the front mark (↑) is
pointing to the center of the protection area.
Note
The front mark should be pointed to the area where the alarm LED is checked
at walk test.

For dimensional drawings, refer to External dimensions, PA-6810E sensor on


page 13.
Optionally, the BCW-401 bracket can be used for wall or ceiling mounting. Refer to
External dimensions, BCW-401 bracket on page 14.
3 Break knockout and put the wire through the wire lead on the base unit, when
exposed wiring.

4 Connect the wires to the terminals referring to Wiring, terminal arrangement on


page 15.
5 Match up a front mark on the base unit with that on the sensor unit.

10 378596/A
Installation procedure

6 Put a sensor unit into a base unit from the front mark side.

7 Push the sensor unit until the release lever will click.

8 When the sensor unit is detached, hold it and slide release lever as illustrated.

9 When the sensor unit is locked, tighten the locking screw.

378596/A 11
Passive IR Sensor

Test procedure

1 Turn the power ON, and wait for 1 minute until the alarm LED stops flashing.
2 Walk test in the protection area to check if an alarm is activated.
Check on both the alarm LED and control panel.
3 After correct operation has been confirmed, turn the alarm LED OFF with mode
selector on the rear of the sensor unit.
When set at OFF, the alarm LED does not light even if an alarm is activated.

12 378596/A
Installation drawings

Installation drawings

Figure 4 External dimensions, PA-6810E sensor

378596/A 13
Passive IR Sensor

Figure 5 External dimensions, BCW-401 bracket

14 378596/A
Installation drawings

Figure 6 Wiring, terminal arrangement

Figure 7 Wiring, basic connection (for two units)

378596/A 15
©2012 Kongsberg Maritime

You might also like