You are on page 1of 14

1 2 3 4

S-6
2
36'-0" (typical)
x 24 0x3
3
0x3
3 x 24
W8 W1 W1 W8
A
30'-0" (typical)

E ngineers
D esign
A ISC
33 49 49 33
0x 0x 0x 0x
W1 W1 W1 W1
B

AISC Office Building


Steel Building Case Study
Lawrence, Kansas
33 49 49 33
0x 0x 0x 0x
W1 W1 W1 W1
C

1 1
S-6 S-6

Sheet # :

W8
x 24
W1
0x
33
W1
0x
33
W8
x 24
S-1
D
S-6
2

1 1st Floor Plan Sheet:


S-1 1 of 9
1 2 3 4

S-6
2
36'-0" (typical)

x 24 x 33 x 33 x 24
W8 W 12 x 22 W 10 W 12 x 22 W 10 W 12 x 22 W8
A

( T.O.S. ) - ( 2 1 2" )

( T.O.S. ) - ( 2 1 2" )

( T.O.S. ) - ( 2 1 2" )

)
2"
30'-0" (typical)

E ngineers
1
W 21 x 44

W 21 x 44
W 24 x 68

W 24 x 68

( T.O.S. ) - ( 2

D esign
( 9 ) 28 K 9 's ( 9 ) 28 K 9 's ( 9 ) 28 K 9 's

A ISC
@ 3.0 ft. O.C. @ 3.0 ft. O.C. @ 3.0 ft. O.C.

x 33 W 24 x 62 x 49 x 49 x 33
W 10 W 10 W 16 x 26 W 10 W 27 x 84 W 10
B
( T.O.S. ) - ( 2 1 2" )
W 12 x 16

AISC Office Building


W 24 x 84 ( T.O.S. ) - ( 2 1 2" )
W 16 x 26

Steel Building Case Study


( T.O.S. ) - ( 2 1 2" )

( T.O.S. ) - ( 2 1 2" )

)
5'-0"

( T.O.S. ) - ( 2 1 2" )
2"
W 21 x 83

Lawrence, Kansas
W 24 x 68
W 24 x 68
W 21 x 44

( T.O.S. ) - ( 2

W 24 x 84
5'-0" ( 9 ) 28 K 9 's ( 9 ) 28 K 9 's
W 18 x 35
@ 3.0 ft. O.C. @ 3.0 ft. O.C.
5'-0" W 12 x 16
W 21 x 83
( T.O.S. ) - ( 2 1 2" )

5'-0"
W 12 x 16

W 16 x 26 ( 2 ) 28 K 9 's
3
x3 x 49 x 33
10 5'-0" x 49
W W 24 x 62 W 10 W 16 x 26 W 10 W 27 x 84 W 10
C
1 1
S-6 S-6
( T.O.S. ) - ( 2 1 2 " )

( T.O.S. ) - ( 2 1 2 " )

( T.O.S. ) - ( 2 1 2 " )

)
2"
1
W 21 x 44

W 24 x 68

W 24 x 68

W 21 x 44
( T.O.S. ) - ( 2
( 9 ) 28 K 9 's ( 9 ) 28 K 9 's ( 9 ) 28 K 9 's
@ 3.0 ft. O.C. @ 3.0 ft. O.C. @ 3.0 ft. O.C. Sheet # :

W8
x 24 W 12 x 22 W 10
x 33 W 12 x 22 W 10
x 33 W 12 x 22 W8
x 24
S-2
D
S-6
2

1 2nd and 3rd Floor Plans Sheet:


S-2 2 of 9
1 2 3 4

S-6
2
36'-0" (typical)

x 24 W 14 x 22 x 33 W 14 x 22 x 33 W 14 x 22 x 24
W8 W 10 W 10 W8
A

( T.O.S. ) - ( 2 1 2" )

( T.O.S. ) - ( 2 1 2" )

( T.O.S. ) - ( 2 1 2" )

)
2"
30'-0" (typical)

E ngineers
1
W 14 x 26

W 14 x 26
W 16 x 40

W 16 x 40

( T.O.S. ) - ( 2

D esign
( 4 ) 24 K 6 's ( 4 ) 24 K 6 's ( 4 ) 24 K 6 's

A ISC
@ 6 ft. O.C. @ 6 ft. O.C. @ 6 ft. O.C.

x 33 x 49 W 14 x 22 x 49 W 14 x 22 x 33
W 10 W 24 x 62 W 10 W 10 W 10
B
( T.O.S. ) - ( 2 1 2" )
W 12 x 16

AISC Office Building


(3) 28 K 10's
2.5' O.C.

Steel Building Case Study


( T.O.S. ) - ( 2 1 2" )

( T.O.S. ) - ( 2 1 2" )

( T.O.S. ) - ( 2 1 2" )

)
W 21 x 62

2"
1

Lawrence, Kansas
( 1 ) 28 K 10 W 24 x 62
W 24 x 76

W 16 x 40

W 14 x 26
( T.O.S. ) - ( 2
W 16 x 26 ( 4 ) 24 K 6 's ( 4 ) 24 K 6 's
@ 6 ft. O.C. @ 6 ft. O.C.
( 5 ) 28 K 10 's
2.5' O.C.

x 33
10 x 49 W 14 x 22 x 49 W 14 x 22 x 33
W W 24 x 62 W 10 W 10 W 10
C
1 1
S-6 S-6
( T.O.S. ) - ( 2 1 2 " )

( T.O.S. ) - ( 2 1 2 " )

( T.O.S. ) - ( 2 1 2 " )

)
2"
1
W 14 x 26

W 14 x 26
W 16 x 40

W 16 x 40

( T.O.S. ) - ( 2
( 4 ) 24 K 6 's ( 4 ) 24 K 6 's ( 4 ) 24 K 6 's
@ 6 ft. O.C. @ 6 ft. O.C. @ 6 ft. O.C. Sheet # :

W8
x 24 W 14 x 22 W 10
x 33 W 14 x 22 W 10
x 33 W 14 x 22 W8
x 24
S-3
D
S-6
2

1 Roof Plan and Penthouse Floor Plan Sheet:


S-3 3 of 9
1 2 3 4

S-6
2
36'-0" (typical)

E ngineers
30'-0" (typical)

D esign
A ISC
x 33 x 49
10 10
W W 12 x 14 W
B

AISC Office Building


5'

Steel Building Case Study


(2) 24 K 6's
)

)
5'

Lawrence, Kansas
2"

2"
1

1
W 14 x 26

W 14 x 26
( T.O.S. ) - ( 2

( T.O.S. ) - ( 2
5'
W 14 x 22
5'

5' (2) 24 K 6's


x 49
x 33 5' 10
W
10 W 12 x 14 W
C

1 1
S-6 S-6

Sheet # :

S-4
D
1 Penthouse Roof Plan Sheet:
S-6
2

S-4 4 of 9
Corner Columns Edge Columns Interior Columns
152' A1, A4, D1, D4 A2, A3, B1, B4, C1, C4, D2, D3 B2, B3, C2, C3

E ngineers
T.O. STEEL

D esign
A ISC
139' W 8 x 24 W 10 x 33 W 10 x 49
T.O. STEEL
COLUMN

AISC Office Building


SPLICE

Steel Building Case Study


Lawrence, Kansas
126' 4' - 0"

T.O. STEEL

113'
T.O. STEEL
W 8 x 24 W 10 x 33 W 10 x 49

100' Sheet # :
T.O. SLAB

BASE
PLATE 14" x 14" x 1" (36 ksi) 14" x 14" x 1" (36 ksi) 14" x 14" x 1" (36 ksi)
S-5
1 Column Schedule Sheet:
S-5
5 of 9
6
13' x 7/1
8x4
2L

E ngineers
6
13' x 7/1
8x4
2L

D esign
A ISC
6
13' x 7/1
8x4
2L

13' x 1/2
8x4
2L

AISC Office Building


Steel Building Case Study
36'-0" 36'-0" 36'-0"

Lawrence, Kansas
1 N-S Section/Elevation
S-6
2L
4x
3
13' /2 x 5/1 -1/2 x
3-1 6
4 x 5/16
2L
2L
6x
13' 4x 5/1 4 x
6x 6 6
2L 5/1
2L
/2 6x
13' 4 x1 4x
1/2
6x
2L
2L Sheet # :
/4 6x
13' 4 x3 4x
3/4
6x
2L
S-6
30'-0" 30'-0" 30'-0"
2 E-W Section/Elevation
S-6 Sheet:
6 of 9
LR = 20 psf *
DL = 30 psf

LL = 80 psf LR = 20 psf * LR = 20 psf *


DL = 100 psf DL = 30 psf DL = 30 psf

E ngineers
LL = 80 psf LL = 80 psf LL = 80 psf

D esign
DL = 61 psf DL = 61 psf DL = 61 psf

A ISC
LL = 80 psf LL = 80 psf LL = 80 psf
DL = 61 psf DL = 61 psf DL = 61 psf

AISC Office Building


Steel Building Case Study
* - Consult Section 4.9.1 in ASCE 7-02 for Reduction

Lawrence, Kansas
1 N-S Section (Service) Load Diagrams
LR = 20 psf *
S-7
DL = 30 psf

LR = 20 psf * LL = 80 psf LR = 20 psf *


DL = 30 psf DL = 100 psf DL = 30 psf

LL = 80 psf LL = 80 psf LL = 80 psf


DL = 61 psf DL = 61 psf DL = 61 psf

LL = 80 psf LL = 80 psf LL = 80 psf


DL = 61 psf DL = 61 psf DL = 61 psf
Sheet # :

S-7
* - Consult Section 4.9.1 in ASCE 7-02 for Reduction

2 E-W Section (Service) Load Diagrams Sheet:


S-7
7 of 9
Wind Loading :
Exposure B
Type II
I = 1.0

E ngineers
V = 90 mph

D esign
A ISC
Gust Factor = 0.85
Cp (Windward) = 0.8
Cp (Leeward) = 0.5

AISC Office Building


Steel Building Case Study
Lawrence, Kansas
11.6 psf
7.2 psf

10.7 psf

9.3 psf

6.7 psf

8.0 psf

Sheet # :

1/3 Windward Wind Loading 2/4 Leeward Wind Loading


S-8 S-8 S-8
Sheet:
8 of 9
Seismic Loading :
7.6 kips 7.6 kips
Soil Profile D
Seismic Performance
42.3 kips 42.3 kips
Category C

E ngineers
Occupancy Category II

D esign
A ISC
36.1 kips 36.1 kips
Importance Factor = 1.0
V = 97 kips
9.0 kips 9.0 kips
K = 2.0

AISC Office Building


Steel Building Case Study
1 N-S Seismic Loading 2 E-W Seismic Loading

Lawrence, Kansas
S-9 S-9

Rain Loading : Snow Loading :


10.4 psf 25 psf
d s = 2 in. Class II
d h = 0 in. Exposure B
Cs = 1.0
Add 5 psf Rain-on-Snow
Surcharge Load Sheet # :

S-9
3 Rain Loading 4 Snow Loading
S-9 S-9 Sheet:
9 of 9
A
C
D

B
30'-0" (typical)
A-1
1

1,2,3
A-4

1
1st Floor Plan

36'-0" (typical)
2
3
4

A ISC
A-1

AISC Office Building


Sheet # :
1 of 5
Sheet:

Steel Building Case Study D esign


Lawrence, Kansas E ngineers
A
C
D

B
30'-0" (typical)
A-2
1

1,2,3
A-4

1
2nd and 3rd Floor Plans

36'-0" (typical)
2
3
4

A ISC
A-2

AISC Office Building


Sheet # :
2 of 5
Sheet:

Steel Building Case Study D esign


Lawrence, Kansas E ngineers
1 2 3 4
36'-0" (typical)

E ngineers
30'-0" (typical)

D esign
A ISC
B

AISC Office Building


Steel Building Case Study
Lawrence, Kansas
1,2,3
A-4

MECHANICAL

Sheet # :

A-3
D

1 Roof Plan and Penthouse Floor Plan Sheet:


A-3 3 of 5
COPING STRIP
DIMENSIONED LUMBER
CAP FLASHING
6" BATT INSULATION
1 152' 6" STEEL STUD 1 1/2" STONE BALLAST
T.O. STEEL SINGLE-WYTHE BRICK VENEER CANT STRIP
A-4 ADJUSTABLE BRICK TIE
BUILT-UP ROOF MEMBRANE
2" RIGID INSULATION
TYVEK INFILTRATION BARRIER 1 1/2" STEEL DECKING
O.S.B. RIGID SHEATHING
BATT FILL INSULATION
RUNNER

E ngineers
STEEL W-SECTION

D esign
STEEL TRACK (RUNNER)

A ISC
5/8" GYPSUM BOARD (DRYWALL)
9 MIL POLYETHYLENE AIR / VAPOR BARRIER
139'
1 Detail 6" STEEL STUD
6" BATT INSULATION
T.O. STEEL A-4

WALL CONSTRUCTION AS SHOWN BELOW


VINYL FINISH TRIM
SINGLE-WYTHE BRICK VENEER FINISH FLOORING

AISC Office Building


ADJUSTABLE BRICK TIE 3" REINFORCED CONCRETE TOPPING
TYVEK INFILTRATION BARRIER 1 1/2" STEEL FLOOR DECKING

Steel Building Case Study


O.S.B. RIGID SHEATHING
BATT FILL INSULATION

Lawrence, Kansas
OPEN-WEB STEEL JOIST
126'
STEEL W-SECTION
2 T.O. STEEL

A-4 STEEL TRACK (RUNNER)


5/8" GYPSUM BOARD (DRYWALL)
9 MIL POLYETHYLENE AIR / VAPOR BARRIER
2 Detail 6" STEEL STUD
6" BATT INSULATION
A-4
RUNNER
6" CONCRETE SLAB
4" GRANULAR FILL
113'
T.O. STEEL

Sheet # :

100'
A-4
T.O. SLAB
3 3 Detail
A-4 Sheet:
A-4
4 of 5
A-5

A-5
2

1
E-W Section/Elevation

N-S Section/Elevation

AISC Office Building A ISC


A-5
Sheet # :
5 of 5
Sheet:

Steel Building Case Study D esign


Lawrence, Kansas E ngineers