Cabinet specifications
Table of contents
Page Page description supplementary page field Date Edited by
+ESB1/48 Cooling Coil Pump Chick Take Off Room 16/07/2018 eplangebruiker
1 3
Table of contents
Page Page description supplementary page field Date Edited by
2 4
Table of contents
Page Page description supplementary page field Date Edited by
3 5
Table of contents
Page Page description supplementary page field Date Edited by
4 7
UT 2,5 0,5-0,6Nm
UT 4 0,6-0,8Nm
UT 6 1,5-1,8Nm
UT 10 1,5-1,8Nm
UT 16 2,5-3Nm
UT 35 3,2-3,7Nm
UKH50 6-8Nm
UKH95 15-20Nm
UKH150 25-30Nm
UKH240 25-30Nm
5 8
Nr.
0
Modification
1
Date
2
Name
10F4
X1
38313038
FUSERBLOC T2 3x400A F/L
3
OFF
OFF
info@callewaertnv.be
221K3 37F1 45K8 45F1
41A1 34K7 33Q1
OFF
OFF
37A1
OFF
50A1 44F1
10H4
48Q1
222K4 50F1 52K7 49Q1
222K5 50F5 53K7 52Q1
222K6 54F1 56K7 53Q1
222K7 54F5 56K8 56Q1
222K8 56Q3
54F6
10S4
9870 Zulte
Centrumstraat 125
Petersime
OFF
5
OFF
10X3
X3
X2
XV
50A2 38K2
57K4 XL
47A2
OFF
252K1
OFF
252K2 400A3
OFF
400A6
OFF
400A6.1 22F1
405K1 400A7 X02
Cabinet layout
OFF
35K6 405K2
400A7.1
OFF
405K3 22F4
405K3.1 400A8
6
X03
37K6 405K5
405K5.1 401A1
405K6 401A1.1
41K6 405K7
405K8 401A2
Electrical Switchboard 1
405K8.1 401A2.1
X51
44K6 420K1
10H5
420K2
TE
420K3 20F1.1
50K6 420K4
420K5
54K6 420K6
420K7 20F5
420K8
421K1 X01
421K2
421K3
421K4
421K5
421K6
421K7
421K8
390A1
X52
391A1
7
22T1
10S7
°C
X53
10S5
20G1
WB
PSE18-64681
8
16/07/2018
=
+ ESB1
9
8 Page
9
0 1 2 3 4 5 6 7 8 9
403S6
MAIN
SWITCH
1390
1300
391X7
10M7
8 10
L1 L1
L1 / 20.0
L2 L2
L2 / 20.0
L3
L3 / 20.0
L1 L2 L3
!!WARNING!!
Always under
voltage
1 3 1 3
-10F3 -10F7
C16A C6A 2 4
iC60H iT60N
2 4
1 3 5
4
-10F0 XL 1 2 XL 3 4 5 6 XL 7 8 9 10 -10S7 Θ
400A 5
2 4 6
-10W4 BL BR -10W5 BL BR -10W4 BL BR -10W5 BL BR
/10.6 /10.6 /10.4 /10.5
1 1 PE
-10S4 -10S6
2 2 XV 1 2 PE
PE PE -10H4 -10H5
-10W7 BL BR GG
LIYY-JZ
N PE L 3x1,5
L1 L2 L3 PE -10X3 N L
-10W1 BR ZW GR GG M
-10M7 1~
PE
L1 L2 L3 PE
9 20
L1
10.9 / L1 L1 / 22.0
10.9 / L2 L2 / 22.0
L3
10.9 / L3 L3 / 22.0
1 3
-20F1
C6A 2 4
iT60N
N L
-20G1
230Vac
24Vdc 10A
+ PE -
PE1
PE
-20F1.1 -20F5
+24V ON ON' 13 14 +24V' +24V ON ON' 13 14 +24V'
Input Input
(+)16² Alarm (+)16² (+)16² Alarm (+)16²
-X01 1L+ 1M 2L+ 2M 3L+ 3M 4L+ 4M -X01 5L+ 5M 6L+ 6M 7L+ 7M 8L+ 8M
1L+
1M
2L+
2M
3L+
3M
4L+
4M
5L+
5M
6L+
6M
7L+
7M
8L+
8M
390.0 /
402.0 /
403.0 /
403.8 /
430.0 /
440.0 /
460.0 /
395.2 /
390.0 /
402.0 /
403.0 /
403.8 /
430.0 /
440.0 /
460.0 /
395.2 /
Power Power Power Power Power Power Power Power
Supply Supply Supply Supply Supply Supply Supply Supply
Switch & PLC Digital Digital Analog Analog Temperature HMI's
HMI in Inputs Outputs Inputs Outputs Inputs Field
Cabinet
10 22
L1
20.9 / L1 L1 / 31.0
L2 L2
20.9 / L2 L2 / 31.0
L3
20.9 / L3 L3 / 31.0
1 3 5 1 3
-22Q1 -22F4
1-1,6A C6A 2 4
1,2A I> I> I> iT60N
2 4 6
-22T1
230V +-15% PE1
24VAC
250VA PE1
1 3
-22F1
C10A 2 4
iT60N
N24
N10
L10
32.2 /
31.7 /
32.2 /
31.7 /
Control Control
voltage voltage
24Vac 240Vac
20 31
L1
22.9 / L1 L1 / 32.0
L2
22.9 / L2 L2 / 32.0
L3
22.9 / L3 L3 / 32.0
1 3 5 13 21
-31Q1 230Vac
24-32A 14 22 22.4 / L10 L10 / 32.8
25,5A I> I> I>
/31.7
/250.1
2 4 6
13
-31Q1
/31.1 14
1 3 5
-31K7
/31.7 2 4 6
11
-405K5.1
/405.5 14 12
A1
-31K7
A2
-X1 1 2 3
PE 230Vac
22.4 / N10 N10 / 32.8
1 2 /31.1
-1018 BN GY BK GY 3 4 /31.1
H05VV-F 5 6 /31.1
4G6
13 14
21 22
+FIELD U V W PE
-31M0
3x240V AC 60Hz
7,5kW
25,5A M
3
TP80-290/2 A-F-A-BQQE
AHU main 1
Cooling Coil Section
TECHNICAL ROOM
22 32
L1
31.9 / L1 L1 / 33.0
L2
31.9 / L2 L2 / 33.0
L3
31.9 / L3 L3 / 33.0
24Vac
22.1 / L24 L24 / 33.2
0Vac
1 3 5 13 21 22.1 / N24 N24 / 33.2
-32Q1
3231 / 252.2
3241 / 252.1
3242 / 440.4
3243 / 440.4
230Vac
65A 14 22 31.8 / L10 L10 / 34.8
/32.8
/250.1
2 4 6
13
-32Q1
/32.1 14
AO+
Drive fault
MAin AHU
Drive Running
AHU MAin 1
AO-
1 3 5
-32K7 12 14
PE
/32.8 2 4 6 -405K6
/405.6 11
PE
-X81 1 2 -X81 3 4 -X81 5 6 7 8
3261 / 430.3
3271 / 430.3
-X1 4 5 6
-1021 BN GY BK GY -1022 1 2 3 4 5 6 7 8
XVB-F2 LIYCY-DIN
4G25 8x0,75
AI+
AI-
+FIELD LI1 24V R1A R1B R1C R2A R2C AI1 COM SH
PE
L1 L2 L3 PE
-32U1 Start Speed 0-10V A1
-32K7
Fault Running -X51 1 2 -X51 3 4 A2
100mA
U V W PE TE ALTIVAR
ATV312HD11M3 230Vac
31.8 / N10 N10 / 34.8
1 2 /32.1
Max 20920 m³/h
-A1023 BN GY BK GY SH Working point @55Hz -1020 1 2 3 4 3 4 /32.1
2YSLCY-J LIYCY-DIN 5 6 /32.1
4x25 4x0,75
13 14
21 22
+FIELD L N + -
7 6 5 4
-32U5 Output
4-20mA
U V W
+FIELD M
-32M1 3~ KIMO CP110-AO
Plug Fan
3x240 VAC PE
11kW
39A
31 33
L1
32.9 / L1 L1 / 34.0
L2
32.9 / L2 L2 / 34.0
L3
32.9 / L3 L3 / 34.0
1 3 5 13 21
-33Q1
13-18A 14 22
16A I> I> I>
/250.2
2 4 6
24Vac
32.6 / L24 L24 / 34.2
0Vac
32.6 / N24 N24 / 34.2
A2 11 A2
-33K3 -33K8 -33K8
A1 /33.8 14 12 A1
14 11 /250.2 14 11 /33.6
12 12
-1012 BN GY BK GY
H05VV-F
-1013 1 2 3 4 -CLIENT 1 2
4G2,5
LIYY-DIN
4x0,75
DI1 GND
+FIELD L1 L2 L3 PE +FIELD
NO C1 NC NO C1 NC 10 4 2 5 6 A Y B
-33M0 -33S8
3x240V AC 60Hz RELAY 1 RELAY 2
3kW
16A M
3
Hydro Solo-E 1 CRE 05-09 A-FGJ-A-E-HQQE
WATERTANK
32 34
33.9 / L1 L1 / 35.0
L2
33.9 / L2 L2 / 35.0
L3
33.9 / L3 L3 / 35.0
24Vac
33.9 / L24 L24 / 35.3
0Vac
1 3 5 13 21 33.9 / N24 N24 / 35.3
-34Q1
3431 / 250.7
3441 / 252.3
3442 / 440.6
3443 / 440.6
230Vac
10A 14 22 32.9 / L10 L10 / 36.8
2 4 6 /34.8
13
-34Q1
/34.1 14
AO+
Drive fault
Supply Ventilator SR1
Drive Running
Supply Ventilator SR1
AO-
1 3 5
-34K7 12 14
PE
/34.8 2 4 6 -405K7
/405.7 11
PE
-X81 15 16 -X81 17 18 -X81 19 20 21 22
3461 / 430.5
3471 / 430.5
-X11 1 2
-1030 BU BN GY -1028 1 2 3 4 5 6 7 8
XVB-F2 LIYCY-DIN
3G1,5 8x0,75
AI+
AI-
+FIELD LI1 24V R1A R1B R1C R2A R2C AI1 COM SH
PE
L1 L2 PE
-34U1 Start Speed 0-10V A1
-34K7
Fault Running -X51 5 6 -X51 7 8 A2
U V W PE TE
100mA
ALTIVAR
ATV312H055M2 230Vac
32.9 / N10 N10 / 36.8
1 2 /34.1
Master setting
-A1031 BN GY BK GY SH Min 900m³/h -1026 1 2 3 4 3 4 /34.1
2YSLCY-J Max 2900m³/h LIYCY-DIN 5 6 /34.1
4x1,5 4x0,75
13 14
21 22
+FIELD L N + -
7 6 5 4
-34U5 Output
4-20mA
U V W
+FIELD M
-34M1 3~ KIMO CP111-AO
AXUS AX400/3-6/25°/AL/3H
3x240 VAC 60Hz PE
0,55kW
1,38A
33 35
L1 L1
34.9 / L1 L1 / 36.0
L2 L2
34.9 / L2 L2 / 36.0
L3
34.9 / L3 L3 / 36.0
3521 / 440.8
24Vac
34.6 / L24 L24 / 35.7
0Vac
34.6 / N24 N24 / 35.7
-35F1 -35F5
10x38 10x38
AO+
25A gR 20A gG
-35A2 24Vac
Y E G G0 35.4 / L24 L24 / 36.2
Analog Digital
1 3 5 Signal Signal
System 1 3 5 0Vac
0-10V 0/10V
Voltage
35.4 / N24 N24 / 36.2
-221K1 -221K2
/221.1 2 4 6 /221.2 2 4 6
Signal
Output
Y1 G
SEM61.4
-35A1 A1
L Y1 G -35K6
Control System
A2
Signal Voltage 13 14 /250.3
21 22 /221.1
Q 33 34
SEA45.1
43 44
+FIELD L1 L2 PE L1 L2 L3 PE 1 2 3 4 PE
-35U0
2x240V AC 60Hz
5kW-23A
3x240V AC 60Hz
7kW-16A
Overheating Overheating
Step 1 Step 2 protection with protection with
VFLPG-M-400-400-500-12,0-3x230V-A-IP43-NI-50°C automatic reset manual reset
34 36
L1
35.9 / L1 L1 / 37.0
35.9 / L2 L2 / 37.0
L3
35.9 / L3 L3 / 37.0
24Vac
35.8 / L24 L24 / 37.3
0Vac
1 3 5 13 21 35.8 / N24 N24 / 37.3
-36Q1
3631 / 250.8
3641 / 252.4
3642 / 441.2
3643 / 441.2
230Vac
10A 14 22 34.9 / L10 L10 / 38.8
2 4 6 /36.8
13
-36Q1
/36.1 14
AO+
Drive fault
Supply Ventilator SR2
Drive Running
Supply Ventilator SR2
AO-
1 3 5
-36K8 12 14
PE
/36.8 2 4 6 -405K8.1
/405.8 11
PE
-X81 23 24 -X81 25 26 -X81 27 28 29 30
3661 / 430.6
3671 / 430.6
X11 3 4
-1035 BU BN GY -1029 1 2 3 4 5 6 7 8
XVB-F2 LIYCY-DIN
3G1,5 8x0,75
AI+
AI-
+FIELD LI1 24V R1A R1B R1C R2A R2C AI1 COM SH
PE
L1 L2 PE
-36U1 Start Speed 0-10V A1
-36K8
Fault Running -X51 9 10 -X51 11 12 A2
U V W PE TE
100mA
ALTIVAR
ATV312H055M2 230Vac
34.9 / N10 N10 / 38.8
1 2 /36.1
Max 2900m³/h
-A1036 BN GY BK GY SH Min 900m³/h -1027 1 2 3 4 3 4 /36.1
2YSLCY-J LIYCY-DIN 5 6 /36.1
4x1,5 4x0,75
13 14
21 22
+FIELD L N + -
7 6 5 4
-36U5 Output
4-20mA
U V W
+FIELD M
-36M1 3~ KIMO CP110-AO
AXUS 400/3-6/25°/AL/3H
3x240 VAC 60Hz PE
0,55kW
1,38A
35 37
L1
36.9 / L1 L1 / 38.0
L2 L2
36.9 / L2 L2 / 38.0
L3 L3
36.9 / L3 L3 / 38.0
3721 / 441.4
24Vac
36.6 / L24 L24 / 37.7
0Vac
36.6 / N24 N24 / 37.7
-37F1 -37F5
10x38 10x38
AO+
25A gR 20A gG
-37A2 24Vac
Y E G G0 37.4 / L24 L24 / 38.3
Analog Digital
1 3 5 Signal Signal
System 1 3 5 0Vac
0-10V 0/10V
Voltage
37.4 / N24 N24 / 38.3
-221K3 -221K4
/221.3 2 4 6 /221.4 2 4 6
Signal
Output
Y1 G
SEM61.4
-37A1 A1
L Y1 G -37K6
Control System
A2
Signal Voltage 13 14 /250.3
21 22 /221.3
Q 33 34
SEA45.1
43 44
+FIELD L1 L2 PE L1 L2 L3 PE 1 2 3 4 PE
-37U0
2x240V AC 60Hz
5kW-23A
3x240V AC 60Hz
7kW-16A
Overheating Overheating
Step 1 Step 2 protection with protection with
VFLPG-M-400-400-500-12,0-3x230V-A-IP43-NI-50°C automatic reset manual reset
36 38
L1
37.9 / L1 L1 / 39.0
L2
37.9 / L2 L2 / 39.0
37.9 / L3 L3 / 39.0
1 3 12 14
-38F1 230Vac
C6A 2 4 11 36.9 / L10 L10 / 39.7
iC60N /38.8
11
24Vac
-38F1
37.8 / L24 L24 / 40.2 /38.1 14 12
1 3 5 0Vac
37.8 / N24 N24 / 40.2
-38K8
/38.8 2 4 6 3821 / 441.6
3822 / 441.6
3861 / 430.6
3871 / 430.7
A2
AO+
AO-
-38K2
A1
14 11 /250.4
AI+
AI-
12
PE PE
A1
-38K8
-X51 13 14 -X51 15 16 A2
-X11 5 6 -X52 1 2 -X52 3 4 100mA
PE 230Vac
36.9 / N10 N10 / 39.7
1 2 /38.1
Maximum 5800m³/h
37 39
L1
38.9 / L1 L1 / 40.0
L2
38.9 / L2 L2 / 40.0
L3
38.9 / L3 L3 / 40.0
1 3 5 13 21
-39Q1 230Vac
1,6-2,5A 14 22 38.9 / L10 L10 / 40.7
1,65A I> I> I>
2 4 6 /39.7
13
-39Q1
/39.1 14
1 3 5
-39K7
/39.7 2 4 6
11
-420K2
/420.2 14 12
A1
-39K7
A2
-X1 10 11 12
PE 230Vac
38.9 / N10 N10 / 40.7
1 2 /39.1
3 4 /39.1
-1051 BN GY BK GY
5 6 /39.1
H05VV-F 13 14
4G1,5
21 22
+FIELD U V W PE
-39M0
3x240V AC 50Hz
0,37kW
1,65A M
3
CR 1S-2 A-FGJ-A-E-HQQE 96517389
TECHNICAL ROOM
38 40
L1
39.9 / L1 L1 / 41.0
39.9 / L2 L2 / 41.0
L3
39.9 / L3 L3 / 41.0
24Vac
38.6 / L24 L24 / 41.3
0Vac
1 3 5 13 21 38.6 / N24 N24 / 41.3
-40Q1
4031 / 250.8
4041 / 252.5
4042 / 442.2
4043 / 442.2
230Vac
14A 14 22 39.8 / L10 L10 / 42.8
2 4 6 /40.7
13
-40Q1
/40.1 14
AO+
Drive fault
AHU Transfer Room
Drive Running
AHU Transfer Room
AO-
1 3 5
-40K7 12 14
PE
/40.7 2 4 6 -420K3
/420.3 11
PE
-X81 31 32 -X81 33 34 -X81 35 36 37 38
-X11 7 8
-1054 BU BN GY -1053 1 2 3 4 5 6 7 8
XVB-F2 LIYCY-DIN
3G1,5 8x0,75
+FIELD LI1 24V R1A R1B R1C R2A R2C AI1 COM SH
L1 L2 PE
-40U1 Start Speed 0-10V A1
-40K7
Fault Running
A2
U V W PE TE ALTIVAR
ATV312HU11M2 230Vac
39.8 / N10 N10 / 42.8
1 2 /40.1
Fix workpoint @62Hz Max.67Hz
-A1056 BN GY BK GY SH Fix 2500m³/h 3 4 /40.1
2YSLCY-J 5 6 /40.1
4x2,5
13 14
21 22
U V W
+FIELD M
-40M1 3~
3x240 VAC 60Hz
1,1kW PE
4,85A
39 41
L1
40.9 / L1 L1 / 42.0
L2 L2
40.9 / L2 L2 / 42.0
L3 L3
40.9 / L3 L3 / 42.0
4121 / 442.4
24Vac
40.4 / L24 L24 / 41.7
0Vac
40.4 / N24 N24 / 41.7
-41F1 -41F5
10x38 10x38
AO+
20A gR 16A gG
-41A2 24Vac
Y E G G0 41.4 / L24 L24 / 42.5
Analog Digital
1 3 5 Signal Signal
System 1 3 5 0Vac
0-10V 0/10V
Voltage
41.4 / N24 N24 / 42.5
-221K5 -221K6
/221.5 2 4 6 /221.6 2 4 6
Signal
Output
Y1 G
SEM61.4
-41A1 A1
L Y1 G -41K6
Control System
A2
Signal Voltage 13 14 /250.4
21 22 /221.5
Q 33 34
SEA45.1
43 44
+FIELD L1 L2 PE L1 L2 L3 PE 1 2 3 4 PE
-41U0
2x240V AC 60Hz
3kW-13,7A
3x240V AC 60Hz
6kW-15,5A
Overheating Overheating
Step 1 Step 2 protection with protection with
VFLPG-M-400-400-500-9,0-3x230V-A-IP43-NI-50°C automatic reset manual reset
40 42
L1
41.9 / L1 L1 / 43.0
L2
41.9 / L2 L2 / 43.0
41.9 / L3 L3 / 43.0
1 3 12 14
-42F1 230Vac
C6A 2 4 11 40.8 / L10 L10 / 43.8
iC60N /42.8
11
24Vac
-42F1
41.8 / L24 L24 / 43.2 /42.1 14 12
1 3 5 0Vac
41.8 / N24 N24 / 43.2
-42K8
/42.8 2 4 6 4221 / 442.6
4222 / 442.6
4261 / 431.3
4271 / 431.3
AO+
AO-
AI+
AI-
PE PE
A1
-42K8
-X51 17 18 -X51 19 20 A2
-X11 9 10 -X52 5 6 100mA
PE 230Vac
40.8 / N10 N10 / 43.8
1 2 /42.1
Maximum 2500m³/h
41 43
L1
42.9 / L1 L1 / 44.0
42.9 / L2 L2 / 44.0
L3
42.9 / L3 L3 / 44.0
24Vac
42.6 / L24 L24 / 44.3
0Vac
1 3 5 13 21 42.6 / N24 N24 / 44.3
-43Q1
4331 / 250.9
4341 / 252.6
4342 / 442.8
4343 / 442.8
230Vac
10A 14 22 42.9 / L10 L10 / 45.8
2 4 6 /43.8
13
-43Q1
/43.1 14
AO+
Drive fault
Supply Ventilaotr HR1
Drive Running
Supply Ventilaotr HR1
AO-
1 3 5
-43K8 12 14
PE
/43.8 2 4 6 -420K5
/420.5 11
PE
-X81 39 40 -X81 41 42 -X81 43 44 45 46
4361 / 431.4
4371 / 431.4
-X11 11 12
-1071 BU BN GY -1072 1 2 3 4 5 6 7 8
XVB-F2 LIYCY-DIN
3G1,5 8x0,75
AI+
AI-
+FIELD LI1 24V R1A R1B R1C R2A R2C AI1 COM SH
PE
L1 L2 PE
-43U1 Start Speed 0-10V A1
-43K8
Fault Running -X51 21 22 -X51 23 24 A2
U V W PE TE
100mA
ALTIVAR
ATV312H055M2 230Vac
42.9 / N10 N10 / 45.8
1 2 /43.1
Max 3600m³/h
-A1073 BN GY BK GY SH Min 1200m³/h -1070 1 2 3 4 3 4 /43.1
2YSLCY-J LIYCY-DIN 5 6 /43.1
4x1,5 4x0,75
13 14
21 22
+FIELD L N + -
7 6 5 4
-43U5 Output
4-20mA
U V W
+FIELD M
-43M1 3~ KIMO CP111-AO
AXUS AX400/3-6/30°/AL/3H
3x240 VAC 60Hz PE
0,55kW
1,37A
42 44
L1 L1
43.9 / L1 L1 / 45.0
L2 L2 L2
43.9 / L2 L2 / 45.0
L3 L3 L3
43.9 / L3 L3 / 45.0
4421 / 444.2
24Vac
43.6 / L24 L24 / 44.7
0Vac
43.6 / N24 N24 / 44.7
-44F1 -44F5 -44F6
10x38 10x38 10x38
AO+
20A gR 16A gG 25A gG
-44A2 24Vac
Y E G G0 44.4 / L24 L24 / 46.5
Analog Digital
1 3 5 Signal Signal
System 1 3 5 1 3 5 0Vac
0-10V 0/10V
Voltage
44.4 / N24 N24 / 46.5
-222K1 -222K2 -222K3
/222.1 2 4 6 /222.2 2 4 6 /222.3 2 4 6
Signal
Output
Y1 G
SEM61.4
-44A1 A1
L Y1 G -44K6
Control System
A2
Signal Voltage 13 14 /250.5
21 22 /222.1
Q 33 34
SEA45.1
43 44
KABELNUMMER?
H05VV-F 1 2 GY -1075 BN GY BK GY -1076 BN GY BK GY -1077 1 2 GY
3G4 H05VV-F H05VV-F XVB-F2
4G2,5 4G4 3G1,5
+FIELD L1 L2 PE L1 L2 L3 PE L1 L2 L3 PE 1 2 3 4 PE
-44U0
2x240V AC 60Hz
3kW-13,7A
2x240V AC 60Hz
5kW-11,4A
2x240V AC 60Hz
9kW-21A Overheating Overheating
Step 1 Step 2 Step 3 protection with protection with
VFLPG-M-500-500-630-17,0-3x230V-A-IP43-NI-50°C automatic reset manual reset
43 45
L1
44.9 / L1 L1 / 46.0
L2
44.9 / L2 L2 / 46.0
44.9 / L3 L3 / 46.0
1 3 12 14
-45F1 230Vac
C6A 2 4 11 43.9 / L10 L10 / 46.8
iC60N /45.8
11
-45F1
/45.1 14 12
1 3 5
-45K8
/45.8 2 4 6 4521 / 444.4
4522 / 444.4
AO+
AO-
PE
A1
-45K8
A2
-X11 13 14 -X52 7 8
PE 230Vac
43.9 / N10 N10 / 46.8
1 2 /45.1
230V AC 60Hz
0,17kW
M Control
Signals
1,53A 1~
EBM W3G300-DN02-53
Maximum 1200m³/h
HATCHER ROOM 1
44 46
L1
45.9 / L1 L1 / 47.0
45.9 / L2 L2 / 47.0
L3
45.9 / L3 L3 / 47.0
1 3 12 14
-46F1 230Vac
C6A 2 4 11 45.9 / L10 L10 / 47.8
iC60N /46.8
11
24Vac
-46F1
44.8 / L24 L24 / 47.5 /46.1 14 12
1 3 5 0Vac
44.8 / N24 N24 / 47.5
-46K8
/46.8 2 4 6 4621 / 444.6
4622 / 444.6
4661 / 431.6
4671 / 431.6
AO+
AO-
AI+
AI-
PE PE
A1
-46K8
-X51 25 26 -X51 27 28 A2
-X11 15 16 -X52 9 10 100mA
PE 230Vac
45.9 / N10 N10 / 47.8
1 2 /46.1
Maximum 1800m³/h
45 47
46.9 / L1 L1 / 48.0
L2
46.9 / L2 L2 / 48.0
L3
46.9 / L3 L3 / 48.0
1 3 12 14
-47F1 230Vac
C6A 2 4 11 46.9 / L10 L10 / 48.7
iC60N /47.8
11
24Vac
-47F1
46.6 / L24 L24 / 49.2 /47.1 14 12
1 3 5 0Vac
46.6 / N24 N24 / 49.2
-47K8
/47.8 2 4 6 4721 / 444.8
4722 / 444.8
4761 / 431.6
4771 / 431.7
AO+
AO-
AI+
AI-
PE PE
A1
-47K8
-X51 29 30 -X51 31 32 A2
-X11 17 18 -X52 11 12 100mA
PE 230Vac
46.9 / N10 N10 / 48.7
1 2 /47.1
Maximum 1800m³/h
46 48
L1
47.9 / L1 L1 / 49.0
L2
47.9 / L2 L2 / 49.0
L3
47.9 / L3 L3 / 49.0
1 3 5 13 21
-48Q1 230Vac
1,6-2,5A 14 22 47.9 / L10 L10 / 49.8
1,65A I> I> I>
2 4 6 /48.7
13
-48Q1
/48.1 14
1 3 5
-48K7
/48.7 2 4 6
11
-420K8
/420.8 14 12
A1
-48K7
A2
-X1 13 14 15
PE 230Vac
47.9 / N10 N10 / 49.8
1 2 /48.1
3 4 /48.1
-1096 BN GY BK GY
5 6 /48.1
H05VV-F 13 14
4G1,5
21 22
+FIELD U V W PE
-48M0
3x240V AC 50Hz
0,37kW
1,65A M
3
CR 1S-2 A-FGJ-A-E-HQQE 96517389
47 49
L1
48.9 / L1 L1 / 50.0
L2
48.9 / L2 L2 / 50.0
48.9 / L3 L3 / 50.0
24Vac
47.6 / L24 L24 / 50.3
0Vac
1 3 5 13 21 47.6 / N24 N24 / 50.3
-49Q1
4931 / 250.9
4941 / 252.7
4942 / 445.4
4943 / 445.4
230Vac
14A 14 22 48.8 / L10 L10 / 51.8
2 4 6 /49.8
13
-49Q1
/49.1 14
AO+
Drive fault
AHU Chick
Take Off Room
Drive Running
AHU Chick
Take Off Room
AO-
1 3 5
-49K7 12 14
PE
/49.8 2 4 6 -421K1
/421.1 11
PE
-X81 47 48 -X81 49 50 -X81 51 52 53 54
4961 / 431.7
4971 / 431.8
-X11 19 20
-1101 BU BN GY -1102 1 2 3 4 5 6 7 8
XVB-F2 LIYCY-DIN
3G1,5 8x0,75
AI+
AI-
+FIELD LI1 24V R1A R1B R1C R2A R2C AI1 COM SH
PE
L1 L2 PE
-49U1 Start Speed 0-10V A1
-49K7
Fault Running -X51 33 34 -X51 35 36 A2
U V W PE TE
100mA
ALTIVAR
ATV312HU11M2 230Vac
48.8 / N10 N10 / 51.8
1 2 /49.1
Winter: Max 1430m³/h
-A1103 BN GY BK GY SH Summer: Max 720m³/h -1100 1 2 3 4 3 4 /49.1
2YSLCY-J Max.1430m³/h LIYCY-DIN 5 6 /49.1
4x2,5 Workpoint @49Hz 4x0,75
13 14
21 22
+FIELD L N + -
7 6 5 4
-49U5 Output
4-20mA
U V W
+FIELD M
-49M1 3~ KIMO CP111-AO
Plug Fan
3x240 VAC 60Hz PE
1,1kW
3,3A
48 50
L1 L1
49.9 / L1 L1 / 51.0
L2
49.9 / L2 L2 / 51.0
L3 L3
49.9 / L3 L3 / 51.0
5021 / 445.6
24Vac
49.6 / L24 L24 / 50.7
0Vac
49.6 / N24 N24 / 50.7
-50F1 -50F5
10x38 10x38
AO+
20A gR 10A gG
-50A2 24Vac
Y E G G0 50.4 / L24 L24 / 53.2
Analog Digital
1 3 5 Signal Signal
System 1 3 5 0Vac
0-10V 0/10V
Voltage
50.4 / N24 N24 / 53.2
-222K4 -222K5
/222.4 2 4 6 /222.5 2 4 6
Signal
Output
Y1 G
SEM61.4
-50A1 A1
L Y1 G -50K6
Control System
A2
Signal Voltage 13 14 /250.5
21 22 /222.4
Q 33 34
SEA45.1
43 44
+FIELD L1 L2 PE L1 L2 L3 PE 1 2 3 4 PE
-50U0
2x240V AC 60Hz
3kW-13,7A
3x240V AC 60Hz
3kW-6,7A
Overheating Overheating
Step 1 Step 2 protection with protection with
VFLPG-M-400-400-500-6,0-3x230V-A-IP43-NI-50°C automatic reset manual reset
49 51
50.9 / L1 L1 / 52.0
L2
50.9 / L2 L2 / 52.0
L3
50.9 / L3 L3 / 52.0
1 3 12 14
-51F1 230Vac
C6A 2 4 11 49.9 / L10 L10 / 52.7
iC60N /51.8
11
-51F1
/51.1 14 12
1 3 5
-51K8
/51.8 2 4 6 5121 / 445.8
5122 / 445.8
AO+
AO-
PE
A1
-51K8
A2
-X11 21 22 -X52 13 14
PE 230Vac
49.9 / N10 N10 / 52.7
1 2 /51.1
230V AC 60Hz
0,17kW
M Control
Signals
1,35A 1~
EBM W3G300-YN0238
Maximum 1430m³/h
50 52
L1
51.9 / L1 L1 / 53.0
L2
51.9 / L2 L2 / 53.0
L3
51.9 / L3 L3 / 53.0
1 3 5 13 21
-52Q1 230Vac
4-6,3A 14 22 51.9 / L10 L10 / 53.8
4,5A I> I> I>
2 4 6 /52.7
13
-52Q1
/52.1 14
1 3 5
-52K7
/52.7 2 4 6
11
-421K3
/421.3 14 12
A1
-52K7
A2
-X1 16 17 18
PE 230Vac
51.9 / N10 N10 / 53.8
1 2 /52.1
-1121 BN GY BK GY 3 4 /52.1
H05VV-F 5 6 /52.1
4G1,5
13 14
21 22
+FIELD U V W PE
-52M0
3x240V AC 60Hz
1,1kW
4,5A M
3
TP32-190/4 A-F-A-BAQE
TECHNICAL ROOM
51 53
L1
52.9 / L1 L1 / 54.0
L2
52.9 / L2 L2 / 54.0
L3
52.9 / L3 L3 / 54.0
24Vac
50.8 / L24 L24 / 54.3
0Vac
1 3 5 13 21 50.8 / N24 N24 / 54.3
-53Q1
5331 / 250.9
5341 / 252.8
5342 / 446.4
5343 / 446.4
230Vac
25A 14 22 52.8 / L10 L10 / 55.8
2 4 6 /53.8
13
-53Q1
/53.1 14
AO+
Drive fault
AHU Chick
Handling Room
Drive Running
AHU Chick
Handling Room
AO-
1 3 5
-53K7 12 14
PE
/53.8 2 4 6 -421K4
/421.4 11
PE
-X81 55 56 -X81 57 58 -X81 59 60 61 62
5361 / 432.3
5371 / 432.3
-X1 19 20 21
-1126 BN GY BK GY -1127 1 2 3 4 5 6 7 8
XVB-F2 LIYCY-DIN
4G2,5 8x0,75
AI+
AI-
+FIELD LI1 24V R1A R1B R1C R2A R2C AI1 COM SH
PE
L1 L2 L3 PE
-53U1 Start Speed 0-10V A1
-53K7
Fault Running -X51 37 38 -X51 39 40 A2
U V W PE TE
100mA
ALTIVAR
ATV312HU11M2 230Vac
52.8 / N10 N10 / 55.8
1 2 /53.1
Workpoint @49Hz
-A1128 BN GY BK GY SH -1125 1 2 3 4 3 4 /53.1
2YSLCY-J LIYCY-DIN 5 6 /53.1
4x2,5 4x0,75
13 14
21 22
+FIELD L N + -
7 6 5 4
-53U5 Output
4-20mA
U V W
+FIELD M
-53M1 3~ KIMO CP110-AO
3x240 VAC 60Hz
0,86kW PE
3,3A
52 54
L1 L1 L1
53.9 / L1 L1 / 55.0
L2 L2 L2
53.9 / L2 L2 / 55.0
L3 L3
53.9 / L3 L3 / 55.0
5421 / 446.6
24Vac
53.6 / L24 L24 / 54.7
0Vac
53.6 / N24 N24 / 54.7
-54F1 -54F5 -54F6
10x38 10x38 10x38
AO+
25A gR 20A gG 25A gG
-54A2 24Vac
Y E G G0 54.4 / L24 L24 / 55.3
Analog Digital
1 3 5 Signal Signal
System 1 3 5 1 3 5 0Vac
0-10V 0/10V
Voltage
54.4 / N24 N24 / 57.4
-222K6 -222K7 -222K8
/222.6 2 4 6 /222.7 2 4 6 /222.8 2 4 6
Signal
Output
Y1 G
SEM61.4
-54A1 A1
L Y1 G -54K6
Control System
A2
Signal Voltage 13 14 /250.6
21 22 /222.6
Q 33 34
SEA45.1
43 44
+FIELD L1 L2 PE L1 L2 L3 PE L1 L2 L3 PE 1 2 3 4 PE
-54U0
2x240V AC 60Hz
5kW-23A
3x240VAC 60Hz
7kW-15,33A
3x240VAC 60Hz
9kW-19,7A Overheating Overheating
Step 1 Step 2 Step 3 protection with protection with
VFLPG-M-710-710-600-21,0-3x230V-M-A-IP43-NI-50°C automatic reset manual reset
53 55
L1
54.9 / L1 L1 / 56.0
54.9 / L2 L2 / 56.0
L3
54.9 / L3 L3 / 56.0
1 3 12 14
-55F1 230Vac
C6A 2 4 11 53.9 / L10 L10 / 56.6
iC60N /55.8
11
24Vac
-55F1
54.8 / L24 L24 / 57.3 /55.1 14 12
1 3 5
5541 / 57.3
-55K8
/55.8 2 4 6 5521 / 446.8
5522 / 446.8
AO+
AO-
AO-
5522 / 57.2
AO+ PE
5521 / 57.2 A1
-55K8
A2
-X11 23 24 -X52 15 16 -X52 17 18
PE 230Vac
53.9 / N10 N10 / 56.6
1 2 /55.1
230V AC 60Hz
0,5kW
M Control Status contact
Signals break = Failure
2,2A 1~
EBM W3G450IL03H4
Maximum 4115m³/h
Exhaust Ventilator 1
Chick Handling Room
54 56
L1
55.9 / L1 L1 / 57.0
L2 L2
55.9 / L2 L2 / 57.0
L3
55.9 / L3 L3 / 57.0
1 3 5 13 21 1 3 5 13 21
-56Q1 -56Q3 230Vac
1-1,6A 14 22 1-1,6A 14 22 55.9 / L10 L10 / 57.8
1,5A I> I> I> 1,5A I> I> I>
/56.7
/56.8
2 4 6 2 4 6
13
-412K7
14
1 3 5 1 3 5
-56K7 -56K8
/56.7 2 4 6 /56.8 2 4 6
13 13
-56Q1 -56Q3
/56.1 14 /56.3 14
A1 A1
-56K7 -56K8
A2 A2
-X11 25 26 -X11 27 28
PE PE 230Vac
55.9 / N10 N10 / 57.8
1 2 /56.1 1 2 /56.3
3 4 /56.1 3 4 /56.3
-1139 BN BK GY -1140 BN BK GY
5 6 /56.1 5 6 /56.3
XVB-F2 XVB-F2 13 14 13 14
3G1,5 3G1,5
21 22 21 22
N L N L
+FIELD M +FIELD M
-56M1 1~ -56M3 1~
T4D40K8M81160 PE T4D40K8M81160 PE
230V 60Hz 230V 60Hz
0,27kW/1,5A 0,27kW/1,5A
CHICK HANDLING ROOM CHICK HANDLING ROOM CHICK HANDLING CHICK HANDLING
ROOM ROOM
55 57
L1
56.9 / L1 L1 /
56.9 / L2 L2 /
L3
56.9 / L3 L3 /
1 3 12 14
-57F1 230Vac
C6A 2 4 11 56.8 / L10 L10 / 220.0
iC60N /57.8
11
24Vac
-57F1
55.4 / L24 L24 / 250.0 /57.1 14 12
1 3 5
55.4 / 5541
-57K8
/57.8 2 4 6 5521 / 55.3
5522 / 55.3
A1
-57K4
A2
14 11 /250.6
12
AO+
AO-
0Vac
54.8 / N24 N24 / 250.0
PE
A1
-57K8
A2
-X11 29 30 -X52 19 20 -X52 21 22
PE 230Vac
56.8 / N10 N10 / 220.0
1 2 /57.1
230V AC 60Hz
0,5kW
M Control Status contact
Signals break = Failure
2,2A 1~
EBM W3G450IL03H4
Maximum 4115m³/h
Exhaust Ventilator 2
Chick Handling Room
56 220
230V
57.9 / L10 L10 / 221.0
230V
57.9 / N10 N10 / 221.0
11
-405K2
/405.2
14 12
1 2
PE
-X2 100mA
100mA
-1014 1 2 GY
H05VV-F
3G1,5
+FIELD 1 2 PE
-220Y0
SXE210C094
Watertank
Magnetic
Filling
Valve
57 221
43
-252K1
/252.1 44
AHU Main
Running
L221 / 222.0
21 21 21
-35K6 -37K6 -41K6
/35.7 22 /37.7 22 /41.7 22
High High High
Temperature Temperature Temperature
Heating Heating Heating
Setter Room 1 Setter Room 2 Tranfer Room
11 11 11
A1 A1 A1 A1 A1 A1
-221K1 -221K2 -221K3 -221K4 -221K5 -221K6
A2 A2 A2 A2 A2 A2
Supply Step 1 Supply Step 2 Supply Step 1 Supply Step 2 Supply Step 1 Supply Step 2
Electrical Heating Electrical Heating Electrical Heating Electrical Heating Electrical Heating Electrical Heating
Setter Room 1 Setter Room 1 Setter Room 2 Setter Room 2 Transfer Room Transfer Room
PLENUM SETTER ROOM PLENUM SETTER ROOM PLENUM SETTER ROOM PLENUM SETTER ROOM TRANSFER ROOM TRANSFER ROOM
220 222
221.9 / L221
21 21 21
-44K6 -50K6 -54K6
/44.7 22 /50.7 22 /54.7 22
High High High
Temperature Temperature Temperature
Heating Heating Heating
Hatcher Room 1 Chick Take Chick
Off Room Handling Room
11 11 11 11 11
A1 A1 A1 A1 A1 A1 A1 A1
-222K1 -222K2 222K3 -222K4 -222K5 -222K6 -222K7 -222K8
A2 A2 A2 A2 A2 A2 A2 A2
Supply Step 1 Supply Step 2 Supply Step 3 Supply Step 1 Supply Step 2 Supply Step 1 Supply Step 2 Supply Step 3
Electrical Heating Electrical Heating Electrical Heating Electrical Heating Electrical Heating Electrical Heating Electrical Heating Electrical Heating
Hatcher Room 1 Hatcher Room 1 Hatcher Room 1 Chick Take Off Room Chick Take Off Room Chick Handling Room Chick Handling Room Chick Handling Room
HATCHER ROOM 1 HATCHER ROOM 1 HATCHER ROOM 1 ABOVE CHICK AREA ABOVE CHICK AREA ABOVE CHICK AREA ABOVE CHICK AREA ABOVE CHICK AREA
221 230
21
-405K1
/405.1 24 22
X82 1 X82 2
-1001 1 2
LIYY-DIN
2x0,75
+ALARM_PANEL
General alarm
ESB 1
to alarm panel
Technical Room
222 250
24Vac
57.5 / L24 L24 / 251.0
3431 / 34.3
3631 / 36.3
4031 / 40.3
4331 / 43.3
4931 / 49.3
5331 / 53.3
21 21 21 11 13 13 11 13 13 13 13 11 11
-31Q1 -32Q1 -33Q1 -33K3 -35K6 -37K6 -38K2 -41K6 -44K6 -50K6 -54K6 -57K4 -252K2
/31.1 /32.1 /33.1 /33.3 /35.7 /37.7 /38.4 /41.7 /44.7 /50.7 /54.7 /57.5 /252.2
Drive fault
Supply Ventilator SR1
Drive fault
Supply Ventilator SR2
Drive fault
AHU Transfer Room
Drive fault
Supply Ventilaotr HR1
Drive fault
AHU Chick
Take Off Room
Drive fault
AHU Chick
Handling Room
22 22 22 14 12 14 14 14 12 14 14 14 14 14 12 14 12
General alarm Supply Pressure Pressure High High Fault High High High High Fault Control Relay
motor rising Rising Pump Temperature Temperature Exhaust Temperature Temperature Temperature Temperature Exhaust Drive Fault
Dry Running Heating Heating Ventilator Heating Heating Heating Heating Ventilator 1/2 AHU Main 1
AHU main 1 pump Setter Room 1 Setter Room 2 Plenum SR Tranfer Room Hatcher Room 1 Chick Take Chick Chick
incubators Off Room Handling Room Handling Room
A1
-250K1
A2
0Vac
57.5 / N24 N24 / 251.0
14 11 /403.2
12
General alarm
230 251
24Vac
250.9 / L24 L24 / 252.0
11 13 23 33 21
inside panel
/403.3
Alarm Off
0=Off
1=Alarm Off
x1 x1 x1 x1
-251H1 -251H2 -251H3 -251H4
RD x2 RD x2 GN x2 RD x2
General Attention Running Overload
Alarm Alarm Off
0Vac
250.9 / N24 N24 / 252.0
250 252
24Vac
251.9 / L24 L24 / 440.0
3241 / 32.4
3231 / 32.3
3441 / 34.4
3641 / 36.4
4041 / 40.4
4341 / 43.4
4941 / 49.4
5341 / 53.4
Drive Running
AHU MAin 1
Drive fault
MAin AHU
Drive Running
Supply Ventilator SR1
Drive Running
Supply Ventilator SR2
Drive Running
AHU Transfer Room
Drive Running
Supply Ventilaotr HR1
Drive Running
AHU Chick
Take Off Room
Drive Running
AHU Chick
Handling Room
A1 A1 A1 A1 A1 A1 A1 A1
-252K1 -252K2 -252K3 -252K4 -252K5 -252K6 -252K7 -252K8
AHU Main A2 A2 A2 A2 A2 A2 A2 A2
Running
0Vac
251.9 / N24 N24 / 440.0
13 14 14 11 /250.7 14 11 /404.2 14 11 /404.3 14 11 /404.4 14 11 /404.4 14 11 /404.5 14 11 /404.6
21 22 12 12 12 12 12 12 12
33 34 /251.3 24 21 /251.4
22
43 44 /221.1
53 54 /403.7
61 62
71 72
83 84
Control Relay Control Relay Control Relay Control Relay Control Relay Control Relay Control Relay Control Relay
Drive Running Drive Fault Drive Running Drive Running Drive Running Drive Running Drive Running Drive Running
AHU Main 1 AHU Main 1 Supply Ventilator Supply Ventilator AHU Transfer Room Supply Ventilator AHU Chick AHU Chick
Setter Room 1 Setter Room 2 Hatcher Room 1 Take Off Room Handling Room
251 390
PE
-390A1
+24V 0V PE
X1 X2 X3 X4 X5
TCSESU053FN0
SWITCH 2
PLC 1
HMI
HMI
HMI
ETH1
ETH2
ETH3
ETH4
ETH5
402.7 /
395.0 /
395.3 /
395.5 /
391.2 /
252 391
PE
-391A1 -391X7
+24V 0V PE /395.2 RJ45 RJ45
/395.4
OUTLET 1
OUTLET 2
/395.6
Panduit
X1 X2 X3 X4 X5 surfbox
TCSESU053FN0
+FIELD
ETH5
ETH6
390.4 /
395.7 /
390 395
ETH2 / 390.3
ETH3 / 390.3
ETH4 / 390.4
ETH6 / 391.3
PE PE PE
OUTLET 3
OUTLET 4
OUTLET 5
surfbox surfbox surfbox
Chick Area
391 400
-400W6
Patch
TMC4TI2
Cartridge
2 temperature
inputs
TM241CEC24T
TM3DQ16R
TM3XTRA1
TM3XREC1
TM3AQ4
TM3AQ4
TM3AQ4
TM3AQ4
TM3AQ4
TM3AQ4
TM3AI8
TM3AI8
TM3AI8
Insert batterie
into device
-400A0 -400A2 -400A3 -400A3.1 -400A4 -400A4.1 -400A5 -400A5.1 -400A6 -400A6.1 -400A7 -400A7.1 -400A8
/402.0 /420.0 /430.0 /431.0 /432.0 /440.0 /441.0 /442.0 /443.0 /444.0 /445.0 /446.0
/403.0 /421.0
/404.0
/405.0
/463.0
395 401
TM3TI4
TM3TI4
TM3TI4
400 402
-X85 1 2 3
ETH1 / 390.2
-402W3 1 2 3
LIYCY-JZ
3x0,75
PE
-400A0
/400.0 + - PE NC CAN_H CAN_L GND SH COM SH D0 D1
Ethernet
401 403
X3 1 X3 3 X3 5 7 8 X3 9
VT NR RG
+FIELD +FIELD
QBM 81.3
+FIELD +FIELD
11 23 -403S3 -403S4 13 53 -403U7 S1 1 2
-403U8 1
24VAC
-250K1 -251S2 -403S6 -252K1
/250.1 14 12 /251.2 AHU Main 1 /252.1
24 Off/Auto
14 Feedback
54
SF24A-S2
AHU Main S3 S2 3 2
Running
BC
X3 2 X3 4 X3 6 X3 10
PE
-400A0 I0 I1 I2 I3 I4 I5 I6 I7
/400.0 NC NC COM0 E0.0 E0.1 E0.2 E0.3 PE COM1 E0.4 E0.5 E0.6 E0.7
DC IN DC IN
TM241CEC24T PART 2 OF 4
Alarm Alarm Off Level Switch 1 Level Switch 2 Off/Auto Switch Feedback Servo motor Security
motor switch in Filling Point Dryrunning Main AHU 1 AHU Main Damper Filter
protectors ESB1 Watertank 5000l Watertank 5000l Running Main AHU 1 Main AHU 1
402 404
11 11 11 11 11 11
-252K3 -252K4 -252K5 -252K6 -252K7 -252K8
/252.3 14 12 /252.4 14 12 /252.5 14 12 /252.6 14 12 /252.7 14 12 /252.8 14 12
TM241CEC24T PART 3 OF 4
403 405
DC IN DC IN DC IN
V0+ V0- A0.0 A0.1 A0.2 A0.3 PE V1+ V1- A0.4 A0.5 A0.6 A0.7 V2+ V2- A1.0 A1.1
Q0 Q1 Q2 Q3 Q4 Q5 Q6 Q7 Q8 Q9
PE
A1 A1 A1 A1 A1 A1 A1 A1 A1 A1
-405K1 -405K2 -405K3.1 -405K3.2 -405K5 -405K5.1 -405K6 -405K7 -405K8 -405K8.1
A2 A2 A2 A2 A2 A2 A2 A2 A2 A2
403.8 / 4M 4M / 420.0
403.8 / 4L+ 4L+ / 420.0
14 11 /251.1 14 11 /220.1 14 14 14 11 /403.8 14 11 /31.7 14 11 /32.2 14 11 /34.2 14 11 /221.2 14 11 /36.2
12 12 12 11 12 11 12 12 12 12 12 12
24 21 /230.1
22
General Magnetic Spare Spare Servo motor Cooling On/Off On/Off Heating On/Off
alarm Filling Damper Coil Main AHU Ventilator Setter Ventilator
Valve Main AHU 1 Section Setter Room 1 Room 1 Setter Room 2
Watertank 5000l AHU MAin 1 Step 2
ESB1
404 420
A1.2 A1.3 A1.4 A1.5 A1.6 A1.7 A2.0 A2.1 COM0 COM0
0 1 2 3 4 5 6 7 + +
A1 A1 A1 A1 A1 A1 A1 A1
-420K1 -420K2 -420K3 -420K4 -420K5 -420K6 -420K7 -420K8
A2 A2 A2 A2 A2 A2 A2 A2
405.9 / 4M 4M / 421.0
405.9 / 4L+ 4L+ / 421.0
14 11 /221.4 14 11 /39.7 14 11 /40.2 14 11 /221.6 14 11 /43.2 14 11 /222.2 14 11 /222.3 14 11 /48.7
12 12 12 12 12 12 12 12
405 421
A2.2 A2.3 A2.4 A2.5 A2.6 A2.7 A3.0 A3.1 COM1 COM1
8 9 10 11 12 13 14 15 + +
A1 A1 A1 A1 A1 A1 A1 A1
-421K1 -421K2 -421K3 -421K4 -421K5 -421K6 -421K7 -421K8
A2 A2 A2 A2 A2 A2 A2 A2
420.9 / 4M 4M /
420.9 / 4L+ 4L+ /
14 11 /49.2 14 11 /222.5 14 11 /52.7 14 11 /53.2 14 11 /222.7 14 11 /222.8 14 14
12 12 12 12 12 12 12 11 12 11
420 430
+ - + - + -
WH BN WH BN WH BN
3261 / 32.6
3271 / 32.7
3461 / 34.6
3471 / 34.7
3661 / 36.6
3671 / 36.7
3861 / 38.6
3871 / 38.7
-1011 1 2 -1025 1 2 -1046 1 2
LIYCY-DIN LIYCY-DIN LIYCY-DIN
2x0,75 2x0,75 2x0,75
AI+
AI+
AI+
AI+
AI-
AI-
AI-
AI-
SH SH SH
PE
+ - PE I0+ I0- I1+ I1- I2+ I2- I3+ I3- I4+ I4- I5+ I5- I6+ I6- I7+ I7-
-400A3
/400.3 24V 0V PE NC
Fresh air Tunnel HR&SR Tunnel Setter Room+ Setter Room 1 Setter Room 2 Tunnel Setter Room+ Plenum Setter
tunnel Hatcher Room Hatcher Room Room
421 431
+FIELD +FIELD
-431U1 -431U4
EE061 EE061
+ - + -
WH BN WH BN
4261 / 42.6
4271 / 42.7
4361 / 43.6
4371 / 43.7
4661 / 46.6
4671 / 46.7
4761 / 47.6
4771 / 47.7
4961 / 49.6
4971 / 49.7
-1059 1 2 -1079 1 2
LIYCY-DIN LIYCY-DIN
2x0,75 2x0,75
AI+
AI+
AI+
AI+
AI+
AI-
AI-
AI-
AI-
AI-
SH SH
X51 47 48 X51 49 50
100mA 100mA
PE
+ - PE I0+ I0- I1+ I1- I2+ I2- I3+ I3- I4+ I4- I5+ I5- I6+ I6- I7+ I7-
-400A3.1
/400.3 24V 0V PE NC
Transfer Room Transfer Room Hatcher Room 1 Hatcher Room 1 Fluff Tunnel 1 Fluff Tunnel 2 Chick Take Off
HR1 HR1 Room
430 432
5361 / 53.6
5371 / 53.7
-1108 1 2 -1134 1 2 -1135 1 2 3
LIYCY-DIN LIYCY-DIN LIYCY-DIN
2x0,75 2x0,75 4x0,75
AI+
AI-
SH SH SH
PE
+ - PE I0+ I0- I1+ I1- I2+ I2- I3+ I3- I4+ I4- I5+ I5- I6+ I6- I7+ I7-
-400A4
/400.4 24V 0V PE NC
Take Off Room Chick Handling Room Chick Handling Room Chick Handling Room
431 440
24V 0V PE
+ - Q0+ Q0- Q1+ Q1- Q2+ Q2- Q3+ Q3-
PE
24Vac
252.9 / L24 L24 / 441.0
0Vac
252.9 / N24 N24 / 441.0
AO+
AO+
AO+
AO-
AO-
X52 23 24 25
3242
3243
3442
3443
3521
32.4 /
32.4 /
34.4 /
34.4 /
35.2 /
-1017 1 2 3
LIYY-DIN
4x0,75
BL RD WH
- + Y
+FIELD
-440U1 1 2 3
24VAC
H779N+NV24A-
SZ-TPC
432 441
24V 0V PE
+ - Q0+ Q0- Q1+ Q1- Q2+ Q2- Q3+ Q3-
PE
24Vac
440.9 / L24 L24 / 442.0
0Vac
440.9 / N24 N24 / 442.0
AO+
AO+
AO+
AO-
AO-
X52 26 27 28
3642
3643
3721
3821
3822
36.4 /
36.4 /
37.2 /
38.2 /
38.2 /
-1050 1 2 3
LIYY-DIN
4x0,75
BL RD WH
Y
+FIELD
-441U7 1 2 3
24VAC
R513+NRF24A-SZ+
ZR4515
Plenum Setter Room Plenul Setter Room Plenum Setter Room Above Transfer Room
440 442
24V 0V PE
+ - Q0+ Q0- Q1+ Q1- Q2+ Q2- Q3+ Q3-
PE
24Vac
441.9 / L24 L24 / 444.0
0Vac
441.9 / N24 N24 / 444.0
AO+
AO+
AO+
AO+
AO-
AO-
AO-
4042
4043
4121
4221
4222
4342
4343
40.4 /
40.4 /
41.2 /
42.2 /
42.2 /
43.4 /
43.4 /
Speed Control Electrical Heater Speed Control Speed Control
AHU Transfer Transfer Room Exhaust Ventilator 1 Supply Ventilator
Room Step 1 Transfer Room Hatcher Room 1
Above Transfer Room Transfer Room Transfer Room Plenum Setter Room
441 443
402.9 / 2L+
402.9 / 2M
PE
+ - PE
-400A6.1
/400.6 24V 0V PE
Power supply
receiver
module
442 444
24V 0V PE
+ - Q0+ Q0- Q1+ Q1- Q2+ Q2- Q3+ Q3-
PE
24Vac
442.9 / L24 L24 / 445.0
0Vac
442.9 / N24 N24 / 445.0
AO+
AO+
AO+
AO+
AO-
AO-
AO-
4421
4521
4522
4621
4622
4721
4722
44.2 /
45.2 /
45.2 /
46.2 /
46.2 /
47.2 /
47.2 /
Electrical Heater Speed Control Speed Control Speed Control
Hatcher Room 1 COR Ventilator Exhaust Ventilator Exhaust Ventilator
Step 1 Hatcher Room 1 Fluff Tunnel A Fluff Tunnel B
24V 0V PE
+ - Q0+ Q0- Q1+ Q1- Q2+ Q2- Q3+ Q3-
PE
24Vac
444.9 / L24 L24 / 446.0
0Vac
444.9 / N24 N24 / 446.0
AO+
AO+
AO+
AO-
AO-
X52 29 30 31
4942
4943
5021
5121
5122
49.4 /
49.4 /
50.2 /
51.2 /
51.2 /
-1095 1 2 3
LIYY-DIN
4x0,75
BL RD WH
Y
+FIELD
-445U0 1 2 3
24VAC
R512+NRF24A-SZ+
ZR4515
Above Transfer Room Above Transfer Room Above Chick Area Take Off Room
444 446
24V 0V PE
+ - Q0+ Q0- Q1+ Q1- Q2+ Q2- Q3+ Q3-
PE
24Vac
445.9 / L24 L24 / 447.0
0Vac
445.9 / N24 N24 / 447.0
AO+
AO+
AO+
AO-
AO-
X52 32 33 34
5342
5343
5421
5521
5522
53.4 /
53.4 /
54.2 /
55.2 /
55.2 /
-1120 1 2 3
LIYY-DIN
4x0,75
BL RD WH
Y
+FIELD
-446U1 1 2 3
24VAC
R529+NRF24A-SZ+
ZR4532
Above Transfer Room Above Transfer Room Above Chick Area Chick Handling Room
445 447
24Vac
446.9 / L24 L24 /
0Vac
446.9 / N24 N24 /
X52 35 36 37 X52 38 39 40
Spare Spare
446 460
B M B M B M B M
PE
B M B M B M B M B M B M B M
PE
Plenul Setter Room Transfer room Transfer room Transfer room Transfer room Hatcher room 1 Take Off Room
460 462
B M B M B M B M B M B M B M
PE
Chick Handling Room Chick Handling Room Chick Handling Room Chick Handling Room Technical Room Technical Room Technical Room
461 463
+FIELD
-463U3
QAE 2111.010
B M
-1153 1 2 3
LIYY-DIN
4x0,75
X53 55 56 57 X53 58 59 60
PE
Temperature Spare
Sensor
Water Chiller
Return
Technical Room
462 800
18 mm
18 mm
Alarm Off
18 mm
General
0=Off Running Overload Alarm Off
Alarm
1= Alarm Off On-Off
27 mm 27 mm 27 mm 27 mm 27 mm
20 mm
20 mm
20 mm
Main Switch Main AHU Alarms
96 mm 96 mm 96 mm
403S6
Off/On
27 mm
463 1000
Device tag Quantity Type number Designation Supplier Ordering number Page
-35A1 1 SEA45.1 Current valve 25A for pulse/pause control, 0-10V control signal Siemens SEA45.1 35
-35A2 1 SEM61.4 Signal converter, input continuous analog signal dc 0-10V or 0/10V, output puls/pause 2pos. 24Vac Siemens SEM61.4 35
-37A1 1 SEA45.1 Current valve 25A for pulse/pause control, 0-10V control signal Siemens SEA45.1 37
-37A2 1 SEM61.4 Signal converter, input continuous analog signal dc 0-10V or 0/10V, output puls/pause 2pos. 24Vac Siemens SEM61.4 37
-41A1 1 SEA45.1 Current valve 25A for pulse/pause control, 0-10V control signal Siemens SEA45.1 41
-41A2 1 SEM61.4 Signal converter, input continuous analog signal dc 0-10V or 0/10V, output puls/pause 2pos. 24Vac Siemens SEM61.4 41
-44A1 1 SEA45.1 Current valve 25A for pulse/pause control, 0-10V control signal Siemens SEA45.1 44
-44A2 1 SEM61.4 Signal converter, input continuous analog signal dc 0-10V or 0/10V, output puls/pause 2pos. 24Vac Siemens SEM61.4 44
-50A1 1 SEA45.1 Current valve 25A for pulse/pause control, 0-10V control signal Siemens SEA45.1 50
-50A2 1 SEM61.4 Signal converter, input continuous analog signal dc 0-10V or 0/10V, output puls/pause 2pos. 24Vac Siemens SEM61.4 50
-54A1 1 SEA45.1 Current valve 25A for pulse/pause control, 0-10V control signal Siemens SEA45.1 54
-54A2 1 SEM61.4 Signal converter, input continuous analog signal dc 0-10V or 0/10V, output puls/pause 2pos. 24Vac Siemens SEM61.4 54
-390A1 1 TCSESU053FN0 Connexium switch 5 portS 10/100Base-TX Schneider TCSESU053FN0 390
-390A1 1 DK-1617-010 Digitus professional CAT 6 U-UTP Patch cable, LSOH, Cu, AWG 26/7, lenght 1m, grey Assman DK-1617-010 390
-390A1 5 DK-1617-030 Digitus professional CAT 6 U-UTP Patch cable, LSOH, Cu, AWG 26/7, lenght 3.0m, grey Assman DK1617030 390
-391A1 1 TCSESU053FN0 Connexium switch 5 portS 10/100Base-TX Schneider TCSESU053FN0 391
-400A0 1 TM241CEC24T Controller M241 24 IO transistor PNP Ethernet CAN master Schneider TM241CEC24T 400
-400A0 1 TMC4TI2 Cartridge for M241 with 2 temperature inputs Schneider TMC4TI2 400
-400A0 1 TMASD1 Memory card for M2xx controller Schneider TMASD1 400
-400A0 1 DK-1617-020 Digitus professional CAT 6 U-UTP Patch cable, LSOH, Cu, AWG 26/7, lenght 2.0m, grey Assman DK1617020 400
-400A2 1 TM3DQ16R Module TM3 - 16 Discrete output relays Schneider TM3DQ16R 400
-400A3 1 TM3AI8 Module TM3 - 8 analog inputs Schneider TM3AI8 400
-400A3.1 1 TM3AI8 Module TM3 - 8 analog inputs Schneider TM3AI8 400
-400A4 1 TM3AI8 Module TM3 - 8 analog inputs Schneider TM3AI8 400
-400A4.1 1 TM3AQ4 Module TM3 - 4 analog outputs Schneider TM3AQ4 400
-400A5 1 TM3AQ4 Module TM3 - 4 analog outputs Schneider TM3AQ4 400
-400A5.1 1 TM3AQ4 Module TM3 - 4 analog outputs Schneider TM3AQ4 400
-400A6 1 TM3XTRA1 Remote transmitter module TM3 - bus Schneider TM3XTRA1 400
-400A6 1 DK-1617-010 Digitus professional CAT 6 U-UTP Patch cable, LSOH, Cu, AWG 26/7, lenght 1m, grey Assman DK-1617-010 400
-400A6.1 1 TM3XREC1 Remote receiver module TM3 - bus Schneider TM3XREC1 400
-400A7 1 TM3AQ4 Module TM3 - 4 analog outputs Schneider TM3AQ4 400
-400A7.1 1 TM3AQ4 Module TM3 - 4 analog outputs Schneider TM3AQ4 400
-400A8 1 TM3AQ4 Module TM3 - 4 analog outputs Schneider TM3AQ4 400
-401A1 1 TM3TI4 Module TM3 - 4 inputs temperature Schneider TM3TI4 401
-401A1.1 1 TM3TI4 Module TM3 - 4 inputs temperature Schneider TM3TI4 401
-401A2 1 TM3TI4 Module TM3 - 4 inputs temperature Schneider TM3TI4 401
-ESB1 2 NSYSF2012502DP Enclosure Spacial SF, 1200x2000x500 BxHxD, 2 doors, mounting plate included, RAL 7035 Schneider NSYSF2012502DP 10
-ESB1 1 NSY2SP205 Spacial SF side panels, 500x2000 WxH, RAL 7035 Schneider NSY2SP205 10
-ESB1 2 NSYEC1251 Spacial SF 1 entry cable gland plate for enclosure 1200x500 WxD Schneider NSYEC1251 10
800 1001
Device tag Quantity Type number Designation Supplier Ordering number Page
-ESB1 2 NSYSPF12200 Spacial SF/SM plinth front & back, 1200x200 WxH, RAL 7022 Schneider NSYSPF12200 10
-ESB1 2 NSYSPS5200 Spacial SF/SM side panel plinth, 500x200 WxH, RAL 7022 Schneider NSYSPS5200 10
-ESB1 1 NSYSFBK Spacial SF standard coupling kit IP55 Schneider NSYSFBK 10
-ESB1 1 NSYSFBKR Reinforced coupling kit Spacial SF Schneider NSYSFBKR 10
-ESB1 1 NSYSFEB Set of 4 Spacial SF M12 lifting eyebolts Schneider NSYSFEB 10
-ESB1 3 NSYSDCR6 Spacial SF/SM door cross rail, width 600mm Schneider NSYSDCR6 10
-ESB1 1 NSYSLCR50 Spacial SF/SM cross rail for eclosure depth 500mm Schneider NSYSLCR50 10
-10F0 1 38313038 Fuserbloc 3P, 400A, size 2, fuses GR2, external front and right side operation Socomec 38313038 10
-10F0 1 14212111 Black handle for external front operation sirco 125-630A IP55 Socomec 14212111 10
-10F0 1 14001050 Shaft for external handle, type S2, lenght 500mm Socomec 14001050 10
-10F0 3 NH2GG50V400 NH fuse link GR2 400A gG 500Vac Ferraz NH2GG50V400 10
-10F3 1 A9F89216 Circuit breaker iC60H 30kA C16A 2P Schneider A9F89216 10
-10F3 1 A9Q14225 Add-on residual current module Vigi iC60, 2P 25A 300A type AC Schneider A9Q14225 10
-10F7 1 A9F68206 Circuit breaker iT60N 6kA C6A 2P Schneider A9F68206 10
-20F1 1 A9F68206 Circuit breaker iT60N 6kA C6A 2P Schneider A9F68206 20
-20F1.1 1 9000-41034-0100600 Mico electronic ciruit protection 24Vdc, 4 channels, 1-2-4-6A, group alarm contact MURR 9000-41034-0100600 20
-20F5 1 9000-41034-0100400 Mico electronic ciruit protection 24Vdc, 4 channels, 1-2-3-4A, group alarm contact Murr 9000-41034-0100400 20
-20F5 1 900-41034-0000002 Mico bridging set (1set) Murr 900-41034-0000002 20
-22F1 1 A9F68210 Circuit breaker iT60N 6kA C10A 2P Schneider A9F68210 22
-22F4 1 A9F68206 Circuit breaker iT60N 6kA C6A 2P Schneider A9F68206 22
-35F1 1 57010020 Holder for cilindrical fuses 10x38mm, 2 poles Socomec 57010020 35
-35F1 2 FR10GR69V25 Protistor cilindrical fuse-link 10x38, 25A, gR, High speed Ferraz FR10GR69V25 35
-35F5 1 57010018 Holder for cilindrical fuses 10x38mm, 3 poles Socomec 57010018 35
-35F5 3 FR10GG50V20 Ferrule fuse-link 10x38, 20A, gG, 400-690V Ferraz FR10GG50V20 35
-37F1 1 57010020 Holder for cilindrical fuses 10x38mm, 2 poles Socomec 57010020 37
-37F1 2 FR10GR69V25 Protistor cilindrical fuse-link 10x38, 25A, gR, High speed Ferraz FR10GR69V25 37
-37F5 1 57010018 Holder for cilindrical fuses 10x38mm, 3 poles Socomec 57010018 37
-37F5 3 FR10GG50V20 Ferrule fuse-link 10x38, 20A, gG, 400-690V Ferraz FR10GG50V20 37
-38F1 1 A9F79206 Circuit breaker iC60N 6kA C6A 2P Schneider A9F79206 38
-38F1 1 A9A26924 Auxiliary contact iOF, 1C/O Schneider A9A26924 38
-41F1 1 57010020 Holder for cilindrical fuses 10x38mm, 2 poles Socomec 57010020 41
-41F1 2 FR10GR69V20 Protistor cilindrical fuse-link 10x38, 20A, gR, High speed Ferraz FR10GR69V20 41
-41F5 1 57010018 Holder for cilindrical fuses 10x38mm, 3 poles Socomec 57010018 41
-41F5 3 FR10GG50V16 Ferrule fuse-link 10x38, 16A, gG, 400-690V Ferraz FR10GG50V16 41
-42F1 1 A9F79206 Circuit breaker iC60N 6kA C6A 2P Schneider A9F79206 42
-42F1 1 A9A26924 Auxiliary contact iOF, 1C/O Schneider A9A26924 42
-44F1 1 57010020 Holder for cilindrical fuses 10x38mm, 2 poles Socomec 57010020 44
-44F1 2 FR10GR69V20 Protistor cilindrical fuse-link 10x38, 20A, gR, High speed Ferraz FR10GR69V20 44
-44F5 1 57010018 Holder for cilindrical fuses 10x38mm, 3 poles Socomec 57010018 44
1000 1002
Device tag Quantity Type number Designation Supplier Ordering number Page
-44F5 3 FR10GG50V16 Ferrule fuse-link 10x38, 16A, gG, 400-690V Ferraz FR10GG50V16 44
-44F6 1 57010018 Holder for cilindrical fuses 10x38mm, 3 poles Socomec 57010018 44
-44F6 3 FR10GG50V25 Ferrule fuse-link 10x38, 25A, gG, 400-690V Ferraz FR10GG50V25 44
-45F1 1 A9F79206 Circuit breaker iC60N 6kA C6A 2P Schneider A9F79206 45
-45F1 1 A9A26924 Auxiliary contact iOF, 1C/O Schneider A9A26924 45
-46F1 1 A9F79206 Circuit breaker iC60N 6kA C6A 2P Schneider A9F79206 46
-46F1 1 A9A26924 Auxiliary contact iOF, 1C/O Schneider A9A26924 46
-47F1 1 A9F79206 Circuit breaker iC60N 6kA C6A 2P Schneider A9F79206 47
-47F1 1 A9A26924 Auxiliary contact iOF, 1C/O Schneider A9A26924 47
-50F1 1 57010020 Holder for cilindrical fuses 10x38mm, 2 poles Socomec 57010020 50
-50F1 2 FR10GR69V20 Protistor cilindrical fuse-link 10x38, 20A, gR, High speed Ferraz FR10GR69V20 50
-50F5 1 57010018 Holder for cilindrical fuses 10x38mm, 3 poles Socomec 57010018 50
-50F5 3 FR10GG50V10 Ferrule fuse-link 10x38, 10A, gG, 400-690V Ferraz FR10GG50V10 50
-51F1 1 A9F79206 Circuit breaker iC60N 6kA C6A 2P Schneider A9F79206 51
-51F1 1 A9A26924 Auxiliary contact iOF, 1C/O Schneider A9A26924 51
-54F1 1 57010020 Holder for cilindrical fuses 10x38mm, 2 poles Socomec 57010020 54
-54F1 2 FR10GR69V25 Protistor cilindrical fuse-link 10x38, 25A, gR, High speed Ferraz FR10GR69V25 54
-54F5 1 57010018 Holder for cilindrical fuses 10x38mm, 3 poles Socomec 57010018 54
-54F5 3 FR10GG50V20 Ferrule fuse-link 10x38, 20A, gG, 400-690V Ferraz FR10GG50V20 54
-54F6 1 57010018 Holder for cilindrical fuses 10x38mm, 3 poles Socomec 57010018 54
-54F6 3 FR10GG50V25 Ferrule fuse-link 10x38, 25A, gG, 400-690V Ferraz FR10GG50V25 54
-55F1 1 A9F79206 Circuit breaker iC60N 6kA C6A 2P Schneider A9F79206 55
-55F1 1 A9A26924 Auxiliary contact iOF, 1C/O Schneider A9A26924 55
-57F1 1 A9F79206 Circuit breaker iC60N 6kA C6A 2P Schneider A9F79206 57
-57F1 1 A9A26924 Auxiliary contact iOF, 1C/O Schneider A9A26924 57
-20G1 1 6EP1334-3BA10 Sitop power supply PSU200M 230-500V/24VDC 10A Siemens 6EP1334-3BA10 20
-10H4 1 NSYLAMT5LD1 Cost effective LED lamp 120/230Vac 50/60Hz, 5W, 500lm, 4000K, 310x30,5 LxH Schneider NSYLAMT5LD1 10
-10H5 1 NSYLAMT5LD1 Cost effective LED lamp 120/230Vac 50/60Hz, 5W, 500lm, 4000K, 310x30,5 LxH Schneider NSYLAMT5LD1 10
-251H1 1 XB4BVB4 Complete pilot light red Ø22 plain lens with integral LED 24V AC/DC Schneider XB4BVB4 251
-251H2 1 XB4BVB4 Complete pilot light red Ø22 plain lens with integral LED 24V AC/DC Schneider XB4BVB4 251
-251H3 1 XB4BVB3 Complete pilot light green Ø22 plain lens with integral LED 24V AC/DC Schneider XB4BVB3 251
-251H4 1 XB4BVB4 Complete pilot light red Ø22 plain lens with integral LED 24V AC/DC Schneider XB4BVB4 251
-31K7 1 LC1D32P7 Contactor LC1D32P7, 3P, 32A, Coil 230 Vac Schneider LC1D32P7 31
-32K7 1 LC1D50AP7 Contactor LC1D50AP7, 3P, 50A, 1NO1NC, Coil 230 Vac Schneider LC1D50AP7 32
-33K3 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 33
-33K3 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 33
-33K8 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 33
-33K8 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 33
-34K7 1 LC1D09P7 Contactor LC1D09P7, 3P, 9A, Coil 230 Vac Schneider LC1D09P7 34
1001 1003
Device tag Quantity Type number Designation Supplier Ordering number Page
1002 1004
Device tag Quantity Type number Designation Supplier Ordering number Page
-222K6 1 LC1D32P7 Contactor LC1D32P7, 3P, 32A, Coil 230 Vac Schneider LC1D32P7 222
-222K7 1 LC1D18P7 Contactor LC1D18P7, 3P, 18 A, Coil 230 Vac Schneider LC1D18P7 222
-222K8 1 LC1D25P7 Contactor LC1D25P7, 3P, 25A, Coil 230 Vac Schneider LC1D25P7 222
-250K1 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 250
-250K1 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 250
-252K1 1 CA2KN31B7 Control Relay 3NO/1NC, coil 24Vac Schneider CA2KN31B7 252
-252K1 1 LA1KN22 Auxiliary contact block, 2NO+2NC Schneider LA1KN22 252
-252K2 1 G2R-2-SNI 24VAC Interface relais 24VAC 10A 2P, LED, test button Omron G2R-2-SNI 24VAC 252
-252K2 1 P2RF-08-E Relay base P2RF-08-E for relay G2R-2 Omron P2RF-08-E 252
-252K3 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 252
-252K3 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 252
-252K4 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 252
-252K4 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 252
-252K5 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 252
-252K5 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 252
-252K6 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 252
-252K6 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 252
-252K7 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 252
-252K7 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 252
-252K8 1 G2R-1-SNI 24VAC Interface relais 24VAC 10A 1WS, LED, test button Omron G2R-1-SNI 24VAC 252
-252K8 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 252
-405K1 1 G2R-2-SNI 24VDC Interface relais 24VDC 10A 2P, LED, test button Omron G2R-2-SNI 24VDC 405
-405K1 1 P2RF-08-E Relay base P2RF-08-E for relay G2R-2 Omron P2RF-08-E 405
-405K2 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K2 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
-405K3.1 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K3.1 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
-405K3.2 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K3.2 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
-405K5 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K5 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
-405K5.1 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K5.1 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
-405K6 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K6 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
-405K7 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K7 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
-405K8 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K8 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
1003 1005
Device tag Quantity Type number Designation Supplier Ordering number Page
-405K8.1 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 405
-405K8.1 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 405
-420K1 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 420
-420K1 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 420
-420K2 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 420
-420K2 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 420
-420K3 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 420
-420K3 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 420
-420K4 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 420
-420K4 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 420
-420K5 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 420
-420K5 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 420
-420K6 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 420
-420K6 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 420
-420K7 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 420
-420K7 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 420
-420K8 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 420
-420K8 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 420
-421K1 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 421
-421K1 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 421
-421K2 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 421
-421K2 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 421
-421K3 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 421
-421K3 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 421
-421K4 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 421
-421K4 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 421
-421K5 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 421
-421K5 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 421
-421K6 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 421
-421K6 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 421
-421K7 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 421
-421K7 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 421
-421K8 1 G2R-1-SNI 24VDC Interface relais 24VDC 10A 1P, LED, test button Omron G2R-1-SNI 24VDC 421
-421K8 1 P2RF-05-E Relay base P2RF-05-E for relay G2R-1 Omron P2RF-05-E 421
-10M7 1 SK3240100 SK TopTherm fan-and-filter unit, 180/160 m³/h, 230 V, 1~, 50/60 Hz Rittal 3240100 10
-10M7 1 SK3240200 SK Outlet filter, for fan-and-filter units, WHD: 255x255x25 mm Rittal 3240200 10
-22Q1 1 GV2RT06 Thermal magnetic transfo protection 1-1,6A Schneider GV2RT06 22
-31Q1 1 GV2ME32 Thermal-magnetic motor protection 24-32A Schneider GV2ME32 31
-31Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 31
1004 1006
Device tag Quantity Type number Designation Supplier Ordering number Page
-32Q1 1 GV3L65 Magnetic motor circuit breaker GV3L40, 3P 40A Schneider GV3L65 32
-32Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 32
-33Q1 1 GV2ME20 Thermal-magnetic motor protection 13-18A Schneider GV2ME20 33
-33Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 33
-34Q1 1 GV2L14 Magnetic motor circuit breaker GV2L14, 3P 10A Schneider GV2L14 34
-34Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 34
-36Q1 1 GV2L14 Magnetic motor circuit breaker GV2L14, 3P 10A Schneider GV2L14 36
-36Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 36
-39Q1 1 GV2ME07 Thermal magnetic motor protection 1,6-2,5A Schneider GV2ME07 39
-39Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 39
-40Q1 1 GV2L16 Magnetic motor circuit breaker GV2L16, 3P 14A Schneider GV2L16 40
-40Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 40
-43Q1 1 GV2L14 Magnetic motor circuit breaker GV2L14, 3P 10A Schneider GV2L14 43
-43Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 43
-48Q1 1 GV2ME07 Thermal magnetic motor protection 1,6-2,5A Schneider GV2ME07 48
-48Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 48
-49Q1 1 GV2L16 Magnetic motor circuit breaker GV2L16, 3P 14A Schneider GV2L16 49
-49Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 49
-52Q1 1 GV2ME10 Thermal-magnetic motor protection 2.5-4A Schneider GV2ME10 52
-52Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 52
-53Q1 1 GV2L22 Magnetic motor circuit breaker GV2L22, 3P 25 A Schneider GV2L22 53
-53Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 53
-56Q1 1 GV2ME06 Thermal magnetic motor protection GV2ME06, 3P 1-1,6A Schneider GV2ME06 56
-56Q1 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 56
-56Q3 1 GV2ME06 Thermal magnetic motor protection GV2ME06, 3P 1-1,6A Schneider GV2ME06 56
-56Q3 1 GVAE11 Auxiliairy block for GV2 & GV3, 1NO+1NC Schneider GVAE11 56
-10S4 1 NSYDCM20 Spacial SF door switch 10A/500V, M20 connection Schneider NSYDCM20 10
-10S6 1 NSYDCM20 Spacial SF door switch 10A/500V, M20 connection Schneider NSYDCM20 10
-10S7 1 SK3110000 SK enclosure thermostat, 24-230V Rittal 3110000 10
-251S2 1 XB4BD21 Black selector switch Ø22, 2-position stay put, 1NO Schneider XB4BD21 251
-251S2 1 ZBE101 Single contact block 1NO Schneider ZBE101 251
-251S2 1 A9A15151 DIN rail mounting base, diameter 22mm, for control & signal unit Schneider A9A15151 251
-403S6 1 XB4BD21 Black selector switch Ø22, 2-position stay put, 1NO Schneider XB4BD21 403
-22T1 1 ABL6TS25B Single phase control transformers 250VA 230Vac +-15%/24Vac Schneider ABL6TS25B 22
-395U0 1 HMISTU855 Magelis touch panel HMISTU855, 5,7", 24VDC Schneider HMISTU855 395
-X1 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X1 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X1 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X1 3 UT 6 Feed-through terminal block 0,2 mm² - 10 mm², width 8,2mm, grey Phoenix contact 3044131 31
1005 1007
Device tag Quantity Type number Designation Supplier Ordering number Page
-X1 3 UT 35 Feed-through terminal block UT35, 1,5-50mm², width 16mm, grey Phoenix contact 3044225 32
-X1 15 UT 4 Feed-through terminal block UT4, 0,14-6mm², width 6,2mm, grey Phoenix contact 3044102 33;39;48;52
-X01 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X01 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X01 1 D-UT 2,5/4-QUATTRO End cover for terminal UT2,5-4 Quattro, grey Phoenix contact 3047170
-X01 16 UT 2,5-QUATTRO Feed-through terminal block UT 2,5 Quattro, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044542 20
-X2 1 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X2 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X2 2 UT 4-HESILA 250 Fuse terminal block UT4-HESILA 250, 50x20, 0,14 mm²-6 mm², black Phoenix contact 3046100 220
-X2 2 522507 Cilindrical fuses 5x20 100mA S ESKA 522507 220
-X02 1 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X02 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X02 1 D-UT 2,5/4-QUATTRO End cover for terminal UT2,5-4 Quattro, grey Phoenix contact 3047170
-X02 2 UT 2,5-QUATTRO Feed-through terminal block UT 2,5 Quattro, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044542 22
-X3 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X3 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X3 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X3 10 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 403
-X03 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X03 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X03 1 D-UT 2,5/4-QUATTRO End cover for terminal UT2,5-4 Quattro, grey Phoenix contact 3047170
-X03 2 UT 2,5-QUATTRO Feed-through terminal block UT 2,5 Quattro, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044542 22
-X11 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X11 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X11 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X11 30 UT 4 Feed-through terminal block UT4, 0,14-6mm², width 6,2mm, grey Phoenix contact 3044102 34;36;38;40
-X12 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X12 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X12 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X12 10 UT 6 Feed-through terminal block 0,2 mm² - 10 mm², width 8,2mm, grey Phoenix contact 3044131 35;54
-X12 26 UT 4 Feed-through terminal block UT4, 0,14-6mm², width 6,2mm, grey Phoenix contact 3044102 35;37;41;44
-X51 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X51 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X51 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X51 39 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 32;34;36;38
-X51 18 UT 4-HESI Fuse terminal block UT4-HESI, 50x20, 0,14 mm²-6 mm², black Phoenix contact 3046032 32;34;36;38
-X51 18 522507 Cilindrical fuses 5x20 100mA S ESKA 522507 32;34;36;38
-X52 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X52 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
1006 1008
Device tag Quantity Type number Designation Supplier Ordering number Page
-X52 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X52 40 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 38;42
-X53 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X53 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X53 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X53 60 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 460...463
-X81 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X81 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X81 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X81 62 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 32...34;36
-X82 1 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X82 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X82 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X82 2 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 230
-X83 1 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X83 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X83 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X83 12 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 35;37;41;44
-X84 1 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X84 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X84 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X84 6 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 395
-X85 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-X85 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-X85 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-X85 3 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 402
-10X3 1 A9A15310 DIN socket 2P, 16A German standard Schneider A9A15310 10
-391X7 1 CBXF6AW-A Mini-Com surface mount box, accepts 6 minicom modules, white, HxB 170X120mm Panduit CBXF6AW-A 391
-391X7 4 CJ688TGAW Mini-Com UTP jack module, cat6, arctic white Panduit CJ688TGAW 391
-XL 2 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-XL 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-XL 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-XL 10 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 10
-XV 1 CLIPFIX35 Quick mounting end clamp CLIPFIX 35 for DIN rail 25/7, 35/15, width 9,5mm Phoenix contact 3022218
-XV 1 KLM Terminal strip markers KLM, 25x6mm Phoenix contact 1004306
-XV 1 D-UT2,5/10 End cover for terminals UT2,5-UT10, grey Phoenix contact 3047028
-XV 2 UT 2,5 Feed-through terminal block UT2,5, 0,14-4mm², width 5,2mm, grey Phoenix contact 3044076 10
-XV 1 UT 2,5-PE Ground modular terminal block UT2,5-PE, 0,14-4mm², width 5,2mm, yellow green Phoenix contact 3044092 10
1007 1500
-1012 -X1 +FIELD-33M0 H05VV-F 4G 2,5 4 Pressure Rising Pump Incubators TECHNICAL ROOM
-PE
-PE
-1015 -X3 +FIELD-403U7 LIYY-DIN 4 0,75 4 Servo motor Damper Main AHU 1
-1017 -X52 +FIELD-440U1 LIYY-DIN 4 0,75 3 Cooling Coil Regulating Valve Technical Room
-1018 -X1 +FIELD-31M0 H05VV-F 4G 6 4 AHU main 1 Cooling Coil Section TECHNICAL ROOM
-PE
-1020 -X51 +FIELD-32U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter SETTER & HATCHER AIR TUNNEL
-1021 -X1 +FIELD-32U1 XVB-F2 4G 25 4 Supply Motor AHU Main 1 TECHNICAL ROOM
-PE
-1022 -X81 +FIELD-32U1 LIYCY-DIN 8 0,75 8 Supply Motor AHU Main 1 TECHNICAL ROOM
-1025 -X51 +FIELD-430U4 LIYCY-DIN 2 0,75 2 Tunnel Setter Room+ Hatcher Room
-1026 -X51 +FIELD-34U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter SETTER ROOM 1
-1027 -X51 +FIELD-36U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter SETTER ROOM 2
-1028 -X81 +FIELD-34U1 LIYCY-DIN 8 0,75 8 Supply Ventilator Setter Room 1 PLENUM SETTER ROOM
-1029 -X81 +FIELD-36U1 LIYCY-DIN 8 0,75 8 Supply Ventilator Setter Room 2 PLENUM SETTER ROOM
-1030 -X11 +FIELD-34U1 XVB-F2 3G 1,5 3 Supply Ventilator Setter Room 1 PLENUM SETTER ROOM
-PE
-1032 -X12 +FIELD-35U0 H05VV-F 3G 6 3 Electrical Heating Setter Room 1 PLENUM SETTER ROOM
-PE
-1033 -X12 +FIELD-35U0 H05VV-F 4G 4 4 Electrical Heating Setter Room 1 PLENUM SETTER ROOM
-PE +FIELD-35U0-PE
-1034 -X83 +FIELD-35U0-PE XVB-F2 3G 1,5 3 Electrical Heating Setter Room 1 PLENUM SETTER ROOM
-PE
-1035 -X11 +FIELD-36U1 XVB-F2 3G 1,5 3 Supply Ventilator Setter Room 2 PLENUM SETTER ROOM
-PE
-1037 -X12 +FIELD-37U0 H05VV-F 3G 6 3 Electrical Heating Setter Room 2 PLENUM SETTER ROOM
1008 1501
-1038 -X12 +FIELD-37U0 H05VV-F 4G 4 4 Electrical Heating Setter Room 2 PLENUM SETTER ROOM
-PE
-1039 -X83 +FIELD-37U0 XVB-F2 3G 1,5 3 Electrical Heating Setter Room 2 PLENUM SETTER ROOM
-PE
-1040 -X11 +FIELD-38M0 H05VV-F 3G 1,5 3 Exhaust Ventilator Plenum Setter Room PLENUM SETTER ROOM
-PE
-1041 -X52 +FIELD-38M0 LIYCY-DIN 4 0,75 4 Exhaust Ventilator Plenum Setter Room PLENUM SETTER ROOM
-1042 -X51 +FIELD-38U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter TUNNEL HR & SR
-1045 -X53 +FIELD-461U2 LIYY-DIN 4 0,75 3 Temperature Sensor Setter Room 1&2
-1046 -X51 +FIELD-430U7 LIYCY-DIN 2 0,75 2 Humidity Sensor Setter Rooms 1&2
-1047 -X12 +FIELD-41U0 H05VV-F 3G 4 3 Electrical Heating Transfer Room TRANSFER ROOM
-PE
-1048 -X12 +FIELD-41U0 H05VV-F 4G 4 4 Electrical Heating Transfer Room TRANSFER ROOM
-PE
-1049 -X83 +FIELD-41U0 XVB-F2 3G 1,5 3 Electrical Heating Transfer Room TRANSFER ROOM
-PE
-1050 -X52 +FIELD-441U7 LIYY-DIN 4 0,75 3 Cooling Coil Regulating Valve Transfer Room
-1051 -X1 +FIELD-39M0 H05VV-F 4G 1,5 4 Cooling Coil Section Transfer Room TECHNICAL ROOM
-PE
-1053 -X81 +FIELD-40U1 LIYCY-DIN 8 0,75 8 AHU Transfer Room ABOVE TRANSFER ROOM
-PE
-PE
-1062 -X51 +FIELD-42U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter TRANSFER ROOM
1500 1502
-1071 -X11 +FIELD-43U1 XVB-F2 3G 1,5 3 Supply Ventilator Hatcher Room 1 PLENUM SETTER ROOM
-PE
-1072 -X81 +FIELD-43U1 LIYCY-DIN 8 0,75 8 Supply Ventilator Hatcher Room 1 PLENUM SETTER ROOM
-1075 -X12 +FIELD-44U0 H05VV-F 4G 2,5 4 Electrical Heating Hatcher Room 1 HATCHER ROOM 1
-PE
-1076 -X12 +FIELD-44U0 H05VV-F 4G 4 4 Electrical Heating Hatcher Room 1 HATCHER ROOM 1
-PE
-1077 -X83 +FIELD-44U0 XVB-F2 3G 1,5 3 Electrical Heating Hatcher Room 1 HATCHER ROOM 1
-PE
-1080 -X11 +FIELD-45M0 H05VV-F 3G 1,5 3 COR Ventilator Hatcher Room 1 HATCHER ROOM 1
-PE
-1081 -X52 +FIELD-45M0 LIYCY-DIN 2 0,75 2 COR Ventilator Hatcher Room 1 HATCHER ROOM 1
-1085 -X11 +FIELD-46M0 H05VV-F 3G 1,5 3 Exhaust Ventilator Fluff Tunnel A FLUFF TUNNEL 1 HR1
-PE
-1086 -X52 +FIELD-46M0 LIYCY-DIN 2 0,75 2 Exhaust Ventilator Fluff Tunnel A FLUFF TUNNEL 1 HR1
-1087 -X51 +FIELD-46U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter FLUFF TUNNEL 1 HR1
-1088 -X11 +FIELD-47M0 H05VV-F 3G 1,5 3 Exhaust Ventilator Fluff Tunnel B FLUFF TUNNEL 2 HR1
-PE
-1089 -X52 +FIELD-47M0 LIYCY-DIN 2 0,75 2 Exhaust Ventilator Fluff Tunnel B FLUFF TUNNEL 2 HR1
-1090 -X51 +FIELD-47U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter FLUFF TUNNEL2 HR1
-1095 -X52 +FIELD-445U0 LIYY-DIN 4 0,75 3 Cooling Coil Regulating Valve Chick Take Off Room
-1096 -X1 +FIELD-48M0 H05VV-F 4G 1,5 4 Cooling Coil Pump Chick Take Off Room ABOVE TRANSFER ROOM
-PE
-1100 -X51 +FIELD-49U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter CHICK TAKE OFF ROOM
-1101 -X11 +FIELD-49U1 XVB-F2 3G 1,5 3 AHU Chick Take Off Room ABOVE TRANSFER ROOM
-PE
-1102 -X81 +FIELD-49U1 LIYCY-DIN 8 0,75 8 AHU Chick Take Off Room ABOVE TRANSFER ROOM
-1104 -X12 +FIELD-50U0 XVB-F2 3G 2,5 3 Electrical Heating Chick Take Off Room ABOVE CHICK AREA
-PE
-1105 -X12 +FIELD-50U0 XVB-F2 4G 2,5 4 Electrical Heating Chick Take Off Room ABOVE CHICK AREA
-PE
1501 1503
-PE
-1107 -X53 +FIELD-461U8 LIYY-DIN 4 0,75 3 Temperature Sensor Chick Take Off Room
-1108 -X51 +FIELD-432U1 LIYCY-DIN 2 0,75 2 Humidity Sensor Chick Take Off Room
-1109 -X11 +FIELD-51M0 H05VV-F 3G 1,5 3 Exhaust Ventilator Chick Take Off Room TAKE OFF ROOM
-PE
-1110 -X52 +FIELD-51M0 LIYCY-DIN 2 0,75 2 Exhaust Ventilator Chick Take Off Room TAKE OFF ROOM
-1120 -X52 +FIELD-446U1 LIYY-DIN 4 0,75 3 Cooling Coil Regulating Valve Chick Handling Room
-1121 -X1 +FIELD-52M0 H05VV-F 4G 1,5 4 Cooling Coil Pump Chick Handling Room TECHNICAL ROOM
-PE
-1125 -X51 +FIELD-53U5 LIYCY-DIN 4 0,75 4 Differential pressure transmitter CHICK HANDLING ROOM
-1126 -X1 +FIELD-53U1 XVB-F2 4G 2,5 4 AHU Chick Handling Room ABOVE TRANSFER ROOM
-PE
-1127 -X81 +FIELD-53U1 LIYCY-DIN 8 0,75 8 AHU Chick Handling Room ABOVE TRANSFER ROOM
-1129 -X12 +FIELD-54U0 H05VV-F 3G 6 3 Electrical Heating Chick Handling Room ABOVE CHICK AREA
-PE
-1130 -X12 +FIELD-54U0 H05VV-F 3G 4 4 Electrical Heating Chick Handling Room ABOVE CHICK AREA
-PE
-1131 -X12 +FIELD-54U0 H05VV-F 3G 6 4 Electrical Heating Chick Handling Room ABOVE CHICK AREA
-PE
-1132 -X83 +FIELD-54U0 XVB-F2 3G 1,5 3 Electrical Heating Chick Handling Room ABOVE CHICK AREA
-PE
-1133 -X53 +FIELD-462U3 LIYY-DIN 4 0,75 3 Temperature Sensor 4 Chick Handling Room
-1134 -X51 +FIELD-432U3 LIYCY-DIN 2 0,75 2 Humidity Sensor Chick Handling Room
-1136 -X11 +FIELD-55M0 H05VV-F 3G 1,5 3 Exhaust Ventilator 1 Chick Handling Room CHICK HANDLING ROOM
-PE
-1137 -X52 +FIELD-55M0 LIYCY-DIN 4 0,75 4 Exhaust Ventilator 1 Chick Handling Room CHICK HANDLING ROOM
-PE
-PE
-1141 -X11 +FIELD-57M0 H05VV-F 3G 1,5 3 Exhaust Ventilator 2 Chick Handling Room CHICK HANDLING ROOM
-PE
1502 1504
-1143 -X53 +FIELD-462U0 LIYY-DIN 4 0,75 2 Temperature Sensor 1 Chick Handling Room
-1144 -X53 +FIELD-462U1 LIYY-DIN 4 0,75 3 Temperature Sensor 2 Chick Handling Room
-1145 -X53 +FIELD-462U2 LIYY-DIN 4 0,75 2 Temperature Sensor 3 Chick Handling Room
-1150 -X53 +FIELD-462U4 LIYY-DIN 4 0,75 3 Temperature Sensor Water Incubators Supply
-1151 -X53 +FIELD-462U5 LIYY-DIN 4 0,75 3 Temperature Sensor Water Incubators Return
-1152 -X53 +FIELD-462U6 LIYY-DIN 4 0,75 3 Temperature Sensor Water Chiller Supply
-1153 -X53 +FIELD-463U3 LIYY-DIN 4 0,75 3 Temperature Sensor Water Chiller Return
-1201 -X84 +FIELD-395U2 H05VV-F 3G 1,5 3 HMI Egg Handling Room Chick Area
-PE
-PE
-PE
-A1023 +FIELD-32M1 +FIELD-32U1 2YSLCY-J 4 25 4 Supply Motor AHU Main 1 TECHNICAL ROOM
-A1031 +FIELD-34M1 +FIELD-34U1 2YSLCY-J 4 1,5 4 Supply Ventilator Setter Room 1 PLENUM SETTER ROOM
-A1036 +FIELD-36M1 +FIELD-36U1 2YSLCY-J 4 1,5 4 Supply Ventilator Setter Room 2 PLENUM SETTER ROOM
-A1056 +FIELD-40M1 +FIELD-40U1 2YSLCY-J 4 2,5 4 AHU Transfer Room ABOVE TRANSFER ROOM
-A1073 +FIELD-43M1 +FIELD-43U1 2YSLCY-J 4 1,5 4 Supply Ventilator Hatcher Room 1 PLENUM SETTER ROOM
-A1103 +FIELD-49M1 +FIELD-49U1 2YSLCY-J 4 2,5 4 AHU Chick Take Off Room ABOVE TRANSFER ROOM
-A1128 +FIELD-53M1 +FIELD-53U1 2YSLCY-J 4 2,5 4 AHU Chick Handling Room ABOVE TRANSFER ROOM
-CLIENT -X81 +FIELD-33S8 2 Level detection (Client) Dry Running protection WATERTANK
-PE -L2
-L3
-PE
-10H5
-10S6
1503 1505
-395W5 -391X7 +FIELD-395U4 UTP 1 HMI Egg Handling Room Chick Area
-400W6 Patch 0
-1014a -X3 +FIELD-403S3 LIYY-DIN 2 0,75 2 Level Switch 1 Filling Point Watertank 5000l
-1014b -X3 +FIELD-403S4 LIYY-DIN 2 0,75 2 Level Switch 2 Dryrunning Watertank 5000l
1504 2000
Terminals
Graphical page
Terminal strip Terminal strip definition text
first last Total PE Total N Total number of terminal diagrams
1505 2001
-1126
-1121
-1096
-1051
-1012
-1021
-1018
Strip
Cable name
Cable name
=+ESB1-X1
Power terminals 3x240Vac
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
AHU main 1 Cooling Coil Section TECHNICAL ROOM BN +FIELD-31M0 U 1 -31K7 2 /31.1
Cooling Coil Section Transfer Room TECHNICAL ROOM BN +FIELD-39M0 U 10 -39K7 2 /39.1
Cooling Coil Pump Chick Take Off Room ABOVE TRANSFER ROOM BN +FIELD-48M0 U 13 -48K7 2 /48.1
Cooling Coil Pump Chick Handling Room TECHNICAL ROOM BN +FIELD-52M0 U 16 -52K7 2 /52.1
AHU Chick Handling Room ABOVE TRANSFER ROOM BN +FIELD-53U1 L1 19 -53K7 2 /53.1
2000 2002
Strip
Cable name
Cable name
=+ESB1-X01
Control voltage 24Vdc
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Power Supply Switch & HMI in Cabinet 1L+ -20F1.1 OUT:1 /20.1
-390A1 +24V
-390A1 0V
-400A0 +
-250K1 11
-405K5 11
-400A3 24V
-400A4.1 24V
-401A1 24V
-X84 1
-X84 2
2001 2003
-1014
Strip
Cable name
Cable name
=+ESB1-X2
Control voltage 240Vac valves
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
-221K1 A2
2002 2004
Strip
Cable name
Cable name
=+ESB1-X02
Control voltage 24Vac
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
-X81 4
-X51 2
2003 2005
-1016
-1015
-1014b
-1014a
Strip
Cable name
Cable name
=+ESB1-X3
Digital inputs
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
-400A0 V0-
2004 2006
Strip
Cable name
Cable name
=+ESB1-X03
Control voltage 230Vac
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
-31K7 A2
-31Q1 13
2005 2007
-1085
-1080
-1071
-1060
-1054
-1040
-1035
-1030
Strip
Cable name
Cable name
=+ESB1-X11
Power terminals single-phase 240V
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Supply Ventilator Setter Room 1 PLENUM SETTER ROOM BU +FIELD-34U1 L1 1 -34K7 2 /34.1
Supply Ventilator Setter Room 2 PLENUM SETTER ROOM BU +FIELD-36U1 L1 3 -36K8 2 /36.1
Exhaust Ventilator Plenum Setter Room PLENUM SETTER ROOM BU +FIELD-38M0 3 5 -38K8 2 /38.1
Supply Ventilator Hatcher Room 1 PLENUM SETTER ROOM BU +FIELD-43U1 L1 11 -43K8 2 /43.1
Exhaust Ventilator Fluff Tunnel A FLUFF TUNNEL 1 HR1 BU +FIELD-46M0 N 15 -46K8 2 /46.1
2006 2008
-1141
-1140
-1139
-1136
-1109
-1101
-1088
Strip
Cable name
Cable name
=+ESB1-X11
Power terminals single-phase 240V
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Exhaust Ventilator Fluff Tunnel B FLUFF TUNNEL 2 HR1 BU +FIELD-47M0 N 17 -47K8 2 /47.1
AHU Chick Take Off Room ABOVE TRANSFER ROOM BU +FIELD-49U1 L1 19 -49K7 2 /49.1
Exhaust Ventilator Chick Take Off Room TAKE OFF ROOM BU +FIELD-51M0 N 21 -51K8 2 /51.1
Exhaust Ventilator 1 Chick Handling Room CHICK HANDLING ROOM BU +FIELD-55M0 3 23 -55K8 2 /55.1
Exhaust Ventilator 2 Chick Handling Room CHICK HANDLING ROOM BU +FIELD-57M0 3 29 -57K8 2 /57.1
2007 2010
-1076
-1075
-1048
-1047
-1038
-1037
-1033
-1032
Strip
Cable name
Cable name
=+ESB1-X12
Power terminals heaters
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Electrical Heating Setter Room 1 PLENUM SETTER ROOM 1 +FIELD-35U0 L1 1 -221K1 2 /35.1
Electrical Heating Setter Room 2 PLENUM SETTER ROOM 1 +FIELD-37U0 L1 6 -221K3 2 /37.1
2008 2011
-1131
-1130
-1129
-1105
-1104
Strip
Cable name
Cable name
=+ESB1-X12
Power terminals heaters
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Electrical Heating Chick Take Off Room ABOVE CHICK AREA 1 +FIELD-50U0 L1 24 -222K4 2 /50.1
Electrical Heating Chick Handling Room ABOVE CHICK AREA 1 +FIELD-54U0 L1 29 -222K6 2 /54.1
2010 2012
-1087
-1070
-1062
-1042
-1027
-1026
-1020
Strip
Cable name
Cable name
=+ESB1-X51
Analog inputs & power supplies 24Vac field devices
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Differential pressure transmitter SETTER & HATCHER AIR TUNNEL 1 +FIELD-32U5 7 1 -X81 6 /32.5
-X81 10
Differential pressure transmitter SETTER & HATCHER AIR TUNNEL 2 +FIELD-32U5 6 2 -X02 N24 /32.6
-33K3 A2
Differential pressure transmitter SETTER & HATCHER AIR TUNNEL 3 +FIELD-32U5 5 3 -400A3 I1+ /32.6
-35A2 G
-35A2 G0
-37A2 G
-37A2 G0
-X81 34
-41A2 G0
-X81 42
-44A2 G
2011 2013
-1059
-1046
-1025
-1011
-1125
-1100
-1090
-1087
Strip
Cable name
Cable name
=+ESB1-X51
Analog inputs & power supplies 24Vac field devices
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 2 +FIELD-47U5 6 30 /47.6
Differential pressure transmitter CHICK TAKE OFF ROOM 1 +FIELD-49U5 7 33 -X81 52 /49.5
-50A2 G
Differential pressure transmitter CHICK TAKE OFF ROOM 2 +FIELD-49U5 6 34 -50A2 G0 /49.6
-54A2 G
-54A2 G0
Differential pressure transmitter CHICK HANDLING ROOM 3 +FIELD-53U5 5 39 -400A4 I1+ /53.6
2012 2014
-1135
-1134
-1108
-1079
Strip
Cable name
Cable name
=+ESB1-X51
Analog inputs & power supplies 24Vac field devices
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Humidity Sensor Chick Take Off Room 1 +FIELD-432U1 + 51 -400A4 24V /432.2
= 1 +FIELD-432U4 V+ 55 /432.4
CO2 Sensor Chick Handling Room 2 +FIELD-432U4 GND 56 -400A4 I2- /432.4
-400A4 I3-
2013 2016
-1142
-1137
-1110
-1089
-1086
-1081
-1061
-1041
Strip
Cable name
Cable name
=+ESB1-X52
Analog outputs & signals 24Vac field devices
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Exhaust Ventilator Plenum Setter Room PLENUM SETTER ROOM 1 +FIELD-38M0 11 1 -400A5 Q2+ /38.2
-X51 13
COR Ventilator Hatcher Room 1 HATCHER ROOM 1 1 +FIELD-45M0 2 7 -400A7 Q1+ /45.2
Exhaust Ventilator Fluff Tunnel A FLUFF TUNNEL 1 HR1 1 +FIELD-46M0 2 9 -400A7 Q2+ /46.2
Exhaust Ventilator Fluff Tunnel B FLUFF TUNNEL 2 HR1 1 +FIELD-47M0 2 11 -400A7 Q3+ /47.2
Exhaust Ventilator Chick Take Off Room TAKE OFF ROOM 1 +FIELD-51M0 2 13 -400A7.1 Q3+ /51.2
Exhaust Ventilator 1 Chick Handling Room CHICK HANDLING ROOM 1 +FIELD-55M0 11 15 -400A8 Q3+ /55.2
= 4 +FIELD-55M0 6 18 /55.4
Exhaust Ventilator 2 Chick Handling Room CHICK HANDLING ROOM 1 +FIELD-57M0 11 19 /57.2
= 2 +FIELD-57M0 8 20 /57.2
2014 2017
-1120
-1095
-1050
-1017
Strip
Cable name
Cable name
=+ESB1-X52
Analog outputs & signals 24Vac field devices
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Cooling Coil Regulating Valve Chick Take Off Room 1 +FIELD-445U0 1 29 /445.1
Spare 35 /447.3
= 36 /447.4
= 37 /447.4
= 38 /447.5
= 39 /447.5
= 40 /447.6
2016 2018
-1064
-1063
-1058
-1045
-1044
-1043
-1024
-1010
Strip
Cable name
Cable name
=+ESB1-X53
Temperature inputs
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 18 /461.4
= 24 /461.6
2017 2019
-1150
-1133
-1145
-1144
-1143
-1107
-1078
-1065
Strip
Cable name
Cable name
=+ESB1-X53
Temperature inputs
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 3 +FIELD-461U6 M 27 /461.6
Temperature Sensor Chick Take Off Room 1 +FIELD-461U8 B 31 -401A1.1 I3+ /461.8
= 36 /462.0
= 42 /462.2
2018 2020
-1153
-1152
-1151
Strip
Cable name
Cable name
=+ESB1-X53
Temperature inputs
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 60 -400A0 NC /463.4
2019 2021
-1053
-1029
-1028
-CLIENT
-1013
-1022
Strip
Cable name
Cable name
=+ESB1-X81
Command signals field motors
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Supply Motor AHU Main 1 TECHNICAL ROOM 1 +FIELD-32U1 LI1 1 -405K6 11 /32.2
Level detection (Client) Dry Running protection WATERTANK 1 +FIELD-33S8 13 -33K8 A1 /33.8
= 2 +FIELD-33S8 14 /33.9
Supply Ventilator Setter Room 1 PLENUM SETTER ROOM 1 +FIELD-34U1 LI1 15 -405K7 11 /34.2
Supply Ventilator Setter Room 2 PLENUM SETTER ROOM 1 +FIELD-36U1 LI1 23 -405K8.1 11 /36.2
AHU Transfer Room ABOVE TRANSFER ROOM 1 +FIELD-40U1 LI1 31 -420K3 11 /40.2
2020 2022
-1127
-1102
-1072
-1053
Strip
Cable name
Cable name
=+ESB1-X81
Command signals field motors
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
AHU Transfer Room ABOVE TRANSFER ROOM 6 +FIELD-40U1 R2C 36 -41A2 G /40.4
Supply Ventilator Hatcher Room 1 PLENUM SETTER ROOM 1 +FIELD-43U1 LI1 39 -420K5 11 /43.2
AHU Chick Take Off Room ABOVE TRANSFER ROOM 1 +FIELD-49U1 LI1 47 -421K1 11 /49.2
AHU Chick Handling Room ABOVE TRANSFER ROOM 1 +FIELD-53U1 LI1 55 -421K4 11 /53.2
2021 2023
-1001
Strip
Cable name
Cable name
=+ESB1-X82
Control signals to alarm panel
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= 2 2 -405K1 24 /230.1
2022 2024
-1132
-1106
-1077
-1049
-1039
-1034
Strip
Cable name
Cable name
=+ESB1-X83
Control signales heaters
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
Electrical Heating Setter Room 1 PLENUM SETTER ROOM 1 +FIELD-35U0-PE 1 1 -35K6 A2 /35.7
-X81 26
Electrical Heating Setter Room 2 PLENUM SETTER ROOM 1 +FIELD-37U0 1 3 -37K6 A2 /37.7
-X52 4
-X51 17
-X51 25
Electrical Heating Chick Take Off Room ABOVE CHICK AREA 1 +FIELD-50U0 1 9 -50K6 A2 /50.7
-X81 58
Electrical Heating Chick Handling Room ABOVE CHICK AREA 1 +FIELD-54U0 1 11 -54K6 A2 /54.7
-X52 17
2023 2025
-1204
-1202
-1201
Strip
Cable name
Cable name
=+ESB1-X84
Control voltage HMI's field
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
HMI Egg Handling Room Chick Area 1 +FIELD-395U2 + 1 -X01 8L+ /395.3
= 2 +FIELD-395U4 - 4 /395.5
= 2 +FIELD-395U6 - 6 /395.7
2024 2026
-402W3
Strip
Cable name
Cable name
=+ESB1-X85
CAN bus network
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
2025 2027
-10W5
-10W4
Strip
Cable name
Cable name
=+ESB1-XL
Terminals Cabinet Lighting
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
= BR -10H4 4 /10.4
= BR -10S4 2 6 /10.5
= BR -10H5 8 /10.6
= BR -10S6 2 10 /10.7
2026 2028
-10W7
Strip
Cable name
Cable name
=+ESB1-XV
Terminals cabinet fan
Connection
Connection
Cable type
Cable type
Terminal
Jumper
point
point
Function text Target designation Target designation Page / column
2027