Technical Specification for silent generator mandatory

Point for generator


No Description SIINQEE Requirement Remarks Supplier’s
offer
1 General specifications
1.1 Brand and model Should be specified
1.2 Genset Rating Prime power Mandatory
1.3 Genset output 0 1q2qe
1.4 Engine rating or Max. Power at rated Not less than 284(386) Mandatory
RPM, in KW BHP)
1.5 Engine Type Natural aspirated
1.6 Engine Model Should be specified
1.7 No. of Cylinder/Cylinder arrangement 8/V-type Mandatory
1.8 Stroke 4
1.9 Displacement(L) Should be specified
1.10 Bore & stroke(mm) Should be specified
1.11 Compression ratio Should be specified
1.12 Rated RPM 1500 RPM
1.13 Governor: Type/Class of Governing Electronic and mechanical Mandatory
1.14 Over speed trip(rpm) 1650 Mandatory
1.15 Air cleaner type / Qty Dry/02 Mandatory
1.16 Maximum allowable back pressure 5.5 kpa Mandatory
1.17 Charging alternator Voltage 24V/44 Amps
/Current(DC)
1.18 Battery Voltage (DC)/ Capacity (AH) 24V,2*180AH
1.19 Oil consumption (%SFC) Mandatory

1.20 Engine Brand and Make Cummins/Perkins/Greaves/Escort/Cat Mandatory


1.21 Design operating ambient Temperature Should be friendly up to 50 0C Mandatory
1.22 Fuel type Diesel Mandatory
1.23 Fuel tank Capacity Minimum able to run for 14 hrs at 75% load
1.24 Cooling method Water cooled Mandatory
1.25 Starting system Combination of Electrical and mechanical starting Mandatory
1.26 Fuel Consumption (prime)at 110% Should be specified
1.27 Fuel Consumption (prime) at 100% Should be specified
1.28 Fuel consumption (prime) at 75% Should be specified
1.29 Fuel Consumption (prime) at 50% Should be specified
2 Alternator Maker Stamford Mandatory
2.1 Voltage 380-440V
2.2 Phase Three phase
2.3 Frequency 50Hz
2.4 Current @ 0.8PF (Amps) 440-450 Amp/phase
2.5 Type 4 pole ,rotating field
2.6 Excitation and Type Self-Excited and Brushes less(permanent magnet Mandatory
optional)
2.7 Leads: Quantity, type 6,fixed.12-re-connectable (optional) Mandatory
2.8 Voltage regulator Solid state Mandatory
2.9 Insulation Class H
2.10 Temperature rise 95 to 125 0C(Class H) Mandatory
2.11 Bearing: Quantity, type 1,sealed
2.12 Coupling Flexible disc , CLOSE COUPLED
2.13 Voltage regulation : No load to full load 2 phase sensing ,
2.14 One step load acceptance 100% OF rating
2.15 Unbalance load capability Minimum 25% of rated current Mandatory
3 AMF panel/Automatic Transfer Should be equipped with DG set. The power supply Mandatory
Switch: should restart automatically in 20 seconds (main as
well as DG set in both cases)
3.1 FEATURES A remote controllable panel. Simple controller user
friendly ,LCD Display ,the unique integrated DG
set controller ,in corporate engine & Alternator
parameter ,Remote start & stop ,with Automatic
change
3.2 DISPLAY PARAMETER Low engine oil pressure indication at fault ,High oil
temperature indication at fault ,Emergency stop
,Battery voltage, DG set running hours ,fault
display
3.3 SHUT DOWN WITH AUDIO VISUAL Low oil pressure, High coolant temperature, Engine
ANNUNCIATION over/under speed, low fuel, over load, under
voltage, over voltage, over frequency, under
frequency.
3.4 AUDIO VISUAL WARNING Low oil pressure ,High coolant temperature ,Fault
LED over/under speed
3.5 Engine, Alternator & panel Monitoring Deepsea controller Mandatory
system:
3.6 Genset protection & alarms available The following should be included, low lub oil
pressure, High Temp,over speed , Reverse, power,
Frequency Abnormally, overload & short circuit
Breaker, Hour meter
4 Battery charger
4.1 Input voltage 170-270 Volt AC
4.2 Input voltage frequency 40Hz to 65Hz
4.3 Input current 2.6A Typical at 230V AC
4.4 Input Inrush current Limited by NTC thermistor to 35A
4.5 Leakage current mA at 230V AC
4.6 Output voltage: Float mode:26.2 to 26.5V DC Mandatory
Boost mode:27.8V to 28.4V DC
4.7 Charging current in boost mode 3amps to 10 amps Mandatory
4.8 Charging current in float mode 0amps to 3 amps
4.9 Output power 280 V Mandatory
4.10 Stand-by power consumption Not less than 3W Mandatory
4.11 Line Regulation
4.12 Load Regulation
4.13 Ripple and noise 250 mv p-p
4.14 Operating Temperature (-)20 to (+)850C
4.15 Storage Temperature (-)20 to (+)850C
4.16 Operating Humidity 20 to 95%RH
4.17 Storage Humidity 10 to 95%RH
4.18 Input under voltage Cutoff level 140V AC Turn on voltage 160V AC
4.19 Input over voltage 320V AC units shuts off if voltage goes above this
value and automatic restart when input is less than
275V AC
4.20 Output over voltage (Battery charger 29V DC
included)
4.21 Output short circuit and overload Continuously Protected Mandatory
4.22 Externally induced over voltage Externally induced over voltage protected against Mandatory
output over-voltage caused by parallel connection
of alternator, etc.
4.23 Annunciation Potential free NO/NC contact for charger ON/Fail Mandatory
induction
5 Acoustic enclosure Polyester powder coated, high class sheet metal
fabricated enclosure for reducing the noise level of
DG set & also acts as weather proof housing.
Generator set will be an integral part of acoustic
enclosure & whole construction will be on multi-
fold sheet channels & ISMC sections. Enclosure
construction is fully bolted keeping in view the
major service requirements all doors are provided
with specially designed hinges & lockable handles,
battery is housed inside the enclosure. Engine
alternator assembly mounted on AVM with silencer
and S.S exhaust bellow suitably optimized to meet
stringent sound emission standards.
5.1 Sound attention level Not greater than 75dB at 2 meter
5.2 Fuel tank Sub-base fuel tank with 14 hours capacity at 75%
load.
5.3 Tools ,manuals and spare parts included
5.4 Tools Software, list of tools free of charge to be provided
Adjustable wrench, Filter removal, fixer wrench,
knife, pliers , different size wrenches , hammer
,monkey wrench, flat screw driver, Philips screw
driver
5.5 Spare parts: The bidder should keep stock of necessary spare
parts for all Genset locally on servicing:-indicate
the number of line items of spare parts you have in
stock, the floor area of the store and its specific
location. This shall be verified by site visit

6 Delivery period Should be specified


7 Commissioning/installation The supplier must visit the site and include the
necessary accessories like cables, cable lug and
other accessories needs for installation. Note: The
bidders have responsible to install the generator
with the existing generator and EEU incoming lines
and commission the product.
8 Training and knowledge Practical training should be done by the supplier’s
trained technicians.
9 Certificate 3 years
10 Warranty period The Genset should be manufactured as per the Mandatory
bank’s brand color
11 Color/Icon
12 TESTING
12.1 Sample testing The following test shall be conducted on alternator Mandatory
and DG set.
Factor test , type test, routine test, high voltage test,
short circuit current test, insulation resistance
test.(All testing should be done at showroom in
Ethiopia.)The original test certificate shall be
furnished with supply of DG Set.
Insulation resistance of the generator, speed, no
load voltage and full load voltage regulation.
Frequency at no load, half load and full load.
The reading shall be observed with calibrated
materials. Only one meter shall be used for the test.
The readings shall be properly submitted in
triplicate.
13 Mandatory –load testing equipment availability by supplier is required. Attach the
evidence of load bank or testing equipment (invoice or ownership certificate), Warranty,
MAF and Quality Certificate should be submitted.
Technical specification for 15KVA Generator
Mandatory point for generator
No. Description SIINQEE Requirement Supplier’s offer
1 General specification
1.1 Brand and model Should be specified
1.2 Genset Rating Prime power
1.3 Genset Rating Prime power
1.4 Genset output 15KVA/12KW
1.5 Engine rating or max. power at rated Not less than 15.9(21.6)
RPM ,in KW(BHP)
1.6 Engine type Natural Aspirated
1.7 Engine model Should be specified
1.8 No. of cylinders /cylinder arrangement 2/Inline
1.9 Stroke 4
1.10 Displacement (L) 1.56
1.11 Bore & stroke(mm) 91 110
1.12 Compression ratio 17.5
1.13 Rated RPM 1500 RPM
1.14 Governor: Type/class of Governing Mechanical
1.15 Over speed trip(rpm) 1650
1.16 Air cleaner type /Qty Dry/01
1.17 Maximum allowable black pressure 4 kPa
1.18 Charging alternator voltage/current(DC) 12V /35Amps
1.19 Battery voltage (DC)/capacity(AH) 12V,65AH
1.2 Oil consumption (%SFC)
1.21 Engine brand and make Cummins/Perkins/Greaves/Escort/Cat
1.22 Designed operating ambient Tem. Should be friendly up to 50 0C
1.23 Fuel type Preferable diesel
1.24 Fuel tank capacity Minimum able to run for 18 hrs at 75%
load
1.25 Cooling method Water cooled
1.26 Starting system Combination of electrical and
mechanical starting
1.27 Fuel consumption(prime) at 110% Should be specified
1.28 Fuel consumption(prime) at 100% Should be specified
1.29 Fuel consumption(prime) at 75% Should be specified
1.30 Fuel consumption(prime) at 50% Should be specified
2 Alternator maker Stamford/Leroy somer
2.1 Voltage 380-440 V
2.2 Phase Three phase
2.3 Frequency 50Hz
2.4 Current @ 0.8PF (Amps) 20 to 22 Amp/phase
2.5 Type 4 pole, rotating field
2.6 Exciter type Brushless
2.7 Leads: quantity , type 6,fixed
2.8 Voltage regulator Solid state , volts/Hertz
2.9 Insulation Class H
2.10 Temperature rise 95 to 125 0C(Class H)
2.11 Bearing: quantity , type 1,sealed
2.12 Coupling Flexible disc , CLOSE COUPLED
2.13 Voltage regulation : No load to full load 2 phase sensing ,
2.14 One step load acceptance 100% OF rating
2.15 Unbalance load capability Minimum 25% of rated current
3 AMF panel/Automatic Transfer Should be equipped with DG set. The
Switch: power supply should restart
automatically in 20 seconds (main as
well as DG set in both cases)
3.1 FEATURES A remote controllable panel. Simple
controller user friendly ,LCD Display
,the unique integrated DG set controller
,in corporate engine & Alternator
parameter ,Remote start & stop ,with
Automatic change
3.2 DISPLAY PARAMETER Low engine oil pressure indication at
fault ,High oil temperature indication at
fault ,Emergency stop ,Battery voltage,
DG set running hours ,fault display
3.3 SHUT DOWN WITH AUDIO VISUAL Low oil pressure, High coolant
ANNUNCIATION temperature, Engine over/under speed,
low fuel, over load, under voltage, over
voltage, over frequency, under
frequency.
3.4 AUDIO VISUAL WARNING Low oil pressure ,High coolant
temperature ,Fault LED over/under
speed
3.5 Engine, Alternator & panel Monitoring Deepsea controller
system:
3.6 Genset protection & alarms available The following should be included, low
lub oil pressure, High Temp,over speed ,
Reverse, power, Frequency Abnormally,
overload & short circuit Breaker, Hour
meter
4 Battery charger
4.1 Input voltage 170-270 Volt AC
4.2 Input voltage frequency 40Hz to 65Hz
4.3 Input current 2.6A Typical at 230V AC
4.4 Input Inrush current Limited by NTC thermistor to 35A
4.5 Leakage current mA at 230V AC
4.6 Output voltage: Float mode:13.3 to 13.5V DC
Boost mode:13.8V to 14V DC
4.7 Charging current in boost mode 10 amps
4.8 Charging current in float mode 0amps to 3 amps
4.9 Line Regulation
4.10 Load Regulation
4.11 Ripple and noise 150 mv p-p
4.12 Operating Temperature (-)20 to (+)850C
4.13 Storage Temperature (-)20 to (+)850C
4.14 Operating Humidity 20 to 95%RH
4.15 Storage Humidity 10 to 95%RH
4.16 Input under voltage Cutoff level 140V AC Turn on voltage
160V AC
4.17 Input over voltage 320V AC units shuts off if voltage goes
above this value and automatic restart
when input is less than 275V AC
4.18 Output over voltage (Battery charger 15V DC
included)
4.19 Output short circuit and overload Continuously Protected
4.20 Externally induced over voltage Externally induced over voltage
protected against output over-voltage
caused by parallel connection of
alternator, etc.
4.21 Annunciation Potential free NO/NC contact for
charger ON/Fail
induction
5 Acoustic enclosure Polyester powder coated, high class
sheet metal fabricated enclosure for
reducing the noise level of DG set &
also acts as weather proof housing.
Generator set will be an integral part of
acoustic enclosure & whole construction
will be on multi-fold sheet channels &
ISMC sections. Enclosure construction
is fully bolted keeping in view the major
service requirements all doors are
provided with specially designed hinges
& lockable handles, battery is housed
inside the enclosure. Engine alternator
assembly mounted on AVM with
silencer and S.S exhaust bellow suitably
optimized to meet stringent sound
emission standards.
5.1 Sound attention level Not greater than 75dB at 2 meter
5.2 Fuel tank Sub-base fuel tank with 14 hours
capacity at 75% load.
5.3 Tools ,manuals and spare parts included
5.4 Tools list of tools free of charge to be
provided Adjustable wrench, Filter
removal, fixer wrench, knife, pliers ,
different size wrenches , hammer
,monkey wrench, flat screw driver,
Philips screw driver
5.5 Spare parts: Spare parts supplied with genset Should
be specified
6 Delivery period Should be specified
7 Commissioning/installation Should be specified
8 Training and knowledge Should be specified
9 Dealership certificate Should have dealership certificate from
maker
10 Warranty period 3 years
11 Icon The Genset should be manufactured as
per the bank’s brand color
12 TESTING
13.1 Factory testing The following test shall be conducted on
alternator and DG set.
Factor test , type test, routine test, high
voltage test, short circuit current test,
insulation resistance test.(All testing
should be done at showroom in
Ethiopia.)The original test certificate
shall be furnished with supply of DG
Set.

13.2 Site test Insulation resistance of the generator,


speed, no load voltage and full load
voltage regulation. Frequency at no
load, half load and full load.
The reading shall be observed with
calibrated materials. Only one meter
shall be used for the test. The readings
shall be properly submitted in triplicate.
14 Mandatory –load testing equipment availability by supplier is required. Attach
the evidence of load bank or testing equipment (invoice or ownership
certificate), Warranty, MAF and Quality Certificate should be submitted.
Technical specification for 15KVA generator rating point for generator

No. Description SIINQEE Requirement Evaluation


1 No. cylinder Specify 5
2 Flywheel Suitable diameter and weight.(indicate) 2
3 Overload capacity Providing 10% over load for 1/12 hrs. Continuous running at 4
full load.
4 Aspiration Naturally 3
5 Silencer Residential type with exhaust piping, vibration isolators, thermal 4
insulation for exhaust line with glass wool aluminum sheet.
6 Starting system Solenoid switch: supply with required current to the starter 3
motor & pull in & out pinion drive. Starter motor 12V DC.
7 Fuel system Fuel injection pumps with hand (manual), electric fuel solenoid 3
should be provided.
8 Remote control & operation system must be capable of operating and controlling by remote access 5
via SIM and Cloud system
9 Air filter Dry type, heavy duty with replaceable element 2
10 Lubrication system Full pressure lubricating oil system oil cooler to be fitted oil pre- 3
heating required. Oil drainage: external hose pipe.
11 Protective device Oil pressure, high To, high oil To, low radiator water level, fail to 3
start, over/ under speed/, low battery voltage, charge fail etc…
12 Control & display unit (Electronic card) Operation mode selection. Auto, manual, test off modes. Digital 4
instruments: AC voltage, AC voltage, AC current, KVA, HZ,
running hrs, DC voltage, DC Amp, oil pressure, Temp. Value.
Indicators alarms: fail to start, G.S working normal , high engine
temp low oil pressure, battery charge fail
13 Battery charger Automatic battery charger (shall be adjustable charge current & 2
voltage (up to 5 a)), 12 DC . In addition the battery charger shall
provide individual indication and common alarm at the
following fault conditions:- AC failure charger failure –output
voltage drops abnormally
14 Control panel 1.description (operating manual) 5
2.control module manual
3. fault-finding manual.
4. Component lists-inciting country of origin, make, etc.
5.one original software program for control panel & ten
softcopies
6.softawre cable link(ten)
7.spare part list-indicating make, model, and rating etc.
15 Fuel consumption l/hr in full load in full load 4
16 Instrument for adjusting speed Electronically 3
17 Alternator General 5
1) The alternator shall be three phases, 0.8 PF (lagging), four
wires, 400/230V with a frequency of 50Hz, star
connected.
Total 60