Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Test conditions
Page 2/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 101.2 0.85 27.0 HP 19 ST Trap Passing
Measure point 2 103.3 0.85 27.0 -
Measure point 3 101.6 0.85 27.0 -
Measure point 4 102.9 0.85 27.0 -
Page 3/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 168.9 0.85 27.0 -
Measure point 2 97.4 0.85 27.0 Traps near 25 P 007
Measure point 3 98.7 0.85 27.0 Found OK
Page 4/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 120.3 0.85 27.0 Passing of HP 19 Steam Trap
Measure point 2 45.0 0.85 27.0 -
Measure point 3 101.9 0.85 27.0 -
Measure point 4 43.3 0.85 27.0 -
Measure point 5 98.4 0.85 27.0 -
Measure point 6 104.0 0.85 27.0 -
Page 5/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 129.2 0.85 27.0 LP Steam line view from EP B
19
Measure point 2 138.9 0.85 27.0 -
Measure point 3 70.2 0.85 27.0 -
Measure point 4 74.3 0.85 27.0 -
Measure point 5 117.5 0.85 27.0 -
Measure point 6 73.6 0.85 27.0 -
Page 6/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 40.2 0.85 27.0 Steam Line near CH 107 KTI
Boiler
Measure point 2 167.8 0.85 27.0 -
Measure point 3 203.2 0.85 27.0 -
Page 7/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 129.1 0.85 27.0 Trap passing
Measure point 2 103.3 0.85 27.0 -
Measure point 3 125.2 0.85 27.0 -
Measure point 4 103.8 0.85 27.0 -
Measure point 5 120.2 0.85 27.0 -
Page 8/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 115.1 0.85 27.0 Steam Trap found passing near
KTI Boiler
Measure point 2 126.2 0.85 27.0 -
Measure point 3 103.7 0.85 27.0 -
Page 9/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 64.6 0.85 27.0 Drain passing near KTI
Measure point 2 146.8 0.85 27.0 -
Measure point 3 50.1 0.85 27.0 -
Measure point 4 128.2 0.85 27.0 -
Page 10/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 74.5 0.85 27.0 Drain Valve passing Location
near CH 111
Measure point 2 76.9 0.85 27.0 -
Measure point 3 98.2 0.85 27.0 -
Page 11/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 32.1 0.85 27.0 Trap between IAEC Boilers and
HRSG 2 SL-2
Measure point 2 103.1 0.85 27.0 -
Measure point 3 96.7 0.85 27.0 -
Measure point 4 105.1 0.85 27.0 -
Measure point 5 101.4 0.85 27.0 -
Page 12/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 30.7 0.85 27.0 Steam Trap between IAEC
Boilers and HRSG 2 passing
continuously
Measure point 2 77.6 0.85 27.0 -
Measure point 3 149.9 0.85 27.0 -
Measure point 4 72.1 0.85 27.0 -
Page 13/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 109.4 0.85 27.0 Steam passing thorugh trap MP
104
Measure point 2 98.9 0.85 27.0 -
Measure point 3 99.2 0.85 27.0 -
Measure point 4 40.7 0.85 27.0 -
Measure point 5 36.1 0.85 27.0 -
Page 14/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 224.4 0.85 27.0 Steam line insulation absent and
the existing insulation being poor
Measure point 2 70.0 0.85 27.0 -
Measure point 3 59.3 0.85 27.0 -
Measure point 4 48.7 0.85 27.0 -
Measure point 5 45.4 0.85 27.0 -
Measure point 6 85.1 0.85 27.0 -
Measure point 7 60.7 0.85 27.0 -
Page 15/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 13.9 0.85 27.0 Steam line Insulation absent
near valve near IAEC Boilers
Measure point 2 150.2 0.85 27.0 -
Measure point 3 150.6 0.85 27.0 -
Measure point 4 135.0 0.85 27.0 -
Measure point 5 44.0 0.85 27.0 -
Page 16/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 190.8 0.85 27.0 IAEC Boiler Steam line Valves
and Flanges found un-insulated
Measure point 2 188.5 0.85 27.0 and the condition of insulation is
slightly poor
Measure point 3 164.7 0.85 27.0 -
Measure point 4 131.9 0.85 27.0 -
Measure point 5 60.3 0.85 27.0 -
Measure point 6 58.2 0.85 27.0 -
Page 17/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 42.9 0.85 27.0 -
Measure point 2 50.7 0.85 27.0 -
Page 18/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 145.5 0.85 27.0 -
Measure point 2 31.7 0.85 27.0 -
Page 19/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 176.5 0.85 27.0 -
Measure point 2 28.9 0.85 27.0 -
Page 20/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 106.9 0.85 27.0 Steam trap near Blow Down trap
Measure point 2 121.1 0.85 27.0 -
Measure point 3 185.0 0.85 27.0 -
Page 21/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 200.0 0.85 27.0 Steam trap near Cogen plant
passing
Measure point 2 105.6 0.85 27.0 -
Measure point 3 78.7 0.85 27.0 -
Page 22/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 197.6 0.85 27.0 Steam line insulation on flange to
be provided
Measure point 2 37.3 0.85 27.0 -
Measure point 3 96.1 0.85 27.0 -
Measure point 4 89.2 0.85 27.0 -
Measure point 5 78.7 0.85 27.0 -
Page 23/24
Steam Line Insulation Condition and Steam Trap Report of Co-
gen Plant
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 158.2 0.85 27.0 Steam traps near CH 110 Heavy
passing observed
Measure point 2 166.2 0.85 27.0 -
Measure point 3 99.6 0.85 27.0 -
Measure point 4 94.5 0.85 27.0 -
Project data
Name Street Place Phone E-mail
Makarpura
Page 24/24