You are on page 1of 2

Single VFD for Multiple Motors

A single variable frequency drive (VFD) may control 2 or 3 motors at a time, multiple motors
control is usually done because of budget considerations. When in this example below, a
cooling tower with 4 equally sized motors are controlled by one variable frequency drive.

Motors are to have the same capacity and operate at the same speed. In this example the
4 motors are 2 amps each.

The variable frequency drive parameters must be set to accommodate the total capacity. In
the case the variable frequency drive parameter is set to 8 amps (2 amps x 4 motors). Each
variable frequency drive parameters that are meant for one motor should be turned off. For
example slip compensation (calculating the difference between the field speed and rotor
speed) should be set to off in multi-motor controls.

A single motor has its own overload protection. In this example, if the cooling tower fans
were operating with a very light load, say 1 amps each, and if one of the 4 motors became
failure, the the amp draw on the failed motor would need to surpass, 5 amps (8 amps - – (3
x 1 amps)) before the variable frequency drive caused any problem.

Wiring multiple motors on a single VFD, certain conditions, considerations and safety must
be met, here are few guidelines you'd better follow to avoid failures:

 Variable frequency drive should be at least 20% more power of the two or three
motors' power clubbed together.
 Set variable frequency drive to V/F mode, no vector control at all.
 Set correct current rating.
 Don't perform Auto tuning.
 At the variable frequency drive output put right OLR for individual motor.
 NC of OLR should be wired to variable frequency drives enable terminal, so that
any of the motor goes to fault variable frequency drive should be disabled.
 NOs of OLR and variable frequency drives can be used for fault display.

But please keep in mind that you can only set the VFD to V/F mode control if you control
multiple motors by one variable frequency drive, never set variable frequency drive to any
vector control, even at open loop with vector control, otherwise the variable frequency drive
will fail.

So the bottom line, go ahead with multiple motors. It is absolutely fine to run more than one
motor on a single variable frequency drive till the power capacity is matched and the
parameters are set correctly. This is the key of any variable frequency drive application.

You might also like