You are on page 1of 5

Load Performance Curve

Transformer Load Performance Curve

of JUPITER-6000K-H1 for SUN2000-330KTL-H1/H2

Huawei Technologies Co., Ltd.

Version Created by Date Remarks


V1.0 Wangwei; Leiying 2023.01.15

Huawei proprietary, Restricted Distribution Page 1


Load Performance Curve

Load Performance Curve

Performance Curve VS. Load Factor of JUPITER-6000K-H1 @40°C @50Hz

The characteristic of transformer inside JUPITER-6000K-H1 shall perfectly match the output
characteristic of SUN2000-330KTL-H1/H2.When the ambient environments is 40°C and rated
frequency 50Hz, the capacity of JUPITER -6000K-H1 shall be 6600 kVA, and the detailed load

performance curve is listed as below:

Load Performance Curve


Power factor 0.8 Power factor 0.9 Power factor 1
99.600%

99.500%

99.400%
Efficiency

99.300%

99.200%

99.100%

99.000%

98.900%
0 0.2 0.4 0.6 0.8 1
Load Factor

Load factor
Model 1 0.75 0.5 0.25
Power factor

1 99.147% 99.316% 99.460% 99.503%

JUPITER-6000K-
0.9 99.052% 99.240% 99.400% 99.447%
H1

0.8 98.934% 99.145% 99.325% 99.378%

Note: The data above are the design calculation values.

Huawei proprietary, Restricted Distribution Page 2


Load Performance Curve

Load Performance Curve

Performance Curve VS. Load Factor of JUPITER-6000K-H1 @40°C @60Hz

The characteristic of transformer inside JUPITER-6000K-H1 shall perfectly match the output
characteristic of SUN2000-330KTL-H1/H2.When the ambient environments is 40°C and rated
frequency 60Hz, the capacity of JUPITER -6000K-H1 shall be 6600 kVA, and the detailed load

performance curve is listed as below:

Load Performance Curve


Power factor 0.8 Power factor 0.9 Power factor 1
99.600%
99.500%
99.400%
99.300%
Efficiency

99.200%
99.100%
99.000%
98.900%
98.800%
98.700%
0 0.2 0.4 0.6 0.8 1
Load Factor

Load factor
Model 1 0.75 0.5 0.25
Power factor

1 99.262% 99.394% 99.495% 99.475%

JUPITER-6000K-
0.9 99.180% 99.326% 99.439% 99.416%
H1

0.8 99.078% 99.242% 99.368% 99.343%

Note: The data above are the design calculation values.

Huawei proprietary, Restricted Distribution Page 3


Load Performance Curve

Load Performance Curve

Performance Curve VS. Load Factor of JUPITER-6000K-H1 @50°C @50Hz

The characteristic of transformer inside JUPITER -6000K-H1 shall perfectly match the output
characteristic of SUN2000-330KTL-H1/H2.When the ambient environments is 50°C and rated
frequency 50Hz , the capacity of JUPITER -6000K-H1 shall be 6050 kVA, and the detailed load

performance curve is listed as below:

Load Performance Curve


Power factor 0.8 Power factor 0.9 Power factor 1
99.600%

99.500%

99.400%

99.300%
Efficiency

99.200%

99.100%

99.000%

98.900%

98.800%
0 0.2 0.4 0.6 0.8 1
Load Factor

Load factor
Model 1 0.75 0.5 0.25
Power factor

1 99.205% 99.355% 99.478% 99.491%

JUPITER-6000K-
0.9 99.117% 99.284% 99.421% 99.435%
H1

0.8 99.006% 99.194% 99.348% 99.364%

Note: The data above are the design calculation values.

Huawei proprietary, Restricted Distribution Page 4


Load Performance Curve

Load Performance Curve

Performance Curve VS. Load Factor of JUPITER-6000K-H1 @50°C @60Hz

The characteristic of transformer inside JUPITER -6000K-H1 shall perfectly match the output
characteristic of SUN2000-330KTL-H1/H2.When the ambient environments is 50°C and rated
frequency 60Hz , the capacity of JUPITER -6000K-H1 shall be 6050 kVA, and the detailed load

performance curve is listed as below:

Load Performance Curve


Power factor 0.8 Power factor 0.9 Power factor 1
99.600%
99.500%
99.400%
99.300%
99.200%
Efficiency

99.100%
99.000%
98.900%
98.800%
98.700%
98.600%
0 0.2 0.4 0.6 0.8 1
Load Factor

Load factor
Model 1 0.75 0.5 0.25
Power factor

1 99.308% 99.423% 99.505% 99.455%

JUPITER-6000K-
0.9 99.231% 99.359% 99.450% 99.394%
H1

0.8 99.135% 99.279% 99.381% 99.319%

Note: The data above are the design calculation values.

Huawei proprietary, Restricted Distribution Page 5