Document Name: Calculation Sheet for Main transformers and HAVC equipments cooling water system
Rev. No.: R3
Approved:
LEVEL 2
Oct. 2018
TABLE OF CONTENTS
1 GENERAL ............................................................................................................................. 2
2 COOLING WATER CONSUMPTION ........................................................................................ 2
2.1 COOLING WATER CONSUMPTION DATA ARE AS FOLLOWS: ........................................................................ 2
3 MODE OF WATER SUPPLY .................................................................................................... 2
3.1 MODE OF WATER SUPPLY FOR MAIN TRANSFORMERS ............................................................................... 2
3.2 MODE OF WATER SUPPLY FOR HVAC EQUIPMENTS .................................................................................... 3
4 CALCULATIONS OF DIAMETER OF PIPES ............................................................................... 3
4.1 FLOW VELOCITY IN PIPES ............................................................................................................................. 3
4.2 CACULATIONS OF DIAMETER OF PIPES FOR MAIN TRANSFORMER AND HVAC EQUIPMENTS: ................ 4
i
ZUNGERU HYDROELECTRIC PROJECT
1 GENERAL
The Main transformers and HAVC equipments cooling water system is used for the cooling water
supply of the Main transformer and the HVAC equipments.
Page 2 of 15
ZUNGERU HYDROELECTRIC PROJECT
According to the water consumption , the pressure requirement and the water head of the
project, pressure reducing mode will be used for cooling water supply system.
The temperature of cold cooling water will be considered as 30°C, the assumption of temperature
difference between cold and hot water will not exceed 5 °K.
References are made to “Schematic diagram of cooling water System (D-ME-HM-01 R1) and
Schematic diagram of transformer and HAVC equipments wate supply system (D-ME-HM-02 R1)”.
According to the water consumption and the pressure requirement, in order to ensure the
reliability of water supply, independent pump water supply mode will be used for HVAC
equipments cooling water supply system.
The temperature of cold cooling water will be considered as 30°C, the assumption of temperature
difference between cold and hot water will not exceed 5 °K.
References are made to Schematic diagram of transformer and HAVC equipments wate supply
system (D-ME-HM-02 R2)”.
The flow velocity in cooling water pipes shall in general around 2.0~3.0 m/s to avoid sand
sedimentation and over abrasion. However, as pressure reducing mode is used for cooling water
sysytem, the flow velocity can be increased to 3.0~5.0 m/s for facilitating pressure reducing in
cooling water pipes before reducing valves. The flow velocity after reducing valves shall be
adopted to 2.0~3.0 m/s.
Page 3 of 15
ZUNGERU HYDROELECTRIC PROJECT
References are made to “Schematic diagram of cooling water System (D-ME-HM-01 R1) and
Schematic diagram of transformer and HAVC equipments wate supply system (D-ME-HM-02 R1)”.
4Q
D 1000
3600V
where,
V is the water flow velocity in the piping system, the flow velocity after reducing valves shall be
adopted to 2.0~3.0 m/s, the flow velocity before reducing valves could be adopted to 3.0~5.0
m/s.
Nominal Diameter
Description Flow (m3/h) Flow Velocity (m/s) (outside diameter × pipe wall
thickness) (mm)
Dmt 420 2.3 DN250(ø273.1×9.5)
Dmt’ 420 2.3 DN250(ø273.1×9.5)
Dbht 105 1.58 DN150 (ø168.3×7.5)
Dmhc 652 2.5 DN300 (ø323.9×10)
Dmh 592 2.27 DN300 (ø323.9×10)
Dmc 60 2.03 DN100 (ø114.3×6)
Dmt1 105 1.58 DN150 (ø168.3×7.5)
Notes:
Page 4 of 15
ZUNGERU HYDROELECTRIC PROJECT
Dmt is diameter of the main water supply pipe (before reducing valves) for 4 Main transformers
(mm).
Dmt' is diameter of the main water supply pipe (after reducing valves) for 4 Main transformers
(mm).
Dbht is diameter of the branch water supply pipe (before reducing valves) for 1 Main transformer
(mm).
Dmt1 is diameter of the branch water supply pipe for one Main transformer (mm).
Dmhc is diameter of the water supply pipe for HVAC equipments and air compressors (mm).
Dmh is diameter of the water supply pipe for HVAC equipments (mm).
Dmc is diameter of the water supply pipe for air compressors (mm).
The frictional head loss of pipes will be estimated by Hazen Williams formula
L Q
h f 1.13 10 9 4.871
( )1.852 ;
D C
Where:
5.1.2 Formula for local head loss he of pipe auxiliaries and valves
The local head loss he of pipe auxiliaries and valves will be calculated by their equivalent length.
Document no: C-ME-HM-009R3 Revision status: 03 Date Printed: Oct. 2018
Page 5 of 15
ZUNGERU HYDROELECTRIC PROJECT
Nominal Diameter
Name
DN32 DN40 DN50 DN65 DN80 DN100
45°eblow 0.3 0.6 0.6 0.9 0.9 1.2
90°eblow 0.9 1.2 1.5 1.8 2.1 3.1
Tee 1.8 2.4 3.1 3.7 4.6 6.1
Gate valve / / 0.3 0.3 0.3 0.6
Non-return valve 1.5 2.1 2.7 3.4 4.3 4.9
Nominal Diameter
Name
DN150 DN200 DN250 DN300 DN350 DN400
45°eblow 2.1 2.7 3.3 4 4.8 5.6
90°eblow 4.3 5.5 6.8 8.2 9.7 11.3
Tee 9.2 10.7 15.3 18.3 21.3 24.3
Gate valve 0.9 1.2 1.5 1.8 2.1 2.4
Non-return valve 9.8 13.7 16.8 19.8 22.7 25.5
5.2.1 The head loss of cooling supply water system for the main transformers
The head loss of cooling supply water system for the main transformers are shown in Table 1.
According to the results in Table 1, the inlet water pressure of the each coolers is 20.70m which
is satisfied with the pressure requirement of Cooling water consumers.
Page 6 of 15
ZUNGERU HYDROELECTRIC PROJECT
Table1 The head loss of cooling supply water system for the Turbine-generator
Page 7 of 15
ZUNGERU HYDROELECTRIC PROJECT
Page 8 of 15
ZUNGERU HYDROELECTRIC PROJECT
93.00 * is the pipe inlet water pressure which caused by upper reservoir water level (223m to 230m), the pipe inlet water pressure is equal to (223-130=93)m.
1-2(form DN350/DN150 tee in the main cooling water pipe to the DN250/DN150 tee)
Page 9 of 15
ZUNGERU HYDROELECTRIC PROJECT
5-6(form the DN250/DN150 tee to the inlet of the Main transformer collers )
5.2.2 The head loss of cooling supply water system for HVAC equipments
The head loss of cooling supply water system for the main transformers and HVAC equipments are shown in Table 2.
Page 10 of 15
ZUNGERU HYDROELECTRIC PROJECT
Page 11 of 15
ZUNGERU HYDROELECTRIC PROJECT
Page 12 of 15
ZUNGERU HYDROELECTRIC PROJECT
The net head of pump should be greater than the elevation difference He between the elevation
of pipe outlet and elevation of tailrace water level with the addition of head loss of pump pipes
and valves Hc (Hc=4.36+1.86=6.22m).
Hn> Hc + He+Hco=6.22+14.94+15=36.16m
Where , He= 148.80-133.86=14.94m, 148.80 m is the elevation of pipe intet of HAVC equipments
coolers, 133.86m is the tailrace water level (one unit operation with 220m3/h flow);
So, Hn=37m
Where ,
In consideration of some margin and series of motor, the power of pump motor will be chose to
110 kW:
Page 13 of 15
ZUNGERU HYDROELECTRIC PROJECT
7 EQUIPMENTS PARAMETERS
7.1 PUMP PARAMETERS
Type of pumps: horizontal centrifugal pump
Number of pumps: 2
Head loss: ≤ 2m
Page 14 of 15