Unit independent system: 1 protection areas is protected with one CO2 firefighting system.
Combined distribution system: 2 protection areas are protected with only one CO2 firefighting
system.
Combined distribution system
Unit independent system
2 Main components of agent cylinder,
actuating cylinder and pipeline system
The Unit independent CO2 firefighting system is applied in Zungeru hydropower plant .
This system mainly consists of agent cylinder (including head valve, weighing device),
actuating cylinder (including head valve with solenoid valve), check valve, pressure switch,
rack, nozzles and pipelines, etc.
2.1 Agent Cylinder
Nominal Connecting
Nominal
Type operating screw with
diameter
pressure flexible tube
HYD12/17.2 17.2 MPa 12 mm M24 × 1.5
Type YD6/6.6
Type HDG0.5/8
Design pressure 8.0 MPa
Actuating gas
Open pressure ≤0.1MPa cylinder
Close pressure ≥0.5MPa
2.8 Pressure Switch/signal feedback
device (XF0.8/17.2)
Safety valve
Leakage
indicator light
Weighting device
All the alarm signal circuits of weighing devices are
connected in parallel.
Leakage
indicator light
2.11 Spray nozzle +Y
°
? 18
40
500
? 16
500
40°
8°
model of extended release
40°
nozzle is EPT5/15.
40
°
55°
600
400
? 10
°
? 11
45° 40
?2
7X
40°
?8
9X
)
8
00
(5
30
0
Type RcX D
EPT5/15 Rc1/2 2.6
EPT14/20 Rc3/4 7.3
Schematic diagram generator
CO2 firefighting system
3 Fire alarm system
The generator firefighting system of Fire alarm Optical Fiber Power supply DC24V power
Zungeru HPP is equipped with a fire control panel control panel ATS supply module
alarm controller, the model is NFS2-
3030. It is responsible for the fire
alarm of four generators.
+Y
0
00
11
°
60
60
? 18
°
500
60
60
°
Optical fiber linear temperature detection system includes linear
temperature optical cable and detecting host. The temperature optical
60°
fiber is installed in the generator pit (top side of rotor), and the
temperature detecting host is installed at the downstream side of the
power (next to the fire alarm control panel) [floor 4, EL.139.50].
0
One Micra100 high sensitivity aspirating smoke detector is
00
11
°
60
60
? 18
°
500
? 16
500
installed outside each generator unit pit (close to the generator 500
1500
+X
60
60
°
60°
1. Fire. Fire indicator illuminates when the
alarm level has been reached and the
appropriate time delays have expired.
One P900 audible and visual alarm is installed on the top of the
entrance door of each generator pit. The alarm operates when the
generator catches fire.
3.7 Agent released indicator
One FS.C type agent released indicator is installed on the top of
the entrance door of each generator pit. When the generator is in
fire, and the CO2 firefighting system released, this indicator will
light to prompt all personnel not to enter the generator pit.
3.8 Pressure relief device
1. Automatic start
Under normal circumstances, the system
3. Mechanical emergency start
adopts automatic mode. That is, when there is a
fire in the generator, the fire alarm cabinet
When the generator is in fire and the automatic
sends out alarm signals and the agent release
mode and the electrical manual mode are invalid,
controller automatically controls the CO2
the operator can use "Emergency Mechanical
system to extinguish the fire.
Manual" to extinguish the fire.
4.2 Automatic start
Function of the control panel under auto mode:
The input of the manual start signal has the starting priority,
which means when the system receives a input of manual start
signal, no matter what circumstances the system is under, it will
enter the delay spraying state:
Light the manual start indicator and keep it locked until the
reset of the controller or there comes a manual stop input.
There will be an alarm when starting the buzzer and the buzzer
can be muffled.
Start the acoustic-optic alarm system and it can be stop or start
alone. During the delay, you can manually stop all the output;
control output 1, selector value. Light the corresponding
indicator.
After the delay, light the start spraying indicator and keep it
locked until the reset of the controller. Start the control output 2、
bottle value and light the corresponding indicator.
Wait for the gas spraying feedback signal. When receiving the
feedback signal, light the gas spraying indicator and the buzzer
makes a sound of spraying.
4.4 Manual stop
During the gas spraying delay, when the input is When the system has entered the gas
“manually stopped”: spraying status, the buzzer makes a sound
of spraying, all the output can not be
stopped by manual stop, which means that
Light the manual stop indicator until the reset the manual stop only effects before or
of the controller or there comes a manual start during the delay.
input.
Locking device
Solenoid valve of
actuating cylinder
3 Maintenance RP-1002PLUS
(a) Reset the fire alarm panel and agent release control.
NFS2-3030
Pressure switch
(c) Fill the actuating cylinder with actuating gas. The
filling pressure is 60 × 105 Pa.
Locking device
(1) Clean the gas cylinder to be filled twice with (3) Connect the filling hose to the cylinder
N2 of 0.2 MPa. valve.
Compression screw (8) Remove the charging hose and immediately screw on
the outlet plug of the cylinder valve.