You are on page 1of 1

Section 3 - TECHNICAL SPECIFICATIONS OF MATERIALS AND EQUIPMENT OF THE DISTRIBUTION SYSTEM

Isolator PIN (PIN), porcelain, WITH RADIO INTERFERENCE,15 kV, ANSI 55- 5 Review: 04
Date: 2012-07-30
ITEM Description Specification Offered
1 MATERIAL Porcelain processed in wet Porcelain processed in wet
1.1 Manufacturing Standard ANSI C29.5 ANSI C29.5
1.2 Insulation Class ANSI 55-5 ANSI 55-5
1.3 Rule of enamel ANSI C29.5 ANSI C29.5
2 Critical distances
2.1 Arc distance 159 mm 159 mm
2.2 Distance of leak 305 mm 305 mm
2.3 The espigo mìnima Height 152 mm 152 mm
3 Mechanical values
3.1 Cross resistance to effort 13 kN 13 kN
4 Electrical values
4.1 Voltage of buckling of low frequency in dry 80 kV 80 kV
4.2 Voltage of buckling of low frequency in wet 45 kV 45 kV
4.3 Voltage of buckling critical to the positive momentum. 130 kV 130 kV
4.4 Voltage of buckling critical to the Negative Pulse 150 kV 150 kV
4.5 Voltage of drilling at low frequency 115 kV 115 kV
5 RADIO INFLUENCE
5.1 Enamel anti-radio interference RF If RF
5.2 Test voltage rms to ground 15 kV 15 kV
5.3 RIV Maximum to 1000 kHz 100 μV 100 μV
6 Details CONTRUCTIVOS Note 1 Yes
7 Finishing
7.1 The color of the enamel Coffee Coffee
8 The Isolator Thread
8.1 Diameter 25 mm 25.4mm
8.2 Features Note 2 Yes
9 Packaging
9.1 Packaging of the batch According to requirements of the EDs According to requirements of the EDs
9.2 Units per batch
9.3 Approximate net weight of the Lot
10
Documents and certificates of mandatory compliance Note 3 Yes

11 Samples According to requirements of the EDs According to requirements of the EDs


Notes:
The porcelain insulators must be manufactured by wet process. All the exposed surface of the porcelain insulators must be covered with
a vitrified compression type hard, smooth, glossy and impervious to moisture, which enable him, by means of washing of natural rain, easily
maintained free of dust or residual dirt caused by environmental pollution. The total surface of the insulator, with the exception of the area of burning,
must be glazed and free of imperfections. The porcelain used does not have to submit Porosities; shall be of high dielectric strength, high
1 mechanical resistance, chemically inert and high melting point.
Each insulator must be marked legibly and indelibly and durable in time with the following information as a minimum: name, symbol or logo that
identifies the manufacturer, year of manufacture and model of isolator.
2 The thread should be part of the same body of the isolator, by any concept can be an element engaged.
The certificates of conformity of product or of compliance with standards required in the present document, should be issued by accredited
certification bodies, documentation to be endorsed by the EFA.
3 In the case of the test reports, these must be issued by the accredited laboratories, documentation to be endorsed by the EFA. These
certificates and reports, will be a requirement that the bidders submit for procurement processes.