P&H Shovel Options Overview

Purpose
The purpose of this document is to show the reconstructed option screens for the
P&H shovel’s GUI application and supply a description of each item.

Discussion
The option screens have been reconstructed in attempts to show a more user friendly
view. Some options have also been slightly re-written for better clarification to its
function. The main option screen that you are familiar with is now divided up into
two main screens. These two main screens are further divided into special
classifications, refer to figure 1 and figure 2.

Figure 1

_P&H Shovel Option Screens.doc 1 of 21 PJW 12/15/08


Technology Options
Refer to figure 1 for the following items

Automatic Shovel Technology Configurator


Enables the input from Automatic Shovel Technology Configurator executable
program for configuring the Centurion application for Payload, Payload with Loadpin
and TrackShield.

Track Shield
Activation of Track Shield system and associated system monitoring software.
Enables communication between the AC800 and the Track Shield embedded
computer system. Also enables the Swing Resolver hardware fault enunciation code.

Payload
Activation of Payload system and associated system monitoring software. Enables
communication between AC800 and the Payload embedded computer system.

Payload with Loadpin


Enables the AC800 loadpin signal from the Payload Loadpin system.

Convert Payload Units to Metric


Converts Payload dipper load data from English to Metric. The Payload option is a
prerequisite for this option.

Payload Reporter
Activates software in the GUI to transfer the database file to the Payload Reporter
server. This database file contains all data critical to payload. Ensure that the
Payload Reporter server is running properly before activating this option. The
Payload option is a prerequisite for this option.

Dipper Position Calibration (Laser)


Activates the AC800 code and GUI screens for crowd and hoist resolver calibration
using the distance measuring laser and torsion box reflector. Either this option or the
Dipper Position Calibration (Inclinometer) option must be selected for Payload and
Track Shield systems.

Dipper Position Calibration (Inclinometer)


Activates the AC800 code and GUI screens for crowd and hoist resolver calibration
using the saddle and machine house inclinometers. Either this option or the Dipper
Position Calibration (Laser) option must be selected for Payload and Track Shield
systems.

Swing Calibration
Allows for calibration of the swing resolver via the GUI. This option is a prerequisite
for the Track Shield option.

_P&H Shovel Option Screens.doc 2 of 21 PJW 12/15/08


Modular Mining Interface
Enables the Modular Mining Interface executable file on the GUI. The Payload
option is a prerequisite for this option.

ShovelLink II
Opens communication connection between the GUI and the ShovelLink II server.
This allows for the viewing of flow charts, parts books, trending and schematics via
the GUI. Note that the ShovelLink II server must be installed and functional before
activating this option.

RHM
This is currently not tied to anything in the AC800 application. Note that the Remote
Health Monitoring data recording hardware must be installed on the shovel for this
option.

Vibration Monitor
A new vibration monitoring system will be installed on Shovel (both AC and DC).
The vibration system will read data from PH OPC DanServer via AC800 OPC server.
The option will make a button available on the GUI to allow the operator to start the
vibration testing procedure. Also the option will prompt the Centurion GUI to start
the DanServer.

Power Monitor
When the option is enabled, the GUI will display General Power Information coming
from the power meter.

Miscellaneous
Refer to figure 1 for the following items.

Fire Suppression System  Configure Fire Suppression System Button


Activates the fire suppression system monitoring and enables the Configure Fire
System button. This button provides access to the Fire Suppression System screen for
further customization of the fire system. See section Fire Suppression System for
further details.

Lube System  Configure Lube System Button


Provides access to the Filtration and Lubrication System screen. See section
Filtration and Lubrication System for further detail.

RPC System  Configure RPC Button


Provides access to the RPC Option Screen. See section RPC Option Screen for
further detail.

Right Hand Console IO Enable (28147 & 28148)


Enable monitoring and use of Right Hand Console. The original centurion design
called for two separate IO drops for the console. After the first two machines this

_P&H Shovel Option Screens.doc 3 of 21 PJW 12/15/08


function was consolidated into a singular IO drop. The standard offering is a single
console IO drop, but to accommodate the first two machines this option has been
made available.

Deactivate Logarithmic Master Switch


Joystick reference will be linear instead of logarithmic.

AccuWay Interface
Flanders Payload System. Activates software that transmits data to their third party
system via Profibus.

Retrofit Options
Refer to figure 1 for the following items.

Centurion RETROFIT Application


This option should be selected if your machine is a Retrofit. This would include
complete centurion retrofits, C500, and C750 upgrades.

Centurion 500 Application


The centurion option that only requires the replacement of the plc with the AC800
control cabinet. Option Centurion RETROFIT Application is required with this
option.

Centurion 500 – Motivator ½ Bank


If the Centurion 500 option is selected and the machine is in Motivator mode this
option will force the ½ bank on, 15 seconds after the main contactor is closed.
Centurion 500 – Motivator Bank 1
If the Centurion 500 option is selected and the machine is in Motivator mode this
option will force the Bank 1 on, 15 seconds after the main contactor is closed.

Centurion 750 Application


The centurion option that involves the replacement of the PLC control cabinet as well
as the Allen Bradley and FLEX I/O racks with Siemens I/O. Option Centurion
RETROFIT Application is required with this option.

RPC Cabinet Pancake Fans


Enables the control software and I/O monitoring for the RPC pancake fans. Make
sure the pancake fans are installed before activating this option. These fans are
located in each cabinet between the capacitors and reactors.

Righthand room Exhaust Blower


Enables the I/O monitoring for the right hand room exhaust blower. Make sure the
exhaust blower is installed before activating this option.

Bleed Blowers (Sold Option or Retrofit)

_P&H Shovel Option Screens.doc 4 of 21 PJW 12/15/08


Alternative system to AirScrubPro. If AirScrubPro is not installed this should be
active. This enables the I/O monitoring for the bleed blowers. Make sure the bleed
blowers are installed before activating this option.

Hide Lube Tank Level Display


When selected, the tank lube level bar graph display on the Lube System Status
screen of the GUI will be removed.

Disable Inclinometer Screen Navigation


When selected, the navigation button to the Inclinometer screen of the GUI will be
disabled (Grayed Out).

Drive Model Configuration


Refer to figure 1 for the following items.
Control Cabinet Fan
Enables the control software and I/O monitoring for the control cabinet fan. Make
sure the fan is installed before activating this option.

RPC Cabinet Fan


Enables the control software and I/O monitoring for the RPC cabinet fan. Make sure
the fan is installed before activating this option.

Boom Resolver 6 Inch (5 inch unchecked)


Selects the resolver model for ABSS. This option should be selected for all new
machines and old 41XPBs. This is the standard, but some older machines (retrofits)
may have a 5 inch stroke resolver. To verify the type that you have looked at the
manufacturer’s part number stamped on the unit. In the last 3 digits you will either
see a 501 or 601, where 501 would be the 5 inch unit and 601 would be the 6 inch
unit.

Aux Transformer Temperature Switch


Enables a delayed shutdown for aux transformer over temperature when selected.

Drive Model DCS600 / DCS800  Configure Drives


Configuration tool for selecting the model of drives (ABB DCS600 or DCS800)
installed for the hoist, crowd and swing motions. All drives for a motion must be the
same model type e.g. HP1, H2 and HF are identical, CP2 and CPF are identical and
SWG and SF are identical.

_P&H Shovel Option Screens.doc 5 of 21 PJW 12/15/08


Figure 2

_P&H Shovel Option Screens.doc 6 of 21 PJW 12/15/08


Sold Options
Refer to figure 2 for the following items.

Extended temperature monitoring – Lower


Activation of GUI screens and monitoring software for the following RTD locations:
- Right Propel Gear case Oil
- Right Propel Gear case Drive Bearing
- Left Propel Gear case Oil
- Left Propel Gear case Drive Bearing

Extended temperature monitoring – Upper


Activation of GUI screens and monitoring software for the following RTD locations:
- Hoist Front Input Pinion Inner
- Hoist Front Input Pinion Outer
- Hoist Front First Reduction Inner
- Hoist Front First Reduction Outer
- Hoist Rear Input Pinion Inner
Extended temperature monitoring – Upper Cont…
- Hoist Rear Input Pinion Outer
- Hoist Rear First Reduction Inner
- Hoist Rear First Reduction Outer
- Hoist Gearcase Oil
- Hoist Drum Gear Box Bearing
- Crowd Input Pinion Inner
- Crowd Input Pinion Outer
- Crowd First Reduction Inner
- Crowd First Reduction Outer
- Crowd Gearcase Oil
- Center Gudgeon Hub
- Rear Swing Gearcase Oil
- Rear Swing Shaft Bearing
- Swing RH Front Gearcase Oil (41xpb only)
- Swing RH Front Shaft Bearing (41xpb only)
- Swing LH Front Gearcase Oil
- Swing LH Front Shaft Bearing

_P&H Shovel Option Screens.doc 7 of 21 PJW 12/15/08


Sold Options Cont…
Refer to figure 2 for the following items.

Enable Temperature Open Sensor Warning


When active, warning messages will be sent out alerting the operator that the wire to
the RTD or RTD has opened or doesn’t exist. By placing a 56 ohm resistor in place of
the RTD the GUI will display -57 and no Warning message will be sent.

Desiccant Air Dryer System


When active, the functionality of the Air Dryer solenoid is enabled. The air receiver
solenoid will be activated based on pressure instead of a time interval.

MineAir GUI Control


Enables communication to the MineAir system and activates the GUI Screen for
controlling and monitoring the MineAir system. Must have centurion version 4.7 or
higher.

AirScrubPro Option
Enables AirScrubPro functionality. Make sure AirScrubPro is installed before
activating this option.

ASP Pulse Board Monitor


Enables monitoring of the AirScrubPro pulse board. Will enable a 30s shutdown if
the board is not sensed. Must have pulse board monitoring relay installed.

ASP No Air Monitor


Enables monitoring of the AirScrubPro pressure switch to monitor air pressure at the
AirScrubPro filters.

House Blower Reversing


Activates GUI screen that controls blower reversal. House blower reversing will not
function if the AirScrubPro option is selected.

Slack Rope Detection


Enables monitoring of slack rope detection digital input. This monitoring determines
if the hoist ropes are slack/loose. If a slack rope condition occurs, the hoist brakes
will set and not release until the ropes are no longer slack.

Fragmentation Camera
Enables software that will allow a camera to take pictures of the bank face. Also
enables a GUI screen for calibrating/setup of the camera trigger point.

_P&H Shovel Option Screens.doc 8 of 21 PJW 12/15/08


Sold Options Cont…
Refer to figure 2 for the following items.

Motivator Monitoring Freq/Volts


When enabled, allows for the conversion of analog input signals to the Motivator
mode frequency and voltage readings respectively.

Hydraulic Cable Reel Option Enable


Enables the functionality of the cable reel on/off switch in the operator coop to allow
the operator to de-tension the cable reel. Also enables monitoring the feedback from
the cable reel hydraulic pump starter. If the hydraulic system shuts down with the
propel brakes released, an immediate shutdown fault will occur.

Cable Reel Protection


Enables the monitoring of Hoist, Crowd and Swing resolvers to prevent the dipper
coming into contact with the cable reel if installed. If the program detects a possible
collision all brakes will be set. This option should not be confused with the limit
switch (whisker) located on the rear of the machine which is used to protect the cable
reel if the counterweight comes in close proximity. For this protection either the
whisker is installed or a jumper is required giving the AC800 program a constant high
value.

MCC(Motor Control Center) used, no Aux. Cabinet


Enables monitoring of the Starter Control Supply Breakers. These breakers provide
power the MCC IO.

Hoist Drum Lock, Single Switch


Enables monitoring of the Hoist Drum Lock engaged switch. On 4100 Class shovels,
this switch is actually several sensors wired in series which detect a pin being
engaged in an intermediate gear in the hoist gear box. On 2800 Class shovels, this
switch is a limit switch that detects the engaged position of the “hockey stick” lever.
With this option enabled, if the hoist drum lock is engaged the operator can operate
remote hoist at a reduced reference. This option will prohibit the machine from
operating in Run Mode if the hoist drum lock is engaged. The “Engaged” sensor
should be wired such that the sensor is Open (off) with the hoist drum lock engaged,
and Closed (on) with the hoist drum lock disengaged.

Hoist Drum Lock, Two Switches


This option is the same as the Single Switch option above, except with the addition of
a second sensor on “hockey stick” style hoist drum locks on 2800 Class shovels. The
second sensor detects when the lever is placed in the “stored” position. The
“Engaged” sensor should be wired such that the sensor is Open (off) with the hoist
drum lock engaged, and Closed (on) with the hoist drum lock disengaged. The
“Stored” sensor should be wired such that the sensor is Closed (on) with the hoist
drum lock stored, and Open (off) with the hoist drum lock not in the stored position.

_P&H Shovel Option Screens.doc 9 of 21 PJW 12/15/08


Sold Options Cont…
Refer to figure 2 for the following items.

Center Gudgeon Wear Limit Switch


Enables monitoring of wear to the center gudgeon. Will enunciate a warning message
if the limit switch signal is lost due to excessive wear of the center gudgeon.

Extra Earth Leakage Devices


Enables ground fault monitoring logic for the following:
- 415V Motor Control Center Supply
- 415V Power Distribution Supply
- 200V Relay Supply
- 236V Control Supply
- 415V Air Conditioner Supply

Aux transformer lighting winding ground fault


Enables ground fault monitoring logic for 240V Light and Power Supply.

Main Transformer Blower


Enables the control software and I/O monitoring for the main transformer blowers.

Bleed blowers (sold option or retrofit)


See Retrofit Options Section. This is a sold option, however, this would affect
retrofit machines the most.
Main Xfr Transient Filters Installed
Enables logic that monitors the circuit breaker of the main transformer transient filter.
If active, a warning message will be sent to the GUI when the circuit breaker trips.
(Make sure that the applied transient filter has this functionality available).

AC800M compact flash card enable


Enables logic that monitors the hardware state of the compact flash. Also enables the
saving of defined cold retain values that are defined in the AC800 program.

AC800M processor battery enable


Enables logic that monitors the state of the processor battery. If the battery is
removed or needs to be replaced, a warning message is generated.

OptiDig II Enabled
Enables OptiDig II.

RPC Monitor
Enables RPC Monitor function. See section RPC Monitor for further details.

_P&H Shovel Option Screens.doc 10 of 21 PJW 12/15/08


Dipper trip system
Refer to figure 2 for the following items.

Enhanced Crowd Belt Tensioner System Installed


Select if kit R62844D_ is installed. This is an upgrade kit which replaces the
standard crowd belt tensioner cylinder and hydraulic manifold assembly which
shipped standard with 4100XPB/C’sES4192 through ES41200.

Crowd Belt Tensioner Brake Release Proximity Switch


When selected the crowd belt tensioner program will expect to see the rod brake
released when the brake release solenoid (SOL2A) is energized.

No TripRite system
TripRite system software disabled.

TripRite with 12:1 gear ratio


Setting the maximum slack take up speed of the TripRite system to 440rpm. This
should be selected for any non-41xpb/c model that has TripRite. (The only 41xpb/c
this may be applicable to are those on Kennecott Utah Copper property).

TripRite with 17:1 gear ratio


Setting the maximum slack take-up speed of the TripRite system to 625rpm. (This is
only applicable to non-Kennecott Utah Copper 41xpb/c model machines).

Quick Transfer En
Enable quick transfer software. Before activating this feature verify the following
signals in the parameter file via drive window:
- Signal 4.02 should equal 15623h.
- Signal 4.03 should equal PH_F_Dxx where xx is the revision level of the
firmware. The PH_F_D is the indication that you have quick transfer.

Turn Cab Buzzer OFF for Swing Impact


When selected, the output to the Swing Impact buzzer is disabled.

Set all brakes when ladder down


When selected and in normal operation, all brakes will set when the ladder is
down. When not selected and in normal operation, only the swing and propel
brakes will set.

Static Brake Test


Enables static brake test functionality. Static brake test is designed to allow for the
testing of the brakes by applying a torque reference for a specified amount of time.
By monitoring the slip of the motion, it can be determined if the brakes need to be
serviced or replaced. This functionality is only valid for ES41156/57 as of 12/8/08.

_P&H Shovel Option Screens.doc 11 of 21 PJW 12/15/08


Featured Selections
Refer to figure 2 for the following items.

Disable Auto Brake Set


Disables logic that sets the hoist or crowd brakes when in run mode and no motion is
detected for more than 90 seconds. If selected, this functionality will be disabled.

Propel Boost
If enabled, the operator will be allowed to activate this function via the GUI that will
provide a 10% increase in current limits for the propel motors. The increased current
limits only apply when propelling strait forward or backward. The boost is active for
1 minute intervals, and the operator cannot exceed 20 boosts within a 12hr time
interval.

Brake Pressure Switches Only – No Transducer


Enable when there are no brake pressure transducers, only pressure switches. When
selected, the brake logic for all motions will use the pressure switches to determine
when to set and release the brakes instead of the pressure transducer (analog)
readings.

Polyfit Boom Profile


When selected, the polyfit boom profile limit configuration algorithm and setup will
be enabled.

_P&H Shovel Option Screens.doc 12 of 21 PJW 12/15/08


Fire Suppression System

Figure 3
Note: That this option screen is made available only by the selection of option “Fire
Suppression System”. A button to the right of “Fire Suppression System” option will be
enabled allowing you to open this screen when selected, refer to the miscellaneous
section of figure 1.

(See module 2.25.5 for reference to the following inputs.)


Machine House Alarm
Enables monitoring of input signal for machinery house fire alarm. When selected,
alarm “FireSystem – Machine House Fire” will be triggered when the input goes low.

Fire System Fault


Enables monitoring of input signal for system trouble. When selected, alarm
“FireSystem – System Trouble” will be triggered when the input goes low.

Lube Room Alarm


Enables monitoring of input signal for lube room fire alarm. When selected, alarm
“FireSystem – Lube Room Alarm” will be triggered when the input goes low.

RPC Cabinet Alarm


Enables monitoring of input signal for RPC cabinet fire alarm. When selected, alarm
“FireSystem – RPC Cab Alarm” will be triggered when the input goes low.

_P&H Shovel Option Screens.doc 13 of 21 PJW 12/15/08


Fire Suppression System Cont…
Refer to figure 3 for the following items.

(See module 2.25.5 for reference to the following inputs.)


Cable Trough Alarm
Enables monitoring of input signal for cable trough fire alarm. When selected, alarm
“FireSystem – Cable Trough Alarm” will be triggered when the input goes low.

Operator Cab Alarm


Enables monitoring of input signal for Operator Cab fire alarm. When selected,
alarm “FireSystem – Operator Cab Alarm” will be triggered when the input goes low.

Converter Cabinet Alarm


Enables monitoring of input signal for Converter Cabinet fire alarm. When selected,
alarm “FireSystem – Conv Cab Alarm” will be triggered when the input goes low.

RH Room Alarm
Enables monitoring of input signal for right hand room fire alarm. When selected,
alarm “FireSystem – Right Hand Room Alarm” will be triggered when the input goes
low.

Bypass switch
Enables monitoring of input signal system bypass switch. When selected, alarm
“FireSystem – System Bypass” will be triggered when the input goes low.

Shutdown Activation
Enables monitoring of the shutdown signal from the fire system. When selected, the
machine will perform a 30s shutdown if the input goes low and the system is not
bypassed.

RPC Cabinet Suppression Activated


Enables monitoring of input signal for the RPC cabinet fire suppression system.
When selected, alarm “FireSystem – RPC Cab Suppression Active” will be triggered
when the input goes low.

Converter Cabinet Suppression Activated


Enables monitoring of input signal for the Converter cabinet fire suppression system.
When selected, alarm “FireSystem – Conv Cab Suppression Active” will be triggered
when the input goes low.

Lube Room Suppression Activated


Enables monitoring of input signal for the lube room fire suppression system. When
selected, alarm “FireSystem – Lube Room Suppression Active” will be triggered
when the input goes low.

_P&H Shovel Option Screens.doc 14 of 21 PJW 12/15/08


Filtration and Lubrication System

Figure 4
Lube system = 3-pump/3-zone
Enables software to operate and monitor a Lincoln lube system that has three pumps
and three zones. The zones that will be controlled and monitored are the upper,
lower, and open gear zones.

Lube system = 2-pump/4—zone


Enables software to operate and monitor a Lincoln lube system that has two pumps
and four zones. The zones that will be controlled and monitored are the upper grease,
lower grease, crowd open gear and swing open gear zones.
• Some 2 pump / 4 zone lubrication applications do not have Boom Point
Grease pressure & Saddle block pressure switches. For these applications
option bits have been added for the Boom Point Grease pressure & Saddle
block pressure to allow the system to operate properly if these are not
installed. When the 2 pump / 4 zone lubrication application is selected the
option bits are selected automatically, if they are not installed they must be
un-checked.

_P&H Shovel Option Screens.doc 15 of 21 PJW 12/15/08


Filtration and Lubrication System Cont…
Refer to figure 4 for the following items.

Normally open zone valves


When enabled, this allows for normally open zone valves. If the upper grease system
is required to be greased, then the grease pump operates but the lower grease zone
valve closes which allows grease to flow through the upper grease system. This
works vise versa when the lower system is being operated. This method also applies
to the open gear systems as well. The “Gearcase Filtration System” is a prerequisite
to this option.

Normal zone valves


System operates normal. The “Gearcase Filtration System” is a prerequisite to this
option.

Milltronics Lube Level Sensor Option


Enables the Profibus drop for the Milltronics level controller and lube level
indications on the GUI. This system contains two ultra-sonic sensors which are used
to detect the level of the lube tanks.

Legacy Shovel – Large Lube Tank


For C500 model, this option enables the monitoring software for the right and left
large lube tank level sensors.

Farval
Enables software to operate and monitor a Farval lube system that has three pumps
and three zones. The zones that will be controlled and monitored are the upper,
lower, and open gear zones. Option “Lube System = 3-Pump / 3-Zone” must be
selected in order for this to work properly. The difference between the Farval and
Lincoln system is the valve assembly. The Farval system uses a reversing valve
assembly as oppose to the venting valve assembly used for the Lincoln system.

Gearcase Filtration System


Enables the filtration system software for the hoist, crowd, and swing motions.

Crowd Lube Pump 7 GPM


When enabled, the flow scales and flow setpoints are set to correspond to 7 GPM for
the crowd lube filtration system. This option is only available when option Gearcase
Filtration System is enabled. This is a prerequisite to “Gearcase Filtration System”.

Crowd Gear Case Low Level Detection


Enables level detection for the crowd gearcase only, the option bit ‘Fail-Safe Low
Level Detection’ state dictates if the sensor indicates low oil level when open or
closed.

_P&H Shovel Option Screens.doc 16 of 21 PJW 12/15/08


Filtration and Lubrication System Cont…
Refer to figure 4 for the following items.

Enhanced Swing Gearcase Filtration System


Enables the new swing gear case pump control program which circulates oil when the
swing brakes are set or for 2 hours when the shovel is off. This option can only be
utilized when the gear case filtration system is installed.

Filtration Level
Selection for the installed filter size. When selected, the filter differential pressure is
monitored.

Transmission Lube Pump(s): Crowd


Enables software that will operate and monitor the crowd transmission lube pump(s).

Transmission lube pump(s): Swing


Enables software that will operate and monitor the swing transmission lube pumps.

Hoist Lube Pump Flow Switches


Enables software for monitoring the hoist lube pump flow switches.

Swing Lube Pump Flow Switches


Enables software for monitoring the swing lube pump flow switches.

Hoist Lube Pump Variable Freq Drive


Enables the software that operates and monitors the variable frequency drive hoist
lube pump system. The drive is typically located inside the field drive cabinet.

Hoist Gearcase Low Level Detection Only


Enables the detection and fault indication of low oil level in the hoist gearcase with
the use of a low oil level sensor.

Gearcase Low Level Detection


Enables the detection and fault indication of low oil level in all gearcases and
transmissions with the use of a low oil level sensor.

Fail-Safe Low Level Detection 1 = OK


When enabled, all of the oil level low sensor input signals change to the fail-safe
configuration. Fail-safe meaning that the sensor indicates low oil when the signal
goes low instead of high.

_P&H Shovel Option Screens.doc 17 of 21 PJW 12/15/08


RPC Option Screen

Figure 5
Special RPC
2-300F,4-450S
Enables the proper operation of the RPC system when the machine is equipped
with two 300 KVAR fixed banks, four 450 KVAR switched banks and no ½
banks. This configuration was first applied on KH0023.
2-1/2,1-FullS
Enables the proper operation of the RPC system when the machine is equipped
with two ½ banks switched and one full bank switched. This configuration was
first applied on ES2370 and ES2371.

Special Bank Rotation


Force Bank Type 2
Enables the reversal of ½ bank and bank 3. Also reverses bank 1 and bank 2.
This was first used on ES39365 and ES39380 MKII

Compensation Level Adjustment


This can be used on 2800XPB, 4100C and 4100C BOSS models to correct the
compensation curve to account for a change in the RPC current transducer ratios.

_P&H Shovel Option Screens.doc 18 of 21 PJW 12/15/08


RPC Monitoring System

Figure 6

Bank Configuration
Enter the bank sizes for the banks present. See the electrical schematics for further
details.
Complete Test
Triggers complete automatic test of the RPC system following the shovel start in run
mode.
Partial Test
Test for conducting branches in the RPC following a shovel start in run mode.
Test Trigger Time and Day

_P&H Shovel Option Screens.doc 19 of 21 PJW 12/15/08


Tests will be conducted when the shovel is started in run mode at the top of the hour
configured on the selected day of week. If daily tests are selected then only the
trigger hour is applicable.

Drive Model Selection

_P&H Shovel Option Screens.doc 20 of 21 PJW 12/15/08


Boom Limits Offset Calibration

Figure 8

Zero Offset
Resolver offset from the physical limit. Used to trigger the zero speed region to the
motion exceeding the limit. Based in resolver counts of the motion limited (i.e. hoist
limit zero offset in hoist resolver counts). This parameter is modifiable but do NOT
set it lower then default, only increase the value if collisions are occurring.

Warning Offset
Resolver offset from the zero speed limit. Used to trigger the slow down region to
the motion entering the limit. Based in resolver counts of the motion limited. This
parameter is modifiable but do NOT set it lower then default, only increase the value
if the motion does not stop in time for the zero speed command.

Absolute Limit
Resolver counts identifying the position of a physical limit (i.e. boom, sheaves, etc.).

Zero Limit
Resolver counts identifying the start of the zero speed region.

Warning Limit
Resolver counts identifying the start of the slow down region.