The ambient condition may be taken to be 100 kPa and 25°C
1. Refrigerant-134a enters the compressor of a refrigerator as saturated vapor at 140
kPa at a rate of 0.3 m3/min and leaves at 1 MPa. The isentropic efficiency of the compressor is 78 percent. The refrigerant enters the throttling valve as a saturated liquid. Determine (a) the power input to the compressor, (b) the rate of heat removal from the refrigerated space, (c) the COP, (d) exergy destroyed and (e) the second law efficiency. Saturation data at 140 kPa are as follows: T sat = -18.77°C, vg=0.14014 m3/kg, hf=27.08 kJ/kg, hg=239.16 kJ/kg, sf=0.11087 kJ/kg.K and sg=0.94456 kJ/kg.K [112.7 kW, 282.2 kW, 2.5, 64.1 kW, 43.11%]
2. A commercial refrigerator with refrigerant-134a as the working fluid is used to keep
the refrigerated space at -30°C by rejecting its waste heat to cooling water that enters the condenser at 18°C at a rate of 0.25 kg/s and leaves at 26°C. The refrigerant enters the condenser at 1.2 MPa and 60°C and leaves at 40°C. The inlet state of the compressor is 80 kPa and -20°C and the compressor is estimated to gain a net heat of 450 W from the surroundings. Determine (a) the mass flow rate of the refrigerant, (b) the quality of the refrigerant at the evaporator inlet, (c) the refrigeration load (d) the COP of the refrigerator, (e) the temperature of the cold region assuming no irreversibilities in the evaporator and (f) the second law efficiency of the cycle. [0.046 kg/s, 0.441, 6.07 kW, 3.32, -30.5°C, 75.98%]
3. R134a enters the adiabatic compressor of a refrigerator as superheated vapor at
0.14 MPa and -10°C at a rate of 0.12 kg/s, and it leaves at 0.7 MPa and 50°C. The refrigerant is cooled in the condenser to 25°C, and it is throttled to 0.15 MPa. Show the cycle on a P-h diagram with respect to saturation lines, and determine (a) the rate of heat removal from the refrigerated space and the power input to the compressor, (b) isentropic efficiency of the compressor, (c) COP of the refrigerator, (d) temperature of the refrigerated space assuming that there are no irreversibilities and (e) exergy destroyed. [19.2 kW, 5.052 kW, 82.7%, 3.8, -18.385°C, 1.78 kW]