You are on page 1of 31

List of drawings Prepared: Damlin K.

 Generated: 2020-08-03


Checked: Pietilä T.
Approved: Pietilä T.

Location Title Document Document number Pages Revision Remark


=Automation Layout Automation Layout List of drawings 4JFI000037P0042 1 - Final Design
=Automation Layout Automation Layout E3 Drawings 4JFI000037P0039 10 A Final Design
=Automation Layout Automation Layout Cable list 4JFI000037P0040 2 A Final Design
=Automation Layout Automation Layout Cable connection list 4JFI000037P0041 18 A Final Design

Bantayan 25MW Power Plant =Automation Layout


ABB OY
IAEN 2xW16V32 + 3xW6L32 4JFI000033P0042, Rev.-
CAD-051237 Page 1 / 1
1 2 3 4 5 6 7 8

A A

B B
Customer : Bantayan 25MW Power Plant
Wärtsilä Power Plant
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

Order : CAD-051237

C C
Plant : 2xW16V32 + 3xW6L32
Philippines

Equipment : Automation layout

D Title : D

E E

Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Title page Ref.Des.
F F
A FINAL DESIGN 2020-08-03 Damlin K. Checked 2020-08-03 Pietila T. DCC EAA
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Title page Resp. dept. IAEN Rev. ind. A Language en
Bantayan 25MW Power Plant Sheet A01
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 No.sheets 10
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Index Note Description Date Author Changed sheets

A A FINAL DESIGN Updated according to redpen 2020-08-03 Damlin K. A01-A03, A09 A

B B
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

C C

D D

E E

Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Revision history Ref.Des.
F F
A FINAL DESIGN 2020-08-03 Damlin K. Checked 2020-08-03 Pietila T. DCC EBH
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Revision history Resp. dept. IAEN Rev. ind. A Language en
Bantayan 25MW Power Plant Sheet A02
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet A03
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Sheet n.sh. Description 1 Description 2 Rev. Revision note Sheet n.sh. Description 1 Description 2 Rev. Revision note

A A01 A03 Title page Title page A FINAL DESIGN A

A03 A09 List of contents A01 - A15 A FINAL DESIGN

A02 Revision history A FINAL DESIGN

A09 A10 CFR901 / Control room A FINAL DESIGN

A10 A11 CFA901

A11 A12 CFA902


B B
A12 A13 CFC011-051

A13 A14 MV Switchgear

A14 A15 Reactive load sharing bus


We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

A15 Active load sharing bus

C C

D D

E E

Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. List of contents Ref.Des.
F F
A FINAL DESIGN 2020-08-03 Damlin K. Checked 2020-08-03 Pietila T. DCC EAB
Print: 2020-08-03

Approved 2020-08-03 Pietila T. List of contents Resp. dept. IAEN Rev. ind. A Language en
Bantayan 25MW Power Plant Sheet A03
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet A09
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 9 10 11 12

CAT5e FTP 100 Mbit/s *


SC FO 1000 Mbit/s**
A =CR =GPS Profibus *** A
Control room GPS antenna cable #
-CWC901 -CWC902 -CWC921 -CWP901 LC FO 1000 Mbit/s ##
-Antenna S7-400 CPU synch cable ###
Dream report + Data cable ~
Operator Operator
Archiving
station 1 station 2
station Report printer
RJ45
* #
Thin Client Desktop Thin Client Desktop Thin Client Desktop
RJ45 RJ45 RJ45
RJ45 RJ45 RJ45

* * *

B B

=CFR901
Server rack

-59 200
C C

ANTENNA
GPS
Receiver
RJ45
*
-CWT901
-59 015

-59 016

-59 018
-59 019
-59 017
D -59 010 D
-59 011 -59 009

-CWS904 -CNS901 -CNS902 ## *


* * * * * * ## * *
GB2 GB1 23 1 2 3 4 5 6 7 8 9 10 11 12 15 27 28 23 1 10
LENOVO SR530
Historian server Switch Switch
FS-124E FS-124E
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

21 22 25 26 28 27 21 25 26 22
* * ## ## ## ## * ## ## *
-59 008 -59 014
-59 012 -59 021
-59 013
E E
-CWS901 * * * * -CWS902
GB2 GB1 GB1 GB2
LENOVO SR530 LENOVO SR530
Physical server Physical server
-59 005

-59 006
-59 004

-59 007
F -CNF901 ## ## ## ## -CNF902 F
DMZ1 DMZ2 DMZ2 DMZ1

Firewall Firewall
FG-140E-POE FG-140E-POE

29 HA WAN1 WAN2 HA 29 WAN1 WAN2


* * * -59 020 * * *
-59 003
-59 001

-59 002

G G
=CFA901-A12:P2

=CFA901-A13:P3
74

74
/A10.B2

/A10.B4

H Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Circuit diagram Ref.Des. H
A FINAL DESIGN 2020-08-03 Damlin K. Checked 2020-08-03 Pietila T. CFR901 / Control room DCC EFS
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Resp. dept. IAEN Rev. ind. A Language en


Bantayan 25MW Power Plant Sheet A09
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet A10
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8

FROM CNF901 FROM CNF902 TO MV SWITCHGEAR CAT5e FTP 100 Mbit/s *


A SC FO 1000 Mbit/s**
A

/A09.H4

/A09.H6

/A13.A5
Profibus ***
GPS antenna cable #
LC FO 1000 Mbit/s ##

=CFR901-CNF901:29

=CFR901-CNF902:29

+BAO901-AA1:P6
74

74

74
S7-400 CPU synch cable ###
Data cable ~

=CFA901 =BFA901
Common control panel LV switchgear PMU
B B
-59 031
-A1 * -A1.1 * -A11
LAN 1 VAMP 96
Firewall Connector CPU
EDR-G902 RJ45
X1
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

WAN RJ45 X2:P1

* *
-59 001

-59 002

-59 039

-59 040
-59 050
-59 030
-59 032
=NGA901 =NGA902
Weather station 1 Weather station 2
C -A12 * * * * * * * * -A13 * * * * * * * * -A14 * * * * * * * * C
P1 P2 P3 P4 P5 P6 P7 P8 P1 P2 P3 P4 P5 P6 P7 P8 P1 P2 P3 P4 P5 P6 P7 P8

EDS-208A EDS-208A EDS-208A HMT331 HMT331

RJ45 RJ54
-59 033

-59 035

-59 037
-A7 * -A8 * -A9 *
WAN WAN LAN

Firewall Firewall Firewall


EDR-G902 EDR-G902 EDR-G902
LAN LAN WAN
D D
* * *

-59 041
-59 036
-59 038

-59 042
-59 043
-59 034

-59 107 #11431


/A11.E1 TO FUEL TREATMENT HOUSE CFA902
-A15 * =CFA902-A1:P8
**
P1 P2 P3 P4 P5 P6 P7 P8

EDS-208A-M-SC

-A2 * * * -A3 * * *
P3 P4 P5 P3 P4 P5
E E
EDS-405A -59 106 EDS-405A -59 105
* * * * #11295
P1 P2 P1 P2
=CFC051-A1.:P2 /A12.D12 TO CFC051

-59 100 CFC011


/A12.D1 TO CFC011
=CFC011-A1.:P1

Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Circuit diagram Ref.Des.
F F
Checked 2020-08-03 Pietila T. CFA901 DCC EFS
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Resp. dept. IAEN Rev. ind. A Language en


Bantayan 25MW Power Plant Sheet A10
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet A11
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

CAT5e FTP 100 Mbit/s *


A SC FO 1000 Mbit/s**
A
Profibus ***
GPS antenna cable #
LC FO 1000 Mbit/s ##
S7-400 CPU synch cable ###
Data cable ~

=BJL901 =BJL902 =BJC901


=BJM901
HFO feeder LFO feeder LFO unloading pump unit
Feeder/booster unit
B B
-A1 -A1 -A1 -A1
FLOW
METER EDS-208A-M-SC EDS-205A-M-SC EDS-205A-M-SC
Q001
RS485 1 2 3 4 5 6 7 8 1 2 3 4 5 1 2 3 4 5
~ ** ** **
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

=CFA902
Fuel treatment house RIO panel -59 303
-59 305
-59 307

-52 400
=BJF901 =BJF904 =BJD901
C HFO transfer pump unit 1 HFO transfer pump unit 2 HFO unloading pump unit C
-A11 -A3 -A4 ** -A5 ** -A6 **
FO FO FO -A1 -A1 -A1
ET 200M MB3170 IMC-21A- IMC-21A- IMC-21A-
RJ45:1 RJ45:2
M-SC M-SC M-SC
EDS-205A-M-SC EDS-205A-M-SC EDS-205A-M-SC
X2P1 * P1:RS485 RJ45 RJ45 RJ45
* ~ 1 2 3 4 5 1 2 3 4 5 1 2 3 4 5
** ** **

-59 309
-59 311
-59 313
-A7 ** -A8 ** -A9 **
D D
FO FO FO
IMC-21A- IMC-21A- IMC-21A-
M-SC M-SC M-SC
-59 302 RJ45 RJ45 RJ45
-59 304
-59 306
-59 308
-59 301
-59 300

-59 299 -59 310


-59 312
-A1 * * * * * * *
P1 P2 P3 P4 P5 P6 P7

EDS-208A-M-SC
E -59 107
E
/A10.D7
=CFA901-A15:P8 ** P8
#11431 -A2 * * * * * * *
P1 P2 P3 P4 P5 P6 P7

EDS-208A-M-SC
P8

Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Circuit diagram Ref.Des.
F F
Checked 2020-08-03 Pietila T. CFA902 DCC EFS
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Resp. dept. IAEN Rev. ind. A Language en


Bantayan 25MW Power Plant Sheet A11
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet A12
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8 9 10 11 12

CAT5e FTP 100 Mbit/s *


SC FO 1000 Mbit/s**
A Profibus *** A
GPS antenna cable #
LC FO 1000 Mbit/s ##
S7-400 CPU synch cable ###
Data cable ~

=CFC011 =BLP011 =CFC021 =BLP021 =CFC031 =BLP031 =CFC041 =BLP041 =CFC051 =BLP051
Genset control panel Radiators Genset control panel Radiators Genset control panel Radiators Genset control panel Radiators Genset control panel Radiators

-A11 -B10 -F01 -A11 -B10 -F01 -A11 -B10 -F01 -A11 -B10 -F01 -A11 -B10 -F01

CPU VAMP260 P3G32 CPU VAMP260 P3G32 CPU VAMP260 P3G32 CPU VAMP260 P3G32 CPU VAMP260 P3G32
B FC FC FC FC FC B
X1 X1 X1 X1 X1
X2.P1 X5 X5 RJ45 X2.P1 X5 X5 RJ45 X2.P1 X5 X5 RJ45 X2.P1 X5 X5 RJ45 X2.P1 X5 X5 RJ45
* * * * * * * * * * * * * * * * * * * *
-11 111

-12 111

-13 111

-14 111

-15 111
-11 112
-11 113

-11 115

-12 112
-12 113

-12 115

-13 112
-13 113

-13 115

-14 112
-14 113

-14 115

-15 112
-15 113

-15 115
-11 114

-12 114

-13 114

-14 114

-15 114
-11 118 -11 116 =BLQ011 -12 118 -12 116 =BLQ021 -13 118 -13 116 =BLQ031 -14 118 -14 116 =BLQ041 -15 118 -15 116 =BLQ051
-A3. ** * * * * * * -A2. * * -A3. ** * * * * * * -A2. * * -A3. ** * * * * * * -A2. * * -A3. ** * * * * * * -A2. * * -A3. ** * * * * * * -A2. * *
P7 P8 P1 P2 P3 P4 P5 P6 LAN RJ45 P7 P8 P1 P2 P3 P4 P5 P6 LAN RJ45 P7 P8 P1 P2 P3 P4 P5 P6 LAN RJ45 P7 P8 P1 P2 P3 P4 P5 P6 LAN RJ45 P7 P8 P1 P2 P3 P4 P5 P6 LAN RJ45

C Firewall Firewall Firewall Firewall Firewall C


EDR-G902 FC EDR-G902 FC EDR-G902 FC EDR-G902 FC EDR-G902 FC
EDS-208A-M-SC EDS-208A-M-SC EDS-208A-M-SC EDS-208A-M-SC EDS-208A-M-SC
WAN WAN WAN WAN WAN

* * * * *
-11 117 Inlet ventilation -12 117 Inlet ventilation -13 117 Inlet ventilation -14 117 Inlet ventilation -15 117 Inlet ventilation

-A1. * * * -A1. * * * -A1. * * * -A1. * * * -A1. * * *


P3 P4 P5 P3 P4 P5 P3 P4 P5 P3 P4 P5 P3 P4 P5

EDS-405A EDS-405A EDS-405A EDS-405A EDS-405A


CFC011 -59 100 * * -59 101 * * -59 102 * * -59 103 * * -59 104 * * -59 105 #11295
/A10.F7 =CFA901-A2:P1
P1 P2 P1 P2 P1 P2 P1 P2 P1 P2
=CFA901-A3:P2
/A10.E7

D D

=BJA011 =PCC011 =BJA021 =PCC021 =BJA031 =PCC031 =BJA041 =PCC041 =BJA051 =PCC051
Local control panel Local control panel Local control panel Local control panel Local control panel
-A11 -A3 -A1 -A11 -A3 -A1 -A11 -A3 -A1 -A11 -A3 -A1 -A11 -A3 -A1
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

MB3170 FLOW MB3170 FLOW MB3170 FLOW MB3170 FLOW MB3170 FLOW
ET 200M ET 200M ET 200M ET 200M ET 200M
RJ45:1 RJ45:2 METER RJ45:1 RJ45:2 METER RJ45:1 RJ45:2 METER RJ45:1 RJ45:2 METER RJ45:1 RJ45:2 METER
X2.P1 * P1:RS485 RS485 X2.P1 * P1:RS485 RS485 X2.P1 * P1:RS485 RS485 X2.P1 * P1:RS485 RS485 X2.P1 * P1:RS485 RS485

* ~ ~ * ~ ~ * ~ ~ * ~ ~ * ~ ~

-11 400 -13 400 -14 400 -15 400


E -12 400 E
-11 119
-11 120

-12 119
-12 120

-13 119
-13 120

-14 119
-14 120

-15 119
-15 120
-11 121 -12 121 -13 121 -14 121 -15 121
-A1 * * * * * * * -A1 * * * * * * * -A1 * * * * * * * -A1 * * * * * * * -A1 * * * * * * *
1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7 1 2 3 4 5 6 7

EDS-208A-M-SC EDS-208A-M-SC EDS-208A-M-SC EDS-208A-M-SC EDS-208A-M-SC


** 8 ** 8 ** 8 ** 8 ** 8

F F
=CFE011 =CFE021 =CFE031 =CFE041 =CFE051
AVR Panel AVR Panel AVR Panel AVR Panel AVR Panel

-A1 -A1 -A1 -A1 -A1

EDS-205A * EDS-205A * EDS-205A * EDS-205A * EDS-205A *


2 2 2 2 2
1 3 4 5 1 3 4 5 1 3 4 5 1 3 4 5 1 3 4 5
* * * * * * * * * * * * * * * * * * * *
-11 122

-11 123

-12 122

-12 123

-13 122

-13 123

-14 122

-14 123

-15 122

-15 123
-11 124

-12 124

-13 124

-14 124

-15 124
G G

=SCA011 =SCA021 =SCA031 =SCA041 =SCA051


Engine Engine Engine Engine Engine

-A11 * -G10 * * -A11 * -G10 * * -A11 * -G10 * * -A11 * -G10 * * -A11 * -G10 * *
X2P1 RJ45 RJ45 X2P1 RJ45 RJ45 X2P1 RJ45 RJ45 X2P1 RJ45 RJ45 X2P1 RJ45 RJ45

ET 200M AVR -UNIC ET 200M AVR -UNIC ET 200M AVR -UNIC ET 200M AVR -UNIC ET 200M AVR -UNIC

H Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Circuit diagram Ref.Des. H
Checked 2020-08-03 Pietila T. CFC011-051 DCC EFS
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Resp. dept. IAEN Rev. ind. A Language en


Bantayan 25MW Power Plant Sheet A12
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet A13
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8

/A10.B6
CAT5e FTP 100 Mbit/s *
A SC FO 1000 Mbit/s**
A

=CFA901-A14:P3
74
Profibus ***
GPS antenna cable #
LC FO 1000 Mbit/s ##
S7-400 CPU synch cable ###
Data cable ~

-59 040
B B

=MV
MV Switchgear
We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

+BAE011 +BAA901 +BAE021 +BAO901 +BAE031 +BAE041 +BAO902 +BAE051


-BCF1 -PGM1 -BCF1 -PGM1 -BCF1 -PGM1

P3U30 VAMP260 VAMP230 VAMP260 VAMP230 VAMP260

C RJ45 RJ45 RJ45 RJ45 RJ45 RJ45 C


* * * * * *

-AA1 -AA1
P1 P2 P3 P4 P5 P6 P7 P8 P1 P2 P3 P4 P5 P6 P7 P8

EDS308 EDS308
D D

E E

Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Circuit diagram Ref.Des.
F F
Checked 2020-08-03 Pietila T. MV Switchgear DCC EFS
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Resp. dept. IAEN Rev. ind. A Language en


Bantayan 25MW Power Plant Sheet A13
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet A14
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Note! Note!
Cable should be twisted pair, shielded. Cable should be twisted pair, shielded.
A A
UNITROL 1020 - max bus length 500m Cable shield to be grounded at the end only.

UNITROL 1020: On first and last UNITROL, UNITROL 1000 - max bus length 250m
place jumper over X1300 terminals,
remove jumpers from X1300 terminals on UNITROL 1000-15: On first and last
UNITROL not located at the end. UNITROL, place jumper over J2 terminals.
(See Unitrol 1020 Manual)

B B

=CFE011 =CFE021 =CFE031 =CFE041 =CFE051


AVR panel AVR panel AVR panel AVR panel AVR panel

-G10_ -G10_ -G10_ -G10_ -G10_


We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

Auto voltage regulator Auto voltage regulator Auto voltage regulator Auto voltage regulator Auto voltage regulator

Communication interface Communication interface Communication interface Communication interface Communication interface

RS-485 RS-485 RS-485 RS-485 RS-485


57.6 kbps 57.6 kbps 57.6 kbps 57.6 kbps 57.6 kbps
shield - + shield - + shield - + shield - + shield - +

C 72 74 70 72 74 70 72 74 70 72 74 70 72 74 70 C

-11 191 -12 191 -13 191 -14 191


-11 191 -12 191 -13 191 -14 191

D D

E E

Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Circuit diagram Ref.Des.
F F
Checked 2020-08-03 Pietila T. Reactive load sharing bus DCC EFS
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Resp. dept. IAEN Rev. ind. A Language en


Bantayan 25MW Power Plant Sheet A14
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet A15
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

Note!
Use termination resistor 120 ohm
A in both end of the CAN bus. A

Cable shield to be grounded


at one end only.

B B
-11 192 -12 192 -13 192 -14 192
-11 192 -12 192 -13 192 -14 192

=SCA011 =SCA021 =SCA031 =SCA041 =SCA051


We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

-MCM-1 -MCM-1 -PE -MCM-1 -MCM-1 -PE -MCM-1 -MCM-1 -PE -MCM-1 -MCM-1 -PE -PE -MCM-1 -MCM-1
X34-5 X34-6 - X34-5 X34-6 - X34-5 X34-6 - X34-5 X34-6 - - X34-5 X34-6

120 ohm 120 ohm

C C

D D

E E

Rev. Revision note Date Name Project CAD-051237 Prepared 2020-06-10 Pietilä T. Title Automation layout Doc. kind. Circuit diagram Ref.Des.
F F
Checked 2020-08-03 Pietila T. Active load sharing bus DCC EFS
Print: 2020-08-03

Approved 2020-08-03 Pietila T. Resp. dept. IAEN Rev. ind. A Language en


Bantayan 25MW Power Plant Sheet A15
2xW16V32 + 3xW6L32 ABB Oy Doc. no. 4JFI000037P0039 n. sheet
1 2 3 4 5 6 7 8
CABLE LIST Bantayan 25MW Power Plant
CAD-051237

© Copyright 2020 ABB, We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

Cable From To
Name Type Spare Cores Function Location Function Location Remark
-11 111 Cat5e FTP 0 =CFC011 =CFC011 Preinstalled
-11 112 Cat5e FTP 0 =CFC011 =CFC011 Preinstalled
-11 113 Cat5e FTP 0 =CFC011 =CFC011 Preinstalled
-11 114 Cat5e FTP 0 =BLP011 =CFC011
-11 115 Cat5e FTP 0 =BLQ011 =CFC011
-11 116 Cat5e FTP 0 =CFC011 =CFC011 Preinstalled
-11 117 Cat5e FTP 0 =CFC011 =CFC011 Preinstalled
-11 118 1x50/125 SC 0 =BJA011 =CFC011
-11 119 Cat5e FTP 0 =BJA011 =BJA011 Preinstalled
-11 120 Cat5e FTP 0 =BJA011 =BJA011 Preinstalled
-11 121 Cat5e FTP 0 =BJA011 =CFE011
-11 122 Cat5e FTP 0 =CFE011 =CFE011 Preinstalled
-11 123 Cat5e FTP 0 =CFE011 =CFE011 Preinstalled
-11 124 Cat5e FTP 0 =CFE011 =SCA011
-11 191 4x2x0.5mm² 6 =CFE011 =CFE021
-11 192 CAN Bus cable 1x2x0.5mm² 0 =SCA011 =SCA021
-11 400 4x2x0.5mm² 7 =BJA011 =PCC011
-12 111 Cat5e FTP 0 =CFC021 =CFC021 Preinstalled
-12 112 Cat5e FTP 0 =CFC021 =CFC021 Preinstalled
-12 113 Cat5e FTP 0 =CFC021 =CFC021 Preinstalled
-12 114 Cat5e FTP 0 =BLP021 =CFC021
-12 115 Cat5e FTP 0 =BLQ021 =CFC021
-12 116 Cat5e FTP 0 =CFC021 =CFC021 Preinstalled
-12 117 Cat5e FTP 0 =CFC021 =CFC021 Preinstalled
-12 118 1x50/125 SC 0 =BJA021 =CFC021
-12 119 Cat5e FTP 0 =BJA021 =BJA021 Preinstalled
-12 120 Cat5e FTP 0 =BJA021 =BJA021 Preinstalled
-12 121 Cat5e FTP 0 =BJA021 =CFE021
-12 122 Cat5e FTP 0 =CFE021 =CFE021 Preinstalled
-12 123 Cat5e FTP 0 =CFE021 =CFE021 Preinstalled
-12 124 Cat5e FTP 0 =CFE021 =SCA021
-12 191 4x2x0.5mm² 6 =CFE021 =CFE031
-12 192 CAN Bus cable 1x2x0.5mm² 0 =SCA021 =SCA031
-12 400 4x2x0.5mm² 7 =BJA021 =PCC021
-13 111 Cat5e FTP 0 =CFC031 =CFC031 Preinstalled
-13 112 Cat5e FTP 0 =CFC031 =CFC031 Preinstalled
-13 113 Cat5e FTP 0 =CFC031 =CFC031 Preinstalled
-13 114 Cat5e FTP 0 =BLP031 =CFC031
-13 115 Cat5e FTP 0 =BLQ031 =CFC031
-13 116 Cat5e FTP 0 =CFC031 =CFC031 Preinstalled
-13 117 Cat5e FTP 0 =CFC031 =CFC031 Preinstalled
-13 118 1x50/125 SC 0 =BJA031 =CFC031
-13 119 Cat5e FTP 0 =BJA031 =BJA031 Preinstalled
-13 120 Cat5e FTP 0 =BJA031 =BJA031 Preinstalled
-13 121 Cat5e FTP 0 =BJA031 =CFE031
-13 122 Cat5e FTP 0 =CFE031 =CFE031 Preinstalled
-13 123 Cat5e FTP 0 =CFE031 =CFE031 Preinstalled
-13 124 Cat5e FTP 0 =CFE031 =SCA031
-13 191 4x2x0.5mm² 6 =CFE031 =CFE041
-13 192 CAN Bus cable 1x2x0.5mm² 0 =SCA031 =SCA041
-13 400 4x2x0.5mm² 7 =BJA031 =PCC031
-14 111 Cat5e FTP 0 =CFC041 =CFC041 Preinstalled
-14 112 Cat5e FTP 0 =CFC041 =CFC041 Preinstalled
-14 113 Cat5e FTP 0 =CFC041 =CFC041 Preinstalled
-14 114 Cat5e FTP 0 =BLP041 =CFC041
-14 115 Cat5e FTP 0 =BLQ041 =CFC041
-14 116 Cat5e FTP 0 =CFC041 =CFC041 Preinstalled
-14 117 Cat5e FTP 0 =CFC041 =CFC041 Preinstalled
-14 118 1x50/125 SC 0 =BJA041 =CFC041
-14 119 Cat5e FTP 0 =BJA041 =BJA041 Preinstalled
-14 120 Cat5e FTP 0 =BJA041 =BJA041 Preinstalled
-14 121 Cat5e FTP 0 =BJA041 =CFE041
-14 122 Cat5e FTP 0 =CFE041 =CFE041 Preinstalled
-14 123 Cat5e FTP 0 =CFE041 =CFE041 Preinstalled
-14 124 Cat5e FTP 0 =CFE041 =SCA041
-14 191 4x2x0.5mm² 6 =CFE041 =CFE051
-14 192 CAN Bus cable 1x2x0.5mm² 0 =SCA041 =SCA051
-14 400 4x2x0.5mm² 7 =BJA041 =PCC041
-15 111 Cat5e FTP 0 =CFC051 =CFC051 Preinstalled
-15 112 Cat5e FTP 0 =CFC051 =CFC051 Preinstalled
-15 113 Cat5e FTP 0 =CFC051 =CFC051 Preinstalled
-15 114 Cat5e FTP 0 =BLP051 =CFC051
-15 115 Cat5e FTP 0 =BLQ051 =CFC051
-15 116 Cat5e FTP 0 =CFC051 =CFC051 Preinstalled
-15 117 Cat5e FTP 0 =CFC051 =CFC051 Preinstalled
-15 118 1x50/125 SC 0 =BJA051 =CFC051
-15 119 Cat5e FTP 0 =BJA051 =BJA051 Preinstalled
-15 120 Cat5e FTP 0 =BJA051 =BJA051 Preinstalled
-15 121 Cat5e FTP 0 =BJA051 =CFE051
-15 122 Cat5e FTP 0 =CFE051 =CFE051 Preinstalled
-15 123 Cat5e FTP 0 =CFE051 =CFE051 Preinstalled
-15 124 Cat5e FTP 0 =CFE051 =SCA051
-15 400 4x2x0.5mm² 7 =BJA051 =PCC051
-52 400 4x2x0.5mm² 7 =BJM901 =CFA902
-59 001 Cat5e FTP 0 =CFA901 =CFR901
-59 002 Cat5e FTP 0 =CFA901 =CFR901
-59 003 Cat5e FTP 0 =CFR901 =CFR901 Preinstalled

ABB Oy Automation Layout_2020-08-03_CableList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 1 of 2
CABLE LIST Bantayan 25MW Power Plant
CAD-051237

© Copyright 2020 ABB, We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden.

Cable From To
Name Type Spare Cores Function Location Function Location Remark
-59 004 F/O Duplex MultiMode LC-LC, XXm 1 =CFR901 =CFR901 Preinstalled

-59 005 F/O Duplex MultiMode LC-LC, XXm 1 =CFR901 =CFR901 Preinstalled

-59 006 F/O Duplex MultiMode LC-LC, XXm 1 =CFR901 =CFR901 Preinstalled

-59 007 F/O Duplex MultiMode LC-LC, XXm 1 =CFR901 =CFR901 Preinstalled

-59 008 F/O Duplex MultiMode LC-LC, XXm 1 =CFR901 =CFR901

-59 009 F/O Duplex MultiMode LC-LC, XXm 1 =CFR901 =CFR901

-59 010 Cat5e FTP 0 =CFR901 =CFR901 Preinstalled


-59 011 Cat5e FTP 0 =CFR901 =CFR901 Preinstalled
-59 012 Cat5e FTP 0 =CFR901 =CFR901 Preinstalled
-59 013 Cat5e FTP 0 =CFR901 =CFR901 Preinstalled
-59 014 Cat5e FTP 0 =CFR901 =CFR901 Preinstalled
-59 015 Cat5e FTP 0 =CFR901 =CR
-59 016 Cat5e FTP 0 =CFR901 =CFR901 Preinstalled
-59 017 Cat5e FTP 0 =CFR901 =CR
-59 018 Cat5e FTP 0 =CFR901 =CR
-59 019 Cat5e FTP 0 =CFR901 =CR
-59 020 Cat5e FTP 0 =CFR901 =CFR901
-59 021 Cat5e FTP 0 =CFR901 =CFR901 Preinstalled
-59 030 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 031 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 032 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 033 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 034 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 035 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 036 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 037 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 038 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 039 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 040 Cat5e FTP 0 +BAO901 =CFA901
-59 041 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 042 Cat5e FTP 0 =CFA901 =NGA901
-59 043 Cat5e FTP 0 =CFA901 =NGA902
-59 050 Cat5e FTP 0 =BFA901 =CFA901
-59 100 Cat5e FTP 0 =CFA901 =CFC011
-59 101 Cat5e FTP 0 =CFC011 =CFC021
-59 102 Cat5e FTP 0 =CFC021 =CFC031
-59 103 Cat5e FTP 0 =CFC031 =CFC041
-59 104 Cat5e FTP 0 =CFC041 =CFC051
-59 105 Cat5e FTP 0 =CFA901 =CFC051
-59 106 Cat5e FTP 0 =CFA901 =CFA901 Preinstalled
-59 107 1x50/125 SC 0 =CFA901 =CFA902
-59 200 RG58 0 =CFR901 =GPS
-59 299 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 300 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 301 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 302 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 303 1x50/125 SC 0 =BJL901 =CFA902
-59 304 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 305 1x50/125 SC 0 =BJL902 =CFA902
-59 306 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 307 1x50/125 SC 0 =BJC901 =CFA902
-59 308 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 309 1x50/125 SC 0 =BJF901 =CFA902
-59 310 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 311 1x50/125 SC 0 =BJF904 =CFA902
-59 312 Cat5e FTP 0 =CFA902 =CFA902 Preinstalled
-59 313 1x50/125 SC 0 =BJD901 =CFA902

ABB Oy Automation Layout_2020-08-03_CableList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 2 of 2
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -11 111 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC011-A11 CABLE
To =CFC011-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B2 #11138 =CFC011 -A11 X2.P1 GY =CFC011 -A3. P1 /A12.C2

NAME / NUMBER: -11 112 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC011-A3. CABLE
To =CFC011-B10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C2 #11139 =CFC011 -A3. P2 GY =CFC011 -B10 X5 /A12.B2

NAME / NUMBER: -11 113 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC011-A3. CABLE
To =CFC011-F01
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C2 #11139 =CFC011 -A3. P3 GY =CFC011 -F01 X5 /A12.B3

NAME / NUMBER: -11 114 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLP011- CABLE To =CFC011-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B3 #11131 =BLP011 - RJ45 GY =CFC011 -A3. P4 /A12.C2

NAME / NUMBER: -11 115 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLQ011- CABLE To =CFC011-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C3 #11117 =BLQ011 - RJ45 GY =CFC011 -A3. P5 /A12.C2

NAME / NUMBER: -11 116 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC011-A2. CABLE To =CFC011-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C3 #11220 =CFC011 -A2. LAN GY =CFC011 -A3. P6 /A12.C2

NAME / NUMBER: -11 117 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC011-A1. CABLE
To =CFC011-A2.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C2 74 =CFC011 -A1. P3 GY =CFC011 -A2. WAN /A12.C3

NAME / NUMBER: -11 118 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJA011-A1 CABLE To =CFC011-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.F2 #11086 =BJA011 -A1 8 OG =CFC011 -A3. P7 /A12.C2

NAME / NUMBER: -11 119 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA011-A1 CABLE To =BJA011-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E2 #11132 =BJA011 -A1 1 GY =BJA011 -A11 X2.P1 /A12.E2

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 1 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -11 120 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA011-A1 CABLE
To =BJA011-A3
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E2 #11133 =BJA011 -A1 2 GY =BJA011 -A3 RJ45:1 /A12.E2

NAME / NUMBER: -11 121 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA011-A1 CABLE
To =CFE011-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E2 #11136 =BJA011 -A1 7 GY =CFE011 -A1 2 /A12.G2

NAME / NUMBER: -11 122 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE011-A1 CABLE To =CFE011-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G2 #11136 =CFE011 -A1 1 GY =CFE011 -A11 X2P1 /A12.G2

NAME / NUMBER: -11 123 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE011-A1 CABLE To =CFE011-G10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G2 #11144 =CFE011 -A1 3 GY =CFE011 -G10 RJ45 /A12.G2

NAME / NUMBER: -11 124 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE011-A1 CABLE To =SCA011-UNIC
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G2 #11116 =CFE011 -A1 4 GY =SCA011 -UNIC RJ45 /A12.G3

NAME / NUMBER: -11 191 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 6


From =CFE011-G10_ CABLE To =CFE021-G10_
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A14.C1 =CFE011 -G10_ 74 1a =CFE021 -G10_ 74 /A14.C3

/A14.C2 =CFE011 -G10_ 70 1b =CFE021 -G10_ 70 /A14.C3

2a
2b
3a

3b
4a

4b

NAME / NUMBER: -11 192 CABLE TYPE: CAN Bus cable 1x2x0.5mm² SPARE CORES: 0
From =SCA011-MCM-1 CABLE To =SCA021-MCM-1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A15.C1 =SCA011 -MCM-1 X34-5 E 1a =SCA021 -MCM-1 X34-5 E /A15.C2

/A15.C2 =SCA011 -MCM-1 X34-6 E 1b =SCA021 -MCM-1 X34-6 E /A15.C3

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 2 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -11 400 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 7


From =BJA011-A3 CABLE To =PCC011-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference
P1:RS4
/A12.E2 74 =BJA011 -A3 1a =PCC011 -A1 RS485 /A12.E3
85
1b
2a
2b
3a
3b
4a
4b

NAME / NUMBER: -12 111 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC021-A11 CABLE To =CFC021-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B4 #11299 =CFC021 -A11 X2.P1 GY =CFC021 -A3. P1 /A12.C4

NAME / NUMBER: -12 112 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC021-A3. CABLE To =CFC021-B10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C4 #11300 =CFC021 -A3. P2 GY =CFC021 -B10 X5 /A12.B4

NAME / NUMBER: -12 113 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC021-A3. CABLE To =CFC021-F01
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C4 #11300 =CFC021 -A3. P3 GY =CFC021 -F01 X5 /A12.B5

NAME / NUMBER: -12 114 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLP021- CABLE To =CFC021-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B5 #11301 =BLP021 - RJ45 GY =CFC021 -A3. P4 /A12.C4

NAME / NUMBER: -12 115 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLQ021- CABLE
To =CFC021-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C5 #11302 =BLQ021 - RJ45 GY =CFC021 -A3. P5 /A12.C4

NAME / NUMBER: -12 116 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC021-A2. CABLE To =CFC021-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C5 #11303 =CFC021 -A2. LAN GY =CFC021 -A3. P6 /A12.C4

NAME / NUMBER: -12 117 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC021-A1. CABLE To =CFC021-A2.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C4 74 =CFC021 -A1. P3 GY =CFC021 -A2. WAN /A12.C5

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 3 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -12 118 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJA021-A1 CABLE
To =CFC021-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.F4 #11298 =BJA021 -A1 8 OG =CFC021 -A3. P7 /A12.C4

NAME / NUMBER: -12 119 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA021-A1 CABLE
To =BJA021-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E4 #11308 =BJA021 -A1 1 GY =BJA021 -A11 X2.P1 /A12.E4

NAME / NUMBER: -12 120 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA021-A1 CABLE
To =BJA021-A3
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E4 #11309 =BJA021 -A1 2 GY =BJA021 -A3 RJ45:1 /A12.E4

NAME / NUMBER: -12 121 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA021-A1 CABLE To =CFE021-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E4 #11310 =BJA021 -A1 7 GY =CFE021 -A1 2 /A12.G5

NAME / NUMBER: -12 122 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE021-A1 CABLE To =CFE021-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G4 #11310 =CFE021 -A1 1 GY =CFE021 -A11 X2P1 /A12.G4

NAME / NUMBER: -12 123 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE021-A1 CABLE To =CFE021-G10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G4 #11311 =CFE021 -A1 3 GY =CFE021 -G10 RJ45 /A12.G4

NAME / NUMBER: -12 124 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE021-A1 CABLE To =SCA021-UNIC
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G4 #11316 =CFE021 -A1 4 GY =SCA021 -UNIC RJ45 /A12.G5

NAME / NUMBER: -12 191 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 6


From =CFE021-G10_ CABLE
To =CFE031-G10_
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A14.C3 =CFE021 -G10_ 74 1a =CFE031 -G10_ 74 /A14.C4

/A14.C3 =CFE021 -G10_ 70 1b =CFE031 -G10_ 70 /A14.C4

2a

2b
3a

3b
4a

4b

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 4 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -12 192 CABLE TYPE: CAN Bus cable 1x2x0.5mm² SPARE CORES: 0
From =SCA021-MCM-1 CABLE To =SCA031-MCM-1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A15.C2 =SCA021 -MCM-1 X34-5 E 1a =SCA031 -MCM-1 X34-5 E /A15.C4

/A15.C3 =SCA021 -MCM-1 X34-6 E 1b =SCA031 -MCM-1 X34-6 E /A15.C4

NAME / NUMBER: -12 400 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 7


From =BJA021-A3 CABLE To =PCC021-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference
P1:RS4
/A12.E4 74 =BJA021 -A3 1a =PCC021 -A1 RS485 /A12.E5
85
1b
2a
2b
3a
3b
4a
4b

NAME / NUMBER: -13 111 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC031-A11 CABLE To =CFC031-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B6 #11328 =CFC031 -A11 X2.P1 GY =CFC031 -A3. P1 /A12.C6

NAME / NUMBER: -13 112 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC031-A3. CABLE To =CFC031-B10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C6 #11329 =CFC031 -A3. P2 GY =CFC031 -B10 X5 /A12.B6

NAME / NUMBER: -13 113 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC031-A3. CABLE
To =CFC031-F01
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C6 #11329 =CFC031 -A3. P3 GY =CFC031 -F01 X5 /A12.B7

NAME / NUMBER: -13 114 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLP031- CABLE
To =CFC031-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B8 #11330 =BLP031 - RJ45 GY =CFC031 -A3. P4 /A12.C6

NAME / NUMBER: -13 115 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLQ031- CABLE To =CFC031-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C8 #11331 =BLQ031 - RJ45 GY =CFC031 -A3. P5 /A12.C7

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 5 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -13 116 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC031-A2. CABLE
To =CFC031-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C7 #11332 =CFC031 -A2. LAN GY =CFC031 -A3. P6 /A12.C7

NAME / NUMBER: -13 117 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC031-A1. CABLE
To =CFC031-A2.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C6 74 =CFC031 -A1. P3 GY =CFC031 -A2. WAN /A12.C7

NAME / NUMBER: -13 118 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJA031-A1 CABLE
To =CFC031-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.F6 #11327 =BJA031 -A1 8 OG =CFC031 -A3. P7 /A12.C6

NAME / NUMBER: -13 119 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA031-A1 CABLE To =BJA031-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E6 #11337 =BJA031 -A1 1 GY =BJA031 -A11 X2.P1 /A12.E6

NAME / NUMBER: -13 120 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA031-A1 CABLE To =BJA031-A3
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E6 #11338 =BJA031 -A1 2 GY =BJA031 -A3 RJ45:1 /A12.E6

NAME / NUMBER: -13 121 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA031-A1 CABLE To =CFE031-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E7 #11339 =BJA031 -A1 7 GY =CFE031 -A1 2 /A12.G7

NAME / NUMBER: -13 122 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE031-A1 CABLE To =CFE031-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G6 #11339 =CFE031 -A1 1 GY =CFE031 -A11 X2P1 /A12.G6

NAME / NUMBER: -13 123 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE031-A1 CABLE
To =CFE031-G10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G6 #11340 =CFE031 -A1 3 GY =CFE031 -G10 RJ45 /A12.G7

NAME / NUMBER: -13 124 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE031-A1 CABLE To =SCA031-UNIC
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G6 #11345 =CFE031 -A1 4 GY =SCA031 -UNIC RJ45 /A12.G8

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 6 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -13 191 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 6


From =CFE031-G10_ CABLE To =CFE041-G10_
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A14.C4 =CFE031 -G10_ 74 1a =CFE041 -G10_ 74 /A14.C5

/A14.C4 =CFE031 -G10_ 70 1b =CFE041 -G10_ 70 /A14.C5

2a
2b
3a
3b
4a
4b

NAME / NUMBER: -13 192 CABLE TYPE: CAN Bus cable 1x2x0.5mm² SPARE CORES: 0
From =SCA031-MCM-1 CABLE To =SCA041-MCM-1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A15.C4 =SCA031 -MCM-1 X34-5 E 1a =SCA041 -MCM-1 X34-5 E /A15.C5

/A15.C4 =SCA031 -MCM-1 X34-6 E 1b =SCA041 -MCM-1 X34-6 E /A15.C5

NAME / NUMBER: -13 400 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 7


From =BJA031-A3 CABLE To =PCC031-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference
P1:RS4
/A12.E7 74 =BJA031 -A3 1a =PCC031 -A1 RS485 /A12.E8
85
1b
2a
2b
3a
3b
4a
4b

NAME / NUMBER: -14 111 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC041-A11 CABLE To =CFC041-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B8 #11357 =CFC041 -A11 X2.P1 GY =CFC041 -A3. P1 /A12.C8

NAME / NUMBER: -14 112 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC041-A3. CABLE To =CFC041-B10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C8 #11358 =CFC041 -A3. P2 GY =CFC041 -B10 X5 /A12.B9

NAME / NUMBER: -14 113 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC041-A3. CABLE To =CFC041-F01
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C9 #11358 =CFC041 -A3. P3 GY =CFC041 -F01 X5 /A12.B9

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 7 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -14 114 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLP041- CABLE
To =CFC041-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B10 #11359 =BLP041 - RJ45 GY =CFC041 -A3. P4 /A12.C9

NAME / NUMBER: -14 115 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLQ041- CABLE
To =CFC041-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C10 #11360 =BLQ041 - RJ45 GY =CFC041 -A3. P5 /A12.C9

NAME / NUMBER: -14 116 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC041-A2. CABLE
To =CFC041-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C9 #11361 =CFC041 -A2. LAN GY =CFC041 -A3. P6 /A12.C9

NAME / NUMBER: -14 117 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC041-A1. CABLE To =CFC041-A2.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C8 74 =CFC041 -A1. P3 GY =CFC041 -A2. WAN /A12.C9

NAME / NUMBER: -14 118 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJA041-A1 CABLE To =CFC041-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.F8 #11356 =BJA041 -A1 8 OG =CFC041 -A3. P7 /A12.C8

NAME / NUMBER: -14 119 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA041-A1 CABLE To =BJA041-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E8 #11366 =BJA041 -A1 1 GY =BJA041 -A11 X2.P1 /A12.E8

NAME / NUMBER: -14 120 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA041-A1 CABLE To =BJA041-A3
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E8 #11367 =BJA041 -A1 2 GY =BJA041 -A3 RJ45:1 /A12.E9

NAME / NUMBER: -14 121 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA041-A1 CABLE
To =CFE041-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E9 #11368 =BJA041 -A1 7 GY =CFE041 -A1 2 /A12.G9

NAME / NUMBER: -14 122 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE041-A1 CABLE To =CFE041-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G8 #11368 =CFE041 -A1 1 GY =CFE041 -A11 X2P1 /A12.G8

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 8 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -14 123 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE041-A1 CABLE To =CFE041-G10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G8 #11369 =CFE041 -A1 3 GY =CFE041 -G10 RJ45 /A12.G9

NAME / NUMBER: -14 124 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE041-A1 CABLE To =SCA041-UNIC
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G8 #11374 =CFE041 -A1 4 GY =SCA041 -UNIC RJ45 /A12.G10

NAME / NUMBER: -14 191 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 6


From =CFE041-G10_ CABLE To =CFE051-G10_
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A14.C5 =CFE041 -G10_ 74 1a =CFE051 -G10_ 74 /A14.C7

/A14.C5 =CFE041 -G10_ 70 1b =CFE051 -G10_ 70 /A14.C7

2a
2b
3a
3b
4a
4b

NAME / NUMBER: -14 192 CABLE TYPE: CAN Bus cable 1x2x0.5mm² SPARE CORES: 0
From =SCA041-MCM-1 CABLE To =SCA051-MCM-1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A15.C5 =SCA041 -MCM-1 X34-5 E 1a =SCA051 -MCM-1 X34-5 E /A15.C6

/A15.C5 =SCA041 -MCM-1 X34-6 E 1b =SCA051 -MCM-1 X34-6 E /A15.C7

NAME / NUMBER: -14 400 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 7


From =BJA041-A3 CABLE To =PCC041-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference
P1:RS4
/A12.E9 74 =BJA041 -A3 1a =PCC041 -A1 RS485 /A12.E10
85
1b
2a

2b
3a

3b
4a

4b

NAME / NUMBER: -15 111 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC051-A11 CABLE To =CFC051-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B10 #11386 =CFC051 -A11 X2.P1 GY =CFC051 -A3. P1 /A12.C11

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 9 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -15 112 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC051-A3. CABLE
To =CFC051-B10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C11 #11387 =CFC051 -A3. P2 GY =CFC051 -B10 X5 /A12.B11

NAME / NUMBER: -15 113 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC051-A3. CABLE
To =CFC051-F01
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C11 #11387 =CFC051 -A3. P3 GY =CFC051 -F01 X5 /A12.B11

NAME / NUMBER: -15 114 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLP051- CABLE
To =CFC051-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.B12 #11388 =BLP051 - RJ45 GY =CFC051 -A3. P4 /A12.C11

NAME / NUMBER: -15 115 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BLQ051- CABLE To =CFC051-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C12 #11389 =BLQ051 - RJ45 GY =CFC051 -A3. P5 /A12.C11

NAME / NUMBER: -15 116 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC051-A2. CABLE To =CFC051-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C11 #11390 =CFC051 -A2. LAN GY =CFC051 -A3. P6 /A12.C11

NAME / NUMBER: -15 117 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC051-A1. CABLE To =CFC051-A2.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.C10 74 =CFC051 -A1. P3 GY =CFC051 -A2. WAN /A12.C11

NAME / NUMBER: -15 118 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJA051-A1 CABLE To =CFC051-A3.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.F10 #11385 =BJA051 -A1 8 OG =CFC051 -A3. P7 /A12.C10

NAME / NUMBER: -15 119 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA051-A1 CABLE
To =BJA051-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E10 #11395 =BJA051 -A1 1 GY =BJA051 -A11 X2.P1 /A12.E10

NAME / NUMBER: -15 120 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA051-A1 CABLE To =BJA051-A3
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E10 #11396 =BJA051 -A1 2 GY =BJA051 -A3 RJ45:1 /A12.E11

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 10 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -15 121 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BJA051-A1 CABLE To =CFE051-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.E11 #11397 =BJA051 -A1 7 GY =CFE051 -A1 2 /A12.G11

NAME / NUMBER: -15 122 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE051-A1 CABLE To =CFE051-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G10 #11397 =CFE051 -A1 1 GY =CFE051 -A11 X2P1 /A12.G10

NAME / NUMBER: -15 123 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE051-A1 CABLE To =CFE051-G10
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G11 #11398 =CFE051 -A1 3 GY =CFE051 -G10 RJ45 /A12.G11

NAME / NUMBER: -15 124 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFE051-A1 CABLE To =SCA051-UNIC
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.G11 #11403 =CFE051 -A1 4 GY =SCA051 -UNIC RJ45 /A12.G12

NAME / NUMBER: -15 400 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 7


From =BJA051-A3 CABLE To =PCC051-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference
P1:RS4
/A12.E11 74 =BJA051 -A3 1a =PCC051 -A1 RS485 /A12.E12
85
1b
2a
2b
3a
3b
4a
4b

NAME / NUMBER: -52 400 CABLE TYPE: 4x2x0.5mm² SPARE CORES: 7


From =BJM901-A1 CABLE
To =CFA902-A3
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference
P1:RS4
/A11.B3 74 =BJM901 -A1 RS485 1a =CFA902 -A3 /A11.C2
85
1b
2a
2b
3a
3b
4a
4b

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 11 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -59 001 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A12 CABLE
To =CFR901-CNF901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.C2 74 =CFA901 -A12 P2 GY =CFR901 -CNF901 29 /A09.F4

NAME / NUMBER: -59 002 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A13 CABLE
To =CFR901-CNF902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.C4 74 =CFA901 -A13 P3 GY =CFR901 -CNF902 29 /A09.F6

NAME / NUMBER: -59 003 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNF901 CABLE
To =CFR901-CNF902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.F4 74 =CFR901 -CNF901 HA GY =CFR901 -CNF902 HA /A09.F6

NAME / NUMBER: -59 004 CABLE TYPE: F/O Duplex MultiMode LC-LC, XXm SPARE CORES: 1
From =CFR901-CNF901 CABLE
To =CFR901-CNS901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.F4 74 =CFR901 -CNF901 DMZ1 1 =CFR901 -CNS901 25 /A09.E4

NAME / NUMBER: -59 005 CABLE TYPE: F/O Duplex MultiMode LC-LC, XXm SPARE CORES: 1
From =CFR901-CNF901 CABLE
To =CFR901-CNS902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.F4 74 =CFR901 -CNF901 DMZ2 1 =CFR901 -CNS902 25 /A09.E6

NAME / NUMBER: -59 006 CABLE TYPE: F/O Duplex MultiMode LC-LC, XXm SPARE CORES: 1
From =CFR901-CNF902 CABLE To =CFR901-CNS901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.F6 74 =CFR901 -CNF902 DMZ2 1 =CFR901 -CNS901 26 /A09.E4

NAME / NUMBER: -59 007 CABLE TYPE: F/O Duplex MultiMode LC-LC, XXm SPARE CORES: 1
From =CFR901-CNF902 CABLE To =CFR901-CNS902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.F6 74 =CFR901 -CNF902 DMZ1 1 =CFR901 -CNS902 26 /A09.E6

NAME / NUMBER: -59 008 CABLE TYPE: F/O Duplex MultiMode LC-LC, XXm SPARE CORES: 1
From =CFR901-CNS901 CABLE To =CFR901-CNS902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

1
/A09.E5 74 =CFR901 -CNS901 28 2 =CFR901 -CNS902 27 /A09.E6

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 12 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -59 009 CABLE TYPE: F/O Duplex MultiMode LC-LC, XXm SPARE CORES: 1
From =CFR901-CNS901 CABLE
To =CFR901-CNS902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.D5 74 =CFR901 -CNS901 27 1 =CFR901 -CNS902 28 /A09.D6

NAME / NUMBER: -59 010 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS902 CABLE
To =CFR901-CWS904
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.D6 #11288 =CFR901 -CNS902 23 GY =CFR901 -CWS904 GB2 /A09.D3

NAME / NUMBER: -59 011 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS901 CABLE
To =CFR901-CWS904
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.D3 74 =CFR901 -CNS901 23 GY =CFR901 -CWS904 GB1 /A09.D3

NAME / NUMBER: -59 012 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS901 CABLE To =CFR901-CWS901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.E3 74 =CFR901 -CNS901 21 GY =CFR901 -CWS901 GB1 /A09.E3

NAME / NUMBER: -59 013 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS902 CABLE To =CFR901-CWS901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.E6 74 =CFR901 -CNS902 21 GY =CFR901 -CWS901 GB2 /A09.E3

NAME / NUMBER: -59 014 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS902 CABLE To =CFR901-CWS902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.E7 74 =CFR901 -CNS902 22 GY =CFR901 -CWS902 GB2 /A09.E8

NAME / NUMBER: -59 015 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS901 CABLE
To =CR-CWC901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.D4 74 =CFR901 -CNS901 1 GY =CR -CWC901 RJ45 /A09.B4

NAME / NUMBER: -59 016 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS901 CABLE
To =CFR901-CWT901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.D4 74 =CFR901 -CNS901 9 GY =CFR901 -CWT901 RJ45 /A09.C8

NAME / NUMBER: -59 017 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS901 CABLE To =CR-CWC921
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.D4 74 =CFR901 -CNS901 2 GY =CR -CWC921 RJ45 /A09.B5

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 13 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -59 018 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS902 CABLE
To =CR-CWC902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.D6 74 =CFR901 -CNS902 1 GY =CR -CWC902 RJ45 /A09.B4

NAME / NUMBER: -59 019 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS902 CABLE
To =CR-CWP901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.D6 74 =CFR901 -CNS902 10 GY =CR -CWP901 RJ45 /A09.B6

NAME / NUMBER: -59 020 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNF901 CABLE
To =CFR901-CNF902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.F5 #11271 =CFR901 -CNF901 WAN2 GY =CFR901 -CNF902 WAN2 /A09.F7

NAME / NUMBER: -59 021 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFR901-CNS901 CABLE To =CFR901-CWS902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A09.E4 74 =CFR901 -CNS901 22 GY =CFR901 -CWS902 GB1 /A09.E8

NAME / NUMBER: -59 030 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A1 CABLE To =CFA901-A12
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.B2 74 =CFA901 -A1 WAN GY =CFA901 -A12 P4 /A10.C2

NAME / NUMBER: -59 031 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A1 CABLE
To =CFA901-A1.1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.B2 74 =CFA901 -A1 LAN GY =CFA901 -A1.1 1 /A10.B3

NAME / NUMBER: -59 032 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A12 CABLE To =CFA901-A13
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.C2 74 =CFA901 -A12 P5 GY =CFA901 -A13 P4 /A10.C4

NAME / NUMBER: -59 033 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A12 CABLE
To =CFA901-A7
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.C2 74 =CFA901 -A12 P1 GY =CFA901 -A7 WAN /A10.D1

NAME / NUMBER: -59 034 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A2 CABLE To =CFA901-A7
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E1 74 =CFA901 -A2 P3 GY =CFA901 -A7 LAN /A10.D1

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 14 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -59 035 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A13 CABLE
To =CFA901-A8
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.C4 74 =CFA901 -A13 P1 GY =CFA901 -A8 WAN /A10.D4

NAME / NUMBER: -59 036 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A3 CABLE
To =CFA901-A8
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E4 74 =CFA901 -A3 P3 GY =CFA901 -A8 LAN /A10.D4

NAME / NUMBER: -59 037 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A14 CABLE
To =CFA901-A9
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.C5 74 =CFA901 -A14 P1 GY =CFA901 -A9 LAN /A10.D5

NAME / NUMBER: -59 038 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A3 CABLE To =CFA901-A9
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E4 74 =CFA901 -A3 P4 GY =CFA901 -A9 WAN /A10.D5

NAME / NUMBER: -59 039 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A11 CABLE To =CFA901-A14
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.B5 74 =CFA901 -A11 X2:P1 GY =CFA901 -A14 P2 /A10.C5

NAME / NUMBER: -59 040 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From +BAO901-AA1 CABLE To =CFA901-A14
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A13.D5 74 +BAO901 -AA1 P6 GY =CFA901 -A14 P3 /A10.C6

NAME / NUMBER: -59 041 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A14 CABLE
To =CFA901-A15
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.C6 74 =CFA901 -A14 P8 GY =CFA901 -A15 P1 /A10.E5

NAME / NUMBER: -59 042 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A15 CABLE
To =NGA901
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E5 74 =CFA901 -A15 P2 GY =NGA901 RJ45 /A10.C7

NAME / NUMBER: -59 043 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A15 CABLE To =NGA902
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E6 74 =CFA901 -A15 P3 GY =NGA902 RJ54 /A10.C8

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 15 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -59 050 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =BFA901 CABLE
To =CFA901-A14
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.B7 74 =BFA901 RJ45 GY =CFA901 -A14 P4 /A10.C6

NAME / NUMBER: -59 100 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A2 CABLE
To =CFC011-A1.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E1 CFC011 =CFA901 -A2 P1 GY =CFC011 -A1. P1 /A12.D2

NAME / NUMBER: -59 101 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC011-A1. CABLE
To =CFC021-A1.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.D2 CFC011 =CFC011 -A1. P2 GY =CFC021 -A1. P1 /A12.D4

NAME / NUMBER: -59 102 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC021-A1. CABLE To =CFC031-A1.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.D5 CFC011 =CFC021 -A1. P2 GY =CFC031 -A1. P1 /A12.D6

NAME / NUMBER: -59 103 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC031-A1. CABLE To =CFC041-A1.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.D7 CFC011 =CFC031 -A1. P2 GY =CFC041 -A1. P1 /A12.D8

NAME / NUMBER: -59 104 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFC041-A1. CABLE To =CFC051-A1.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A12.D9 CFC011 =CFC041 -A1. P2 GY =CFC051 -A1. P1 /A12.D10

NAME / NUMBER: -59 105 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A3 CABLE To =CFC051-A1.
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E4 #11295 =CFA901 -A3 P2 GY =CFC051 -A1. P2 /A12.D11

NAME / NUMBER: -59 106 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA901-A2 CABLE
To =CFA901-A3
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E2 #11175 =CFA901 -A2 P2 GY =CFA901 -A3 P1 /A10.E3

NAME / NUMBER: -59 107 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =CFA901-A15 CABLE To =CFA902-A1
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A10.E6 #11431 =CFA901 -A15 P8 OG =CFA902 -A1 P8 /A11.E2

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 16 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -59 200 CABLE TYPE: RG58 SPARE CORES: 0


From =CFR901-CWT901 CABLE
To =GPS-Antenna
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference
ANTEN
/A09.C8 #11151 =CFR901 -CWT901 1 =GPS -Antenna /A09.B8
NA

NAME / NUMBER: -59 299 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A1 CABLE
To =CFA902-A2
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E2 74 =CFA902 -A1 P7 GY =CFA902 -A2 P1 /A11.E3

NAME / NUMBER: -59 300 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A1 CABLE
To =CFA902-A11
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E2 74 =CFA902 -A1 P1 GY =CFA902 -A11 X2P1 /A11.C2

NAME / NUMBER: -59 301 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A1 CABLE To =CFA902-A3
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E2 74 =CFA902 -A1 P2 GY =CFA902 -A3 RJ45:1 /A11.C2

NAME / NUMBER: -59 302 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A1 CABLE To =CFA902-A4
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E2 74 =CFA902 -A1 P3 GY =CFA902 -A4 RJ45 /A11.C3

NAME / NUMBER: -59 303 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJL901-A1 CABLE
To =CFA902-A4
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.B5 74 =BJL901 -A1 3 OG =CFA902 -A4 FO /A11.C3

NAME / NUMBER: -59 304 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A1 CABLE To =CFA902-A5
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E2 74 =CFA902 -A1 P4 GY =CFA902 -A5 RJ45 /A11.C4

NAME / NUMBER: -59 305 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJL902-A1 CABLE To =CFA902-A5
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.B6 74 =BJL902 -A1 3 OG =CFA902 -A5 FO /A11.C4

NAME / NUMBER: -59 306 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A1 CABLE To =CFA902-A6
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E2 74 =CFA902 -A1 P5 GY =CFA902 -A6 RJ45 /A11.C4

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 17 of 18
CABLE CORE CONNECTION LIST Bantayan 25MW Power Plant
CAD-051237

We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third © Copyright 2020 ABB
parties without express authority is strictly forbidden.

NAME / NUMBER: -59 307 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJC901-A1 CABLE
To =CFA902-A6
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.B7 74 =BJC901 -A1 3 OG =CFA902 -A6 FO /A11.C4

NAME / NUMBER: -59 308 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A1 CABLE
To =CFA902-A7
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E2 74 =CFA902 -A1 P6 GY =CFA902 -A7 RJ45 /A11.D3

NAME / NUMBER: -59 309 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJF901-A1 CABLE
To =CFA902-A7
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.D5 74 =BJF901 -A1 3 OG =CFA902 -A7 FO /A11.D3

NAME / NUMBER: -59 310 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A2 CABLE To =CFA902-A8
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E3 74 =CFA902 -A2 P2 GY =CFA902 -A8 RJ45 /A11.D4

NAME / NUMBER: -59 311 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJF904-A1 CABLE To =CFA902-A8
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.D6 74 =BJF904 -A1 3 OG =CFA902 -A8 FO /A11.D4

NAME / NUMBER: -59 312 CABLE TYPE: Cat5e FTP SPARE CORES: 0
From =CFA902-A2 CABLE To =CFA902-A9
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.E3 74 =CFA902 -A2 P3 GY =CFA902 -A9 RJ45 /A11.D4

NAME / NUMBER: -59 313 CABLE TYPE: 1x50/125 SC SPARE CORES: 0


From =BJD901-A1 CABLE
To =CFA902-A9
Document CORE Document
reference
Signal Function Location Device Pin Side Function Location Device Pin Side reference

/A11.D7 74 =BJD901 -A1 3 OG =CFA902 -A9 FO /A11.D4

ABB Oy Automation Layout_2020-08-03_CableConnectionList.xlsm


Prepared / Pietilä T. Date: 2020-08-03 Rev. ind.: A
Approved / Pietila T. Sheet 18 of 18