Press on “UP” and “DOWN” button at the same time until you see “C.LO” on the
screen
A lowest pressure (i.e. 0 psi) must be applied to the system pressure sensing line
(depressurize); the readout of the reference sensing line gauge must be entered
into the screen.
1|Page
How to Calibrate Pressure Transducer 2014
For Jockey IPD+ Controller
A maximum pressure must be applied to the system pressure sensing line
(pressurize); the readout of the reference sensing line gauge must be entered in
the screen.
Press on “POWER” button until the power light becomes green to exit the
configuration mode.
The pressure calibration procedure can be repeated if the pressure readouts are
satisfied.
2|Page