‫ﻣﺤﺎﺳﺒﻪ ﻇﺮﻓﯿﺖ ‪ Air Dryer‬ﻣﺮﺑﻮط ﺑﻪ ﺧﻂ ‪:Instrument Air‬‬

‫ﺑﺮاي ﻣﺤﺎﺳﺒﻪ ﻣﺼﺮف ﻫﻮاي ﺳﯿﺴﺘﻢ ﭘﻨﻮﻣﺎﺗﯿﮏ و ﺟﺮﯾﺎن ﻫﻮاي ﻣﻮرد ﻧﯿﺎز ﻣﯽ ﺗﻮان از ﻗﺎﻧﻮن ﺑﻮﯾﻞ‪-‬ﭼﺎرﻟﺰ )‪ (pV=nRT‬اﺳﺘﻔﺎده ﮐﺮد‪ .‬در‬
‫ﻣﻮرد ﯾﮏ ﺳﯿﻠﻨﺪر ﺗﮏ ﻋﻤﻞ‪ ،‬ﺑﺎ ﻣﺸﺨﺺ ﺷﺪن ﺣﺠﻢ ﺳﯿﻠﻨﺪر‪ ،‬ﻃﻮل ﻟﻮﻟﻪ‪ ،‬ﻓﺮﮐﺎﻧﺲ ﻋﻤﻠﮑﺮد ﻓﻠﻮرﯾﺖ ﻣﻄﺎﺑﻖ ﻓﺮﻣﻮل زﯾﺮ ﻣﺤﺎﺳﺒﻪ ﻣﯽ ﮔﺮدد‪.‬‬

‫] ‪A: pressure receiving area in actuator of valve [mm2‬‬


‫] ‪a: air pipe inner section area [mm2‬‬
‫)‪p: air supply pressure [MPa] (1MPa = 10bar‬‬
‫]‪N: operation frequency [cycle/min‬‬
‫]‪L: cylinder stroke in actuator of valve [mm‬‬
‫]‪l: air piping length [mm‬‬
‫]‪t: total stroke time [s‬‬
‫)‪T: temperature [K] (K = °C + 273.15‬‬

‫در اﯾﻦ ﭘﺮوژه وﻟﻮ ﻫﺎي ﭘﻨﻮﻣﺎﺗﯿﮏ ‪ on-off‬ﺑﻪ ﺷﺮح زﯾﺮ اﺳﺖ‪.‬‬

‫‪ (3+1) .۱‬وﻟﻮ ﭘﻨﻮﻣﺎﺗﯿﮏ ﺗﺰرﯾﻖ ﻫﯿﭙﻮﮐﻠﺮﯾﺖ ﺑﻪ ﺳﺎﮐﺸﻦ ﭘﻤﭗ ﻫﺎ )‪(UV-41-031A~D‬‬

‫‪ 1 .۲‬وﻟﻮ ﭘﻨﻮﻣﺎﺗﯿﮏ در ﺧﻂ ﻫﻮاي ﻓﺸﺮده ‪(UV-41-031) Plant‬‬

‫ﻫﻤﭽﻨﯿﻦ وﻟﻮ ﻫﺎي ﭘﻨﻮﻣﺎﺗﯿﮏ ﮐﻨﺘﺮﻟﯽ ﺑﻪ ﺷﺮح زﯾﺮ اﺳﺖ‪:‬‬

‫‪ .۱‬وﻟﻮ ﻫﺎي ﮐﻨﺘﺮﻟﯽ ﺑﺎ ﺳﺎﯾﺰ ﺣﺪودا ‪ 2‬ﺗﺎ ‪ 3‬اﯾﻨﭻ ﺑﺮاي واﺣﺪ ‪electro chlorination‬‬

‫‪ 5 .۲‬وﻟﻮ ﮐﻨﺘﺮﻟﯽ ﺑﺎ ﻓﺮض ﻋﻤﻠﮑﺮد ﭘﻨﻮﻣﺎﺗﯿﮏ ﻣﻄﺎﺑﻖ ﺗﮓ ﻫﺎي ‪PV-41- ،PV-41-061A ،FV-41-013 ،PV-41-014‬‬

‫‪PV-41-031 ،061B‬‬

‫ﺑﺎ ﺗﻮﺟﻪ ﺑﻪ ﻣﺪرك ‪(MAN-NPT-0002-FD-IN-JSP-0011) Job Specification for Control Valves‬‬ ‫‪-‬‬

‫" ‪the stroking time shall be lower than 5 seconds for valve up to 4” and 1 second per inch‬‬
‫‪ "diameter for bigger ones‬زﻣﺎن اﺳﺘﺮوك ﺑﺮاﺳﺎس اﯾﻦ ﻣﺪرك در ﺟﺪول زﯾﺮ در ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﺪه اﺳﺖ‪.‬‬
‫ﺗﻤﺎم اﺣﺠﺎم ﺟﺪول زﯾﺮ ﺑﻪ ﺻﻮرت ﻣﻘﻄﻌﯽ از ‪ Air reciever‬ﺗﺎﻣﯿﻦ ﻣﯽ ﮔﺮدد و ﻟﻮد ﮐﻤﺘﺮي ﺑﻪ ﮐﻤﭙﺮﺳﻮر وارد ﻣﯽ ﮔﺮدد‪.‬‬ ‫‪-‬‬

‫ﻓﻠﻮرﯾﺖ ﻫﻮاي ﻓﺸﺮده ﻣﻮرد ﻧﯿﺎز وﻟﻮ ﻫﺎي ﮐﻨﺘﺮﻟﯽ از ﮐﺎﺗﺎﻟﻮگ وﻟﻮ ﻫﺎي ﭘﯿﺸﻨﻬﺎد ﻓﻨﯽ ﺷﺮﮐﺖ ‪ Control Fluid‬و ﻓﺮﻣﻮل ﺑﺎﻻ‬ ‫‪-‬‬

‫ﺑﻪ ﺻﻮرت زﯾﺮ ﻣﺤﺎﺳﺒﻪ ﺷﺪ‪.‬‬

‫ﻫﻤﺰﻣﺎﻧﯽ ﺑﺎز ﺷﺪن ‪ 2‬ﻋﺪد وﻟﻮ ‪ PV-41-061A‬و ‪ PV-41-014‬در ﻧﻈﺮ ﮔﺮﻓﺘﻪ ﺷﺪه اﺳﺖ‪.‬‬ ‫‪-‬‬

‫‪Each Actuator‬‬
‫‪Stroke time‬‬ ‫‪Air flowrate‬‬
‫‪valve Tag‬‬ ‫‪Qty‬‬ ‫‪volume‬‬
‫)‪(sec‬‬ ‫)‪(Nm3/hr‬‬
‫)‪(NL‬‬
‫‪PV-41-061A/B, outfall‬‬ ‫‪2‬‬ ‫‪400‬‬ ‫‪36‬‬ ‫‪40‬‬
‫‪PV-41-014, relief, 0 to‬‬
‫‪1‬‬ ‫‪222‬‬ ‫‪2‬‬ ‫‪40‬‬
‫‪10 % opening‬‬
‫‪PV-41-014, relief, 10%‬‬
‫‪1‬‬ ‫‪222‬‬ ‫‪100‬‬ ‫‪8‬‬
‫‪to 80 % opening‬‬
‫‪on-off valve chlorine‬‬
‫‪4‬‬ ‫‪5‬‬ ‫‪5‬‬ ‫‪1‬‬
‫‪injection+ plant air‬‬
‫‪control valve EC unit‬‬ ‫‪6‬‬ ‫‪35‬‬ ‫‪5‬‬ ‫‪1‬‬
‫‪FV-41-013, free zone‬‬ ‫‪1‬‬ ‫‪300‬‬ ‫‪24‬‬ ‫‪45‬‬
‫‪PV-41-031, in plant air‬‬
‫‪1‬‬ ‫‪35‬‬ ‫‪5‬‬ ‫‪25‬‬
‫‪line‬‬
‫‪TOTAL‬‬
‫‪80‬‬
‫ﺑﺎ ھﻤﺰﻣﺎﻧﯽ ‪ ۲‬آﯾﺘﻢ ﺑﺎﻻ‬

‫ﻇﺮﻓﯿﺖ ‪ Air dryer‬ﺑﺎ در ﻧﻈﺮ ﮔﺮﻓﺘﻦ ﻫﻤﺰﻣﺎﻧﯽ ﺑﺎز ﺷﺪن ‪ 2‬ﻋﺪد وﻟﻮ ‪ PV-41-061A‬و ‪ PV-41-014‬در ﺟﺪول ﺑﺎﻻ ﺑﻪ ﺻﻮرت ‪80‬‬
‫‪ NM3/hr‬ﺑﺪﺳﺖ ﻣﯽ آﯾﺪ‪.‬‬