Professional Documents
Culture Documents
SUBMITTAL
AL MURJAN MEDICAL CENTRE JEDDAH
Project
Consultant
www.SFFECO.com
T E C H N IC A L
SUBMITTAL
AL MURJAN MEDICAL CENTRE JEDDAH Project
IN D E X
1. MATERIAL REFERENCE LIST
2. MATERIAL TECHNICAL SUBMITTAL
3. MATERIAL CERTIFICATES
www.SFFECO.com
\
TECHNICAL
SUBMITTAL
Manual
www.SFFECO.com
Submittal No. : 1010 Date : 10.10.2021
Rev. No. : 00
MATERIAL
LIST
SL.
Item Description Make Part# / Model Approval C.O.O
NO
DOUBLE INTER LOCK PREACTION DELUGE VALVE & ACCESSORIES
PRE-ASSEMBLED, DOUBLE INTERLOCK
PREACTION FIRE PROTECTION
UL & FM
1. SYSTEMS, E/E ACTUATION; C/W TYCO DV-5A NETHERLANDS
APPROVED
GALVANISED TRIM, PRESSURE SWITCH
& SOLENOID VALVE
UL & FM
2. WATER MOTOR ALARM GONG TYCO WMA-1 CHINA
APPROVED
UL & FM
3. AIR MAINTENANCE DEVICE TYCO AMD-1 U.S.A
APPROVED
TECHNICAL
SUBMITTAL
MATERIAL TECHNICAL
SUBMITTAL
www.SFFECO.com
Worldwide
www.tyco-fire.com
Contacts
1
1
3
2
7 5
5 3 1-1/2 AND 2 INCH
9 VALVES ONLY
6
3
7 1
4
8
6
4
9 7 5
6 AND 8 INCH
1 2
VALVES ONLY
FIGURE 1
DV-5 a VALVE ASSEMBLY AND REPLACEMENT PARTS
TABLE A
FLANGE DRILLING SPECIFICATIONS
TFP1466
Page 3 of 20
VALVE SYSTEM
WATERWAY AIR
DIAPHRAGM SUPPLY
SEAT
VALVE
WATERWAY ALARM PORT
DIAPHRAGM WATERFLOW
CHAMBER TO ALARM
DIAPHRAGM
CHAMBER
OPEN TO
AUTOMATIC ATMOSPHERE
DRAIN VALVE AUTOMATIC
OPEN TO DRAIN VALVE
DIAPHRAGM
DIAPHRAGM ATMOSPHERE CLOSED
RETRACTS
CHAMBER
OPENING
SUPPLY
VALVE
FROM
WATERWAY
UPSTREAM WATER SUPPLY
SIDE OF PRESSURE &
SHUT-OFF ALARM TEST
VALVE
WATER SUPPLY WATERFLOW FROM WATER SUPPLY
FIGURE 2A FIGURE 2B
SET CONDITION OPERATED CONDITION
VALVE
WATERWAY
DIAPHRAGM
SEAT
VALVE DIAPHRAGM
WATERWAY AUTOMATICALLY
SYSTEM FLEXES TO SYSTEM
DRAIN ITS SEATED DRAIN
DIAPHRAGM OPEN OPEN
CHAMBER POSTION
OPEN TO
ATMOSPHERE
DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
MAIN SIDE OF MAIN
DRAIN SHUT-OFF DRAIN
OPEN VALVE CLOSED
WATER SUPPLY SHUT OFF WATER SUPPLY SHUT OFF
FIGURE 2C FIGURE 2D
SYSTEM DRAIN CONDITION RESIDUAL DRAIN CONDITION
FIGURE 2
DV-5 a VALVE OPERATION, PREACTION SYSTEMS
TFP1466
Page 4 of 20
DIMENSIONS SHOWN The selection of Electric/Electric versus When the system pressure is greater
ARE APPLICABLE TO Electric/Electric is related to desired than 175 psi (12,1 bar), provision is to be
ALL END CONNECTION system air pressure and system made to replace the standard order 300
CONFIGURATIONS volume that affects water delivery time psi (20,7 bar) Water Pressure Gauges
AVAILABLE PER restraints. with separately ordered 600 psi (41,4
VALVE SIZE bar) Water Pressure Gauges.
NOTICE If the addition of an Alarm Control Valve
The DV-5 a Valves described herein is desired or required by the local AHJ,
10-3/16" must be installed and maintained in the Alarm Control Valve noted as Item
(260 mm) compliance with this document, as H in Figure 8 is to be a separately
well as with the applicable standards ordered electronically supervised nor-
of the NATIONAL FIRE PROTECTION mally open valve.
ASSOCIATION (NFPA), in addition to External trim connections are NPT
1-1/2 Inch (DN40) the standards of any other authorities threaded. EMEA trim is provided with
having jurisdiction. Failure to do so NPT x ISO 7-1 thread adapters.
may impair the performance of these
devices. Pressure Loss
See Graph A
10-3/16" The owner is responsible for main-
(260 mm) taining their fire protection system Actuation Options
and devices in proper operating con- See Electric/Electric Actuation sub-
dition. Contact the installing contrac- section for additional information.
tor or product manufacturer with any
2 Inch (DN50)
questions. Materials of
Technical Construction
13-3/4" Data Valve Body
Epoxy coated ductile iron per ASTM
(349 mm) A536-77, Grade 65-45-12
Approvals
UL/C-UL Listed Diaphragm Cover
FM Approved Epoxy coated ductile iron per ASTM
3 Inch (DN80) Listings and Approvals are based on A536-77, Grade 65-45-12
DV-5a being trimmed as described in Diaphragm
this technical data sheet. Polyester fabric reinforced, TEFLON
DV-5A Valve coated, EPDM rubber per ASTM D2000
Components for the 1 1/2 thru 8 in. Diaphragm Cover Fasteners
16-3/4" (DN40 thru DN200) DV-5a Valves are Aluminum zinc coated steel
(425 mm) shown in Figure 1. The DV-5a Valves
are for vertical installations. They are Common Hardware Trim
rated for use at a service pressures of • Common hardware pipe fittings are
20 to 300 psi (1,4 to 20,7 bar). galvanized or black as required and
4 Inch (DN100) are malleable per ASME B16.3.
The take-out dimensions are shown
in Figure 3, and flanged connections • Common hardware pipe nipples are
are available drilled per ANSI, ISO, galvanized or black as required and
AS, and JIS specifications (See Table are Schedule 40 per ASTM A53 or
A). Threaded inlet and outlet connec- A135.
tions are available in NPT or ISO 7-1. • Common hardware compression
22-3/8" Threaded port connections are NPT fitting are brass per ASTM B16
(569 mm) threaded.
• Common hardware tubing is Type L
NOTE: PN16 flanges are pressure rated per ASTM B88
to 16 bar.
6 Inch (DN150) Valve Trim
The maximum pressure rating for the
Electric/Electric Double Interlock Pre-
action Trim is dependent on separately
ordered solenoid valve per Technical
Data Sheet TFP2180.
27-7/16" Electric/Electric Double Interlock Pre-
(697 mm) action Trim, when using the separately
ordered QRS Electronic Accelerator, is
based on the separately ordered QRS
Electronic Accelerator per Technical
8 Inch (DN200) Data Sheet TFP1100
FIGURE 3
DV-5 a DELUGE VALVE
TAKE-OUT DIMENSIONS
TFP1466
Page 5 of 20
6.0 0,400
5.0
0,300
)
40
4.0
DN
H(
)
3.0 50
0,200
DN
/2
1-1
H(
DN
2I
2.0
H(
0)
NC
10
DN
3I
0,100
H(
0)
NC 0,090
15
0,080
DN
4I
H(
0)
1.0 0,070
20
NC
0.9
DN
0,060
0.8 6I
H(
0,050
NC
0.7
8I
0.6 0,040
0.5
0,030
0.4
0,022
0.3
50 100 200 400 600 1000 2000 3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
DV-5 a VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW
45 Notes:
URE The dew point of the pilot line air pressure must be maintained
IR PRESS below the lowest ambient temperature to which the dry pilot
EM A
AIR PRESSURE IN PSI
open. After the ten minute duration, at alarm of the Low Pressure Switch on The dew point of the air or nitrogen
which point should the Solenoid Valve increasing pressure. The Low Pressure supply, for a system exposed to freezing
become de-energized and close (espe- Switch is field set to alarm at nominally conditions, must be maintained below the
cially while operating under battery 12 psi (0,8 bar) on decreasing pres- lowest ambient temperature to which the
back-up), the MRA-1 will have already sure when using a nominal system air system piping will be exposed. Introduction
automatically opened, thereby prevent- pressure of 15 psi (1,0 bar). It is recom- of moisture into the system piping can
ing the DV-5a Diaphragm Chamber mended that the system air pressure create ice build up which could prevent
from becoming re-pressurized, and be maintained by either of the follow- proper operation of the system.
preventing an inadvertent closing of ing methods: The Air Pressure Relief Valve is typi-
the DV-5a during a fire event. cally field set to crack open at a pres-
• A maximum 200 psi (13,8 bar) plant
air supply in combination with the sure of about 20 psi (1,4 bar) when
WARNING Model AMD-1 Air Maintenance using a nominal system air pressure of
If the delay between electric actua- Device described in Technical Data 15 psi (1,0 bar).
tion and subsequent sprinkler activa- Sheet TFP1221
tion is anticipated to be greater then • A maximum 3000 psi (206,9 bar)
10 minutes, adjust the battery back-up nitrogen cylinder in combination with
calculation accordingly. Inadequate the Model AMD-3 Nitrogen Mainte-
battery back-up may result in failure of nance Device described in Technical
the system to operate in the event of a Data Sheet TFP1241
fire during a power failure.
NOTES:
Releasing Circuit It is recommended that the pressure
The releasing circuit must be equipped maintenance device be of a type that
with a Potter RCDS-1 Releasing Circuit maintains a constant system pressure, i.e.,
Switch, or equivalent. The RCDS-1 a pressure maintenance device that utilizes
provides for a temporary disconnect a pressure regulator versus a pressure
(de-energized) of the Solenoid Valve switch (e.g., the AMD-1 or AMD-3). Use
during Step 9 of the Valve Resetting of a pressure switch operated pressure
Procedure. maintenance device with a cut-in/cut-
System Air Pressure Requirements out differential may result in a delay in
The recommended system air pres- the operation of the system due to a fire,
sure for the Double Interlock Preaction because of the cut-out pressure being
System with Electric/Electric Actuation higher than the recommended nominal
is nominally 15 psi (1,0 bar), irrespective system air pressure.
of the water supply pressure. The use
of a higher system air pressure may or
may not adversely affect water deliv-
ery time, and the use of a lower system
air pressure may prevent clearing the
TFP1466
Page 8 of 20
A3
C5 L
D
C
C3
F
P4 E
P7
A2
A
P5
C2 C4 P6
C7 A7
H P3 A1
J
B
P1 C6
P2
G
A5
K
A4
A5 C1
A6
1-1/2" (DN40) AND 2" (DN50) Assemble in order
VALVES ONLY from A to L
A8
A10
A9
Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C5 are described in Figure 8.
3. When ordering pre-assembled "DV-5A Valve with Galvanized Trim" or pre-assembled "DV-5A Valve with Galvanized Trim and Butterfly Valve", Items A1
through A10 are provided, as applicably related to valve size, and Item A7 is provided as P/N 52-287-1-124 described in Technical Data Sheet TFP2180
4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A10 are separately ordered, as applicably related to valve size. Water
Pressure Gauges for EMEA valve trim are also separately ordered.
FIGURE 5
DV-5 a VALVES
DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION TRIM
SEMI-ASSEMBLED
TFP1466
Page 10 of 20
A3
39 27
28 36
C5
26 51 27
52 57
21
22 1
42 41 47 34
17
P4 30
P7 49 A7
36
20 29 10
A2 P5 55 36
8
36
C4 14 36
13 4
C2 31
P6 54 20 24 6
32
53 16 C3
44 A1 33 43 39
P3
23 15 40
32 P1 C7 29
P2 C6
48 Notes:
12 59 1. Port Connections P1 through P7
50 3
19 A5 37 are described in Figure 2.
24 58 2. External Trim Connections C1
38 5 46 through C5 are described in
56
31 A4 11 56 Figure 8.
3. When ordering pre-assembled
35 37 18 "DV-5A Valve with Galvanized
25 2 Trim" or pre-assembled "DV-5A
Valve with Galvanized Trim
27 1 21 9 and Butterfly Valve", Items A1
37 27
7 45 through A10 are provided, as
19 17 applicably related to valve size,
37 and Item A7 is provided as P/N
A5 52-287-1-124 described in
C1 7 Technical Data Sheet TFP2180
4. When ordering DV-5A Trim
A6 separately from the DV-5A Valve,
A10 Items A1 through A10 are sepa-
A8 A9 rately ordered, as applicably
related to valve size. Water Pres-
sure Gauges for EMEA valve trim
1-1/2" (DN40) AND 2" (DN50) are also separately ordered.
VALVES ONLY
ITEM QTY DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
1 2 1/4” GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
6 1 1/4” PRESSURE RELIEF VALVE 923431020 923431020 923431020 923431020 923431020 923431020
7 2 1/2” BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
8 1 1/2” GLOBE VALVE 460471005 460471005 460471005 460471005 460471005 460471005
9 1 1/2” SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
10 1 1/2” SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007
11 1 1/2” Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
12 1 3/4” ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
13 1 ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
14 1 DRIP FUNNEL BRACKET CONNECTOR 922111005 922111005 922111005 922111005 922111005 922111005
15 1 DRIP FUNNEL BRACKET 922111003 922111003 922111003 922111003 922111003 922111003
16 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
17 2 COMP. FITTING 90° 1/2” MNPT x 1/2” OD TUBE 1001253-01 1001253-01 1001253-01 1001253-01 1001253-01 1001253-01
18 1 COMP. FITTING 90° 1/2” FNPT x 1/2” OD TUBE 1001420-01 1001420-01 1001420-01 1001420-01 1001420-01 1001420-01
19 2 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
20 2 FLARE FITTING 3/4” NPT x 3/4” TUBE 545100063 545100063 545100063 545100063 545100063 545100063
21 2 PIPE PLUG ✓ 1/4” 1/4” 1/4” 1/4” 1/4” 1/4”
22 1 PIPE PLUG ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
23 1 PIPE PLUG ✓ 3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
24 2 UNION ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
FIGURE 6 (1 OF 2)
DV-5 a VALVES
DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION TRIM
EXPLODED VIEW
TFP1466
Page 11 of 20
ITEM QTY DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
25 1 STREET ELBOW ✓ 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90°
26 1 ELBOW ✓ 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45°
27 4 ELBOW ✓ 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90°
28 1 CROSS ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
29 2 TEE ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
30 1 REDUCING TEE ✓ 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2”
31 2 REDUCING TEE ✓ 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4”
32 2 REDUCING TEE ✓ 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4”
33 1 REDUCING TEE ✓ 3/4” x 3/4” x 3/4” 3/4” x 3/4” x 3/4” 1-1/4” x 1-1/4” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4”
34 1 PIPE NIPPLE ✓ 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE
35 1 PIPE NIPPLE ✓ 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2”
36 5 PIPE NIPPLE ✓ 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE
37 4 PIPE NIPPLE ✓ 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2”
38 1 PIPE NIPPLE ✓ 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2”
39 2 PIPE NIPPLE ✓ 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2”
40 1 PIPE NIPPLE ✓ 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2”
41 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5”
42 1 PIPIE NIPPLE ✓ 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2”
43 1 PIPE NIPPLE ✓ 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2”
44 1 PIPE NIPPLE ✓ 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2”
45 1 TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
46 1 TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
47 1 TUBING, SOLENOID DRAIN 535001020 535001020 535000630 535000640 535000660 535000680
48 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
49 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
50 1 PIPE NIPPLE ✓ 1/2” x 3 1/2” 1/2” x 3 1/2” 1/2” x 4 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 3/4”
51 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 1/2”
52 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 4 1/2” 1/2” x 5” 1/2” x 7 1/2” 1/2” x 9 1/2”
53 1 PIPE NIPPLE ✓ 3/4” x 5” 3/4” x 5” 3/4” x 6” 3/4” x 7” 3/4” x 9” 3/4” x 11 1/2”
54 1 PIPE NIPPLE ✓ 3/4” x 4 1/2” 3/4” x 4 1/2” 1-1/4” x 3 1/4” 2” x 3” 2” x 3” 2” x 3”
55 1 PIPE NIPPLE ✓ 3/4” x 6 1/2” 3/4” x 6 1/2” 1-1/4” x 5 1/2” 2” x 5” 2” x 6” 2” x 8”
WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
2 923431005 923431005 923431005 923431005 923431005 923431005
(AMER/APAC)
56
WATER PRESSURE GAUGE, 20 bar / 2000 kPa
2 025500013 025500013 025500013 025500013 025500013 025500013
(EMEA)
AIR PRESSURE GAUGE, 80 PSI / 550 kPa
57 1 923431012 923431012 923431012 923431012 923431012 923431012
RETARDED TO 250PSI / 1750 kPa
58 1 LABEL 545003005 545003005 545003005 545003005 545003005 545003005
59 1 LABEL WIRE — — — — — —
A1 1 DV-5A VALVE SEE ORDERING PROCEDURE, SEPARATE DV-5A VALVES WITHOUT TRIM, FOR PART NUMBERS
WATERFLOW PRESSURE ALARM SWITCH,
1 25710 25710 25710 25710 25710 25710
PS10-2 (AMER/APAC)
A2
WATERFLOW PRESSURE ALARM SWITCH,
1 0260 0260 0260 0260 0260 0260
PS10-1 (EMEA)
LOW AIR PRESSURE ALARM SWITCH, PS40-2
1 25730 25730 25730 25730 25730 25730
(AMER/APAC)
A3
LOW AIR PRESSURE ALARM SWITCH, PS40-1
1 0262 0262 0262 0262 0262 0262
(EMEA)
1 BUTTERFLY VALVE, G x G 51024A 51021A — — — —
A4
1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
2 FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
A5
1 FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A6 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
SOLENOID VALVE NORMALLY CLOSED
A7 1 SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180
(SEPARATELY ORDERED)
A8 1 INVERTED FLARE SHUT-OFF VALVEa 545100100 545100100 545100099 545100100 545100100 545100100
A9 1 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A10 1 TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080
NOTES
a. Not VdS Approved
CH - Common Hardware - Refer to Materials of Construction section for specifications.
FIGURE 6 (2 OF 2)
DV-5 a VALVES
DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION TRIM
EXPLODED VIEW
TFP1466
Page 12 of 20
Nominal
Valve Inches
Size (mm)
ANSI
Inches A B C D E F G H J
(DN)
1 1/2 2.8 9.7 10.4 15.7 16.2 7.3 10.2 8.0 1.2
(40) (71) (246) (264) (399) (412) (185) (259) (203) (31)
2 2.8 9.7 10.4 15.7 16.2 7.3 10.2 3.8 2.9
(50) (71) (246) (264) (399) (412) (185) (259) (97) (74)
3 3.0 10.9 12.0 16.3 18.5 5.8 13.8 3.9 3.6
(80) (76) (277) (305) (414) (470) (147) (351) (99) (91)
4 3.0 12.2 13.1 16.5 21.0 5.1 16.8 4.5 4.3
(100) (76) (310) (333) (419) (533) (129) (427) (114) (109)
6 4.5 13.6 15.0 18.4 24.8 3.4 22.4 5.9 5.7
(150) (114) (345) (381) (467) (630) (86) (569) (150) (145)
8 5.3 16.3 17.2 19.5 29.1 2.9 27.5 5.2 6.7
(200) (135) (414) (437) (495) (739) (74) (699) (132) (170)
Notes:
1. Dimensions based on drain valves being open.
2. Dimensions do not provide installation clearance.
J B C D
H F
FIGURE 7
DV-5 a VALVE
DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION TRIM
NOMINAL DIMENSIONS
TFP1466
Page 13 of 20
Step 6. Inspect for and clear all ice • If the Diaphragm Gauge (K) indicates
plugs where system piping has been no drop in pressure, re-open the Dia-
exposed to freezing conditions and phragm Supply Valve (P) and pro-
when there has been a flow of water ceed to the next step.
into the system. Step 14. Open the Air Supply Valve
Step 7. Replace all damaged or oper- (S) and allow the system to automati-
ated sprinklers. Replacement sprinklers cally re-establish its nominal system
must be of the same type and tempera- air pressure. Observe the Automatic
ture rating as those that operated. Drain Valve (F) for leaks. If there are
leaks, determine/correct the cause of
NOTICE the leakage problem.
In order to prevent the possibility of a • Nominal system air pressure for Elec-
subsequent operation of an overheated tric/Electric Actuation is typically 15
solder type sprinkler, any solder type psi (1,0 bar).
sprinklers possibly exposed to a tem- Step 15. Open the System Shut-Off
perature greater than their maximum Valve (X), as will be the case when
rated ambient must also be replaced. resetting a system after performing an
Step 8. Service the air dryer, if appli- operational test.
cable, in accordance with the manu-
facturer’s instructions.
TFP1466
Page 14 of 20
LOCATION
FOR OPTIONAL C5
ELECTRICALLY
SUPERVISED L
N.O. ALARM
CONTROL
VALVE
C
X P4
P7 V
F
S
P5
C2 T
C4
D
P6
H A C3
P3
P1 C7 M
P2 C6
E
J K
B
Q
G
P
C1
R
NOTES
• Port Connections P1 through P7 are described in Figure 2.
FIGURE 8
DV-5 a VALVE - DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION
(See Figure 6 for specific Bills of Materials)
TFP1466
Page 15 of 20
Step 4. Open the Inspector’s Test Con- Step 11. Manually operate Zone 1 of
Torque nection to relieve system air pressure, the Releasing Panel, and then operate
Nominal lb-ft and verify the following: Zone 2 of the Releasing Panel by par-
Valve Sizes (N∙m)
tially opening the System Drain Valve
ANSI • That the Low Air Pressure Alarm
Inches Short (E) to relieve air pressure at the Low Air
Switch (U) and Zone 2 of the Releas-
(DN) Nuts Hex Pressure Alarm Switch (U), and verify
Bolts ing Panel, as well as its associated
the following:
alarms, operate properly. The Low
1 1/2 44 35 Air Pressure Alarm Switch (U) should • That the DV-5a Valve operates as is
(40) (59,7) (47,5) operate at the previously established indicated by a discharge of water
2 44 35
pressure (see Installation section, from the System Drain Valve (E) and
(50) (59,7) (47,5) Step 9). the Automatic Drain Valve (F). The
Automatic Drain Valve (F) may or may
3 188 150 • That there is no leakage from the
not close depending on the flow past
(80) (254,9) (203,4) Solenoid Valve (V).
the partially open System Main Con-
4 396 316 Step 5. Close the Inspector’s Test trol Valve (B)
(100) (536,9) (428,4) Connection.
• That the Model MRA-1 Manual Reset
6 265 212 NOTE: During this procedure, the Solenoid Actuator (N) has operated as is indi-
(150) (359,3) (287,4) Valve (V) should remain closed and the cated by water discharging into the
DV-5a Valve Diaphragm Chamber should Drip Funnel from the 1/2 in. drain
8 545 436
(200) (738,9) (591,1) remain pressurized. tube connected to the Model MRA-1
This procedure is used to verify that the Manual Reset Actuator (N)
TABLE B DV-5a Valve will remain set if the Low • That the Waterflow Pressure Switch
DIAPHRAGM COVER BOLTS Air Pressure Alarm Switch (U) (Zone 2) (C) and its associated alarms prop-
MINIMUM TORQUE operates due to loss of system air pressure erly operate
and the electric detection system (Zone 1)
Electric/Electric Actuation remains in a normal condition. • That the Water Motor Alarm, if appli-
System Operation Procedure cable, properly operates
Proper operation of the DV-5a Valve for Step 6. Restore the electric fire detec-
tion system to a normal condition in NOTE: This procedure simulates automatic
both opening of the DV-5a Valve in a system operation upon both electric
fire condition, or not opening the DV-5a accordance with the manufacturer’s
instructions after the system air pres- detection and loss of system air pressure.
Valve in a non-fire condition, must be
verified as follows: sure has automatically been restored Internal Valve Inspection
to normal. Once every five years during the annual
Step 1. Close the System Main Control operational test procedure and prior
Valve (B) and then open the Main Drain Step 7. Close the System Shut-Off
Valve (W) after the system air pressure to the DV-5a Valve being reset and
Valve (D). with the DV-5a Valve de-pressurized,
has been restored to normal.
Step 2. Manually operate Zone 1 of the interior of the DV-5a Valve must
the Releasing Panel, and verify the Step 8. Open the System Main Control be cleaned and inspected for wear
following: Valve (B) one turn beyond the position and damage. Damaged or worn parts
at which water just begins to flow from must be replaced. (Replacement of the
• The operation of the Releasing Panel the Main Drain Valve (D). Diaphragm every ten years is recom-
and its associated alarms mended, or more frequently if inspec-
Step 9. Close the Main Drain Valve (D).
• That there is no leakage from the tions and/or wear and tear warrant
Solenoid Valve (V) Step 10. Close the Air Supply Valve (S). more frequent replacement.)
NOTE: During this procedure, the Solenoid
Valve (V) should remain closed and the NOTICE
DV-5a Deluge Valve Diaphragm Chamber The Diaphragm Cover may be removed
should remain pressurized. between Steps 4 and 5 of the reset-
ting instructions, since at that point the
This procedure is used to verify that the
DV-5a Valve should be de-pressurized
DV-5a Deluge Valve will remain set if the
as evident by a zero gauge reading on
electric detection system (Zone 1) operates
the Diaphragm Gauge (K) and Water
but the sprinkler system (Zone 2) remains
Supply Gauge (J), as well as no water
in its normally pressurized condition.
discharging from the Automatic Drain
Step 3. Restore the electric fire detec- Valve (F).
tion system to a normal condition in
accordance with the manufacturer’s
instructions.
TFP1466
Page 17 of 20
Procedure
Grooved x Grooved
Groove x Groove 1 1/2 in. (DN40) ����������������������������������� 550111515
1 1/2 in. (DN40) ���������������������������������� 530010015 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550111520
The TYCO DV-5a Automatic Water 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550111530
Control Valves may be ordered as 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030 4 in. (DN100) ��������������������������������������� 550111540
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040 6 in. (DN150) ��������������������������������������� 550111560
follows: 8 in. (DN200) ��������������������������������������� 550111580
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060
Pre-Assembled Valves 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080 Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550121530
with Trim Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030 4 in. (DN100) ���������������������������������������550121540
DV-5A Valves with Galvanized Trim 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040 6 in. (DN150) ���������������������������������������550121560
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060 8 in. (DN200) ���������������������������������������550121580
and Butterfly Valve
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080 Flange x Grooved ANSI
Specify: Size (specify), DV-5 a Auto-
matic Water Control Valve, G x G con- Flange x Groove ANSI 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550131530
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030 4 in. (DN100) ���������������������������������������550131540
nections with assembled galvanized 6 in. (DN150) ���������������������������������������550131560
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040
Americas Double Interlock Preac- 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060 8 in. (DN200) ���������������������������������������550131580
tion with Electric/Electric Actuation 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080 Flange x Flange ISO
Trim, complete with assembled Model 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550141530
T x T NPT
BFV-300 Butterfly Valve, P/N (specify): 1 1/2 in. (DN40) ���������������������������������� 530060015 4 in. (DN100) ���������������������������������������550141540
1 1/2 in. (DN40) ����������������������������������� 551011515 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020 6 in. (DN150) ���������������������������������������550141560
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 551011520 8 in. (DN200) ���������������������������������������550141580
Notes:
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 551011530 Valves are typically provided with flange Flange x Grooved ISO
4 in. (DN100) ��������������������������������������� 551011540 drilling per ANSI B16.1 (Class 125) or ISO 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550151530
6 in. (DN150) ��������������������������������������� 551011560 (7005-2 PN16). 4 in. (DN100) ���������������������������������������550151540
8 in. (DN200) ��������������������������������������� 551011580 6 in. (DN150) ���������������������������������������550151560
Upon request, valves can be provided with 8 in. (DN200) ���������������������������������������550151580
Notes: flange drilling per JIS B 2210 or AS 2129. In
Americas pressure switches, P/N 52-287- which case part numbers are not assigned. T x T ISO
1-124 Solenoid Valve, and psi/kPa water 1 1/2 in. (DN40) ����������������������������������� 550171515
pressure gauges are provided. DV-5A Valve Trim 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550171520
Specify: Size (specify), finish (specify), Note: Pressure switches, P/N 52-287-1-
This arrangement is available for EMEA Electric/Electric Actuation Trim for 124 solenoid valve, bar/psi water pressure
and APAC upon request. Contact your DV-5a Automatic Water Control Valves gauges, and NPT to ISO threaded trim adap-
local distributor. used in Double Interlock Preaction Fire tors for external connections are provided.
Protection System, P/N (specify): Separate DV-5A Valves without Trim
AMERICAS
Galvanized See Table A for flange drilling
DV-5A Valves with Galvanized Trim 1 1/2 in. (DN40) ���������������������������������� 540001520 specifications.
Specify: Size (specify), DV-5 a Auto- 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 540001520
matic Water Control Valve, (specify) 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 540001530 Specify: Size (specify), DV-5 a Auto-
end connection with assembled galva-
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 540001540 matic Water Control Valve, (specify)
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 540001560 end connection, P/N (specify):
nized Americas, Double Interlock Pre- 8 in. (DN200) �������������������������������������� 540001580
action Electric/Electric Actuation Trim, Groove x Groove
Black 1 1/2 in. (DN40) ���������������������������������� 530010015
P/N (specify): 1 1/2 in. (DN40) ���������������������������������� 542001520 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020
Grooved x Grooved 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 542001520 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030
1 1/2 in. (DN40) ����������������������������������� 550011515 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 542001530 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550011520 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 542001540 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550011530 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 542001560 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080
4 in. (DN100) ���������������������������������������550011540 8 in. (DN200) �������������������������������������� 542001580
6 in. (DN150) ���������������������������������������550011560 Flange x Flange ANSI
8 in. (DN200) ���������������������������������������550011580
Note: Pressure switches and/or solenoid 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030
valves for electric actuation are separately 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040
Flange x Flange ANSI ordered. 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550021530 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550021540
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550021560 Flange x Groove ANSI
8 in. (DN200) �������������������������������������� 550021580 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040
Flange x Grooved ANSI 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550031530 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530030080
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550031540
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550031560 T x T NPT
8 in. (DN200) �������������������������������������� 550031580 1 1/2 in. (DN40) ���������������������������������� 530060015
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020
T x T NPT
1 1/2 in. (DN40) �����������������������������������550061515
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 550061520
TFP1466
Page 19 of 20
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
Worldwide
www.tyco-fire.com
Contacts
3
6
7
4
IMPELLER
NOZZLE
INLET
DRAIN
5
INTERNAL VIEW OF
WATER MOTOR (ITEM 1)
8
FIGURE 1
MODEL WMA-1 WATER MOTOR ALARM
ASSEMBLY
Item 9. Drain water must be directed to • 3/4 in. Check Valve with 3/32 in. the Inlet Nozzle, a high velocity jet is
prevent accidental damage to property orifice (P/N 52-403-1-005) formed that impinges on the Impeller,
or danger to persons when the alarm is causing the Impeller and the Striker
Strainers must be located at the alarm
operating or thereafter. to rotate. With each rotation, the free
outlet in the trim of each of the water-
Item 10. The alarm line drain, at the flow detection valves. Check valves swinging Striker Ring hits the Gong and
waterflow detection valve, must be must be located between each strainer sounds the alarm. The spent water is
maintained at a minimum temperature and the interconnection with the alarm then drained through the 1 in. outlet.
of 40°F (4°C). line from another system. The alarm will sound as long as water
Item 11. A single Water Motor Alarm is flowing into the system and flowing
may be connected to the alarm lines Operation to the Water Motor Alarm. Water in the
alarm line will automatically drain back
from a maximum of three separate fire
protection systems. However, when Upon operation of the alarm check, through the orifice, which is also pro-
two or three alarm lines are intercon- dry pipe, deluge, or preaction valve to vided in the trim of the waterflow detec-
nected, each alarm line must be pro- which the TYCO Model WMA-1 Water tion valve.
vided with the following: Motor Alarm is connected, water will The Water Motor Alarm does not have
flow to the Water Motor and through to be reset after an operation. However,
• 3/4 in. Model WM-1 Y-Strainer the Inlet Nozzle. As water flows through
(P/N 52-271-1001) if the alarm was silenced during oper-
TFP921
Page 3 of 4
2"
(50,8 mm)
7/8" 3/4" NPS
(22,2 mm) 2-3/4" 2-7/16"
1-3/8" (69,9 mm) (61,9 mm)
(34,2 mm)
WATER
MOTOR 8-1/2" DIA.
SLEEVE END (215,9 mm)
2-9/16" T/O 2-1/2" T/O 3/4" NPT
(65,0 mm) (63,5 mm) THREADED
BY INSTALLER
1-13/16"
(46,0 mm) 10"
(254,0 mm)
DRAIN CL
3/4" NPT 1" NPT MINIMUM
INLET DRAIN
A
ation by closing an alarm control (0 mm to 3 mm). Thread the cut end to Step 8. Tighten the 3/4 in. Union.
valve, the alarm control valve must 3/4 in. NPT per ANSI B1.20.1. Install the Wall Plate and tighten the
be reopened after the fire protection 45° Elbow.
Step 4. Install the alarm line piping up
system is restored to service. to and including the Union half per Item Note: Apply pressure against the
4, Figure 2. outside edge of the Water Motor Body
Installation Note: Use thread sealant sparingly on and verify that the Body and Support
Washer sit squarely against the wall. If
The TYCO Model WMA-1 Water Motor male threads only.
not, adjust the alarm line and/or drain
Alarm must be installed in accordance Step 5. Prior to initiating installation piping to suit.
with this section. of the Water Motor Alarm, mount the
Step 9. From the outside wall, insert
Step 1. Mark the through-wall locations Drain Trim (less the Wall Plate and 45°
the Drive Shaft through the Sleeve and
for the centerlines of the Sleeve and Elbow) as well as the balance of alarm
fully insert it into the Impeller.
Drain Outlet. The Drain Outlet must be line piping, including the other Union
located at least 10 in. (250 mm) below half, to the Water Motor. Note: When fully inserted, the Shaft
the Sleeve per Figure 2. should protrude beyond the face of
Step 6. Tighten the NPT threaded end
the wall by approximately 20 minus 2 in.
Step 2. Make 1-1/2 in. (38 mm) diam- of the Sleeve into the Body, hand-tight
(508,0 minus 50,8 mm) wall thickness.
eter holes straight through the wall at plus 1/8 turn.
both locations. Mark the Drive Shaft at a point of
Step 7. Slip the Support Washer over
approximately 1/8 in. to 1/4 in. (3,2 mm
Step 3. Cut the non-threaded end of the Sleeve and place the assembly in
to 6,4 mm) inside the face of the wall.
the Sleeve to a length equal to that of position against the wall.
Remove the Shaft and cut it where pre-
the wall thickness plus 0 in. to 1/8 in.
TFP921
Page 4 of 4
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
Worldwide
www.tyco-fire.com
Contacts
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
2" 16-1/8""
(50,8 mm) (409,6 mm)
BY-PASS VALVE
1/4" NPT
(NORMALLY
GAUGE
CLOSED)
TEST PORT
3-1/4" 1/2" NPT P/N 46-047-1-004
(82,6 mm) OUTLET
CONNECTION
(TO SYSTEM)
8-1/2"
(215,9 mm) 1/2" NPT
LABEL INLET CONNECTION
(FROM COMPRESSED
AIR SUPPLY)
RESTRICTOR
CHECK VALVE
P/N 92-326-1-003
PRESSURE AIR SUPPLY
REGULATOR STRAINER CONTROL VALVE
(ADJUSTABLE) P/N 52-353-1-002 (NORMALLY OPEN)
P/N 92-324-1-012 P/N 46-048-1-002
FIGURE 1
MODEL AMD-1
AUTOMATIC AIR MAINTENANCE DEVICE
NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association
TECHNICAL
SUBMITTAL
MATERIAL CERTIFICATE
www.SFFECO.com
VLFT.EX6022 - Special System Water Control Valves,
Deluge Type
TFP Model DV-5, 1-1/2, 2, 3, 4, 6 and 8 in. deluge valves for vertical and horizontal installation for pressures not exceeding 250 psig. The Model
DV-5 deluge valve is intended for operation by dry pilot line, manually, electrically or wet pilot line of sprinklers.
TFP Model DV-5, 2, 3, 4, 6 and 8 inch size deluge valves with Remote-Resetting with Electric Activation trim for vertical installation for pressures
not exceeding 250 psig.
TFP Model DV-5, 4 and 6 inch valves with Remote-Resetting, Pressure-Reducing trim for vertical and horizontal installation for pressures not
exceeding 250 psig.
TFP Model DV-5, 1-1/2, 2, 3, 4, 6 and 8 in. size deluge valves, rated 250 psig, for use with Single-Interlock Preaction trim, intended for operation by
supervised wet pilot, dry pilot, electrically or manual activation, installed in accordance with the manufacturer's installation instructions.
TFP Model DV-5, 1-1/2, 2, 3, 4, 6 and 8 in. size deluge valves, rated 250 psig, for use with Double-Interlock Preaction trim w/ electric/electric
release and Double-Interlock Preaction w/ electric/pneumatic release, installed in accordance with the manufacturer's installation instructions.
TFP Model DV-5, 4 inch valve with Remote-Resetting, Pressure-Reducing trim in Limited Space cabinet for vertical installation for pressures not
exceeding 250 psi.
Model SV-1, 3, 4, 6 and 8 in. size deluge valves for vertical installation only for pressures not exceeding 175 psig. The Model SV-1 is intended for
operation manually, electrically or wet pilot line of sprinklers.
TFP Model DV-5A, 1-1/2, 2, 3, 4, 6, 165.1mm and 8 in. deluge valves, rated 300 psig, for vertical installation. The Model DV-5A deluge valve is
intended for operation by dry pilot line, manually, electrically or wet pilot line of sprinklers.
TFP Model DV-5A, 1-1/2, 2, 3, 4, 6, 165.1mm and 8 in. size deluge valves, rated 300 psig, for use with Single-Interlock Preaction trim, intended for
operation by supervised wet pilot, dry pilot, electrically or manual activation, installed in accordance with the manufacturer's installation
instructions.
TFP Model DV-5A, 1-1/2, 2, 3, 4, 6, 165.1mm and 8 in. size deluge valves, rated 300 psig, for use with Double-Interlock Preaction trim w/
electric/electric release and Double-Interlock Preaction w/ electric/pneumatic release, installed in accordance with the manufacturer's installation
instructions.
TFP Model DV-5A, 2, 3, 4, 6, 165.1mm and 8 inch size deluge valves with Remote-Resetting with Electric Activation trim for vertical installation for
pressures not exceeding 300 psig.
TFP Model DV-5A in 3, 4, 6, 165.1mm and 8 in deluge valves with Remote-Resetting Pressure-Reducing trim for vertical installation for pressures
not exceeding 250 psi.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format:
"© 2021 UL LLC"
Refrigerated Area Sprinkler Systems
A refrigerated area sprinkler system affords fire protection in refrigerated rooms or buildings and includes special safeguards against
accidental filling with water and subsequent freezing of the system. A fire detection system shall actuate and one or more automatic
sprinklers in the piping shall operate before water will enter the sprinkler system. An alarm sounds if the detection system only is
actuated while pneumatic pressure is maintained in the sprinkler piping. An alarm also sounds if the pneumatic pressure in the
sprinkler piping is not properly maintained. In either case, water does not enter the system piping. These systems should be installed
in accordance with FM Global Loss Prevention Data Sheet 8-29, "Refrigerated Storage". System calculations regarding required
system air capacity should be performed if only one air maintenance device is contemplaed for several sprinkler systems.
Refrigerated area sprinkler systems which are operated pneumatically/hydraulically are FM Approved as complete systems. Only the
listed components for a given system may be used in combination.
Fire detection systems which are operated electrically are FM Approved on a component basis. Only compatible components may be
used in combination. Compatible FM Approved Release Control Panels for use with electric release refrigerated area sprinkler
system(s) are listed under RELEASE CONTROL PANEL COMPATIBILITY.
Product Specification
Rated Working
Release Valve Size End
Pressure Remarks
Type Connection
in (mm) psi (kPa)
1 1/2, 2, 3, (40, 50, 80, 100, a, c, d, e, g, h, i, j, k, l,
Electric / Electric See Remarks Grooved
4, 6, 8 150, 200) m, n
a, b, c, d, e, g, h, i, j,
Electric / Electric 1 1/2, 2 (40, 50) See Remarks Threaded
k, l, m, n
(80, 100, 150, a, c, d, e, g, h, i, j, k, l,
Electric / Electric 3, 4, 6, 8 See Remarks Flanged
200) m, n
(80, 100, 150, a, c, d, e, g, h, i, j, k, l,
Electric / Electric 3, 4, 6, 8 See Remarks Grooved x Flanged
200) m, n
Electric / 1 1/2, 2, 3, (40, 50, 80, 100, a, c, d, e, f, g, h, i, j, l,
See Remarks Grooved
Pneumatic 4, 6, 8 150, 200) m, n
Electric / a, b, c, d, e, f, g, h, i, j,
1 1/2, 2 (40, 50) See Remarks Threaded
Pneumatic l, m, n
Electric / (80, 100, 150, a, c, d, e, f, g, h, i, j, l,
3, 4, 6, 8 See Remarks Flanged
Pneumatic 200) m, n
Electric / (80, 100, 150, a, c, d, e, f, g, h, i, j, l,
3, 4, 6, 8 See Remarks Grooved x Flanged
Pneumatic 200) m, n
Remarks:
a. Approved when supplied with a main control valve body ASTM A536 ductile iron
b. Approved when supplied with a main control valve body ASTM A351 CF8M stainless steel (size 1-1/2 inch NPS threaded end
connections only)
c. The rated working pressure is limited to the rated pressure of the release trim solenoid valve.
d. Approved when equipped with a Skinner Model 73218BN4UNLVN0C111C2 two-way normally closed solenoid valve, 24 V dc, 10
W, 1⁄2 in. NPS, Cv Factor 4.0, Rated Working Pressure of 175 psi (1210 kPa).
e. Approved when equipped with a Skinner Model 73212BN4TNLVN0C322C2 two-way normally closed solenoid valve, 24 V dc, 22.6
W, 1⁄2 in. NPS, Cv Factor 2.8, Rated Working Pressure of 250 psi (1720 kPa).
f. Approved when supplied with a Model DP-1 dry pilot valve
g. Approved when supplied with a Potter PS10-1 or PS10-2 waterflow pressure alarm switch
h. Approved when supplied with a Potter PS40-1 or PS40-2 low pressure alarm switch
i. Approved when supplied with a Potter Model QRS electronic accelerator system
j. Approved when equipped with a Skinner Model 73218BN4UNLVN0H111C2 two-way normally closed solenoid valve, 24 V dc, 10 W,
1⁄2 in. NPS, Cv Factor 4.0, Rated Working Pressure of 175 psi (1210 kPa).
k. Approved for use with Potter Model RCDS-1 releasing circuit disable switch.
l. Approved when factory assembled vertically inside the Model DV-5A Red-E Cabinet. The Red-E cabinet and assembled system
components comprise an integrated fire protection system which is assembled and tested at the factory.
m. Approved when DV-5A valve and trim assembled horizontally or vertically.
n. Approved when equipped with a Ningbo Yongxing two-way normally closed solenoid valve 24 V dc, 12 W, 1⁄2 in. NPS, Rated
Working Pressure of 230 psi (1600 kPa).
© 2018 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2018 UL LLC".
Pressure Maintenance Devices, Dry Pipe Systems
These pressure maintenance devices automatically maintain a predetermined air or nitrogen pressure in dry pipe sprinkler systems.
Some devices may be used with a noncontinuous air supply which is capable of initially filling the system. Other systems require a
continuous air or nitrogen supply. Unless noted otherwise in the listing, these air maintenance devices have a pressure rating of 175
psi (1205 kPa).
Tyco Model AMD-1. 200 psi (1380 kPa) working pressure. Air maintenance.
Tyco Model AMD-2. Air maintenance.
Tyco Model AMD-3. Nitrogen maintenance.
VPLX.EX6872
Valves, Alarm
Page Bottom
Valves, Alarm
See General Information for Valves, Alarm
TYCO FIRE & BUILDING PRODUCTS EX6872
1400 PENNBROOK PKWY
LANSDALE, PA 194463840 USA
Alarm valves, Model AV1175 in the sizes 21/2, 4, 6, 8 in. for horizontal or vertical installation with the following end connections: flanged
flanged, flangedgrooved and groovedgrooved and for rated pressures not exceeding 175 psig.
Model AV1300 in the sizes 21/2, 4, 6, 8 in. for horizontal or vertical installation with the following end connections: flangedflanged,
flangedgrooved and groovedgrooved and for rated pressures not exceeding 300 psig.
Model RC1 retarding chamber, Model WM1 "Y" strainer, Model WMA1, water motor and gong all for rated pressures not exceeding 300 psig.
Models AV1175, AV1300 valves may be provided with flanged connections drilled per ANSI, AS, ISO, and JIS specifications.
Trademark and/or Tradename: "CSC"
Last Updated on 20151121
© 2016 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's FollowUp Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's FollowUp
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2016 UL LLC".
http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=VPLX.EX6872&ccnshorttitle=Valves,+Alarm&objid=1076957713&cfgid=1… 1/1
Water Motor Gongs
Water motor gongs give a locally audible alarm signal when the automatic sprinkler system operates. They may be used with
waterflow alarm, dry pipe, or automatic water control valves.
Model WMA-1
Model WMA-1. U.S. and European versions available.