You are on page 1of 42

TE C H NI C A L

SUBMITTAL
AL MURJAN MEDICAL CENTRE JEDDAH
Project

AL TA'AFUF CO MPANY FOR ELECTRICAL WORKS Main


Contractor

Consultant

DOUBLE INTERLOCK PREACTION VALVE & ACC


Scope

www.SFFECO.com
T E C H N IC A L
SUBMITTAL
AL MURJAN MEDICAL CENTRE JEDDAH Project

AL TA'AFUF CO MPANY FOR ELECTRICAL WORKS Contractor

IN D E X
1. MATERIAL REFERENCE LIST
2. MATERIAL TECHNICAL SUBMITTAL
3. MATERIAL CERTIFICATES

Date: 10.10.2021 Submittal No.: 2003

www.SFFECO.com
\

TECHNICAL
SUBMITTAL
Manual

MATERIAL REFERENCE LIST

www.SFFECO.com
Submittal No. : 1010 Date : 10.10.2021
Rev. No. : 00

MATERIAL
LIST

SL.
Item Description Make Part# / Model Approval C.O.O
NO
 DOUBLE INTER LOCK PREACTION DELUGE VALVE & ACCESSORIES
PRE-ASSEMBLED, DOUBLE INTERLOCK
PREACTION FIRE PROTECTION
UL & FM
1. SYSTEMS, E/E ACTUATION; C/W TYCO DV-5A NETHERLANDS
APPROVED
GALVANISED TRIM, PRESSURE SWITCH
& SOLENOID VALVE
UL & FM
2. WATER MOTOR ALARM GONG TYCO WMA-1 CHINA
APPROVED
UL & FM
3. AIR MAINTENANCE DEVICE TYCO AMD-1 U.S.A
APPROVED
TECHNICAL
SUBMITTAL

MATERIAL TECHNICAL
SUBMITTAL

www.SFFECO.com
Worldwide
www.tyco-fire.com
Contacts

DV-5a Automatic Water Control Valve Electric/


Electric Double Interlock Preaction Fire Protection
Systems 1-1/2 Inch to 8 Inch (DN40 to DN200)
General
Description
The TYCO DV-5 a Automatic Water
Control Valves are diaphragm type
valves that can be used in double inter-
lock preaction fire protection systems.
When properly trimmed, the double
seat design of the DV-5a Valve also
provides actuation of fire alarms upon
system operation.
The diaphragm style design of the
DV-5a Valve allows external resetting,
providing for easy resetting of a deluge
system without having to open a valve
handhole cover to manually reposition
a clapper and/or latch mechanism.
Simply re-pressurizing the diaphragm
chamber resets the valve.
The DV-5a features internal and exter-
nal coating of the valve to provide
corrosion resistance. The external cor-
rosion resistance of the epoxy coating
permits the use of the DV-5a in cor- Available End Connections and Weights — lb/(kg)
rosive atmospheres associated with
many types of industrial processing Nominal Valve Size
plants and outdoor installations. End Connection ANSI Inches
(DN)
The DV-5a Valves are offered with the
1 1/2 2 3 4 6 8
DV-5a Valve and separately ordered Inlet Outlet (40) (50) (80) (100) (150) (200)
semi-assembled trim shown in Figures
6 and 7, or, for ease of installation, with 26 25
Thread Thread N/A N/A N/A N/A
DV-5a Valve completely trimmed with or (11,8) (11,3)
without a System Main Control Valve. 25 25 60 95 177 327
Groove Groove
Double interlock preaction systems are (11,3) (11,3) (27,2) (43,1) (80,3) (148,3)
designed for use in applications, such 66 106 190 346
Flange Groove N/A N/A
as refrigerated areas, requiring the (30,0) (48,1) (86,2) (157,0)
maximum degree of protection against
72 116 204 365
inadvertent flooding of the sprinkler Flange Flange N/A N/A (32,7) (52,6) (92,5) (165,6)
system piping. In order for a double
interlock preaction system to automat-
or just the opening of a sprinkler will A solenoid valve is used in the Elec-
ically activate, two independent events
not allow the DV-5a Valve to open and tric/Electric Actuation to hold the DV-5a
must occur. First, the electric detection
permit water to flow into the normally Valve closed by locking pressure in the
system must operate, and secondly,
dry sprinkler system piping. However, diaphragm chamber of the DV-5a Valve.
an automatic sprinkler on the system
operation of just the electric detec- In the event of a fire, Zone 1 of a releas-
piping must operate. Typically, the
tion system or the opening of a sprin- ing panel is initiated by a fire detection
electric detection system is designed to
kler (loss of system air pressure) will or electric manual pull station, and
operate before any automatic sprinkler.
result in a supervisory alarm to notify Zone 2 of the releasing panel is initi-
Operation of just the electric detection,
the building occupants of a condition ated by a low pressure alarm switch
needing attention so as to avoid inad- triggered by loss of system air pres-
vertent flooding of the system piping. sure due to the opening of an auto-
IMPORTANT matic sprinkler. Initiating of Zone 1 and
Refer to Technical Data Sheet 2 results in opening the solenoid valve
TFP2300 for warnings pertaining to to operate the DV-5a Valve.
regulatory and health information.

Page 1 of 20 DECEMBER 2020 TFP1466


TFP1466
Page 2 of 20

Nominal Valve Size ANSI Inch (DN)


Item Description Qty. 1 1/2 (DN40) 2 (DN50) 3 (DN80) 4 (DN100) 6 (DN150) 8 (DN200)
P/N P/N P/N P/N P/N P/N
1 Valve Body 1 N/R N/R N/R N/R N/R N/R
2 Diaphragm 1 545000020 545000020 545000030 545000040 545000060 545000080
3 Diaphragm Cover 1 N/R N/R N/R N/R N/R N/R
4 Hex Bolt, Short 2a 545100001 545100001 545100002 545100003 545100004 545100003
5 Hex Bolt, Long 2 545100011 545100011 545100012 545100013 545100014 545100015
6 Lift Washer 2b N/A N/A 545100021 545100022 545100023 545100022
7 Hex Nut 2 545100031 545100031 545100032 545100033 545100034 545100033
8 Hoist Ring 2 545100041 545100041 545100041 545100041 545100041 545100041
9 Flat Washer 2 N/A N/A 545100024 545100025 545100026 545100025
NOTES c. N/R = Not Replaceable
a. Hex Bolt, Short, Qty. 6 in 6 and 8 inch (DN150 and DN200) assemblies d. Order replacements parts only via Part Numbers given, do not replace Hex Bolt, Hex
b. Lift Washer not used in 1 1/2 and 2 inch (DN40 and DN50) assemblies Nut, Lift Washer or Hoist Ring with common hardware parts

1
1
3
2
7 5
5 3 1-1/2 AND 2 INCH
9 VALVES ONLY
6

3
7 1
4
8

6
4
9 7 5
6 AND 8 INCH
1 2
VALVES ONLY
FIGURE 1
DV-5 a VALVE ASSEMBLY AND REPLACEMENT PARTS

Flange Drilling Specification Dim. A


Nominal Bolt Circle
Valve Nominal Dimensions in Inches and (mm) Diameter
Size
ANSI ANSI B16.1a ISO 7005-2 JIS B 2210 AS 2129 Dim. B
Inches (Class 125) (PN16)b (10K) (Table E)
(DN) Bolt Hole
Diameter
A B N A B N A B N A B N

3 6.00 0.75 6.30 0.75 5.90 0.59 5.75 0.71 Qty. N


4 (160,0) 8 (150,0) 8 (146,0) 4 Number of
(80) (152,4) (19,0) (19,0) (15,0) (18,0)
Bolt Holes
4 7.50 0.75 7.09 0.75 6.89 0.60 7.00 0.71
8 (180,0) 8 (175,0) 8 178,0) 8
(100) (190,5) (19,0) (19,0) (15,0) (18,0) NOTES:
a. Same drilling as for
6 9.50 0.88 9.45 0.91 9.45 0.75 9.25 0.87 ANSI B16.5 (Class 150) and
8 (240,0) 8 (240,0) 8 8
(150) (241,3) (22,2) (23,0) (19,0) (235) (22,0) ANSI B16.42 (Class 150)
b. Same drilling as for
8 11.75 0.88 11.61 0.91 12 11.42 0.75 12 11.50 0.87 BS 4504 Section 3.2 (PN16) and
8 (295,0) 8 DIN 2532 (PN16)
(200) (298,5) (22,2) (23,0) (290,0) (19,0) (292,0) (22,0)

TABLE A
FLANGE DRILLING SPECIFICATIONS
TFP1466
Page 3 of 20

Port Sizes, NPT Inch per ANSI B1.20.1


Port Port Description 1 1/2 2 3 4 6 8
(DN40) (DN50) (DN80) (DN100) (DN150) (DN200)
P1 Diaphragm Chamber Supply 1/2 1/2 1/2 1/2 1/2 1/2
P2 Water Supply Pressure & Alarm Test 1/2 1/2 1/2 1/2 1/2 1/2
P3 Alarm Actuation 3/4 3/4 3/4 3/4 3/4 3/4
P4 Automatic Drain Valve 1/2 1/2 1/2 1/2 1/2 1/2
P5 System Drain 3/4 3/4 3/4 3/4 3/4 3/4
P6 Main Drain 3/4 3/4 1 1/4 2 2 2
P7 System Air Supply 1/2 1/2 1/2 1/2 1/2 1/2
SYSTEM OPEN TO ATMOSPHERE WATERFLOW TO SYSTEM

VALVE SYSTEM
WATERWAY AIR
DIAPHRAGM SUPPLY
SEAT
VALVE
WATERWAY ALARM PORT
DIAPHRAGM WATERFLOW
CHAMBER TO ALARM
DIAPHRAGM
CHAMBER
OPEN TO
AUTOMATIC ATMOSPHERE
DRAIN VALVE AUTOMATIC
OPEN TO DRAIN VALVE
DIAPHRAGM
DIAPHRAGM ATMOSPHERE CLOSED
RETRACTS
CHAMBER
OPENING
SUPPLY
VALVE
FROM
WATERWAY
UPSTREAM WATER SUPPLY
SIDE OF PRESSURE &
SHUT-OFF ALARM TEST
VALVE
WATER SUPPLY WATERFLOW FROM WATER SUPPLY
FIGURE 2A FIGURE 2B
SET CONDITION OPERATED CONDITION

DRAIN FROM SYSTEM RESIDUAL DRAIN FROM SYSTEM

VALVE
WATERWAY
DIAPHRAGM
SEAT

VALVE DIAPHRAGM
WATERWAY AUTOMATICALLY
SYSTEM FLEXES TO SYSTEM
DRAIN ITS SEATED DRAIN
DIAPHRAGM OPEN OPEN
CHAMBER POSTION
OPEN TO
ATMOSPHERE

DIAPHRAGM
CHAMBER
SUPPLY
FROM
UPSTREAM
MAIN SIDE OF MAIN
DRAIN SHUT-OFF DRAIN
OPEN VALVE CLOSED
WATER SUPPLY SHUT OFF WATER SUPPLY SHUT OFF
FIGURE 2C FIGURE 2D
SYSTEM DRAIN CONDITION RESIDUAL DRAIN CONDITION
FIGURE 2
DV-5 a VALVE OPERATION, PREACTION SYSTEMS
TFP1466
Page 4 of 20

DIMENSIONS SHOWN The selection of Electric/Electric versus When the system pressure is greater
ARE APPLICABLE TO Electric/Electric is related to desired than 175 psi (12,1 bar), provision is to be
ALL END CONNECTION system air pressure and system made to replace the standard order 300
CONFIGURATIONS volume that affects water delivery time psi (20,7 bar) Water Pressure Gauges
AVAILABLE PER restraints. with separately ordered 600 psi (41,4
VALVE SIZE bar) Water Pressure Gauges.
NOTICE If the addition of an Alarm Control Valve
The DV-5 a Valves described herein is desired or required by the local AHJ,
10-3/16" must be installed and maintained in the Alarm Control Valve noted as Item
(260 mm) compliance with this document, as H in Figure 8 is to be a separately
well as with the applicable standards ordered electronically supervised nor-
of the NATIONAL FIRE PROTECTION mally open valve.
ASSOCIATION (NFPA), in addition to External trim connections are NPT
1-1/2 Inch (DN40) the standards of any other authorities threaded. EMEA trim is provided with
having jurisdiction. Failure to do so NPT x ISO 7-1 thread adapters.
may impair the performance of these
devices. Pressure Loss
See Graph A
10-3/16" The owner is responsible for main-
(260 mm) taining their fire protection system Actuation Options
and devices in proper operating con- See Electric/Electric Actuation sub-
dition. Contact the installing contrac- section for additional information.
tor or product manufacturer with any
2 Inch (DN50)
questions. Materials of
Technical Construction
13-3/4" Data Valve Body
Epoxy coated ductile iron per ASTM
(349 mm) A536-77, Grade 65-45-12
Approvals
UL/C-UL Listed Diaphragm Cover
FM Approved Epoxy coated ductile iron per ASTM
3 Inch (DN80) Listings and Approvals are based on A536-77, Grade 65-45-12
DV-5a being trimmed as described in Diaphragm
this technical data sheet. Polyester fabric reinforced, TEFLON
DV-5A Valve coated, EPDM rubber per ASTM D2000
Components for the 1 1/2 thru 8 in. Diaphragm Cover Fasteners
16-3/4" (DN40 thru DN200) DV-5a Valves are Aluminum zinc coated steel
(425 mm) shown in Figure 1. The DV-5a Valves
are for vertical installations. They are Common Hardware Trim
rated for use at a service pressures of • Common hardware pipe fittings are
20 to 300 psi (1,4 to 20,7 bar). galvanized or black as required and
4 Inch (DN100) are malleable per ASME B16.3.
The take-out dimensions are shown
in Figure 3, and flanged connections • Common hardware pipe nipples are
are available drilled per ANSI, ISO, galvanized or black as required and
AS, and JIS specifications (See Table are Schedule 40 per ASTM A53 or
A). Threaded inlet and outlet connec- A135.
tions are available in NPT or ISO 7-1. • Common hardware compression
22-3/8" Threaded port connections are NPT fitting are brass per ASTM B16
(569 mm) threaded.
• Common hardware tubing is Type L
NOTE: PN16 flanges are pressure rated per ASTM B88
to 16 bar.
6 Inch (DN150) Valve Trim
The maximum pressure rating for the
Electric/Electric Double Interlock Pre-
action Trim is dependent on separately
ordered solenoid valve per Technical
Data Sheet TFP2180.
27-7/16" Electric/Electric Double Interlock Pre-
(697 mm) action Trim, when using the separately
ordered QRS Electronic Accelerator, is
based on the separately ordered QRS
Electronic Accelerator per Technical
8 Inch (DN200) Data Sheet TFP1100
FIGURE 3
DV-5 a DELUGE VALVE
TAKE-OUT DIMENSIONS
TFP1466
Page 5 of 20

FLOW RATE IN LITERS PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
200 400 600 1000 2000 3000 5000 7000 10000 15000
9.0 0,600
8.0
7.0 0,500
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)

6.0 0,400
5.0
0,300
)
40

4.0
DN
H(

NOMINAL PRESSURE DROP IN BAR


INC

)
3.0 50
0,200
DN
/2
1-1

H(

(1 PSI = 0,06895 BAR)


)
80
NC

DN
2I

2.0
H(

0)
NC

10
DN
3I

0,100
H(

0)
NC 0,090

15
0,080

DN
4I

H(

0)
1.0 0,070

20
NC
0.9

DN
0,060
0.8 6I

H(
0,050

NC
0.7

8I
0.6 0,040
0.5
0,030
0.4

0,022
0.3
50 100 200 400 600 1000 2000 3000 4000
FLOW RATE IN GALLONS PER MINUTE (GPM)
GRAPH A
DV-5 a VALVE
NOMINAL PRESSURE LOSS VERSUS FLOW

Operation in the DV-5a Diaphragm Chamber. The


force differential applied through the
The TYCO DV-5a Valve is a diaphragm Diaphragm to hold the Diaphragm in
style valve that depends upon water the set position is then reduced below
pressure in the Diaphragm Chamber the valve trip point. The water supply
(see Figure 2A) to hold the Diaphragm pressure then forces the Diaphragm
closed against the water supply open permitting water to flow into
pressure. the system piping, as well as through
the Alarm Port to actuate the system
When the DV-5a Valve is set for service, alarms (see Figure 2B).
the Diaphragm Chamber is pressurized
through the trim connections from the Upon opening of the DV-5a Valve, the
inlet side of the system’s main control Model MRA-1 Manual Reset Actua-
valve. tor opens to constantly vent the DV-5a
Diaphragm Chamber to "hydraulically
Opening of a solenoid valve for Electric/ latch" the DV-5a in the tripped position
Electric Actuation (see Figure 4) trips the until manually reset.
Model MRA-1 Manual Reset Actuator.
Tripping the MRA-1 releases water from See Electric/Electric Actuation sub-
the DV-5a Diaphragm Chamber faster section for additional information.
than it can be replenished through the
1/8 in. (3,2 mm) restriction located in
the diaphragm chamber supply con-
nection. Release of water through the
MRA-1 results in a rapid pressure drop
TFP1466
Page 6 of 20

SYSTEM PIPING WITH AUTOMATIC SPRINKLERS - NORMALLY DRY

MANUAL ELECTRIC PULL STATION


(AS REQUIRED) ELECTRIC DETECTION SYSTEM
(TYPICALLY 24 VOLTS DC) SOLENOID
ZONE HEAT DETECTORS, SMOKE DETECTORS, VALVE
1 MANUAL PULL STATIONS, ETC. (TYPICALLY
CROSS-ZONE 24 VOLTS DC)
DELUGE VALVE
RELEASING PANEL SYSTEM
(AUTOMATIC SHUT-OFF VALVE DRAIN
CONTROL UNIT (NORMALLY OPEN)
WITH BATTERY SYSTEM DRAIN VALVE
BACK-UP) WATERFLOW DV-5A
PRESSURE (NORMALLY CLOSED)
VALVE
AUTOMATIC ALARM
POWER AIR/NITROGEN SWITCH MAIN
SUPPLY SUPPLY DRAIN VALVE
(TYPICALLY TYPICALLY DIAPHRAGM CHAMBER (NORMALLY
DRAIN CLOSED)
120 VOLTS AC) 15 PSI PRESSURE GAUGE

SUPERVISORY ZONE LOCAL


LOW PRESSURE 2 RESTRICTION DRAIN MANUAL
ALARM SWITCH DRAIN CONTROL
MANUAL RESET WATER SUPPLY STATION DRAIN
ACTUATOR PRESSURE
GAUGE MAIN
DIAPHRAGM CONTROL VALVE
SYSTEM AIR CHAMBER SUPPLY (NORMALLY
PRESSURE CONTROL VALVE WATER SUPPLY SHUT-OFF DIAPHRAGM CHAMBER WATER OPEN)
GAUGE (NORMALLY OPEN) (NORMALLY OPEN) SUPPLY CONNECTION SUPPLY
FIGURE 4
DV-5 a VALVE - DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION
SCHEMATIC DIAGRAM

Electric/ electric detection system and one or


more automatic sprinklers. Refer to
package is given in Technical Data
Sheet TFP2180. Nominal installation
Electric Technical Data Sheet TFP1100 for
details regarding installation require-
dimensions for the Double Interlock
Preaction System With Electric/Electric
Actuation ments and pressure ratings.
Note: Use of the Model QRS Electronic
Actuation Trim are shown in Figure 7.
The cross-zone deluge valve releas-
System Design Considerations Accelerator can permit system volumes ing panel (automatic control unit)
Because a double interlock preac- of 750 gallons (2840 Liters) without with battery back-up, fire detection
tion system requires time for a drop in applying the minimum one minute devices, manual pull stations, and sig-
system air pressure to occur (concur- water delivery time. naling devices, that are utilized with the
rently with the response time for the Double Interlock Preaction System with
In order to readily perform the System
separate fire detection system) before Electric/Electric Actuation must be UL
Inspection Procedure described in
it will allow water to enter the system Listed, ULC Listed, C-UL Listed, or FM
the Care and Maintenance section,
piping, this system has characteristics Approved, as applicable.
it is recommended that a System
similar to a dry pipe sprinkler system. Shut-Off Valve be installed above the NOTES:
Therefore, the system design con- DV-5a Valve, as shown in Figure 4. The The normally closed, de-energized
siderations for a dry pipe system are System Shut-Off Valve should be a solenoid Valve is separately ordered and
normally applied to a double interlock listed or approved (as appropriate) indi- selected based on the required laboratory
preaction system, — including: a 30% cating valve with a supervisory switch approval acceptable to the authority having
increase in design area; a maximum to monitor the normally open position. jurisdiction. Refer to technical data Sheet
1 minute water delivery time for system TFP2180 for specific laboratory approvals.
capacities of 500 gallons (1890 liters) Detection System
or more; and, prohibition of gridded The Double Interlock Preaction System Consult with the authority having
system piping. With Electric/Electric Actuation Trim jurisdiction regarding installation criteria
provides for electric operation of the pertaining to electric actuation circuitry.
As an option, the DV-5a Double Inter- DV-5a Valve by a detection system
lock Preaction System with Electric/ Due to the functionality of the Model
consisting of electrical devices such MRA-1 Manual Reset Actuator, the
Electric Actuation may be equipped as heat sensitive thermostats, smoke
with the Model QRS Electronic Accel- release circuit of the releasing panel
detectors, and/or electric manual pull need only provide the typical ten
erator to reduce the time to valve actu- stations. Information on the various
ation following the operation of the minutes of alarm condition intended
types of separately ordered Solenoid to energize the Solenoid Valve to
Valves that may be used with this trim
TFP1466
Page 7 of 20

45 Notes:
URE The dew point of the pilot line air pressure must be maintained
IR PRESS below the lowest ambient temperature to which the dry pilot
EM A
AIR PRESSURE IN PSI

YST actuation system will be exposed. Accumulation of water in the


UM S
30 MINIM pilot line connection to the Actuator will lower the air pressure
at which the actuator will open and possibly prevent proper
SURE
ING PRES operation. Also, introduction of moisture into the pilot lines
OPEN exposed to freezing temperatures can create an ice buildup
TOR
CTUA that could prevent proper operation of the Actuator.
15 E OF A
RANG An air dryer must be installed where the moisture content
of the air supply is not properly controlled at less than the
required value.
0 It is recommended that an AMD-3 Nitrogen Maintenance
Device be utilized in dry pilot actuation system applica-
20 60 100 140 180 200 250
tions where the dew point must be maintained below -20°F
(-29°C). Refer to Technical Data Sheet TFP1241.
WATER SUPPLY PRESSURE IN PSI
GRAPH B
DV-5 a VALVE DOUBLE INTERLOCK PREACTION SYSTEM
AIR PRESSURE REQUIREMENTS

open. After the ten minute duration, at alarm of the Low Pressure Switch on The dew point of the air or nitrogen
which point should the Solenoid Valve increasing pressure. The Low Pressure supply, for a system exposed to freezing
become de-energized and close (espe- Switch is field set to alarm at nominally conditions, must be maintained below the
cially while operating under battery 12 psi (0,8 bar) on decreasing pres- lowest ambient temperature to which the
back-up), the MRA-1 will have already sure when using a nominal system air system piping will be exposed. Introduction
automatically opened, thereby prevent- pressure of 15 psi (1,0 bar). It is recom- of moisture into the system piping can
ing the DV-5a Diaphragm Chamber mended that the system air pressure create ice build up which could prevent
from becoming re-pressurized, and be maintained by either of the follow- proper operation of the system.
preventing an inadvertent closing of ing methods: The Air Pressure Relief Valve is typi-
the DV-5a during a fire event. cally field set to crack open at a pres-
• A maximum 200 psi (13,8 bar) plant
air supply in combination with the sure of about 20 psi (1,4 bar) when
WARNING Model AMD-1 Air Maintenance using a nominal system air pressure of
If the delay between electric actua- Device described in Technical Data 15 psi (1,0 bar).
tion and subsequent sprinkler activa- Sheet TFP1221
tion is anticipated to be greater then • A maximum 3000 psi (206,9 bar)
10 minutes, adjust the battery back-up nitrogen cylinder in combination with
calculation accordingly. Inadequate the Model AMD-3 Nitrogen Mainte-
battery back-up may result in failure of nance Device described in Technical
the system to operate in the event of a Data Sheet TFP1241
fire during a power failure.
NOTES:
Releasing Circuit It is recommended that the pressure
The releasing circuit must be equipped maintenance device be of a type that
with a Potter RCDS-1 Releasing Circuit maintains a constant system pressure, i.e.,
Switch, or equivalent. The RCDS-1 a pressure maintenance device that utilizes
provides for a temporary disconnect a pressure regulator versus a pressure
(de-energized) of the Solenoid Valve switch (e.g., the AMD-1 or AMD-3). Use
during Step 9 of the Valve Resetting of a pressure switch operated pressure
Procedure. maintenance device with a cut-in/cut-
System Air Pressure Requirements out differential may result in a delay in
The recommended system air pres- the operation of the system due to a fire,
sure for the Double Interlock Preaction because of the cut-out pressure being
System with Electric/Electric Actuation higher than the recommended nominal
is nominally 15 psi (1,0 bar), irrespective system air pressure.
of the water supply pressure. The use
of a higher system air pressure may or
may not adversely affect water deliv-
ery time, and the use of a lower system
air pressure may prevent clearing the
TFP1466
Page 8 of 20

Installation burrs before installation. Use pipe


thread sealant sparingly on male pipe
Step 10. A desiccant dryer, when spec-
ified, is to be installed between a drip
The TYCO DV-5a Valve is to be installed threads only. leg and the Air Maintenance Device.
in accordance with this section. Step 2. The DV-5a Valve must be Step 11. The Low Pressure Switch on
trimmed in accordance with one of the falling pressure in the Electric/Electric
NOTICE trim illustrations shown in Figure 5. Actuation is to be adjusted so that the
DV-5A Automatic Water Control Valves low pressure alarm setting is set at
Note: If the addition of an Alarm Control
are designed to be used in freshwater 3 psi (0,21 bar) below the system air
Valve is desired or required by the local
systems. When the supply is from an pressure.
AHJ, the Alarm Control Valve noted as
alternative source such as brackish Item H in Figure 8 is to be a separately Step 12. Unused Pressure Alarm
water, saltwater, or contains additives ordered electronically supervised normally Switch connections must be plugged.
such as foam, the limited warranty is open valve.
reduced to one year from the time of Step 13. The Pressure Relief Valve on
installation. An increase in frequency of Step 3. Care must be taken to ensure rising pressure is to be at 5 psi (0,34 bar)
inspections is required when the valve that check valves, strainers, globe higher than the required system air
is exposed to such supplies and other valves, etc., are installed with the flow pressure, or be reset in accordance
corrosive conditions or chemicals that arrows in the proper direction. with the requirements of the authority
could impact valve materials or the having jurisdiction.
Step 4. Drain tubing to the Drip Funnel
operation of the assembly. The system must be installed with smooth bends To reset the Pressure Relief Valve, first
and all components must be designed that will not restrict flow. loosen the jam nut and then adjust the
accordingly for the increased demand. cap accordingly, clockwise for a higher
It is required to thoroughly flush the Step 5. The Main Drain and Drip Funnel
pressure setting or counter clockwise
valve and trim assembly with freshwa- Drain may be interconnected provided
for a lower pressure setting. After ver-
ter and reset to the set condition after a check valve is located at least 12 in.
ifying the desired pressure setting,
each operation. (300 mm) below the Drip Funnel.
tighten the jam nut.
Proper operation of the DV-5a Valves Step 6. Suitable provision must be
Step 14. Conduit and electrical con-
depends upon their trim being installed made for disposal of drain water. Drain-
nections are to be made in accordance
in accordance with the instructions age water must be directed such that
with the applicable standards of the
given in this technical data sheet. it will not cause accidental damage to
approval agency.
Failure to follow the appropriate trim property or danger to persons.
Step 15. Before a system hydrostatic
diagram may prevent the DV-5a Valve Step 7. Connect the Diaphragm Supply
test is performed, the DV-5a Diaphragm
from functioning properly, as well as Valve to the inlet side of the System
Chamber is to be depressurized, the
void approvals and the manufacturer’s Main Control Valve in order to facilitate
Automatic Drain Valve is to be tem-
warranties. setting of the DV-5a Valve (see Figure
porarily replaced with a plug, and the
The DV-5a Valve must be installed in a 8).
Diaphragm Cover Bolts must be uni-
readily visible and accessible location. Step 8. An Inspector’s Test Connection formly and securely tightened using
The DV-5a Valve and associated trim is to be located on the sprinkler system a cross-draw sequence. After tight-
must be maintained at a minimum tem- at the most hydraulically demanding ening, double-check to make certain
perature of 40°F (4°C). location. that all of the Diaphragm Cover Bolts
Step 9. A suitable automatic air (nitro- are securely tightened. See Table B in
Heat tracing of the DV-5a Valve or its the Care and Maintenance section for
associated trim is not permitted. Heat gen) supply, as described in the appli-
cable Electric/Electric Actuation torque specifications.
tracing can result in the formation of
hardened mineral deposits that are sub-section, is to be installed in accor-
capable of preventing proper operation. dance with the applicable technical
data sheet. The minimum air pressure
Always open the system control valves is to be in accordance with the refer-
slowly to avoid a sudden rush of water enced sub-sections.
entering the system.
The DV-5a Valve is to be installed in
accordance with the following criteria:
Step 1. All nipples, fittings, and devices
must be clean and free of scale and
TFP1466
Page 9 of 20

A3

C5 L

D
C
C3
F
P4 E
P7
A2
A
P5

C2 C4 P6
C7 A7

H P3 A1
J
B
P1 C6
P2
G
A5
K
A4

A5 C1

A6
1-1/2" (DN40) AND 2" (DN50) Assemble in order
VALVES ONLY from A to L
A8

A10
A9

Notes:
1. Port Connections P1 through P7 are described in Figure 2.
2. External Trim Connections C1 through C5 are described in Figure 8.
3. When ordering pre-assembled "DV-5A Valve with Galvanized Trim" or pre-assembled "DV-5A Valve with Galvanized Trim and Butterfly Valve", Items A1
through A10 are provided, as applicably related to valve size, and Item A7 is provided as P/N 52-287-1-124 described in Technical Data Sheet TFP2180
4. When ordering DV-5A Trim separately from the DV-5A Valve, Items A1 through A10 are separately ordered, as applicably related to valve size. Water
Pressure Gauges for EMEA valve trim are also separately ordered.

FIGURE 5
DV-5 a VALVES
DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION TRIM
SEMI-ASSEMBLED
TFP1466
Page 10 of 20

A3

39 27
28 36
C5

26 51 27
52 57
21
22 1
42 41 47 34
17
P4 30
P7 49 A7
36
20 29 10
A2 P5 55 36
8
36
C4 14 36
13 4
C2 31
P6 54 20 24 6
32
53 16 C3
44 A1 33 43 39
P3
23 15 40
32 P1 C7 29
P2 C6
48 Notes:
12 59 1. Port Connections P1 through P7
50 3
19 A5 37 are described in Figure 2.
24 58 2. External Trim Connections C1
38 5 46 through C5 are described in
56
31 A4 11 56 Figure 8.
3. When ordering pre-assembled
35 37 18 "DV-5A Valve with Galvanized
25 2 Trim" or pre-assembled "DV-5A
Valve with Galvanized Trim
27 1 21 9 and Butterfly Valve", Items A1
37 27
7 45 through A10 are provided, as
19 17 applicably related to valve size,
37 and Item A7 is provided as P/N
A5 52-287-1-124 described in
C1 7 Technical Data Sheet TFP2180
4. When ordering DV-5A Trim
A6 separately from the DV-5A Valve,
A10 Items A1 through A10 are sepa-
A8 A9 rately ordered, as applicably
related to valve size. Water Pres-
sure Gauges for EMEA valve trim
1-1/2" (DN40) AND 2" (DN50) are also separately ordered.
VALVES ONLY
ITEM QTY DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
1 2 1/4” GAUGE TEST VALVE 460051003 460051003 460051003 460051003 460051003 460051003
2 1 MRA-1 MANUAL RESET ACTUATOR 545001000 545001000 545001000 545001000 545001000 545001000
3 1 MC-2 MANUAL CONTROL STATION 545002000 545002000 545002000 545002000 545002000 545002000
4 1 AD-3 AUTOMATIC DRAIN VALVE 547932004 547932004 547932004 547932004 547932004 547932004
5 1 PRIMING SUPPLY RESTRICTION 545100051 545100051 545100051 545100051 545100051 545100051
6 1 1/4” PRESSURE RELIEF VALVE 923431020 923431020 923431020 923431020 923431020 923431020
7 2 1/2” BALL VALVE 460501004 460501004 460501004 460501004 460501004 460501004
8 1 1/2” GLOBE VALVE 460471005 460471005 460471005 460471005 460471005 460471005
9 1 1/2” SPRING LOADED CHECK VALVE 923221003 923221003 923221003 923221003 923221003 923221003
10 1 1/2” SWING CHECK VALVE 460491007 460491007 460491007 460491007 460491007 460491007
11 1 1/2” Y-STRAINER 523531006 523531006 523531006 523531006 523531006 523531006
12 1 3/4” ANGLE VALVE 460481010 460481010 460481010 460481010 460481010 460481010
13 1 ANGLE VALVE 460481010 460481010 460481011 460481012 460481012 460481012
14 1 DRIP FUNNEL BRACKET CONNECTOR 922111005 922111005 922111005 922111005 922111005 922111005
15 1 DRIP FUNNEL BRACKET 922111003 922111003 922111003 922111003 922111003 922111003
16 1 DRIP FUNNEL 923431007 923431007 923431007 923431007 923431007 923431007
17 2 COMP. FITTING 90° 1/2” MNPT x 1/2” OD TUBE 1001253-01 1001253-01 1001253-01 1001253-01 1001253-01 1001253-01
18 1 COMP. FITTING 90° 1/2” FNPT x 1/2” OD TUBE 1001420-01 1001420-01 1001420-01 1001420-01 1001420-01 1001420-01
19 2 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
20 2 FLARE FITTING 3/4” NPT x 3/4” TUBE 545100063 545100063 545100063 545100063 545100063 545100063
21 2 PIPE PLUG ✓ 1/4” 1/4” 1/4” 1/4” 1/4” 1/4”
22 1 PIPE PLUG ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
23 1 PIPE PLUG ✓ 3/4” 3/4” 3/4” 3/4” 3/4” 3/4”
24 2 UNION ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”

FIGURE 6 (1 OF 2)
DV-5 a VALVES
DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION TRIM
EXPLODED VIEW
TFP1466
Page 11 of 20

ITEM QTY DESCRIPTION CH 1-1/2 IN. (DN40) 2 IN. (DN50) 3 IN. (DN80) 4 IN. (DN100) 6 IN. (DN150) 8 IN. (DN200)
25 1 STREET ELBOW ✓ 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90° 1/4” x 90°
26 1 ELBOW ✓ 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45° 1/2” x 45°
27 4 ELBOW ✓ 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90° 1/2” x 90°
28 1 CROSS ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
29 2 TEE ✓ 1/2” 1/2” 1/2” 1/2” 1/2” 1/2”
30 1 REDUCING TEE ✓ 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2” 1/2” x 1/4” x 1/2”
31 2 REDUCING TEE ✓ 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4” 1/2” x 1/2” x 1/4”
32 2 REDUCING TEE ✓ 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4” 3/4” x 1/2” x 3/4”
33 1 REDUCING TEE ✓ 3/4” x 3/4” x 3/4” 3/4” x 3/4” x 3/4” 1-1/4” x 1-1/4” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4” 2” x 2” x 3/4”
34 1 PIPE NIPPLE ✓ 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE 1/4” x CLOSE
35 1 PIPE NIPPLE ✓ 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2” 1/4” x 1 1/2”
36 5 PIPE NIPPLE ✓ 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE 1/2” x CLOSE
37 4 PIPE NIPPLE ✓ 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2” 1/2” x 1 1/2”
38 1 PIPE NIPPLE ✓ 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2” 1/2” x 2”
39 2 PIPE NIPPLE ✓ 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2” 1/2” x 2 1/2”
40 1 PIPE NIPPLE ✓ 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2” 1/2” x 4 1/2”
41 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5” 1/2” x 5”
42 1 PIPIE NIPPLE ✓ 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2” 1/2” x 8 1/2”
43 1 PIPE NIPPLE ✓ 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2” 3/4” x 1 1/2”
44 1 PIPE NIPPLE ✓ 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2” 3/4” x 4 1/2”
45 1 TUBING, MRA-1 DRAIN 545100065 545100065 545100066 535002140 535002160 535002180
46 1 TUBING, MC-2 DRAIN 535000220 535000220 535000230 535000240 535000260 535000280
47 1 TUBING, SOLENOID DRAIN 535001020 535001020 535000630 535000640 535000660 535000680
48 1 TUBING ASSY, ALARM TEST INTERCONNECT 535000320 535000320 535000330 535000340 535000360 535000380
49 1 TUBING ASSY, SYSTEM DRAIN 535000420 535000420 535000430 535000440 535000460 535000480
50 1 PIPE NIPPLE ✓ 1/2” x 3 1/2” 1/2” x 3 1/2” 1/2” x 4 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 3/4”
51 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 5 1/2” 1/2” x 6 1/2”
52 1 PIPE NIPPLE ✓ 1/2” x 5” 1/2” x 5” 1/2” x 4 1/2” 1/2” x 5” 1/2” x 7 1/2” 1/2” x 9 1/2”
53 1 PIPE NIPPLE ✓ 3/4” x 5” 3/4” x 5” 3/4” x 6” 3/4” x 7” 3/4” x 9” 3/4” x 11 1/2”
54 1 PIPE NIPPLE ✓ 3/4” x 4 1/2” 3/4” x 4 1/2” 1-1/4” x 3 1/4” 2” x 3” 2” x 3” 2” x 3”
55 1 PIPE NIPPLE ✓ 3/4” x 6 1/2” 3/4” x 6 1/2” 1-1/4” x 5 1/2” 2” x 5” 2” x 6” 2” x 8”
WATER PRESSURE GAUGE, 300 PSI / 2000 kPa
2 923431005 923431005 923431005 923431005 923431005 923431005
(AMER/APAC)
56
WATER PRESSURE GAUGE, 20 bar / 2000 kPa
2 025500013 025500013 025500013 025500013 025500013 025500013
(EMEA)
AIR PRESSURE GAUGE, 80 PSI / 550 kPa
57 1 923431012 923431012 923431012 923431012 923431012 923431012
RETARDED TO 250PSI / 1750 kPa
58 1 LABEL 545003005 545003005 545003005 545003005 545003005 545003005
59 1 LABEL WIRE — — — — — —
A1 1 DV-5A VALVE SEE ORDERING PROCEDURE, SEPARATE DV-5A VALVES WITHOUT TRIM, FOR PART NUMBERS
WATERFLOW PRESSURE ALARM SWITCH,
1 25710 25710 25710 25710 25710 25710
PS10-2 (AMER/APAC)
A2
WATERFLOW PRESSURE ALARM SWITCH,
1 0260 0260 0260 0260 0260 0260
PS10-1 (EMEA)
LOW AIR PRESSURE ALARM SWITCH, PS40-2
1 25730 25730 25730 25730 25730 25730
(AMER/APAC)
A3
LOW AIR PRESSURE ALARM SWITCH, PS40-1
1 0262 0262 0262 0262 0262 0262
(EMEA)
1 BUTTERFLY VALVE, G x G 51024A 51021A — — — —
A4
1 BFV-300 BUTTERFLY VALVE, G x G — — 59300G030WS 59300G040WS 59300G060WS 59300G080WS
2 FIGURE 577 RIGID GROOVED COUPLING 57715ACP 57720ACP — — — —
A5
1 FIGURE 577 RIGID GROOVED COUPLING — — 57730ACP 57740ACP 57760ACP 57780ACP
A6 1 GROOVE x THREADED OUTLET WELDED TEE 545004000 545004001 — — — —
SOLENOID VALVE NORMALLY CLOSED
A7 1 SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180 SEE TFP2180
(SEPARATELY ORDERED)
A8 1 INVERTED FLARE SHUT-OFF VALVEa 545100100 545100100 545100099 545100100 545100100 545100100
A9 1 FLARE FITTING 90° 1/2” NPT x 1/2” TUBE 545100062 545100062 545100062 545100062 545100062 545100062
A10 1 TUBING ASSY, DIAPHRAGM CHAMBER SUPPLY 540000015 540000020 540000030 540000040 540000060 540000080

NOTES
a. Not VdS Approved
CH - Common Hardware - Refer to Materials of Construction section for specifications.

FIGURE 6 (2 OF 2)
DV-5 a VALVES
DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION TRIM
EXPLODED VIEW
TFP1466
Page 12 of 20

Nominal
Valve Inches
Size (mm)
ANSI
Inches A B C D E F G H J
(DN)
1 1/2 2.8 9.7 10.4 15.7 16.2 7.3 10.2 8.0 1.2
(40) (71) (246) (264) (399) (412) (185) (259) (203) (31)
2 2.8 9.7 10.4 15.7 16.2 7.3 10.2 3.8 2.9
(50) (71) (246) (264) (399) (412) (185) (259) (97) (74)
3 3.0 10.9 12.0 16.3 18.5 5.8 13.8 3.9 3.6
(80) (76) (277) (305) (414) (470) (147) (351) (99) (91)
4 3.0 12.2 13.1 16.5 21.0 5.1 16.8 4.5 4.3
(100) (76) (310) (333) (419) (533) (129) (427) (114) (109)
6 4.5 13.6 15.0 18.4 24.8 3.4 22.4 5.9 5.7
(150) (114) (345) (381) (467) (630) (86) (569) (150) (145)
8 5.3 16.3 17.2 19.5 29.1 2.9 27.5 5.2 6.7
(200) (135) (414) (437) (495) (739) (74) (699) (132) (170)
Notes:
1. Dimensions based on drain valves being open.
2. Dimensions do not provide installation clearance.

J B C D

H F

FIGURE 7
DV-5 a VALVE
DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION TRIM
NOMINAL DIMENSIONS
TFP1466
Page 13 of 20

Valve Setting Step 9. De-energize the Solenoid Valve


(V) via the Potter RCDS-1 Releasing
Step 16. Reset the electric detection
system in accordance with the man-
Procedure Circuit Disable Switch, or equivalent.
Step 10. Operate (open) the Manual
ufacturer's instructions. After setting
the releasing panel, return the Potter
RCDS-1 to "green light - releasing
Perform Steps 1 through 20 when ini- Control Station (M) and then open
circuit system normal".
tially setting the TYCO DV-5a Valve, the Diaphragm Supply Valve (P). After
after an operational test of the fire pro- unaerated water ceases to discharge Step 17. Partially open the System
tection system, or after system opera- from the Manual Control Station (M) Main Control Valve (B). Slowly close the
tion due to a fire. See Figure 8. drain tube, slowly close the operating Main Drain Valve (D) as soon as water
lever by pushing it up. Do not close the discharges from the Main Drain Valve
Step 1. Close the System Main Control
hinged cover at this time. (D). Observe the Automatic Drain Valve
Valve (B).
(F) for leaks. If there are leaks, deter-
Step 11. After allowing water to flow out
Step 2. Close the Diaphragm Supply mine/correct the cause of the leakage
of the Manual Reset Actuator (N) drain
Valve (P) and Air Supply Valve (S). problem before proceeding.
tube until aerated water ceases to dis-
Step 3. Open the Main Drain Valve (D), charge, reset the Manual Reset Actua-
System Drain Valve (E), and all auxil- tor (N) by pressing the Reset Knob and NOTICE
iary drains in the system. Close the hold until water stops flowing from its When the System Main Control Valve
auxiliary drain valves and the System drain tube and the pressure builds and (B) is partially opened, the pressure on
Drain Valve (E) after water ceases to reaches approximately 15 psi (1,0 bar) the DV-5a Diaphragm Chamber may
discharge. Leave the Main Drain Valve on the Diaphragm Gauge (K). Pressure increase. This increase in pressure is
(D) open. will then build up in the DV-5a Dia- normal, and if the pressure is greater
At this time make certain that the phragm Chamber. than 300 psi (20,7 bar), the pressure
Pressure Gauge Valves and the Alarm Step 12. Inspect the actuation device is to be relieved by partially and tem-
Control Valve (H), as applicable, are drain connections. Any leaks must be porarily opening the Manual Control
open. corrected before proceeding to the Station (M); however, do not allow
next step. Electric/Electric Actuation the pressure as indicated on the Dia-
drain connection to be inspected are phragm Gauge (K) to drop below the
NOTICE supply pressure shown on the Water
from the Manual Control Station (M)
Do not open the Inspector’s Test Con- and Solenoid Valve (V) shown in Figure Supply Gauge (J), since this action may
nection and auxiliary drains if reset- 4. result in tripping of the DV-5a Valve.
ting after a system test; otherwise,
system air pressure will be relieved Step 13. Verify the ability for the DV-5a Step 18. Close the hinged cover on the
unnecessarily. Diaphragm to hold pressure as follows: Manual Control Station (M) and insert a
new break rod in the small hole through
Step 4. Depress the plunger of the • With the diaphragm chamber pres- the top of the enclosing box.
Automatic Drain Valve (F) to verify that surized per Step 11, temporarily
it is open. close the Diaphragm Supply Valve Step 19. Fully open the System Main
(P), and then observe the Diaphragm Control Valve (B).
Step 5. Clean the Diaphragm Supply Gauge (K) for a drop in pressure.
Strainer (Q) by removing the clean- Step 20. After setting a fire protec-
out plug and strainer basket. The Dia- • If a drop in pressure is noted, the tion system, notify the proper authori-
phragm Supply Strainer (Q) may be DV-5a Diaphragm is to be replaced ties and advise those responsible for
flushed out by momentarily opening and/or any leaks must be corrected monitoring proprietary and/or central
the Diaphragm Supply Valve (P). before proceeding to the next step. station alarms.

Step 6. Inspect for and clear all ice • If the Diaphragm Gauge (K) indicates
plugs where system piping has been no drop in pressure, re-open the Dia-
exposed to freezing conditions and phragm Supply Valve (P) and pro-
when there has been a flow of water ceed to the next step.
into the system. Step 14. Open the Air Supply Valve
Step 7. Replace all damaged or oper- (S) and allow the system to automati-
ated sprinklers. Replacement sprinklers cally re-establish its nominal system
must be of the same type and tempera- air pressure. Observe the Automatic
ture rating as those that operated. Drain Valve (F) for leaks. If there are
leaks, determine/correct the cause of
NOTICE the leakage problem.
In order to prevent the possibility of a • Nominal system air pressure for Elec-
subsequent operation of an overheated tric/Electric Actuation is typically 15
solder type sprinkler, any solder type psi (1,0 bar).
sprinklers possibly exposed to a tem- Step 15. Open the System Shut-Off
perature greater than their maximum Valve (X), as will be the case when
rated ambient must also be replaced. resetting a system after performing an
Step 8. Service the air dryer, if appli- operational test.
cable, in accordance with the manu-
facturer’s instructions.
TFP1466
Page 14 of 20

Item Description Item Description External Trim Connections


A DV-5a Valve N Manual Reset Actuator C1 Diaphragm Supply Connection
B System Main Control Valve P Diaphragm Supply Valve C2 Water Motor Alarm Connection
C Waterflow Pressure Switch Q Diaphragm Supply Strainer C3 Air Supply Connection
D Main Drain Valve R Inverted Flare Shut-Off Valve C4 Waterflow Pressure Alarm Switch
E System Drain Valve S Air Supply Valve Connection
F Automatic Drain Valve T Air Pressure Relief Valve C5 Low Air Pressure Switch
G Alarm Test Valve U Low Air Pressure Alarm Switch Connection
H Alarm Control Valve (Optional) V Solenoid Valve C6 Main Drain Connection
J Water Supply Gauge W Not Used C7 Drip Funnel Drain Connection
K Diaphragm Gauge X System Shut-Off Valve
L System Gauge (Shown in Figure 4)
M Manual Control Station

LOCATION
FOR OPTIONAL C5
ELECTRICALLY
SUPERVISED L
N.O. ALARM
CONTROL
VALVE
C
X P4
P7 V
F
S
P5
C2 T
C4

D
P6

H A C3
P3

P1 C7 M
P2 C6
E

J K
B

Q
G
P
C1
R

NOTES
• Port Connections P1 through P7 are described in Figure 2.

FIGURE 8
DV-5 a VALVE - DOUBLE INTERLOCK PREACTION ELECTRIC/ELECTRIC ACTUATION
(See Figure 6 for specific Bills of Materials)
TFP1466
Page 15 of 20

Care and It is recommended that the System


Inspection Procedure be performed
A drop in the water supply pressure
to below its normal range (as in the
Maintenance at least semi-annually by a quali-
fied Inspection Service. The Double
case of an interrupted water supply
condition) constitutes an emergency
The following procedures and inspec- Interlock Preaction System Inspec- impairment.
tions must be performed as indicated, tion Procedure may be followed in lieu Should this condition occur, immedi-
in addition to any specific require- of performing any of the operational ately close the System Main Control
ments of the NFPA and any applicable tests recommended in the Technical Valve (B) and use the following proce-
standards recognized by the Approval Data Sheets for the 24 VDC Solenoid dure to reset the system:
agency. Any impairment must be imme- Valve and Model MC-1 Manual Control
Station. Step 1. Prior to the water supply pres-
diately corrected. See Figure 8.
sure being restored to the closed
It is recommended that the individuals System Main Control Valve (B), note the
NOTICE responsible for the care and mainte- pressure indicated by the Diaphragm
If the water supply needs to be shut off nance of the Double Interlock Preaction Gauge (K) and determine if the pres-
to the DV-5a valve and trim and cannot System develop a working understand- sure is within the normally expected
be shut off upstream of the system, ing of the system, in general, prior to range.
close the System Main Control Valve performing inspection and/or mainte-
nance procedures. These instructions, Step 2. If the diaphragm chamber pres-
(B), the Diaphragm Supply Valve (P),
as well as individual instructions for sure is below the normal range, check
and the Water Supply Shut-Off Valve
the solenoid valve, dry pilot actuator, for and correct any source of leakage
(R). This will allow any trim above the from the diaphragm chamber prior to
manual control station, switches, and
System Main Control Valve (B) to be resetting the system.
pressure maintenance device should
taken apart for service if necessary. be reviewed. Step 3. After the water supply pres-
The frequency at which the following The following procedures pertain to sure is restored to the System Main
procedures and inspections are to be the automatic control valve portion of Control Valve (B), reset the DV-5a Valve
performed are to be in accordance with the Double Interlock Preaction System. in accordance with the Valve Setting
the NFPA and any applicable specific Refer to the manufacturer’s instructions Procedure section.
requirements of the standards recog- and NFPA 25 for care and maintenance
nized by the Approval agency. procedures for all other devices (e.g., NOTICE
Before closing a fire protection system electric detection, main control and For fire protection systems subject to
main control valve for maintenance system shut-off valves, supervisory an emergency impairment caused by
work on the fire protection system that devices, sprinklers, etc.). an interrupted water supply condition,
it controls, permission to shut down Before performing the System Inspec- it is recommended that consideration
the affected fire protection systems tion Procedure or Waterflow Alarm be given to installing a low water supply
must first be obtained from the proper Test Procedure, which will result in pressure switch with the appropriate
authorities and all personnel who may operation of alarms, notify the proper alarm/indications to monitor the water
be affected by this action must be authorities and all personnel who may supply pressure.
notified. be affected. Waterflow Alarm Test Procedure
The owner is responsible for the To test the waterflow alarm, open the
Drop in Water Supply Pressure
inspection, testing, and maintenance Alarm Test Valve (G), which will allow a
of their fire protection system and Below Normal Range
flow of water to the Waterflow Pressure
devices in compliance with this docu- NOTICE Switch (C) and/or Water Motor Alarm.
ment, as well as with the NFPA and any Upon satisfactory completion of the
applicable standards recognized by the If the water supply pressure is signif-
icantly reduced below the normally test, close the Alarm Test Valve (G).
Approval agency. Contact the install-
ing contractor or product manufacturer expected static pressure range (as To ensure drainage of the alarm line,
with any questions. could occur in the case of a water main depress the plunger on the Automatic
break or repair), and there is a subse- Drain Valve (F).
Some procedures in this section result quent drop in the diaphragm chamber
in the operation of the associated water pressure below its normal range
alarms. Notify the owner and the fire (for example, due to a leak in a piping
department, central station, or other connection to or from the diaphragm
signal station to which the alarms are chamber or, a leak in the diaphragm
connected before performing the tests. chamber check valve caused by dirt or
It is recommended that automatic debris in the check valve seal area), a
sprinkler systems be inspected, tested, deluge valve such as the DV-5a could
and maintained by a qualified Inspec- inadvertently trip, if its water supply
tion Service in accordance with the pressure is quickly restored.
NFPA and any applicable standards
recognized by the Approval agency.
TFP1466
Page 16 of 20

Step 4. Open the Inspector’s Test Con- Step 11. Manually operate Zone 1 of
Torque nection to relieve system air pressure, the Releasing Panel, and then operate
Nominal lb-ft and verify the following: Zone 2 of the Releasing Panel by par-
Valve Sizes (N∙m)
tially opening the System Drain Valve
ANSI • That the Low Air Pressure Alarm
Inches Short (E) to relieve air pressure at the Low Air
Switch (U) and Zone 2 of the Releas-
(DN) Nuts Hex Pressure Alarm Switch (U), and verify
Bolts ing Panel, as well as its associated
the following:
alarms, operate properly. The Low
1 1/2 44 35 Air Pressure Alarm Switch (U) should • That the DV-5a Valve operates as is
(40) (59,7) (47,5) operate at the previously established indicated by a discharge of water
2 44 35
pressure (see Installation section, from the System Drain Valve (E) and
(50) (59,7) (47,5) Step 9). the Automatic Drain Valve (F). The
Automatic Drain Valve (F) may or may
3 188 150 • That there is no leakage from the
not close depending on the flow past
(80) (254,9) (203,4) Solenoid Valve (V).
the partially open System Main Con-
4 396 316 Step 5. Close the Inspector’s Test trol Valve (B)
(100) (536,9) (428,4) Connection.
• That the Model MRA-1 Manual Reset
6 265 212 NOTE: During this procedure, the Solenoid Actuator (N) has operated as is indi-
(150) (359,3) (287,4) Valve (V) should remain closed and the cated by water discharging into the
DV-5a Valve Diaphragm Chamber should Drip Funnel from the 1/2 in. drain
8 545 436
(200) (738,9) (591,1) remain pressurized. tube connected to the Model MRA-1
This procedure is used to verify that the Manual Reset Actuator (N)
TABLE B DV-5a Valve will remain set if the Low • That the Waterflow Pressure Switch
DIAPHRAGM COVER BOLTS Air Pressure Alarm Switch (U) (Zone 2) (C) and its associated alarms prop-
MINIMUM TORQUE operates due to loss of system air pressure erly operate
and the electric detection system (Zone 1)
Electric/Electric Actuation remains in a normal condition. • That the Water Motor Alarm, if appli-
System Operation Procedure cable, properly operates
Proper operation of the DV-5a Valve for Step 6. Restore the electric fire detec-
tion system to a normal condition in NOTE: This procedure simulates automatic
both opening of the DV-5a Valve in a system operation upon both electric
fire condition, or not opening the DV-5a accordance with the manufacturer’s
instructions after the system air pres- detection and loss of system air pressure.
Valve in a non-fire condition, must be
verified as follows: sure has automatically been restored Internal Valve Inspection
to normal. Once every five years during the annual
Step 1. Close the System Main Control operational test procedure and prior
Valve (B) and then open the Main Drain Step 7. Close the System Shut-Off
Valve (W) after the system air pressure to the DV-5a Valve being reset and
Valve (D). with the DV-5a Valve de-pressurized,
has been restored to normal.
Step 2. Manually operate Zone 1 of the interior of the DV-5a Valve must
the Releasing Panel, and verify the Step 8. Open the System Main Control be cleaned and inspected for wear
following: Valve (B) one turn beyond the position and damage. Damaged or worn parts
at which water just begins to flow from must be replaced. (Replacement of the
• The operation of the Releasing Panel the Main Drain Valve (D). Diaphragm every ten years is recom-
and its associated alarms mended, or more frequently if inspec-
Step 9. Close the Main Drain Valve (D).
• That there is no leakage from the tions and/or wear and tear warrant
Solenoid Valve (V) Step 10. Close the Air Supply Valve (S). more frequent replacement.)
NOTE: During this procedure, the Solenoid
Valve (V) should remain closed and the NOTICE
DV-5a Deluge Valve Diaphragm Chamber The Diaphragm Cover may be removed
should remain pressurized. between Steps 4 and 5 of the reset-
ting instructions, since at that point the
This procedure is used to verify that the
DV-5a Valve should be de-pressurized
DV-5a Deluge Valve will remain set if the
as evident by a zero gauge reading on
electric detection system (Zone 1) operates
the Diaphragm Gauge (K) and Water
but the sprinkler system (Zone 2) remains
Supply Gauge (J), as well as no water
in its normally pressurized condition.
discharging from the Automatic Drain
Step 3. Restore the electric fire detec- Valve (F).
tion system to a normal condition in
accordance with the manufacturer’s
instructions.
TFP1466
Page 17 of 20

To perform internal valve inspection Step 3. Using crossdraw sequence


between Steps 4 and 5 of the Valve to assure uniformity, wrench-tighten
Setting Procedure remove the Dia- Long Hex Bolts and Short Hex Bolts
phragm cover as follows: to appropriate torque values. Repeat
crossdraw sequence two to three
Step 1. Close the Inverted Flare Shut-
times at incremental torque valves
Off Valve (R).
until reaching the torque valves found
Step 2. Remove the Copper Tube in Table B.
Fitting between the Diaphragm Supply
Step 4. Inspect to assure all Hex Bolts
Valve (P) and the Inverted Flare Shut-
are securely tightened.
Off Valve (R).
Step 5. Using the union, secure the
Step 3. Loosen the union securing the
MRA-1 Manual Reset Actuator (N) to
Electric/Electric Actuation Trim and
the Diaphragm Cover.
remove the Electric/Electric Actuation
Trim. Step 6. Using the union, secure the
Electric/Electric Actuation Trim.
Step 4. Loosen and remove the union
between the Diaphragm Cover and the Step 7. Replace the Copper Tube
MRA-1 Manual Reset Actuator (N) and Fitting between the Diaphragm Supply
remove the MRA-1 Manual Reset Actu- Valve (P) and the Inverted Flare Shut-
ator (N) subassembly. Off Valve (R).
Step 5. Remove the Diaphragm Valve Step 8. Ensure that the unions and flare
Cover hardware, then slowly remove fittings are securely tightened.
the Diaphragm Cover and perform Step 9. With the Diaphragm Supply
internal valve inspection. Clean the Valve (P) closed, fully open the Inverted
valve interior and replace parts as Flare Shut-Off Valve (R) stainless steel
necessary. screw (approximately 1/2 in.) until resis-
After cleaning and inspecting valve tance is met so as not to break the
interior, and replacing parts as nec- internal roll-pin. The internal roll-pin
essary, reinstall the Diaphragm Cover stops the removal of the Inverted Flare
by completing the following steps to Shut-Off Valve (R) stainless steel screw.
assure the Diaphragm Cover Fasteners Step 10. Proceed with Step 5 of the
are uniformly and securely tightened. Valve Setting Procedures section in this
Step 1. With reference to Figure 1, data sheet.
ensure that the Diaphragm is properly
oriented and that the proper hardware NOTICE
arrangement is utilized when assem-
bling the Diaphragm Covers. The hard- If the water supply contains chemicals
ware arrangements differ depending on which tend to attack a polyester fabric-
the size of the DV-5a Valve. reinforced, EPDM rubber or the five year
inspection indicates a build-up of debris
Step 2. By first using the Long Hex within the DV-5a Valve that could affect
Bolts, support of the Diaphragm Cover its proper operation, then the frequency
will be provided before installing the of the internal valve inspection procedure
Short Hex Bolts. Align Diaphragm in must be appropriately increased.
proper orientation with Valve Body, and
then align Diaphragm Cover in proper With reference to Figure 1, make
orientation with Valve Body. Hand- certain that the Diaphragm is correctly
tighten all fasteners. oriented; otherwise, the DV-5a Valve
cannot be properly set.
Under-tightening the Diaphragm Cover
Bolts can result in internal and external
leakage.
Use only TYCO replacement fasteners
as specified in Figure 1.
Do not apply adhesives, lubricants, or
other substances to the Diaphragm
Valve Body.
TFP1466
Page 18 of 20

Limited Note: Pressure switches, P/N 52-287-1-124


solenoid valve, and psi/kPa water pressure
gauges are provided.
EMEA
DV-5A Valves with Galvanized Trim
Warranty Separate DV-5A Valves without Trim
Specify: Size (specify), DV-5 a Auto-
matic Water Control Valve, (specify)
For warranty terms and conditions, visit See Table A for flange drilling end connection with assembled gal-
www.tyco-fire.com. specifications. vanized EMEA, Double Interlock Pre-
Specify: Size (specify), DV-5 a Auto- action Electric/Electric Actuation Trim,
Ordering matic Water Control Valve, (specify)
end connection, P/N (specify):
P/N (specify):

Procedure
Grooved x Grooved
Groove x Groove 1 1/2 in. (DN40) ����������������������������������� 550111515
1 1/2 in. (DN40) ���������������������������������� 530010015 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550111520
The TYCO DV-5a Automatic Water 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550111530
Control Valves may be ordered as 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030 4 in. (DN100) ��������������������������������������� 550111540
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040 6 in. (DN150) ��������������������������������������� 550111560
follows: 8 in. (DN200) ��������������������������������������� 550111580
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060
Pre-Assembled Valves 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080 Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550121530
with Trim Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030 4 in. (DN100) ���������������������������������������550121540
DV-5A Valves with Galvanized Trim 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040 6 in. (DN150) ���������������������������������������550121560
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060 8 in. (DN200) ���������������������������������������550121580
and Butterfly Valve
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080 Flange x Grooved ANSI
Specify: Size (specify), DV-5 a Auto-
matic Water Control Valve, G x G con- Flange x Groove ANSI 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550131530
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030 4 in. (DN100) ���������������������������������������550131540
nections with assembled galvanized 6 in. (DN150) ���������������������������������������550131560
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040
Americas Double Interlock Preac- 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060 8 in. (DN200) ���������������������������������������550131580
tion with Electric/Electric Actuation 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080 Flange x Flange ISO
Trim, complete with assembled Model 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550141530
T x T NPT
BFV-300 Butterfly Valve, P/N (specify): 1 1/2 in. (DN40) ���������������������������������� 530060015 4 in. (DN100) ���������������������������������������550141540
1 1/2 in. (DN40) ����������������������������������� 551011515 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020 6 in. (DN150) ���������������������������������������550141560
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 551011520 8 in. (DN200) ���������������������������������������550141580
Notes:
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 551011530 Valves are typically provided with flange Flange x Grooved ISO
4 in. (DN100) ��������������������������������������� 551011540 drilling per ANSI B16.1 (Class 125) or ISO 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550151530
6 in. (DN150) ��������������������������������������� 551011560 (7005-2 PN16). 4 in. (DN100) ���������������������������������������550151540
8 in. (DN200) ��������������������������������������� 551011580 6 in. (DN150) ���������������������������������������550151560
Upon request, valves can be provided with 8 in. (DN200) ���������������������������������������550151580
Notes: flange drilling per JIS B 2210 or AS 2129. In
Americas pressure switches, P/N 52-287- which case part numbers are not assigned. T x T ISO
1-124 Solenoid Valve, and psi/kPa water 1 1/2 in. (DN40) ����������������������������������� 550171515
pressure gauges are provided. DV-5A Valve Trim 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550171520
Specify: Size (specify), finish (specify), Note: Pressure switches, P/N 52-287-1-
This arrangement is available for EMEA Electric/Electric Actuation Trim for 124 solenoid valve, bar/psi water pressure
and APAC upon request. Contact your DV-5a Automatic Water Control Valves gauges, and NPT to ISO threaded trim adap-
local distributor. used in Double Interlock Preaction Fire tors for external connections are provided.
Protection System, P/N (specify): Separate DV-5A Valves without Trim
AMERICAS
Galvanized See Table A for flange drilling
DV-5A Valves with Galvanized Trim 1 1/2 in. (DN40) ���������������������������������� 540001520 specifications.
Specify: Size (specify), DV-5 a Auto- 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 540001520
matic Water Control Valve, (specify) 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 540001530 Specify: Size (specify), DV-5 a Auto-
end connection with assembled galva-
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 540001540 matic Water Control Valve, (specify)
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 540001560 end connection, P/N (specify):
nized Americas, Double Interlock Pre- 8 in. (DN200) �������������������������������������� 540001580
action Electric/Electric Actuation Trim, Groove x Groove
Black 1 1/2 in. (DN40) ���������������������������������� 530010015
P/N (specify): 1 1/2 in. (DN40) ���������������������������������� 542001520 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020
Grooved x Grooved 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 542001520 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030
1 1/2 in. (DN40) ����������������������������������� 550011515 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 542001530 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550011520 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 542001540 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550011530 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 542001560 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080
4 in. (DN100) ���������������������������������������550011540 8 in. (DN200) �������������������������������������� 542001580
6 in. (DN150) ���������������������������������������550011560 Flange x Flange ANSI
8 in. (DN200) ���������������������������������������550011580
Note: Pressure switches and/or solenoid 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030
valves for electric actuation are separately 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040
Flange x Flange ANSI ordered. 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550021530 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550021540
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550021560 Flange x Groove ANSI
8 in. (DN200) �������������������������������������� 550021580 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040
Flange x Grooved ANSI 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550031530 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530030080
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550031540
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550031560 T x T NPT
8 in. (DN200) �������������������������������������� 550031580 1 1/2 in. (DN40) ���������������������������������� 530060015
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020
T x T NPT
1 1/2 in. (DN40) �����������������������������������550061515
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 550061520
TFP1466
Page 19 of 20

Flange x Flange ISO Flange x Grooved ANSI Notes:


3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530040030 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550031530 Valves are typically provided with flange
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530040040 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550031540 drilling per ANSI B16.1 (Class 125) or ISO
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530040060 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550031560 (7005-2 PN16).
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530040080 8 in. (DN200) �������������������������������������� 550031580
Upon request, valves can be provided with
Flange x Groove ISO T x T NPT flange drilling per JIS B 2210 or AS 2129. In
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530050030 1 1/2 in. (DN40) �����������������������������������550061515 which case part numbers are not assigned.
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530050040 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 550061520
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530050060 DV-5A Valve Trim
Flange x Flange ISO
8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530050080
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550041530 Specify: Size (specify), finish (specify),
T x T ISO 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550041540 Double Interlock Preaction Electric/
1 1/2 in. (DN40) ���������������������������������� 530070015 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550041560 Electric Actuation Trim for DV-5a Auto-
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530070020 8 in. (DN200) �������������������������������������� 550041580 matic Water Control Valves used in
Notes: Flange x Grooved ISO Deluge Fire Protection System, P/N
Valves are typically provided with flange 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550051530 (specify):
drilling per ANSI B16.1 (Class 125) or ISO 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550051540
Galvanized
(7005-2 PN16). 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550051560
1 1/2 in. (DN40) ���������������������������������� 540001520
8 in. (DN200) �������������������������������������� 550051580
Upon request, valves can be provided with 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 540001520
flange drilling per JIS B 2210 or AS 2129. In Note: Pressure switches, P/N 52-287-1-124 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 540001530
which case part numbers are not assigned. solenoid valve, and psi/kPa water pressure 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 540001540
gauges are provided. 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 540001560
DV-5A Valve Trim 8 in. (DN200) �������������������������������������� 540001580
Specify: Size (specify), finish (specify), Separate DV-5A Valves without Trim
Black
Double Interlock Preaction Electric/ See Table A for flange drilling 1 1/2 in. (DN40) ���������������������������������� 542001520
Electric Actuation Trim for DV-5a Auto- specifications. 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 542001520
matic Water Control Valves used in Specify: Size (specify), DV-5 a Auto- 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 542001530
Deluge Fire Protection System, P/N matic Water Control Valve, (specify)
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 542001540
(specify): 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 542001560
end connection, P/N (specify): 8 in. (DN200) �������������������������������������� 542001580
Galvanized Groove x Groove
1 1/2 in. (DN40) �����������������������������������540101520 1 1/2 in. (DN40) ���������������������������������� 530010015
DV-5A Valve Trim Accessories
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 540101520 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530010020 (for separately ordered valve trim)
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 540101530 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530010030 Specify: (Specify Accessory Descrip-
4 in. (DN100) ���������������������������������������540101540
6 in. (DN150) �������������������������������������� 540101560
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530010040 tion), P/N (specify):
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530010060
8 in. (DN200) ���������������������������������������540101580 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530010080 Model QRS
Quick Release Switch Q1 �������Refer to Technical
Black Flange x Flange ANSI Data Sheet TFP1100
1 1/2 in. (DN40) �����������������������������������542101520 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530020030 Waterflow Pressure Alarm Switch, Potter
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 542101520 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530020040 PS10-2 (America/APAC) ���������������������������� 25720
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 542101530 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530020060 Waterflow Pressure Alarm Switch
4 in. (DN100) ���������������������������������������542101540 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080 PS10-1 (EMEA) �������������������������������������������� 0260
6 in. (DN150) ���������������������������������������542101560
Model WMA-1 Water Motor Alarm
8 in. (DN200) ���������������������������������������542101580 Flange x Groove ANSI
(America/APAC) ������������������������������ 526301001P
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530030030
Note: Pressure switches, solenoid valves for 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530030040
Model WMA-1 Water Motor Alarm
electric actuation, water pressure gauges, 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530030060
(EMEA) . . . . . . . . . . . . . . . . . . . . . . . 526301021R
and BFV-300 Butterfly Valve are separately 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530020080
Model AMD-1 Air
ordered. NPT to ISO threaded adaptors Maintenance Device �������������������������� 523242002
are provided for External Trim Connections T x T NPT Model AMD-3 Nitrogen
(drains, pressure switches, water motor 1 1/2 in. (DN40) ���������������������������������� 530060015 Maintenance Device �������������������������� 523282001
alarms, etc.). 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530060020 Model MC-1 Manual
Control Stations �������������������������������� 522892001
Flange x Flange ISO
APAC 3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530040030
Water Gauges with bar/psi . . . . . . . . 025500013
600 psi Water Gauge psi/kPa
DV-5A Valves with Galvanized Trim 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530040040 (service pressure over 300 psi) �������� 923431004
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530040060
Specify: Size (specify), DV-5 a Auto- 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530040080
Solenoid Valve for
matic Water Control Valve, (specify) Releasing Service . . . . . . . . . . Refer to Technical
Flange x Groove ISO Data Sheet TFP2108
end connection with assembled gal-
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 530050030
vanized APAC, Double Interlock Pre- 4 in. (DN100) . . . . . . . . . . . . . . . . . . . 530050040 DV-5A Valve Replacement Parts
action Electric/Electric Actuation Trim, 6 in. (DN150) . . . . . . . . . . . . . . . . . . . 530050060 Specify: (Description) for use with
P/N (specify): 8 in. (DN200) . . . . . . . . . . . . . . . . . . . 530050080 (specify size) DV-5a Automatic Water
Grooved x Grooved T x T ISO Control Valve, P/N (See Figure 1)
1 1/2 in. (DN40) ����������������������������������� 550011515 1 1/2 in. (DN40) ���������������������������������� 530070015
2 in. (DN50) . . . . . . . . . . . . . . . . . . . . . 550011520 2 in. (DN50) . . . . . . . . . . . . . . . . . . . . 530070020
DV-5A Valve Trim Replacement
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . . 550011530 Parts
4 in. (DN100) ���������������������������������������550011540 Specify: (Description) for use with
6 in. (DN150) ���������������������������������������550011560 DV-5a Valve Trim, P/N (See Figure 6)
8 in. (DN200) ���������������������������������������550011580
Flange x Flange ANSI
3 in. (DN80) . . . . . . . . . . . . . . . . . . . . 550021530
4 in. (DN100) . . . . . . . . . . . . . . . . . . . 550021540
6 in. (DN150) . . . . . . . . . . . . . . . . . . . 550021560
8 in. (DN200) �������������������������������������� 550021580
TFP1466
Page 20 of 20

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
TEFLON is a registered trademark of DuPont
Worldwide
www.tyco-fire.com
Contacts

Model WMA-1 Water Motor Alarm


Hydraulically Operated
Mechanical Sprinkler Alarm
General The owner is responsible for main-
taining their fire protection system
Description and devices in proper operating con-
dition. Contact the installing contrac-
The TYCO Model WMA-1 Water Motor tor or product manufacturer with any
Alarm is a hydraulically operated questions.
outdoor alarm designed for use with
fire protection system waterflow detec-
tion valves. It is lightweight yet rugged,
Technical
and it can be used in conjunction with
alarm check, dry pipe, deluge, and pre-
Data
action valves to sound a local alarm. Approvals
UL and ULC Listed
The Water Motor Alarm is suitable FM, LPCB and VdS Approved
for mounting to any type of rigid wall
and can accommodate a wall thick- Gong Finish
Red or Aluminum
ness range of 2 in. to 18 in. (50 mm
to 450 mm). It is provided with a listed Working Water Pressure Range
and approved TYCO Model WMA-1 7 to 300 psi (0,5 to 20,7 bar)
Y-Strainer for use in the alarm line. Nozzle K-factor
The Model WMA-1 utilizes a lightweight, 0.7 gpm/psi½ (10,1 Lpm/bar½)
impeller design that can produce a very Y-Strainer
high sound pressure level. The Gong, 3/4 in., cast iron, 20 mesh screen
Gong Mount, and Water Motor Housing
are fabricated from corrosion-resistant Trim Components
Galvanized steel nipples and cast iron
aluminum alloys. The polymer drive fittings
bearings do not require lubrication, and Item 5. The alarm line piping must be
the Gong is closely fitted to the Gong
Mount to eliminate the need for a sepa- Design positioned such that it can be drained
back to the waterflow detection valve
rate cover.
The Model WMA-1 Water Motor Alarm
Data trim.
Item 6. The Clean-Out Sump Plug is to
is a re-designation for the Central The TYCO Model WMA-1 Water Motor be located vertically below the Inlet to
Model F-2, Gem Model F630, and Star Alarm must be used in accordance with the Water Motor.
Model S450. the following design criteria: Item 7. Piping from the Water Motor
Item 1. The Y-Strainer is to be located Drain must be a minimum of 1 in.
NOTICE at the alarm outlet of the waterflow (DN25) in size throughout and directed
The TYCO Model WMA-1 Water Motor detection valve trim. to an open drain in order to ensure
Alarm described herein must be proper drainage for obtaining the
Item 2. The Water Motor Alarm maximum sound pressure level.
installed and maintained in compliance
must only be mounted to a rigid
with this document, as well as with the Note: The Water Motor Alarm Drain
wall surface that will not permit the
applicable standards of the NATIONAL may be connected to the main drain
Striker /Gong Mount to loosen and fall
FIRE PROTECTION ASSOCIATION of a waterflow detection valve if a non-
out of alignment.
(NFPA), in addition to the standards spring loaded swing-type check valve
of any authorities having jurisdiction. Item 3. In order to obtain the highest is installed in a horizontal portion of the
Failure to do so may impair the perfor- possible sound level, the Water Motor
water motor alarm drain piping (before
mance of this device. Alarm should be located as close as
possible to the waterflow detecting its connection to the main drain).
valve. For guidance, refer to NFPA 13. Item 8. In order to minimize any wall
Item 4. The alarm line piping from the staining that can be created by drain
alarm outlet of the waterflow detection water, it is recommended that the drain
valve trim to the Water Motor Alarm piping from the Water Motor be galva-
must be 3/4 in. (DN20) in size through- nized steel, brass, or other suitable cor-
out and it must be galvanized steel, rosion-resistant material.
IMPORTANT
Refer to Technical Data Sheet brass, or other suitable corrosion-resis-
TFP2300 for warnings pertaining to tant material.
regulatory and health information.

Page 1 of 4 AUGUST 2018 TFP921


TFP921
Page 2 of 4

NO. DESCRIPTION QTY. REF. STRIKER ARM


1 Water Motor . . . . . . 1 92-630-1-012
COUPLING
2 Support Washer . . . 1 NR
SPACER
3 Drive Shaft Sleeve . 1 NR
4 Drive Shaft . . . . . . . 1 NR COUPLING
5 Gong Mount . . . . . . 1 NR 3/4" NPS
6 Striker . . . . . . . . . . . 1 See (a)
7 Gong . . . . . . . . . . . . 1 See (a) STRIKER
8 Cap Nut . . . . . . . . . 1 See (a) SHAFT
(a) Red Gong Repair STRIKER BEARING
Kit includes items: RING 2
6, 7 (red), and 8 . . . 1 92-630-1-025
CROSS-SECTION VIEW
(a) Aluminum Gong Repair OF STRIKER (ITEM 6)
Kit includes items:
6, 7 (alum.), and 8 . . 1 92-630-2-025

NR: Not Replaceable

3
6

7
4
IMPELLER

NOZZLE

INLET
DRAIN
5

INTERNAL VIEW OF
WATER MOTOR (ITEM 1)
8

FIGURE 1
MODEL WMA-1 WATER MOTOR ALARM
ASSEMBLY

Item 9. Drain water must be directed to • 3/4 in. Check Valve with 3/32 in. the Inlet Nozzle, a high velocity jet is
prevent accidental damage to property orifice (P/N 52-403-1-005) formed that impinges on the Impeller,
or danger to persons when the alarm is causing the Impeller and the Striker
Strainers must be located at the alarm
operating or thereafter. to rotate. With each rotation, the free
outlet in the trim of each of the water-
Item 10. The alarm line drain, at the flow detection valves. Check valves swinging Striker Ring hits the Gong and
waterflow detection valve, must be must be located between each strainer sounds the alarm. The spent water is
maintained at a minimum temperature and the interconnection with the alarm then drained through the 1 in. outlet.
of 40°F (4°C). line from another system. The alarm will sound as long as water
Item 11. A single Water Motor Alarm is flowing into the system and flowing
may be connected to the alarm lines Operation to the Water Motor Alarm. Water in the
alarm line will automatically drain back
from a maximum of three separate fire
protection systems. However, when Upon operation of the alarm check, through the orifice, which is also pro-
two or three alarm lines are intercon- dry pipe, deluge, or preaction valve to vided in the trim of the waterflow detec-
nected, each alarm line must be pro- which the TYCO Model WMA-1 Water tion valve.
vided with the following: Motor Alarm is connected, water will The Water Motor Alarm does not have
flow to the Water Motor and through to be reset after an operation. However,
• 3/4 in. Model WM-1 Y-Strainer the Inlet Nozzle. As water flows through
(P/N 52-271-1001) if the alarm was silenced during oper-
TFP921
Page 3 of 4

2"
(50,8 mm)
7/8" 3/4" NPS
(22,2 mm) 2-3/4" 2-7/16"
1-3/8" (69,9 mm) (61,9 mm)
(34,2 mm)
WATER
MOTOR 8-1/2" DIA.
SLEEVE END (215,9 mm)
2-9/16" T/O 2-1/2" T/O 3/4" NPT
(65,0 mm) (63,5 mm) THREADED
BY INSTALLER

1-13/16"
(46,0 mm) 10"
(254,0 mm)
DRAIN CL
3/4" NPT 1" NPT MINIMUM
INLET DRAIN
A

3/4" (DN20) NPS 1" (DN25) NPS 2-1/16"


GALVANIZED GALVANIZED (52,4 mm) B
STEEL OR 4 STEEL OR INLET CL
BRASS PIPE BRASS PIPE C
1 1
D
3
RIGID WALL
2 STRUCTURE
3/4"
Y-STRAINER 16" (457,2 mm)
LOCATION FOR CLEAN-OUT
OPTIONAL ELECTRICALLY MAXIMUM
STRAINER SUMP PLUG
SUPERVISED N.O. 2" (50,8 mm)
CLEAN-OUT ALARM CONTROL VALVE MINIMUM
CAP (SEE NOTE 4)
NOTES: STANDARD INLET TRIM OPTIONAL DRAIN TRIM
1. All installation dimensions are shown at nominal value. NO. DESCRIPTION QTY. NO. DESCRIPTION QTY.
2. All dimensions are in inches and (mm).
1 3/4" x 3" Nipple . . . . . 2 A 1" 90° Elbow . . . . . . . 1
3. Items shown in dotted lines are not included with the WMA-1. 2 3/4" 90° Elbow . . . . . . 1 B 1" 45° Elbow . . . . . . . 1
4. Consult local Authority Having Jurisdiction for mechanical 3 3/4" x 1/4" x 3/4" Tee C Wall Plate . . . . . . . . . 1
alarm isolating control valve requirements. with 1/4" Plug. . . . . . . 1 D 1" x 1'-6" Pipe,
5. All included trim components are galvanized. 4 3/4" Union . . . . . . . . . 1 T.O.E. . . . . . . . . . . . . 1
FIGURE 2
MODEL WMA-1 WATER MOTOR ALARM
TYPICAL INSTALLATION

ation by closing an alarm control (0 mm to 3 mm). Thread the cut end to Step 8. Tighten the 3/4 in. Union.
valve, the alarm control valve must 3/4 in. NPT per ANSI B1.20.1. Install the Wall Plate and tighten the
be reopened after the fire protection 45° Elbow.
Step 4. Install the alarm line piping up
system is restored to service. to and including the Union half per Item Note: Apply pressure against the
4, Figure 2. outside edge of the Water Motor Body
Installation Note: Use thread sealant sparingly on and verify that the Body and Support
Washer sit squarely against the wall. If
The TYCO Model WMA-1 Water Motor male threads only.
not, adjust the alarm line and/or drain
Alarm must be installed in accordance Step 5. Prior to initiating installation piping to suit.
with this section. of the Water Motor Alarm, mount the
Step 9. From the outside wall, insert
Step 1. Mark the through-wall locations Drain Trim (less the Wall Plate and 45°
the Drive Shaft through the Sleeve and
for the centerlines of the Sleeve and Elbow) as well as the balance of alarm
fully insert it into the Impeller.
Drain Outlet. The Drain Outlet must be line piping, including the other Union
located at least 10 in. (250 mm) below half, to the Water Motor. Note: When fully inserted, the Shaft
the Sleeve per Figure 2. should protrude beyond the face of
Step 6. Tighten the NPT threaded end
the wall by approximately 20 minus 2 in.
Step 2. Make 1-1/2 in. (38 mm) diam- of the Sleeve into the Body, hand-tight
(508,0 minus 50,8 mm) wall thickness.
eter holes straight through the wall at plus 1/8 turn.
both locations. Mark the Drive Shaft at a point of
Step 7. Slip the Support Washer over
approximately 1/8 in. to 1/4 in. (3,2 mm
Step 3. Cut the non-threaded end of the Sleeve and place the assembly in
to 6,4 mm) inside the face of the wall.
the Sleeve to a length equal to that of position against the wall.
Remove the Shaft and cut it where pre-
the wall thickness plus 0 in. to 1/8 in.
TFP921
Page 4 of 4

viously marked. File off burrs from the


cut end of the Drive Shaft. Re-insert the
If the alarm was silenced during opera-
tion, the alarm control valve must be Limited
Drive Shaft through the Sleeve and fully
insert it into the Impeller.
reopened immediately after the fire pro-
tection system is restored to service. Warranty
Step 10. Hold the Gong Mount in The owner is responsible for the inspec- For warranty terms and conditions, visit
position against the wall, engage the tion, testing, and maintenance of their www.tyco-fire.com.
Coupling with the Drive Shaft, and fire protection system and devices in
then carefully thread the Striker Shaft
Bearing onto the Sleeve. Securely
compliance with this document, as well
as with the applicable standards of the
Ordering
tighten the Striker Shaft Bearing using
a pair of tongue-and-groove pliers on
NATIONAL FIRE PROTECTION ASSO-
CIATION (e.g., NFPA 25), in addition to
Procedure
the 1-1/2 in. (38 mm) hex end. the standards of any other authorities Orders for the WMA-1 Water Motor
having jurisdiction. Contact the install- Alarm Assembly, Optional Drain Trim,
Step 11. Spin the Striker by hand and
ing contractor or product manufacturer and replacement parts must include
verify that it spins freely, without any
regarding any questions. the description and Part Number (P/N).
sign of binding. If it does not, make the
necessary adjustments. Automatic sprinkler systems are rec- The complete Model WMA-1 Alarm
ommended to be inspected, tested, Assembly includes the Model WMA-1
Step 12. Install the Gong and securely
and maintained by a qualified Inspec- Water Motor Alarm, Model WM-1
tighten the Cap Nut. The identifica-
tion Service in accordance with local Strainer, and Standard Inlet Trim.
tion sign lettering must be orientated
requirements and/or national codes.
horizontally. WMA-1 Water Motor Alarm
The following procedures and inspec- Assembly
Step 13. Test the Water Motor Alarm by
tions should be performed as indicated, Specify: Model WMA-1 Water Motor
opening the alarm test valve in the trim
in addition to any specific requirements Alarm, (specify) Finish, P/N (specify):
of the waterflow detection valve. The
of the NFPA, and any impairment must
alarm must be clear and steady. If it is Red Finish Gong . . . . . . . . . . P/N 52-630-1-001P
be immediately corrected:
not, make the necessary adjustments. Aluminum Finish Gong �������� P/N 52-630-2-001P
Step 1. The Model WMA-1 Water Motor Optional Drain Trim
NOTICE Alarm does not require any regularly Specify: Optional Drain Trim for
scheduled maintenance. Rotating parts Model WMA-1 Water Motor Alarm,
Testing of the Water Motor Alarm may do not require lubrication. It is recom-
result in operation of other associated P/N 52-630-2-002
mended, however, that fire alarms be
alarms. Consequently, notification periodically operated (inspected) to Separately Ordered Parts for
must be given to the owner and the fire verify that they generate a clear and Multiple Systems
department, central control station, or steady sound. Correct any impairment Specify: Model WM-1 Y-Strainer,
other signal station to which the alarms immediately. P/N 52-271-1-001
are connected.
Step 2. The inspection should be made Note: One Y-Strainer is required for
Care and quarterly or more frequently, as may
be necessary for locations subject to
two systems; two Y-Strainers are
required for three systems.
Maintenance vandalism.
The Y-Strainer and Sump are to be
Specify: 3/4 in. Check Valve with 3/32
in. Orifice, P/N 52-403-1-005
The TYCO Model WMA-1 Water Motor cleaned out after each operation of the
Alarm must be maintained and ser- Note: Two Check Valves are required
Water Motor Alarm and after the alarm
viced in accordance with this section. for two systems; three Check Valves
line piping has been drained.
are required for three systems.
Before closing a fire protection system
main control valve for maintenance NOTICE Replacement Parts for
work on the fire protection system Water Motor Alarm
With reference to Figure 2, in the event
that it controls, obtain permission to Specify: (description) for use with
of a WMA-1 malfunction, inspect and
shut down the affected fire protection Model WMA-1 Water Motor Alarm,
clean the Y-Strainer of obstruction prior
system from the proper authorities P/N (see Figure 1)
to removing the Water Motor.
and notify all personnel who may be
affected by this decision. Make no attempt to disassemble,
repair, or internally clean the Water
Testing of the Water Motor Alarm may Motor. The Water Motor is not a field
result in operation of other associated serviceable part and must be replaced
alarms. Consequently, notification if malfunction is determined.
must be given to the owner and the fire
department, central control station, or
other signal station to which the alarms
are connected.

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2018 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association;
Worldwide
www.tyco-fire.com
Contacts

Model AMD-1 Automatic Air Maintenance Device


Pressure Reducing Type with
Field-Adjustable Pressure Regulator
General Technical
Description Data
The TYCO Model AMD-1 Automatic Air Approvals
Maintenance Device is an automatic, UL and C-UL Listed
field-adjustable, pressure reducing FM Approved
device. It is used to control the pres- NYC Approved under MEA 206-02-E
sure in a dry pipe sprinkler system, pre- Maximum Inlet Air (or Nitrogen)
action system, or dry pilot line system Supply Pressure
of a dry pilot actuated deluge or preac- 200 psi (13,8 bar)
tion valve.
Field-Adjustable Outlet Pressure
The Model AMD-1 Device is utilized Range
in applications where there is a com- 5 to 70 psi (0,4 to 4,8 bar)
pressed air (or nitrogen) source con-
trolled at a higher pressure than the Assembly
desired system pressure. Pressure Major components illustrated in Figure
sources include plant air supplies with
their own automatic compressor con-
1 are factory assembled with galva-
nized steel nipples and malleable iron
Installation
trols or nitrogen supplies with single- pipe fittings. The TYCO Model AMD-1 Automatic
stage, cylinder-mounted pressure Air Maintenance Device should be
regulators. Operation installed in the horizontal position as
shown in Figure 1, as well as in accor-
The Model AMD-1 Automatic Air Main- dance with the following instructions:
The By-Pass Valve in the Model AMD-1
tenance Device is a re-designation for
Automatic Air Maintenance Device is
the Central Model D-2, Gem Model
opened to quickly fill the system during NOTICE
F324, and Star Model S460.
initial pressurization. Once the required Moisture build-up can adversely affect
system pressure has been reached, performance. Suitable consideration
NOTICE the By-Pass Valve is closed and the must be given to the removal of exces-
The Model AMD-1 Automatic Air Main- Air Supply Control Valve is left open to sive moisture from the compressed air
tenance Devices described herein must place the Model AMD-1 Device in auto- supply.
be installed and maintained in compli- matic operation.
ance with this document and with the 1. Make connections a minimum of
When there is a small leak in the 1/2 in. (DN15) pipe size between
applicable standards of the NATIONAL system, the Pressure Regulator auto-
FIRE PROTECTION ASSOCIATION, in the inlet air supply and the Model
matically maintains system pressure at AMD-1 Device, as well as between
addition to the standards of any author- the preset level. The 3/32 in. (2,4 mm)
ities having jurisdiction. Failure to do so the Model AMD-1 Device and the
orifice in the Restrictor Check Valve system to pressurize.
may impair the performance of these limits the flow of air from the Pressure
devices. Regulator into the system to a value 2. Place a 1/2 in. (DN15), non-spring
Owners are responsible for maintain- significantly less than that exhausted loaded, rubber-faced, swing-type
ing their fire protection system and by the operation of a 5.6 K-factor check valve between the Model
devices in proper operating condition. sprinkler. AMD-1 Device and the system to
The installing contractor or sprinkler pressurize. A check valve of this
manufacturer should be contacted type is provided in the air supply
with any questions. trim of TYCO dry pipe and preac-
tion valves.

IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.

Page 1 of 4 FEBRUARY 2020 TFP1221


TFP1221
Page 2 of 4

2" 16-1/8""
(50,8 mm) (409,6 mm)
BY-PASS VALVE
1/4" NPT
(NORMALLY
GAUGE
CLOSED)
TEST PORT
3-1/4" 1/2" NPT P/N 46-047-1-004
(82,6 mm) OUTLET
CONNECTION
(TO SYSTEM)
8-1/2"
(215,9 mm) 1/2" NPT
LABEL INLET CONNECTION
(FROM COMPRESSED
AIR SUPPLY)

RESTRICTOR
CHECK VALVE
P/N 92-326-1-003
PRESSURE AIR SUPPLY
REGULATOR STRAINER CONTROL VALVE
(ADJUSTABLE) P/N 52-353-1-002 (NORMALLY OPEN)
P/N 92-324-1-012 P/N 46-048-1-002
FIGURE 1
MODEL AMD-1
AUTOMATIC AIR MAINTENANCE DEVICE

Setting 6. Open the Air Supply Control Valve


in the Model AMD-1 Device.
10. Open the control valve in the
air supply trim to the system to
Procedure 7. While observing the relocated pres-
sure gauge, adjust the output pres-
pressurize.
11. Open the Air Supply Control Valve
The TYCO Model AMD-1 Automatic sure of the Pressure Regulator. Pull in the Model AMD-1 Device.
Air Maintenance Device must be the knob out and away from the 12. Open the By-Pass Valve in the
set in accordance with the following Pressure Regulator body and then Model AMD-1 Device.
instructions: slowly turn the knob clockwise, as
viewed from the knob end of the 13. Close the By-Pass Valve after the
1. Determine the pressure that meets system is pressurized to approxi-
Pressure Regulator, to increase
the minimum requirements of the mately 5 psi (0,4 bar) less than the
pressure, and counter-clockwise to
system to pressurize. minimum required system pressure
decrease pressure.
2. Close the Model AMD-1 By-Pass determined in Step 1.
When decreasing pressure, the air
Valve, and close the Model AMD-1 14. After the system pressure stabi-
pressure must be relieved down-
Air Supply Control Valve. lizes, note the value and compare
stream of the Pressure Regulator
3. Open the control valve in the air by temporarily opening the control with the requirement. Re-adjust the
supply trim of the system to pres- valve in the air supply trim of the Pressure Regulator, as required.
surize and then reduce the system system to pressurize, assuming that
air pressure to 0 psi. the system to pressurize is at 0 psi. NOTICE
4. Close the control valve in the After the Pressure Regulator is set, If the system was over-pressurized
air supply trim of the system to push the knob in and towards the during manual fill, open a suitable
pressurize. Pressure Regulator body to snap it connection to the system and manu-
5. Remove the system pressure gauge in a locked position. ally reduce the pressure to the desired
from its connection and temporari- 8. Close the Air Supply Control Valve value. The Model AMD-1 Automatic Air
ly install it in the 1/4 in. NPT Model in the Model AMD-1 Device. Maintenance Device then automatically
AMD-1 Gauge Test Port. maintains the preset system pressure.
9. Return the system air pressure The Restrictor Check Valve prevents
gauge to its normal location. Re- the Pressure Regulator from bleeding
CAUTION install the 1/4 in. pipe plug in the down the system pressure.
Before removing the plug, make certain Model AMD-1 Gauge Test Port. Ap-
ply pipe-thread sealant sparingly to In order to minimize the time for system
that the piping to which the Model
the plug threads only. trip in the event of a sprinkler opera-
AMD-1 Gauge Test Port is connected
tion, set the system pressure at the
is at 0 psi. Failure to do so may result
minimum required value.
in personal injury or property damage. CAUTION
Before removing the pressure gauge,
make certain that the piping to which
the Model AMD-1 Gauge Test Port is
connected is at 0 psi. Failure to do so
may result in personal injury or prop-
erty damage.
TFP1221
Page 3 of 4

Care and Automatic sprinkler systems are rec-


ommend to be inspected, tested, Limited
Maintenance and maintained by a qualified Inspec-
tion Service in accordance with local Warranty
The TYCO Model AMD-1 Automatic requirements and/or national code. For warranty terms and conditions, visit
Air Maintenance Device must be main- The Model AMD-1 Device must be www.tyco-fire.com.
tained and serviced in accordance with inspected quarterly in accordance with
the following instructions, in addition to
any specific requirements of the NFPA.
the following instructions: Ordering
1. Verify that the By-Pass Valve is
Any impairment must be immediately
corrected.
closed. Procedure
2. Close the Model AMD-1 Air Sup- Contact your local distributor for avail-
NOTICE ply Control Valve and clean out the ability. When placing an order, indi-
1/4 in. Strainer located at the inlet cate the full product name, including
Before closing a fire protection system to the Restrictor Check Valve. Be
main control valve for maintenance description and Part Number (P/N).
sure to reinstall the strainer screen
work on the fire protection system and tighten the cap securely. Model AMD-1 Device
that it controls, obtain permission to Specify: Model AMD-1 Automatic Air
shut down the affected fire protec- 3. Open the Model AMD-1 Air Sup- Maintenance Device, P/N 52-324-2-002
tion system from the proper authori- ply Valve and verify that the control
ties and notify all personnel who may valve in the air supply trim to the Replacement Parts
be affected by this action. system to pressurize is open. Specify: (description), P/N (specify per
Figure 1)
It is recommended that accumulated 4. Verify that the system pressure is
moisture be removed from air supply essentially the same as the previ-
moisture filtration equipment at least ously established requirement. If
quarterly. More frequent inspections not, adjust the system pressure as
may be necessary in particularly humid follows:
environments. a. Close the system’s main con-
After placing a fire protection system trol valve and open the main
in service, notify the proper authorities drain valve. If the system is so
and advise those responsible for moni- equipped, close the Accelera-
toring proprietary and/or central station tor Control Valve.
alarms. b. Follow Steps 1 to 14 in the
Responsibility lies with owners for the Setting Procedure section.
inspection, testing, and maintenance of c. Slowly open the Accelerator
their fire protection system and devices Control Valve, as applicable.
in compliance with this document, as
well as with the applicable standards d. Slowly open the main con-
of the NATIONAL FIRE PROTECTION trol valve. After water begins
ASSOCIATION (for example, NFPA 25), to flow, slowly close the main
in addition to the standards of any other drain valve, then completely
authorities having jurisdiction. Contact open the main control valve.
the installing contractor or sprinkler The Model AMD-1 Automatic
manufacturer regarding any questions. Air Maintenance Device is now
ready for service.
TFP1221
Page 4 of 4

1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700


© 2020 Johnson Controls. All rights reserved. All specifications and other information shown were current as of document revision date and are subject to change without notice.

NATIONAL FIRE PROTECTION ASSOCIATION and NFPA are registered trademarks of National Fire Protection Association
TECHNICAL
SUBMITTAL

MATERIAL CERTIFICATE

www.SFFECO.com
VLFT.EX6022 - Special System Water Control Valves,
Deluge Type

Special System Water Control Valves, Deluge Type


TYCO FIRE & BUILDING PRODUCTS EX6022
1400 PENNBROOK PKWY
LANSDALE, PA 19446-3840 United States

TFP Model DV-5, 1-1/2, 2, 3, 4, 6 and 8 in. deluge valves for vertical and horizontal installation for pressures not exceeding 250 psig. The Model
DV-5 deluge valve is intended for operation by dry pilot line, manually, electrically or wet pilot line of sprinklers.

TFP Model DV-5, 2, 3, 4, 6 and 8 inch size deluge valves with Remote-Resetting with Electric Activation trim for vertical installation for pressures
not exceeding 250 psig.

TFP Model DV-5, 4 and 6 inch valves with Remote-Resetting, Pressure-Reducing trim for vertical and horizontal installation for pressures not
exceeding 250 psig.

TFP Model DV-5, 1-1/2, 2, 3, 4, 6 and 8 in. size deluge valves, rated 250 psig, for use with Single-Interlock Preaction trim, intended for operation by
supervised wet pilot, dry pilot, electrically or manual activation, installed in accordance with the manufacturer's installation instructions.

TFP Model DV-5, 1-1/2, 2, 3, 4, 6 and 8 in. size deluge valves, rated 250 psig, for use with Double-Interlock Preaction trim w/ electric/electric
release and Double-Interlock Preaction w/ electric/pneumatic release, installed in accordance with the manufacturer's installation instructions.

TFP Model DV-5, 4 inch valve with Remote-Resetting, Pressure-Reducing trim in Limited Space cabinet for vertical installation for pressures not
exceeding 250 psi.

Model SV-1, 3, 4, 6 and 8 in. size deluge valves for vertical installation only for pressures not exceeding 175 psig. The Model SV-1 is intended for
operation manually, electrically or wet pilot line of sprinklers.

TFP Model DV-5A, 1-1/2, 2, 3, 4, 6, 165.1mm and 8 in. deluge valves, rated 300 psig, for vertical installation. The Model DV-5A deluge valve is
intended for operation by dry pilot line, manually, electrically or wet pilot line of sprinklers.

TFP Model DV-5A, 1-1/2, 2, 3, 4, 6, 165.1mm and 8 in. size deluge valves, rated 300 psig, for use with Single-Interlock Preaction trim, intended for
operation by supervised wet pilot, dry pilot, electrically or manual activation, installed in accordance with the manufacturer's installation
instructions.

TFP Model DV-5A, 1-1/2, 2, 3, 4, 6, 165.1mm and 8 in. size deluge valves, rated 300 psig, for use with Double-Interlock Preaction trim w/
electric/electric release and Double-Interlock Preaction w/ electric/pneumatic release, installed in accordance with the manufacturer's installation
instructions.

TFP Model DV-5A, 2, 3, 4, 6, 165.1mm and 8 inch size deluge valves with Remote-Resetting with Electric Activation trim for vertical installation for
pressures not exceeding 300 psig.

TFP Model DV-5A in 3, 4, 6, 165.1mm and 8 in deluge valves with Remote-Resetting Pressure-Reducing trim for vertical installation for pressures
not exceeding 250 psi.

Last Updated on 2021-09-03

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-misleading
manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission
from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following
format:
"© 2021 UL LLC"
Refrigerated Area Sprinkler Systems
A refrigerated area sprinkler system affords fire protection in refrigerated rooms or buildings and includes special safeguards against
accidental filling with water and subsequent freezing of the system. A fire detection system shall actuate and one or more automatic
sprinklers in the piping shall operate before water will enter the sprinkler system. An alarm sounds if the detection system only is
actuated while pneumatic pressure is maintained in the sprinkler piping. An alarm also sounds if the pneumatic pressure in the
sprinkler piping is not properly maintained. In either case, water does not enter the system piping. These systems should be installed
in accordance with FM Global Loss Prevention Data Sheet 8-29, "Refrigerated Storage". System calculations regarding required
system air capacity should be performed if only one air maintenance device is contemplaed for several sprinkler systems.
Refrigerated area sprinkler systems which are operated pneumatically/hydraulically are FM Approved as complete systems. Only the
listed components for a given system may be used in combination.
Fire detection systems which are operated electrically are FM Approved on a component basis. Only compatible components may be
used in combination. Compatible FM Approved Release Control Panels for use with electric release refrigerated area sprinkler
system(s) are listed under RELEASE CONTROL PANEL COMPATIBILITY.

Model DV-5A Double Interlock Preaction System

Product Specification

Rated Working
Release Valve Size End
Pressure Remarks
Type Connection
in (mm) psi (kPa)
1 1/2, 2, 3, (40, 50, 80, 100, a, c, d, e, g, h, i, j, k, l,
Electric / Electric See Remarks Grooved
4, 6, 8 150, 200) m, n
a, b, c, d, e, g, h, i, j,
Electric / Electric 1 1/2, 2 (40, 50) See Remarks Threaded
k, l, m, n
(80, 100, 150, a, c, d, e, g, h, i, j, k, l,
Electric / Electric 3, 4, 6, 8 See Remarks Flanged
200) m, n
(80, 100, 150, a, c, d, e, g, h, i, j, k, l,
Electric / Electric 3, 4, 6, 8 See Remarks Grooved x Flanged
200) m, n
Electric / 1 1/2, 2, 3, (40, 50, 80, 100, a, c, d, e, f, g, h, i, j, l,
See Remarks Grooved
Pneumatic 4, 6, 8 150, 200) m, n
Electric / a, b, c, d, e, f, g, h, i, j,
1 1/2, 2 (40, 50) See Remarks Threaded
Pneumatic l, m, n
Electric / (80, 100, 150, a, c, d, e, f, g, h, i, j, l,
3, 4, 6, 8 See Remarks Flanged
Pneumatic 200) m, n
Electric / (80, 100, 150, a, c, d, e, f, g, h, i, j, l,
3, 4, 6, 8 See Remarks Grooved x Flanged
Pneumatic 200) m, n

Remarks:
a. Approved when supplied with a main control valve body ASTM A536 ductile iron
b. Approved when supplied with a main control valve body ASTM A351 CF8M stainless steel (size 1-1/2 inch NPS threaded end
connections only)
c. The rated working pressure is limited to the rated pressure of the release trim solenoid valve.
d. Approved when equipped with a Skinner Model 73218BN4UNLVN0C111C2 two-way normally closed solenoid valve, 24 V dc, 10
W, 1⁄2 in. NPS, Cv Factor 4.0, Rated Working Pressure of 175 psi (1210 kPa).
e. Approved when equipped with a Skinner Model 73212BN4TNLVN0C322C2 two-way normally closed solenoid valve, 24 V dc, 22.6
W, 1⁄2 in. NPS, Cv Factor 2.8, Rated Working Pressure of 250 psi (1720 kPa).
f. Approved when supplied with a Model DP-1 dry pilot valve
g. Approved when supplied with a Potter PS10-1 or PS10-2 waterflow pressure alarm switch
h. Approved when supplied with a Potter PS40-1 or PS40-2 low pressure alarm switch
i. Approved when supplied with a Potter Model QRS electronic accelerator system
j. Approved when equipped with a Skinner Model 73218BN4UNLVN0H111C2 two-way normally closed solenoid valve, 24 V dc, 10 W,
1⁄2 in. NPS, Cv Factor 4.0, Rated Working Pressure of 175 psi (1210 kPa).
k. Approved for use with Potter Model RCDS-1 releasing circuit disable switch.
l. Approved when factory assembled vertically inside the Model DV-5A Red-E Cabinet. The Red-E cabinet and assembled system
components comprise an integrated fire protection system which is assembled and tested at the factory.
m. Approved when DV-5A valve and trim assembled horizontally or vertically.
n. Approved when equipped with a Ningbo Yongxing two-way normally closed solenoid valve 24 V dc, 12 W, 1⁄2 in. NPS, Rated
Working Pressure of 230 psi (1600 kPa).

© 2007-2021 FM Approvals. All rights reserved. Page 1 of 2


Company Name: Tyco Fire Products LP
Company Address: 1467 Elmwood Ave, Cranston, Rhode Island 02910, USA
Company Website: http://tyco-fire.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved
Class of Work: 1012-Pre-Action Sprinkler Systems

© 2007-2021 FM Approvals. All rights reserved. Page 2 of 2


VIOT.EX15040
Air-pressure-maintenance Devices, Automatic
Page Bottom

Air-pressure-maintenance Devices, Automatic

See General Information for Air-pressure-maintenance Devices, Automatic

TYCO FIRE & BUILDING PRODUCTS EX15040


1400 PENNBROOK PKWY
LANSDALE, PA 19446-3840 USA

Tyco, Grinnell or GEM Models AMD-1, AMD-2, AMD-3.

Authorities having jurisdiction should be consulted before installation.

Last Updated on 2007-10-08

Questions? Print this page Terms of Use Page Top

© 2018 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non-
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2018 UL LLC".
Pressure Maintenance Devices, Dry Pipe Systems
These pressure maintenance devices automatically maintain a predetermined air or nitrogen pressure in dry pipe sprinkler systems.
Some devices may be used with a noncontinuous air supply which is capable of initially filling the system. Other systems require a
continuous air or nitrogen supply. Unless noted otherwise in the listing, these air maintenance devices have a pressure rating of 175
psi (1205 kPa).

Models AMD-1, AMD-2, AMD-3

Tyco Model AMD-1. 200 psi (1380 kPa) working pressure. Air maintenance.
Tyco Model AMD-2. Air maintenance.
Tyco Model AMD-3. Nitrogen maintenance.

Company Name: Tyco Fire Products LP


Company Address: 1467 Elmwood Ave, Cranston, Rhode Island 02910, USA
Company Website: http://tyco-fire.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved
Class of Work: 1032-Air Pressure Maint Dev

© 2007-2021 FM Approvals. All rights reserved. Page 1 of 1


1/5/2017 VPLX.EX6872 ­ Valves, Alarm

VPLX.EX6872
Valves, Alarm
Page Bottom

Valves, Alarm

See General Information for Valves, Alarm

TYCO FIRE & BUILDING PRODUCTS EX6872
1400 PENNBROOK PKWY
LANSDALE, PA 19446­3840 USA

Alarm valves, Model AV­1­175 in the sizes 2­1/2, 4, 6, 8 in. for horizontal or vertical installation with the following end connections: flanged­
flanged, flanged­grooved and grooved­grooved and for rated pressures not exceeding 175 psig.

Model AV­1­300 in the sizes 2­1/2, 4, 6, 8 in. for horizontal or vertical installation with the following end connections: flanged­flanged,
flanged­grooved and grooved­grooved and for rated pressures not exceeding 300 psig.

Model RC­1 retarding chamber, Model WM­1 "Y" strainer, Model WMA­1, water motor and gong all for rated pressures not exceeding 300 psig.

Models AV­1­175, AV­1­300 valves may be provided with flanged connections drilled per ANSI, AS, ISO, and JIS specifications.

Trademark and/or Tradename: "CSC"

Last Updated on 2015­11­21

Questions? Print this page Terms of Use Page Top

© 2016 UL LLC

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow­Up Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's Follow­Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non­
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2016 UL LLC".

http://database.ul.com/cgi­bin/XYV/template/LISEXT/1FRAME/showpage.html?name=VPLX.EX6872&ccnshorttitle=Valves,+Alarm&objid=1076957713&cfgid=1… 1/1
Water Motor Gongs
Water motor gongs give a locally audible alarm signal when the automatic sprinkler system operates. They may be used with
waterflow alarm, dry pipe, or automatic water control valves.

Model WMA-1
Model WMA-1. U.S. and European versions available.

Company Name: Tyco Fire & Building Products


Company Address: 1467 Elmwood Ave, Cranston, Rhode Island 02910, USA
Company Website: http://tyco-fire.com
New/Updated Product Listing: No
Listing Country: United States of America
Certification Type: FM Approved
Class of Work:

© 2007-2019 FM Approvals. All rights reserved. 1 of 1

You might also like