Professional Documents
Culture Documents
and Maintenance
Cross reference to related publications/information for blower coil units with Tracer
ZN controls:
• Installation, Operation, and Programming Guide for Tracer ZN010 and ZN510 Unit
Controllers, CNT-IOP-1
• Installation, Operation, and Programming Guide for Tracer ZN520 Unit Controller,
CNT-SVX04A-EN
• Blower Coil Air Handler Catalog, UNT-PRC003-EN
Installation…………………………………………………………… 2
General Information……………………………………………2
Pre-installation Considerations……………………………… 7
Dimensions/Weights………………………………………… 9
Mechanical Requirements………………………………… 16
Electrical Requirements………………………………………20
Installation Procedure…………………………………………23
Pre-Startup Requirements………………………………… 27
Operation …………………………………………………………29
General Information………………………………………… 29
Sequence of Operation……………………………………… 32
Maintenance………………………………………………………… 43
Maintenance Procedures…………………………………… 43
Troubleshooting………………………………………………49
Diagnostics…………………………………………………… 51
Typical Wiring Diagrams…………………………………… 58
BXCB-SVX01B-EN 3
General
Installation Information
Blower Coil General Two, four, or six-row main coils are All motors have internal thermal and
Information available for either hydronic cooling or current overloads, permanently sealed
heating. Four or six-row direct expansion ball bearings, and a resilient cradle mount
Blower coil units are draw-thru air
(DX) coils are also available for cooling. to reduce noise and vibration transmis-
handlers for cooling load conditions of
An optional one, two, four, or six-row sion.
400-3000 cfm. Units are available in
either horizontal (model BCHC) or vertical heating coil is available factory-installed Variable pitch sheave drive kit options
(model BCVC) configurations. Horizontal in either the preheat or reheat position. help make it possible to more accurately
units are typically ceiling suspended via Also, a one-row preheat steam is select design static pressure. For addi-
threaded rods. Knockouts are provided in available. tional flexibility, 115 volt single phase, two
all four corners to pass the rods through All units have an internal flat filter frame speed motors are optional.
the unit. Horizontal units can also be floor for one or two-inch filters. An optional
mounted. Vertical units are typically floor angle filter box (two inch only), mixing Note: Sheaves are factory set in the
mounted. They have a side inlet for easy box, bottom/top filter access box, or middle of the range.Field adjustment of
duct connection, and do not require a field combination angle filter mixing box is sheaves, motor, and belt are required to
fabricated inlet plenum. Vertical units ship available. arrive at desired rpm. Refer to the
in two pieces and can be set up in either a original sales order and Table GD-1 for
In addition, all units are available with drive information.
pre-swirl or counter-swirl configuration. either a basic or deluxe piping package
Basic unit components consist of a water option that includes a variety of control
coil, condensate drain pan, filter, duct valve sizes in two or three-way configura- Units may have no controls (4 x 4 junction
collars, one fan wheel, and motor with tions. The basic package consists of a box) or any of four different control types:
drive. See Figure GD-1. Drive compo- control valve and stop (ball) valves. The 1. control interface
nents consist of sheaves, belt, and motor. deluxe package consists of a control 2. Tracer ZN010
The coil, drain pan, and motor/drive valve, a stop (ball) valve, a circuit setter, 3. Tracer ZN510
assembly can easily be field-converted and strainer. 4. Tracer ZN520
from right hand to left hand configura- Belt-drive motors range from 1/3 to 3 All control options are factoryinstalled
tions or vice versa. horsepower in a wide range of voltages. and tested.
Unit sizes 12, 18, 24, 36,
Internal filter frame Galvanized steel 54, 72, and 90 MBh
Two, four, or six–row accomodates one or cabinet in 14, 18, 22,
main coil with copper two–inch filters and 28 inch heights
tubes and enhanced Knockouts in all four
aluminum fins corners for hanger
rods
4 BCXC-SVX01A-EN
General
Installation Information
BCXC-SVX01A-EN 5
General
Installation Information
Digit 22 — Electric Heat Controls Digit 29 — Coil #1 Piping Package Digit 35 — Factory Mounted Control
0 = none 0 = none Options
A = 24 volt magnetic contactors 1 = basic piping package 0 = none
B = 24 volt mercury contactors 2 = deluxe piping package A = fan status
B = dirty filter
Digit 23 — Electric Heat Options Digit 30 — Coil #2 Control Valve C = condensate overflow
0 = none 0 = none D = low limit
A = electric heat with heater fuse A = 2-way, 2-position, n.c. E=A&B
B = electric heat interlocking non-fused B = 2-way, 2-position, n.o. F=A&C
disconnect C = 3-way, 2-position, n.c. G=A&D
C=A&B D = 3-way, 2-position, n.o. H=B&C
E = 2-way modulating J=B&D
Digit 24 — Filters F = 3-way modulating K=C&D
0 = none G = field supplied valve, 2-pos., n.c. L = A, B, & D
A = 1” throwaway H = field supplied valve, 2-pos., n.o. M = A, B, & C
B = 2” pleated throwaway J = field supplied modulating valve N = A, C, & D
P = B, C, & D
Digit 25 — Accessory Section Digit 31 — Coil #2 Control Valve Cv R = all (A, B, C, & D)
0 = none 0 = none
A = mixing box only A = 3.3 Cv, 1/2” modulating, 1/2” pipe Digit 36 — Control Options 2
B = angle filter box B = 3.3 Cv, 1/2” modulating, 3/4” pipe 0 = none
C = angle filter/mixing box C = 4.0 Cv, 1/2” modulating, 3/4” pipe A = outside air sensor, field mounted
D = top access filter box D = 6.0 Cv, 1” modulating, 1” pipe B = discharge air sensor
E = bottom access filter E = 8.3 Cv, 1” modulating, 1” pipe C=A&B
F=A&D F = 9.0 Cv, 11/4” modulating, 11/4” pipe
G=A&E G = 3.5 Cv, 1/2” 2-position, 1/2” pipe Digit 37 — Control Options 3
H = 4.4 Cv, 1/2” 2-position, 1/2” pipe 0 = none
Digit 26 — Control Type J = 7.0 Cv, 3-way valve, 1” 2-position, 1” A = dehumidification with communicated
0 = no controls (4 x 4 junction box) pipe OR value
1 = control interface 6.0 Cv, 2-way valve,1” 2-position, 1” pipe B = dehumidification with local humidity
2 = Tracer ZN010 K = 8.0 Cv, 1” 2-position, 1” pipe sensor
3 = Tracer ZN510 L = 8.3 Cv, 1” 2-position, 1” pipe
4 = Tracer ZN520 M = 9.0 Cv, 11/4” 2-position, 11/4” pipe Digit 38 — Zone Sensors
0 = none
Digit 27 — Coil #1 Control Valve Digit 32 — Coil #2 Piping Package 1 = off/auto, setpoint knob, on/cancel, &
0 = none 0 = none comm jack
A = 2-way, 2-position, n.c. 1 = basic piping package 2 = off/auto/high/low, setpoint knob, on/
B = 2-way, 2-position, n.o. 2 = deluxe piping package cancel, and comm jack
C = 3-way, 2-position, n.c. 3 = setpoint knob, on/cancel, comm jack
D = 3-way, 2-position, n.o. Digit 33 — Remote Heat Options 4 = on/cancel, comm jack
E = 2-way modulating 0 = none 5 = sensor only
F = 3-way modulating 1 = staged electric heat 6 = off/auto, celsius setpoint knob, on/
G = field supplied valve, 2-pos., n.c. 2 = 2-position hot water, n.c. cancel, & comm jack
H = field supplied valve, 2-pos., n.o. 7 = off/auto/high/low, celsius setpoint knob,
J = field supplied modulating valve Digit 34 — Mixing Box Damper Actuator on/cancel, & comm jack
0 = none 8 = Celsius setpoint knob, on/cancel, &
Digit 28 — Coil #1 Control Valve Cv 1 = 2-position, n.o., ship loose comm jack
0 = none 2 = modulating, n.c.
A = 3.3 Cv, 1/2” modulating, 1/2” pipe 3 = modulating, n.o. Digit 39 — Extra Belt
B = 3.3 Cv, 1/2” modulating, 3/4” pipe 4 = modulating, ship loose 0 = none
C = 4.0 Cv, 1/2” modulating, 3/4” pipe 5 = field supplied 2-position, n.o. 1 = ship loose extra belt
D = 6.0 Cv, 1” modulating, 1” pipe 6 = field supplied 2-position, n.c.
E = 8.3 Cv, 1” modulating, 1” pipe 7 = field supplied modulating Digit 40 — Extra Filter
F = 9.0 Cv, 11/4” modulating, 11/4” pipe 0 = none
G = 3.5 Cv, 1/2” 2-position, 1/2” pipe 1 = ship loose extra 1” throwaway filter
H = 4.4 Cv, 1/2” 2-position, 1/2” pipe 2 = ship loose extra 2” pleated throwaway
J = 7.0 Cv, 3-way valve, 1” 2-position, 1”
pipe OR
6.0 Cv, 2-way valve,1” 2-position, 1” pipe
K = 8.0 Cv, 1” 2-position, 1” pipe
L = 8.3 Cv, 1” 2-position, 1” pipe
M = 9.0 Cv, 1 1/4” 2-position, 1 1/4” pipe
6 BCXC-SVX01A-EN
Pre-Installation
Installation Considerations
BCXC-SVX01A-EN 7
Pre-Installation
Installation Considerations
top view *
11.25
12.79
front view
BCXC-SVX01A-EN 9
Dimensions
Installation and Weights
11.25
front view
30.00
10 BCXC-SVX01A-EN
Dimensions
Installation and Weights
mixing box
Angle Filter & Mixing Box Dimensions and Weights, in-lbs. NOTES:
Unit 1. ALL DIMENSIONS ARE IN INCHES.
Size H L W A B weight 2. MIXING BOX SHIPS ASSEMBLED FOR FIELD INSTALlatION.
3. LINKAGE BETWEEN DAMPERS IS FACTORY INSTALLED
12 14.12 22.00 24.11 7.06 15.56 36.0
INSIDE MIXING BOX, OPPOSITE DRIVE SIDE. DRIVE ROD ON
18 14.12 22.00 28.11 7.06 19.56 41.0 BACK DAMPER MAY BE EXTENDED THRU KNOCKOUT FOR
24 18.12 19.50 28.11 7.06 19.56 43.0 EXTERNALLY MOUNTED ACTUATOR. TO ADJUST, LOOSEN
36 18.12 24.50 40.11 7.06 31.56 56.0 HEX HD SET scREW ON BLADE.
54 22.12 23.50 40.11 12.81 31.56 72.0 4. UNIT SIZE 36 HAS ONLY ONE ANGLE FILTER TRACK. ALL
72 22.00 23.50 48.00 12.81 31.56 72.5 OTHER UNIT SIZES HAVE 2 FILTER TRACKS AS SHOWN.
5. ALL SECTIONS SHIP SEPARATELY.
90 27.90 27.56 48.00 12.85 31.56 84.1
BCXC-SVX01A-EN 11
Dimensions
Installation and Weights
7.17
.97
NOTES:
1. DIMENSIONS ARE IN INCHES.
2. ROTATE 180° FOR TOP ACCESS.
3. SECTION SHIPS ATTACHED TO THE UNIT.
12 BCXC-SVX01A-EN
Dimensions
Installation and Weights
Electric Heat
top view
BCXC-SVX01A-EN 13
Dimensions
Installation and Weights
Steam Coil
ACCESS PANEL
C B C
0.97
HEATING COIL
NOTES:
1. FILTER ACCESS & ACCESS PANEL LOCATED ON BOTH
SIDES. H A
2. WEIGHT INCLUDES CABINET WITH AVERAGE FILTER,
BUT DOES NOT INCLUDE COIL WEIGHT. SEE GENERAL
DATA SECTION FOR COIL WEIGHTS.
0.97
21.00 W
FILTER ACCESS
Coil Connections Hydronic Coil Connection Sizes, in. High-Capacity Hydronic Coil Connection
Unit Sizes, in.
Size 1-row 2-row 4-row 6-row Unit
12 0.750 0.750 0.750 0.750 Size 2-row 4-row 6-row
18 0.750 0.750 0.750 0.750 12 0.625 0.625 0.625
24 0.875 0.875 0.875 0.875 18 0.625 0.625 0.625
36 0.875 0.875 0.875 0.875 24 0.750 0.750 0.750
54 1.125 1.375 1.375 1.375 36 0.750 0.750 0.750
72 1.125 1.375 1.375 1.375 54 1.125 1.125 1.125
90 1.125 1.375 1.625 1.625 72 1.125 1.125 1.125
90 1.125 1.125 1.125
14 BCXC-SVX01A-EN
Dimensions
Installation and Weights
Piping Packages
B A
B D
A B
AB
F
C
A B C
AB
1
E Two-Way 1 /4” Deluxe Piping Package
A B
F
Piping Package Dimensions, in. A B
AB
Piping nominal actual E
Package size size A B C D E F
2-way 0.50 0.625 12.025 2.650 12.625 5.650 na na
1.00 1.125 13.295 4.260 13.220 9.288 3.020 na
3-way 0.50 0.625 12.088 2.097 12.688 4.497 6.351 6.351
0.75 0.875 15.623 1.750 15.313 6.290 6.701 6.701 C D
1.00 1.125 13.370 3.690 13.210 9.060 9.813 9.813
1.25 1.375 16.885 3.738 16.410 10.023 3.052 10.520 Three-Way, 1/2” & 1” Deluxe Piping Package
BCXC-SVX01A-EN 15
Mechanical
Installation Requirements
16 BCXC-SVX01A-EN
Mechanical
Installation Requirements
CAUTION
Potential coil-freeze condition!
Make provisions to drain the coil when
not in use to prevent coil freeze-up.
BCXC-SVX01A-EN 17
Mechanical
Installation Requirements
Refrigerant Coil Piping indicating sight glass, filter drier, manual CAUTION
The DX cooling coil in a BCHC/BCVC unit ball shutoff valves, access port, and
is equipped with a single distributor possibly a solenoid valve. Position these Disassemble the thermal expansion
(single-circuited). Some condensing units components as close to the evaporator valve before completing the brazing
have two, independent refrigeration as possible. connections. If necessary, wrap the
circuits. Do not manifold two, • Thermal expansion valve (TEV): Select valve in a cool wet cloth while brazing.
independent refrigeration circuits into a the TEV based on the actual evaporator Failure to protect the valve from high
single-circuited DX (evaporator) coil. capacity, considering the full range of temperatures may damage internal
loadings. Verify that the valve will components.
Note: Refer to the “Special Note on successfully operate at the lightest load
Emissions” section on page 2 for condition, considering if hot gas bypass is
information on handling refrigerants. to be used. For improved modulation, Suction Line
choose a TEV with balanced port con- Line sizing: Properly sizing the suction line
Units that are UL listed shall not have struction and an external equalizer is critical for ensuring that the oil returns
refrigerant temperatures and pressures connection. The valve must be designed to the compressor throughout the system
exceeding that listed on the unit name- to operate against a back pressure of 20 operating envelope. If provided, use the
plate. psi higher than actual evaporator suction line size(s) recommended by the
pressure. Install the TEV directly on the manufacturer of the compressor unit. The
Follow accepted refrigeration piping selected tube diameter(s) must maintain
practices and safety precautions for coil liquid connection (distributor pro-
vided). adequate refrigerant velocities at all
typical refrigerant coil piping and compo- operating conditions.
nents. Specific recommendations are The remote expansion-valve bulb should
provided with the compressor unit, be firmly attached to a straight, well- Routing: To prevent residual or con-
including instructions for pressure-testing, drained, horizontal section of the suction densed refrigerant from “free-flowing”
evacuation, and system charging. Leak line. The external equalizer line should be toward the compressor, install the suction
test the entire refrigerant system after all inserted downstream of the remote bulb. line so it slopes slightly — 1 inch per 10
piping is complete. Charge the unit feet of run [1 cm per 3 m] — toward the
• Moisture-indicating sight glass: Install a evaporator. Avoid putting refrigerant
according to approximate weight moisture-indicating sight glass in the
requirements, operating pressures and lines underground. Refrigerant condensa-
liquid line between the expansion valve tion, installation debris inside the line,
superheat/subcooling measurements. and filter drier. The sight glass should be
Adjust the thermal expansion valve service access, and abrasion/corrosion
sized to match the size of the liquid line. can quickly impair system reliability.
setting, if necessary, for proper super-
heat. • Filter drier: Install a properly sized liquid Insulation: After operating the system
line filter-drier upstream from the and testing all fittings and joints to verify
Liquid Line expansion valve and as close to the
Line Sizing: Properly sizing the liquid line the system is leak-free, insulate the
evaporator coil as possible. Select the suction
is critical to a successful application. If filter-drier for a maximum pressure drop
provided, use the liquid line size of 2 psi at the design condition. lines to prevent heat gain and unwanted
recommended by the manufacturer of condensation.
the compressor unit. The selected tube Manual, ball-type shutoff valves on either
side of the filter drier allows replacement Components: Installing the suction line
diameter must be as small as possible, requires field installation of these
while still providing at least 5°F [2.7°C] of of the core without evacuating the entire
refrigerant charge. components: an access port and possibly
subcooling at the expansion valve a suction filter. Position them as close to
throughout the operating envelope. • Access port: The access port allows the the compressor as possible.
Routing: Install the liquid line with a slight unit to be charged with liquid refrigerant
and is used to determine subcooling. This • Access port: The access port is used to
slope in the direction of flow so that it can determine suction pressure and adjust
be routed with the suction line. Minimize port is usually a Schraeder valve with a
core. the TEV. It should be located near the
tube bends and reducers because these external equalizer line connection. This
items tend to increase pressure drop and • Solenoid valve: If required by the port is usually a Schraeder valve with a
reduce subcooling at the expansion compressor unit, install the solenoid core.
valve. valve between the filter drier and sight
glass. • Suction filter: If required by the com-
Insulation: The liquid line is generally pressor unit, a replaceable-core suction
warmer than the surrounding air, so it filter is installed as close to the compres-
does not require insulation. sor unit as possible. Adding manual, ball-
Components: Liquid-line refrigerant type shutoff valves upstream and
components necessary for a successful downstream of the filter simplifies
job include an expansion valve, moisture- replacement of the filter core.
18 BCXC-SVX01A-EN
Mechanical
Installation Requirements
liquid
sight line
glass
distributor
BCXC-SVX01A-EN 19
Electrical
Installation Requirements
20 BCXC-SVX01A-EN
Electrical
Installation Requirements
Minimum Circuit Ampacity (MCA) and Table I-ER-2. Available Electric Heat Kw (min.-max)
Maximum Fuse Size (MFS) Calculations
Unit Size
for Units with Electric Heat
Use these formulas to calculate the MCA Voltage 12 18 24 36 54 72 90
and MFS. 115/60/1 1-3 1-3 1-3 1-3 1-3 1-3 1- 3
208/60/1 1-4 1-6 1-8 1-8 1-8 1- 8 1-8
Heater amps = (heater kW x 1000)/ 230/60/1 1-4 1-6 1-8 1-8 1-8 1-8 1-8
heater voltage 277/60/1 1-4 1-6 1-8 1-11 1-11 1-11 1-11
208/60/3 1-4 1-6 1-8 1-11 1-12 1-12 1-12
Note: Use 120V heater voltage for 115V 230/60/3 1-4 1-6 1-8 1-11 1-12 1-12 1-12
460/60/3 1.5-4 1.5-5 1-8 1-11 1-16 1-21 1-30
units. Use 240V heater voltage for 230V 575/60/3 2-4 2-4 1-8 1-11 1-16 1-21 1-30
units. Use 480V heater voltage for 460V 220/50/1 1-4 1-6 1-8 1-8 1-8 1-8 1-8
units. Use 600V heater voltage for 575V 240/50/1 1-4 1-6 1-8 1-8 1-8 1-8 1-8
380/50/3 1-4 1-5 1-8 1-11 1-16 1-20 1-28
units. 415/50/3 1.5-4 1.5-5 1-8 1-11 1-16 1-21 1-30
190/50/3 na na na na na na na
MCA = 1.25 x (heater amps + all motor Notes:
FLA’s) 1. Heaters are available in the following Kw increments : 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0,
4.5, 5.0, 5.5, 6.0, 6.5, 7.0, 7.5, 8.0, 9.0, 10.0, 11.0, 12.0, 13.0, 14.0, 15.0, 16.0, 17.0, 18.0,
19.0, 20.0, 21.0, 22.0, 24.0, 26.0, 28.0, 30.0.
MFS or HACR type circuit breaker = 2. Magnetic contactors are standard. Mercury contactors are available on horizontal
(2.25 x largest motor FLA) + second units only.
3. Units with electric heat are available with or without door interlocking disconnect
motor FLA switch.
+ heater amps (if applicable) 4. Units with electric heat are available with or without line fuses.
5. Units with electric heat must not be run below the minimum cfm listed in the
HACR (Heating, Air-Conditioning and general data section.
6. Electric heat is balanced staging: 1 stage = 100%, 2 stages = 50%/50%
Refrigeration) type circuit breakers are 7. Electric heat is not available on 190/50/3 units.
required in the branch circuit wiring for all
units with electric heat.
See Table I-ER-2 for electric heat kW and
Table I-ER-3 on page 22 for motor FLAs.
Select a standard fuse size or HACR type
circuit breaker equal to the MCA.
Use the next larger standard size if the
MCA does not equal a standard size.
Standard fuse sizes are: 15, 20, 25, 30, 35,
40, 45, 50, 60 amps
Useful Formulas
kW = (cfm x ∆T)/3145
∆T = (kW x 1000)/voltage
Single phase amps = (kW x 1000)/voltage
Three phase amps = (kW x 1000)/
(voltage x 1.73)
Electric heat MBh = (Heater kW) (3.413)
BCXC-SVX01A-EN 21
Electrical
Installation Requirements
22 BCXC-SVX01A-EN
Installation
Installation Procedure
BCXC-SVX01A-EN 23
Installation
Installation Procedure
24 BCXC-SVX01A-EN
Installation
Installation Procedure
BCXC-SVX01A-EN 25
Installation
Installation Procedure
Installing Wall Mounted • Radiant heat from the sun, fireplaces, installation holes. Ensure the base is
Controls appliances, etc. level.
Wall mounted zone sensors ship taped to • Airflow from adjacent zones or other b. Set the base aside and make the
the control box. Refer to Figure I-IP-5 for units. cutout. Then, drill two 3/16” diameter
zone sensor dimensions. • Unheated or uncooled spaces behind holes approximately one-inch deep.
the controller, such as outside walls or Insert and fully seat the plastic anchors.
Position the controller on an inside wall unoccupied spaces. c. Pull the control wires through the
three to five feet above the floor and at • Concealed pipes, air ducts, or chimneys cutout and attach the module to the wall
least 18 inches from the nearest outside in partition spaces behind the controller. using the screws provided.
wall. Installing the controller at a lower 4. To install the zone sensor module to a
height may give the advantage of standard junction box:
monitoring the temperature closer to the Zone Sensor Installation a. Level and install a 2“ x 4” junction
zone, but it also exposes the controller to Follow the procedure below to install the box (installer supplied) vertically on the
airflow obstructions. Ensure that air flows zone sensor module. See Figure I-IP-5. wall.
freely over the controller. 1. Note the position of the setpoint b. Pull the control wires through the
Before beginning installation, follow the adjustment knob and gently pry the cutout. Attach the module to the wall
wiring instructions below. Also, refer to adjustment knob from the cover using using the screws provided.
the unit wiring schematic for specific the blade of a small screwdriver. 5. Strip the insulation on the
wiring details and point connections. 2. Insert the screwdriver blade behind the interconnection wires back 0.25 inch
cover at the top of the module and and connect to TB1. Screw down the
Wiring Instructions carefully pry the cover away from the terminal blocks.
Avoid mounting the controller in an area base. 6. Replace the zone sensor cover and
subject to the following conditions: 3. To install the zone sensor module adjustment knob.
• Dead spots, such as behind doors or in without a junction box (directly to the
corners that do not allow free air If installing a Tracer ZN510 or ZN520 zone
wall): sensor, see the Tracer Summit Communi-
circulation. a. Using the module base as a
• Air drafts from stairwells, outside doors, cation section regarding communication
template, mark the the rectangular wiring on page 27 for more information.
or unsectioned hollow walls. cutout for the control wiring and module
26 BCXC-SVX01A-EN
Pre-Startup
Installation Requirements
BCXC-SVX01A-EN 27
Pre-Startup
Installation Requirements
28 BCXC-SVX01A-EN
General
Operation Information
BCXC-SVX01A-EN 29
General
Operation Information
30 BCXC-SVX01A-EN
General
Operation Information
BCXC-SVX01A-EN 31
Sequence of
Operation Operation
Tracer ZN Controller Sequence A communicated request will control the Unoccupied Mode
of Operation controller’s occupancy. Typically, this When the controller is in the unoccupied
request comes from the BAS time-of-day mode, the controller attempts to
Power-Up Sequence scheduling to the controller. However, if a maintain space temperature at the
When 24 VAC power is initially applied to communication request from a BAS or stored unoccupied heating or cooling
the Tracer® ZN controller, the following peer controller is lost, the controller setpoint based on the:
sequence occurs: reverts to the default operating mode • measured space temperature,
• all outputs are controlled off (occupied) after 15 minutes (configurable, • active setpoint , and
• Tracer reads all input values to specified by the “receive heartbeat • control algorithm, regardless of the
determine initial values, time”), if no local hardwired occupancy presence of a hardwired or
• the random start time (0-25 seconds) signal exists. communicated setpoint.
expires, and Similar to other controller configuration
• normal operation begins. If the unit is communicating with Tracer
properties, the locally stored unoccupied
Summit and the supply fan control
Tracer ZN Modes of Operation setpoints can be modified using Rover™
programming point is configured for
Tracer ZN controllers operate the fan in service tool.
Tracer (the factory configures as local),
one of the modes listed below as noted: then Tracer Summit will control the fan During cooling mode, when the space
• occupied regardless of the fan mode switch temperature is above the cool setpoint,
• unoccupied position. the primary cooling capacity operates at
• occupied standby (Tracer ZN510 or 100%. If more capacity is needed, the
ZN520 only) For complete information about Tracer
supplementary cooling capacity turns on
• occupied bypass Summit application setup using the
(or opens to 100%).
• Tracer Summit with supply fan control Tracer ZN controller, see the Tracer
(Tracer ZN510 or ZN520 only) Summit product literature. For more During heating mode, when the space
information on the setup of another BAS, temperature is below the heat setpoint,
Note: The Tracer ZN520 controller refer to the product-specific literature the primary heating capacity turns on. All
operates the supply fan continuously from that manufacturer. capacity turns off when the space
when the controller is in the occupied temperature is between the unoccupied
Occupied Mode
and occupied standby modes, for either cooling and heating setpoints. Note that
When the controller is in the occupied
heating or cooling. The controller only primary heating or cooling capacity is
mode, the unit attempts to maintain the
cycles the fan off with heating and defined by the unit type and whether
space temperature at the active occupied
cooling capacity in the unoccupied mode. heating or cooling is enabled or disabled.
heating or cooling setpoint, based on the:
For example, if the economizer is
• measured space temperature,
enabled (Tracer ZN520 only) and
When the communicated occupancy • the discharge air temperature (Tracer
possible, it is the primary cooling capac-
request is unoccupied, the occupancy ZN520 only),
ity. If hydronic heating is possible, it will
binary input (if present) does not affect • the active setpoint, and
be the primary heating capacity.
the controller’s occupancy. When the • the proportional/integral control
communicated occupancy request is algorithm. Occupied Standby Mode (Tracer ZN510
occupied, the controller uses the local The modulating control algorithm used or ZN520 only)
occupancy binary input to switch be- when occupied or in occupied standby is The controller can be placed into the
tween the occupied and occupied described in the following sections. occupied standby mode when a
standby modes. Additional information related to the communicated occupancy request is
handling of the controller setpoints can be combined with the local (hardwired)
Occupancy Sources occupancy binary input signal.
found in the previous setpoint operation
There are four ways to control the Tracer
section. During occupied standby mode, the
ZN controller’s occupancy, as noted
below: Tracer ZN520 controller’s economizer
Note: Heating and cooling setpoint high
1. By pressing the zone sensor’s timed damper position goes to the economizer
and low limits are always applied to the
override “on” button standby minimum position.
occupied and occupied standby
2. Occupancy binary input, either setpoints.
normally open or normally closed, see Note: The economizer standby minimum
Table O-SO-1 for occupancy sensor position can be changed using Rover
states service tool.
3. Default operation of the controller Table O-SO-1. Occupancy Sensor State Table
(occupied mode) Sensor Type Sensor Position Unit Occupancy Mode
4. Communicated request, usually Normally Open Open Occupied
provided by the building automation Normally Open Closed Unoccupied
system (BAS) or peer device (available Normally Closed Open Unoccupied
on Tracer ZN510 and ZN520 only) Normally Closed Closed Occupied
32 BCXC-SVX01A-EN
Sequence of
Operation Operation
In the occupied standby mode, the (Tracer ZN510 or ZN520 only), or DX Cooling (Tracer ZN520 only)
controller uses the occupied standby • unoccupied cooling setpoint. The controller does not use both the DX
cooling and heating setpoints. Because compressor and the economizer at the
The controller uses the measured space
the occupied standby setpoints typically same time. This prevents problems
temperature, the active cooling setpoint,
cover a wider range than the occupied where the entering air temperature is too
and discharge air temperature (Tracer
setpoints, the controller reduces heating/ low for the evaporator coil to operate as
ZN520 only) along with the control
cooling demand for the space. Also, units designed, which leads to compressor
algorithm to determine the requested
with Tracer ZN520 and the fresh air short cycling due to low discharge air
cooling capacity of the unit (0-100%). The
economizer damper use the economizer temperatures.
outputs are controlled based on the unit
standby minimum position to reduce
configuration and the required cooling Discharge Air Tempering (Tracer ZN520
heating and cooling demand.
capacity. To maintain space temperature Only)
When no occupancy request is communi- control, the cooling outputs (modulating Cascade cooling control initiates a
cated, the occupancy binary input or 2-position hydronic valve, or econo- discharge air tempering function if:
switches the controller’s operating mode mizer damper) are controlled based on • the discharge air temperature falls
between occupied and unoccupied. the cooling capacity output. below the discharge air temperature
When no communicated occupancy control low limit,
request exists, the unit cannot switch to Note: Economizer dampers and modulat- • all cooling capacity is at minimum, and
occupied standby mode. ing valves are only available on units • the discharge control loop determines a
with the Tracer ZN520 controller. Two- need to raise the discharge air
Occupied Bypass Mode, Tracer ZN510 or
position dampers are only available on temperature.
ZN520 Only
units with Tracer ZN010 and ZN510.
The controller can be placed in occupied The controller then provides heating
bypass mode by either communicating capacity to raise the discharge air
an occupancy bypass request to the Cooling output is controlled based on the temperature to its low limit.
controller or by using the timed override cooling capacity. At 0% capacity, all
cooling capacities are off and the damper The discharge air tempering function
“on” button on the zone sensor. When
is at minimum position. Between 0 and enables when cold, fresh air is brought in
the controller is in unoccupied mode,
100% capacity, the cooling outputs are through the fresh air damper and causes
pressing the “on” button will place the
controlled according to modulating valve the discharge air to fall below the
controller into occupied bypass mode for
logic (Tracer ZN520 only) or cycled with discharge air temperature control low
the duration of the bypass time (typically
2-position valves. As the load increases, limit. The controller exits the discharge air
120 minutes).
modulating outputs open further and tempering function when heat capacity
Tracer Summit With Supply Fan Control, has been at 0% for five minutes.
binary outputs are energized longer. At
Tracer ZN510 or ZN520 Only
100% capacity, the cooling valve or
All Tracer ZN lockouts (latching
diagnostics) are manually reset
damper is fully open (modulating valves) Heating Operation
or on continuously (2-position valves).
whenever the fan mode switch is set to During heating mode, the Tracer ZN
the off position or when power is restored Note: Unit diagnostics can affect fan controller attempts to maintain the space
to the unit. The last diagnostic to occur is operation, causing occupied and occu- temperature at the active heating
retained until the unit power is pied standby fan operation to be defined setpoint. Based on the controller’s
disconnected. Refer to Trane publication, as abnormal. Refer to the Troubleshoot- occupancy mode, the active heating
CNT-SVX04A-EN Installation Operation ing section for more information about setpoint can be:
and Programming Guide, for specific abnormal fan operation. • occupied heating,
Tracer ZN520 operating procedures. • occupied standby heating (Tracer ZN510
or ZN520 only), or
Cooling Operation Economizer Cooling (Tracer ZN520 Only) • unoccupied heating.
The economizer provides cooling
During cooling mode, the Tracer ZN whenever the outdoor temperature is Note: Unit diagnostics can affect the
controller attempts to maintain the space below the economizer enable setpoint controller operation, causing unit
temperature at the active cooling and there is a need for cooling. The operation to be defined as abnormal.
setpoint. Based on the controller’s economizer operates to meet the space Refer to the Troubleshooting section for
occupancy mode, the active cooling demand, with other forms of cooling more information about abnormal unit
setpoint is either the: enabling when the economizer cannot operation.
• occupied cooling setpoint, meet the demand alone. See economizer
• occupied standby cooling setpoint air damper operation for additional
information. Heating output is controlled based on the
heating capacity. At 0% capacity, the
heating output is off continuously.
BCXC-SVX01A-EN 33
Sequence of
Operation Operation
Between 0 and 100% capacity, the in auto, the fan speed can switch depend-
heating output is controlled according to ing on the error. The fan speed increases
modulating valve logic (ZN520 only) or as the space temperature rises above the
cycled with 2-position valves. As the load active cooling setpoint.
increases, modulating outputs open Additional flexibility built into the control-
further and binary outputs are energized ler allows you to enable or disable the
longer. At 100% capacity, the modulating local fan switch input. The fan mode
valve is fully open (Tracer ZN520 only) or request can be hardwired to any of the
on continuously with 2-position valves. Tracer ZN controllers or communicated to
Economizer Damper (Tracer ZN520 Only) the Tracer ZN510 or ZN520 controller.
The economizer damper option is never When both inputs are present, the
used for as a source for heating, but only communicated request has priority over
for ventilation. Therefore, the damper is the hardwired input. See Table O-SO-2 on
at the occupied minimum position in the page 35.
occupied mode. The damper control is Fan Speed Switch
primarily associated with occupied fan Off: Fan is turned off, two-position
operation. damper option spring-returns closed.
Dehumidification (Tracer ZN520 only) High or Low: Fan runs continuously at the
During dehumidification, the Tracer selected speed. The two-position damper
ZN520 controller adjusts the heating option opens to an adjustable mechanical
setpoint up to the cooling setpoint. This stop-position.
reduces the relative humidity in the
space with a minimum of energy usage. Tracer ZN010 and ZN510
Off: Fan is off; control valves and fresh air
The controller uses the measured space damper option close. Low air
temperature, the active heating setpoint, temperature detection option is still
and discharge air temperature (Tracer active.
ZN520 only) along with the control
algorithm, to determine the requested Auto (Fan Cycling): Fan and fresh air
heating capacity of the unit (0-100%). The damper cycle with control valve option to
outputs are controlled based on the unit maintain setpoint temperature. If the unit
configuration and the required heating has a 2-speed fan, in cooling mode the
capacity. fan cycles from off to high and in heating
mode it cycles from off to low (factory
default that can be field-adjusted using
Fan Mode Operation Rover service software). When no
For multiple fan speed applications, the heating or cooling is required, the fan is
Tracer ZN controller offers additional fan off and the fresh air damper option
configuration flexibility. See Table O-SO-2 closes. Units with 2-speed fans can also
on page 35 for fan operation sequences. be field-configured using Rover to run at
Separate default fan speeds for heating a defined speed when the fan speed
and cooling modes can be configured switch is in the auto position.
using Rover service software. Low or High (Continuous Fan): Fan
The fan runs continuously at selected operates continuously while control valve
speeds, high or low. When the fan mode option cycles to maintain setpoint
switch is in the auto position or a temperature. Fresh air damper option is
hardwired fan mode input does not exist, open.
the fan operates at the default configured Tracer ZN520
speed. See Table O-SO-3 on page 35 for Off: Fan is off; control valve options and
Tracer ZN520 default fan configuration fresh air damper options close. The low
for heating and cooling modes. During air temperature detection option is still
unoccupied mode, the fan cycles be- active.
tween high speed and off with heating
and cooling fan modes. If the requested Auto: Fan speed control in the auto
speed is off, the fan always remains off. setting allows the modulating (three-wire
floating point) control valve option and
During dehumidification, when the fan is
34 BCXC-SVX01A-EN
Sequence of
Operation Operation
Table O-SO-2. Tracer ZN520 Fan Configura- when the unit is off due to a diagnostic or
single or two-speed fan to work coopera-
tion tively to meet precise capacity require- when the unit is in the off mode due to the
Auto Fan ments, while minimizing fan speed local zone sensor module, a communi-
Fan Speed
Operation Default (motor/energy/acoustics) and valve cated request, or the default fan speed
position (pump energy/chilled water (off).
Heating Continuous Off
Low reset). As the capacity requirement If both a zone sensor module and
High increases at low fan speed, the water communicated request exist, the commu-
valve opens. When the low fan speed nicated request has priority. See Table O-
Cooling Continuous Off capacity switch point is reached, the fan
Low SO-6 on page 36.
High switches to high speed and the water
valve repositions to maintain an equiva- Fan Cycling Operation
lent capacity. The reverse sequence Tracer ZN520 does not support fan
takes place with a decrease in required cycling in occupied mode. The fan cycles
capacity. between high speed and off in the
unoccupied mode only. The controller’s
Units with 2-speed fans on low or high: cascade control algorithm requires
The fan will run continously at the continuous fan operation in the occupied
selected speed and the valve option will mode.
cycle to meet setpoint.
Fan Off Delay
Continuous Fan Operation When a heating output is controlled off,
During occupied and occupied standby the Tracer ZN controller automatically
modes, the fan normally is on. For holds the fan on for an additional 30
multiple speed fan applications, the fan seconds. This 30-second delay allows the
normally operates at the selected or fan to blow off any residual heat from the
default speed (off, high, or low). When fan heating source, such as a steam coil.
mode is auto, the fan operates at the When the unit is heating, the fan off delay
default fan speed. is normally applied to control the fan;
During unoccupied mode, the fan is off. otherwise, the fan off delay does not
While unoccupied, the controller will heat apply.
or cool to maintain the unoccupied Fan Start on High Speed
heating and cooling setpoints. In unoccu- On a transition from off to any other fan
pied mode, the fan runs on high speed speed, the Tracer ZN controller
only, with heating or cooling. See Table O- automatically starts the fan on high speed
SO-7 on page 36 and runs the fan at high speed for 0.5
The unit fan is always off during occupied, seconds. This provides ample torque
occupied standby, and unoccupied modes required to start all fan motors from the
off position.
BCXC-SVX01A-EN 35
Sequence of
Operation Operation
Fan Operation During Occupied Heating Table O-SO-4. Fan Mode Operation, Tracer ZN010 and ZN510
Modes Heating Mode Cooling Mode
The ZN520 fan output(s) normally run Fan Mode Occupied Unoccupied Occupied Unoccupied
continuously during the occupied and Off off off off off
occupied standby modes, but cycle
between high and off speeds with Low low off/high (3) low off/high (3)
heating/cooling during the unoccupied High high off/high (3) high off/high (3)
mode. When in the occupied mode or
occupied standby mode and the fan Auto
speed is set at the high or low position, Continuous heat default off/high (3) cool default off/high (3)
the fan runs continuously at the selected Cycling Off off/heat default off/high (3) off/cool default off/high (3)
speed. Refer to the Troubleshooting Notes:
section for more information on 1. During the transition from off to any fan speed but high, Tracer® ZN010 and ZN510 automatically starts the fan on high
speed and runs for one-half of a second before transitioning to the selected speed (if it is other than high). This
abnormal fan operation. provides enough torque to start all fan motors from the off position.
2. When the heating output is controlled off, ZN010 and ZN510 automatically controls the fan on for an additional 30
seconds. This delay allows the fan to dissipate any residual heat from the heating source, such as electric heat.
3. Whenever two states are listed for the fan:
The first state (off) applies when there is not a call for heating or cooling.
The second state (varies) applies when there is a call for heating or cooling.
The heat default is factory configured for low fan speed, and the cool default is high.
Table O-SO-5. Valid Operating Range and Factory Default Setpoints, Tracer ZN010 & ZN510
Setpoint/Parameter Default Setting Valid Operating Range
Unoccupied cooling setpoint 85° F 40 to 115° F
Occupied cooling setpoint 74° F 40 to 115° F
Occupied Heating setpoint 71° F 40 to 115° F
Unoccupied heating setpoint 60° F 40 to 115° F
Cooling setpoint high limit 110° F 40 to 115° F
Cooling setpoint low limit 40° F 40 to 115° F
Heating setpoint high limit 105° F 40 to 115° F
Heating setpoint low limit 40° F 40 to 115° F
Power up control wait 0 sec 0 to 240 sec
36 BCXC-SVX01A-EN
Sequence of
Operation Operation
Two and Four-Pipe Table O-SO-8. Unit Mode as Related to Water Temperature
Changeover Operation Unit Type EWT Sensor Required? Coil Water Temperature
2-pipe changeover Yes • Can cool if: space temp - EWT ≥ 5 deg F
Tracer ZN controllers offer accurate and • Can heat if: EWT - space temp ≥ 5 deg F
reliable unit changeover using 2-way
valves and the controller’s entering water 4-pipe changeover Yes • Can cool if: space temp - EWT ≥ 5 deg F
• Can heat if: EWT - space temp ≥ 5 deg F
temperature sampling function. Only
units using the main hydronic coil for both 2-pipe heating only No Hot water assumed
heating and cooling (2-pipe and 4-pipe
changeover units) use the entering water 2-pipe cooling only No Cold water assumed
temperature sampling function. 4-pipe heat/cool No • Cold water assumed in main coil
Two-pipe and 4-pipe changeover • Hot water assumed in aux. coil
applications require an entering water
temperature sensor to allow the main
coil to be used for heating and cooling.
This sensor is factory-provided and should be five degrees above the Electric Heat Operation
should be field-installed on the entering measured space temperature. Tracer ZN controllers support 1-stage
water pipe. After the controller invokes the function, electric heat. Also, Tracer ZN520
The entering water temperature sam- the unit opens the main hydronic valve supports 2-stage electric heat. Tracer
pling function periodically opens the two- for no more than three minutes before ZN520 cycles the electric heat to control
way valve to allow temporary water considering the measured EWT. The the discharge air temperature. The rate
flow, producing reliable entering water controller allows an initial stabilization of cycling is dependent upon the load in
temperature measurement. To ensure period, equal to 30 seconds plus ½ the the space and the temperature of the
accurate unit changeover without valve stroke time, to flush the coil. Once incoming fresh air from the economizer (if
sacrificing the benefits of 2-way, 2- the temperature stabilization period any). Two-pipe changeover units with
position valves, Tracer ZN controllers expires, the controller compares the electric heat use the electric heat only
periodically test the entering water EWT against the effective space tem- when hot water is not available.
temperature on all hydronic main coil perature (either hardwired or communi-
changeover units. Hydronic heating/ cated) to determine whether the EWT is Economizer Damper (Tracer
cooling changeover operation requires correct for the desired heating or cooling ZN520 Only)
central plant operation, and the unit mode. If the EWT is not usable for the
controller must use an entering water desired mode, the controller continues to With a valid outdoor air temperature
temperature sensor to verify delivery of compare the EWT against the effective (either hardwired or communicated),
the correct water temperature from the space temperature for a maximum of Tracer ZN520 uses the modulating
central plant. three minutes. economizer damper as the highest
priority cooling source. Economizer
Entering Water Temperature Sampling The controller automatically disables the operation is only possible using a
Function entering water temperature sampling modulating damper during the occupied,
The entering water temperature (EWT) and closes the main hydronic valve occupied standby, unoccupied, and
must be five degrees above the space when the measured EWT exceeds the occupied bypass modes.
temperature for hydronic heating and high EWT limit (110°F). When the EWT is
five degrees below the space warmer than 110°F, the controller The controller initiates the economizer
temperature for hydronic cooling. When assumes the EWT is hot because it is function if the fresh air temperature is
water flows normally and frequently unlikely the coil would drift to a high cold enough for use as free cooling
through the coil, the controller does not temperature unless the actual loop capacity. If the fresh air temperature is
invoke the sampling function because the temperature was very high. less than the economizer enable setpoint
EWT is satisfactory. (absolute dry bulb), the controller
If the EWT is unusable — too cool to heat modulates the fresh air damper (be-
However, when the controller detects an or too warm to cool — the controller tween the active minimum damper
incorrect water temperature based on closes the hydronic valve and waits 60 position and 100%) to control the amount
heating or cooling mode, it invokes the minutes before initializing another of fresh air cooling capacity. When the
entering water temperature sampling sampling. If the controller determines the fresh air temperature rises 5°F above the
function. For example, when the mea- EWT is valid for heating or cooling, it economizer enable point, the controller
sured EWT is too cool to heat or too resumes normal heating/cooling control disables economizing and moves the
warm to cool. For cooling the EWT needs and effectively disables entering water fresh air damper back to its predeter-
to be five degrees below the measured temperature sampling until it is required. mined minimum position based on the
space temperature. For heating, the EWT current occupancy mode or communi-
cated minimum damper position.
BCXC-SVX01A-EN 37
Sequence of
Operation Operation
38 BCXC-SVX01A-EN
Sequence of
Operation Operation
Binary Inputs Note: See the “Diagnostics” section for Analog Inputs
Tracer ZN controllers have the following more information. See Table O-SO-11 on page 40 for a
binary inputs, factory-configured for the complete description of analog inputs.
following functions: BIP2: Condensate Overflow Detection
• Binary input 1: low temperature Option Binary Outputs
detection (freezestat) The factory hard wires the condensate
• Binary input 2: condensate overflow Binary outputs are configured to support
overflow sensor to binary input #2 (BIP2) the following:
• Binary input 3: occupancy/ generic on the Tracer ZN controller. The sensor
• Binary input 4: fan status (Tracer ZN520 • Two fan stages (when one or two fan
defaults normally closed (N.C.), and will stages are present, J1-2 can be
only) trip off the unit on a condensate overflow configured as exhaust fan)
Note: The generic binary input can be diagnostic if condensate reaches the trip • One hydronic cooling stage
used with a Tracer Summit® building point. In addition, Tracer ZN controls unit • One hydronic heating stage
automation system only. devices as listed below: (dehumidification requires this to be in
Fan: Off the reheat position)
Valves: Closed • One DX cooling stage
BIP1: Low Temperature Detection Electric heat: Off • One or two-stage electric heat
Option
BIP3: Occupancy Sensor (dehumidification requires this to be in
The factory hard wires the low
Binary input #3 (BIP3) on Tracer ZN is the reheat position)
temperature detection sensor to binary
available for field- wiring an occupancy • Face and bypass damper
input #1 (BIP1) on the Tracer ZN
sensor, such as a binary switch or a • Modulating fresh air damper (Tracer
controller. The sensor defaults normally
timeclock, to detect occupancy. The ZN520 only)
closed (N.C.), and will trip off the unit on a
sensor can be either normally open or • One-stage baseboard heat
low temperature diagnostic when
normally closed. Reference Table 6.
detecting low temperature. In addition,
Tracer ZN controls unit devices as listed BIP4: Fan Status (ZN520 Only)
below: Binary input #4 (BIP4) on Tracer ZN is
Fan: Off available for sensor, such as a binary
Valves: Open switch or a timeclock, to detect
Electric heat: Off occupancy. The sensor defaults normally
Damper: Closed open but can be configured as either
normally open or closed.
Table O-SO-10. Binary Input Configurations
Binary Controller Operation
Input Description Configuration Contact closed Contact open
BI 1 Low temperature NC normal diagnostic
detection (Note 1) (note 5)
BCXC-SVX01A-EN 39
Sequence of
Operation Operation
Analog Input 1 J3-1 Entering water temperature -40° to 212°F (-40° to 100°C) ✓ ✓ ✓
J3-2 Analog ground NA
Analog Input 2 J3-3 Discharge air temperature -40° to 212°F (-40° to 100°C) ✓ ✓ ✓
J3-4 Analog ground NA
Analog Input 3 J3-5 Fresh air temp/generic temp -40° to 212°F (-40° to 100°C) ✓
40 BCXC-SVX01A-EN
Sequence of
Operation Operation
BCXC-SVX01A-EN 41
Sequence of
Operation Operation
Figure O-SO-14. Resistance temperature curve for the zone sensor, entering water temperature sensor, and discharge air sensor.
42 BCXC-SVX01A-EN
Maintenance
Maintenance Procedures
Maintenance Procedures When the sheaves are aligned, the Be careful not to over-tension fan belt.
Perform the following maintenance straigt–edge will touch both sheaves at Excessive tension will reduce fan and
procedures to ensure proper unit points A through D, as shown in Figure motor bearing life, accelerate belt wear
operation. M-MP-5 on page 44. For uneven width and possibly cause shaft failure. Clean
sheaves, place a string in the center the sheaves and belt with a dry cloth.
WARNING groove of both sheaves and pull tight. Keep oil and grease away from the belt
Adjust sheaves and tighten the sheave because they may cause belt
Hazardous Voltage! set screws to the correct torques recom- deterioration and slippage. Trane does
Before servicing unit disconnect all mended in Table M-MP-1. not recommend belt dressing.
electrical power including remote Fan Assembly Set Screws CAUTION
disconnects. Follow proper lockout/ Check and adjust fan wheel, bearing, and
tagout procedures to ensure power sheave set screws whenever a Belt tension!
cannot be inadvertently energized. compnent is removed r an adjustment is Do not over-tension belts. Excessive
Failure to disconnect power before made. Refer to Table M-MP-1 for belt tension will reduce fan and motor
servicing can cause death or serious recommendations. bearing life, accelerate belt wear, and
injury. Fan Belt Tension possibly cause shaft failure.
Proper belt tension is necessary to
Air Filters endure maximum bearing and drive Coil Maintenance
Always install filters with directional component life and is based on fan brake
arrows pointing toward the fan. horsepower requirements. Replace belt
when frayed or worn.
Fan Bearings
Fan bearings are permanently sealed Fan belt tension should only be tight
and lubricated and do not require enough so the belt does not slip and
additional lubrication. maintains adequate airflow.
Fan Motors Note: Check fan belt tension at least
Inspect fan motors periodically for twice during the first days of new belt
excessive vibration or temperature. operation since there is a rapid decrease
Operating conditions will vary the in tension until belts are run-in.
frequency of inspection and lubrication.
Motor lubrication instructions are on the
motor tag or nameplate. If for some
reason these instructions are not
available, contact the motor
manufacturer. Some motor
manufacturers may not provide oil tubes
on motors with permanently sealed
bearings.
BCXC-SVX01A-EN 43
Maintenance
Maintenance Procedures
Table M-MP-2. BCHC/BCVC Fan, Filter, & Mixing Box General Data
Unit Size 12 18 24 36 54 72 90
nominal cfm 400 600 800 1200 1800 2400 3000
airflow
minimum cfm 250 375 500 750 1125 1500 1875
maximum cfm 500 675 1000 1600 2400 3000 4000
Fan Data
fan wheel dia., in. 9.5 x 4.5 9.5 x 4.5 9.5 x 4.5 9.5 x 4.5 9.5 x 4.5 9.5 x 4.5 9.5 x 4.5
max rpm 2300 2300 1800 1800 1500 1500 1500
motor hp 0.33-1.0 0.33-1.0 0.33-1.0 0.33-1.5 0.33-2.0 0.33-3.0 0.33-3.0
Unit Flat Filter
qty. - size, in. 1 - 12x 24 1 - 12x 24 1 - 16x 25 2 - 16x 20 1 - 20x 20 3 - 16x 25 2 - 20x 25
1 - 20x 25 1 - 16x 25
area, sq. ft. 2.000 2.000 2.778 4.444 5.556 6.250 8.333
velocity, ft./min. 200 300 288 270 324 384 360
Angle Filter
qty. - size, in. 2 - 12x24 2 - 12x24 2 - 12x24 2 - 20x20 4 - 16x20 4- 16x20 4- 20x20
area, sq. ft. 4.000 4.000 4.000 5.556 8.889 8.889 11.111
velocity, ft./min. 100 150 200 216 203 270 270
Bottom/Top Access Filter Box
qty. - size, in. 1 - 12x20 1 - 12x24 1 - 16x25 1 - 16x20 1 - 16x20 1 - 20x25 2 - 16x25
1 - 16x16 1 - 20x20 1 - 20x20 1 - 14x25
area, sq. ft. 1.7 2.0 2.8 4.0 5.0 6.3 8.0
velocity, ft./min. 240 300 288 300 360 384 375
Mixing Box
damper opening width, in. 15.5 19.5 19.5 31.5 31.5 31.5 31.5
damper opening height, in. 7 7 7 7 12.75 12.75 12.75
area, sq. ft. 0.753 0.948 0.948 1.531 2.789 2.789 2.789
velocity, ft./min. 531 633 844 784 645 861 1076
Note: Minimum airflow limits apply to units with hot water or electric heat only. There is no minimumairflow limit on cooling on units. Maximum airflow limits are to help prevent
moisture carryover.
44 BCXC-SVX01A-EN
Maintenance
Maintenance Procedures
BCXC-SVX01A-EN 45
Maintenance
Maintenance Procedures
46 BCXC-SVX01A-EN
Maintenance
Maintenance Procedures
Keep coils clean to maintain maximum Steam, Hot Water, and Cooling Coil
performance. For operation at its highest Cleaning Procedure
efficiency, clean the coil often during 1.Don the appropriate personal
periods of high demand or when dirty protective equipment (PPE).
conditions prevail. Clean the coil a 2. Gain access to both sides of the coil
minimum of once per year to prevent dirt section.
buildup in the coil fins, where it may not 3. Use a soft brush to remove loose
be visible. debris from both sides of the coil.
Remove large debris from the coils and 4. Use a steam cleaning machine, starting
straighten fins before cleaning. Remove from the top of the coil and working
filters before cleaning. Rinse coils downward. Clean the leaving air side of
thoroughly after cleaning. the coil first, then the entering air side.
Use a block-off to prevent steam from
Clean the coil fins using one of these blowing through the coil and into a dry
methods: section of the unit.
• steam with detergent 5. Repeat step 4 as necessary. Confirm
• hot water spray and detergent that the drain line is open following
• commercially available chemical coil completion of the cleaning process.
cleaner 7. Allow the unit to dry thoroughly before
putting the system back into service.
CAUTION 8. Straighten any coil fins that may be
Potential unit damage from coil damaged with a fin rake.
cleaners! 9. Replace all panels and parts and
Do not use acidic chemical coil restore electrical power to the unit.
cleaners. Also, do not use alkaline 10. Ensure that contaminated material
chemical coil cleaners with a pH value does not contact other areas of the unit
or building. Properly dispose of all
greater then 8.5 (after mixing) without
contaminated materials and cleaning
using an aluminum corrosion inhibitor
solutions.
in the cleaning solution. Using these
type cleaners may cause unit WARNING
damage.
Hazardous chemicals!
Inspecting and Cleaning Coils Some chemical coil cleaning
Coils become externally fouled as a compounds are caustic or toxic. Use
result of normal operation. Dirt on the coil these substances only in accordance
surface reduces it’s ability to transfer with the manufacturer’s instructions.
heat and can cause comfort problems, Failure to do so may cause equipment
increased airflow resistance and thus damage, injury, or death.
increased operating energy costs. If the
coil surface dirt becomes wet, which
Winterizing the Coil
commonly occurs with cooling coils,
Make provisions to drain coils that are not
microbial growth (mold) may result,
in use, especially when subjected to
causing unpleasant odors and serious
freezing temperatures.
health-related indoor air quality
problems. To drain the coil, first blow out the coil
with compressed air. Next, fill and drain
Inspect coils at least every six months or
the tubes with full-strength ethylene
more frequently as dictated by operating
glycol several times. Then drain the coil
experience. Cleaning frequently is
as completely as possible.
dependent upon system operating hours,
filter maintenance, and efficiency and dirt
load. Follow is the suggested method CAUTION
below: Potential coil-freeze condition!
Make provisions to drain the coil when
not in use to prevent coil freeze-up.
BCXC-SVX01A-EN 47
Maintenance
Maintenance Procedures
48 BCXC-SVX01A-EN
Maintenance Troubleshooting
BCXC-SVX01A-EN 49
Maintenance Troubleshooting
The green LED is turned off when the Table M-T-4. Tracer ZN010 and ZN510 Test Sequence for 1–Heat /1–Cool Configurations
Test button is pressed. To begin the Steps Fan Cool Output (1) Heat Output Damper
manual output test mode, press and hold J1-1, J1-3 J1- J1- J1-
the Test button (turning off the green 1. Off Off Off Off Closed
LED) for at least two seconds. The green
LED will begin to blink, indicating the 2. Fan High High Off Off Closed
controller is in test mode. 3. Exhaust Fan Note 5 Off Off Closed
2: Fan High 2 High Off Off Off Off Off Off Off Off OfF
3: (Note 3) Off Note3 Off Off Off Off Off Off Off Off
4: Fan low Off Off Low Off Off Off Off Off Off Off
5: Main open High Off Off On Off Off Off Off Off Off
6: Main close, High Off Off Off On On Off Off Off Off
EH1 on
7: Aux open, High Exh Off Off Off On Off Off Off Off
EH1 on Note 4
8: Aux close, High Off Off Off Off Off On On Off Off
damper open EH1 off, EH2 on,
9: Damper close High Off Off Off Off Off Off Off On Off
10: Generic/ High Off Off Off Off Off Off Off Off On
baseboard
heat energized
50 BCXC-SVX01A-EN
Maintenance Diagnostics
Translating Multiple Note: The controller implements the Building Automation System (Tracer
Diagnostics automatic diagnostic reset function only ZN510 or ZN520 Only)
once every 24 hours. For the controller Some building automation systems can
The controller senses and records each to increment the 24 hour timer, you reset diagnostics in the Tracer ZN510 or
diagnostic independently of other must maintain power to the controller. ZN520 controller. For more complete
diagnostics. It is possible to have multiple Cycling power resets all timers and information, refer to the product literature
diagnostics present simultaneously. The counters. for the building automation system.
diagnostics are reported in the order
they occur. Rover™ Service Tool
After the controller detects the first low Rover service tool can reset diagnostics
Possible diagnostics include: temperatuare diagnostic, the unit waits in the Tracer® ZN520 controller. For more
• Low temperature detection 30 minutes before invoking the auto- complete information, refer to the
• Condensate overflow matic diagnostic reset function. The Rover™ Installation, Operation, and
• Low air flow - fan status automatic diagnostic reset function Programming manual.
• Discharge air temp limit clears the special diagnostic and at-
• Space temperature failure1 Diagnostic Reset (Tracer ZN510 or
tempts to restore the controller to normal
• Entering water temp failure1 ZN520 Only)
operation. The controller resumes
• Discharge air temp failure1 Any device that can communicate the
normal operation until another diagnostic
• Outdoor air temp failure1 network variable nviRequest
occurs.
• Local setpoint failure1 (enumeration “clear_alarm”) can reset
• Local fan mode failure1 Note: The automatic diagnostic reset diagnostics in the Tracer ZN510 or
• CO2 sensor failure1 function does not operate during the ZN520 controller. The controller also
• Generic AIP failure1 manual output test sequence. attempts to reset diagnostics whenever
• Humidity input failure1 power is cycled.
• Defrosting compressor lockout1 Cycling the Fan Switch (Tracer ZN520
• Maintenance required IIf a special diagnostic occurs within 24
hours after an automatic diagnostic Only)
• Invalid Unit Configuration If the user cycles the fan speed switch
• Generic temperature failure reset, the controller must be manually
reset. Other possible methods of reset- from off to any speed, the controller
• Discharge air low limit resets all diagnostics. Diagnostics may
ting diagnostics are described in the
sections that follow. recur immediately if the problem still
Note: Non-latching diagnostics auto-
exists.
matically reset when the input is Manual Output Test
present and valid. You can use the Test button on the The green LED normally indicates
controller either during installation to whether or not the controller is powered
Resetting Diagnostics verify proper end device operation or on (24 VAC).
There are six ways to reset unit during troubleshooting. When you press Trane’s Service Tool, Rover™
diagnostics: the Test button, the controller exercises Rover™, Trane’s service tool, can reset
1. Automatically by the controller all outputs in a predefined sequence. The diagnostics present in the controller. For
2. By initiating a manual output test at the first and last outputs of the sequence complete information about Rover™,
controller reset the controller diagnostics. See page refer to Trane publication EMTX-IOP-2
3. By cycling power to the controller 49 for more information about the Rover Installation, Operation and
4. By using a building automation system manual output test. Programming Guide.
(Tracer ZN510 or ZN520 only) Cycling Power Alarm Reset
5. By using the Rover service tool When someone turns off the controller’s Any device that can communicate alarm
6. By using any other communicating 24 VAC power, then re-applies power, the reset information can reset diagnostics
device able to access the controller’s unit cycles through a power up present in the controller.
diagnositc reset input (Tracer ZN510 or sequence.By default, the controller
ZN520 only) attempts to reset all diagnostics at power
7. By cycling the fan switch from off to up. Diagnostics present at power-up and
any speed setting (Tracer ZN520 only) those that occur after power-up are
Automatic Reset by the Controller handled according to the defined unit
The controller includes an automatic diagnostics sequences (see previous
diagnostic reset function which attempts Diagnostics table).
to automatically restore the unit when a
low temperature diagnostic occurs.
BCXC-SVX01A-EN 51
Maintenance Diagnostics
Notes:
Priority Level: Diagnostics are listed in order from highest to lowest priority. The controller senses and records each
diagnostic independently of other diagnostics. It is possible to have multiple diagnostics present simultaneously. The
diagnostics affect unit operation according to priority level.
Latching: A latching diagnostic requires a manual reset of the controller; while a non-latching diagnostic automatically
resets when the input is present and valid.
Enabled: End device is allowed to run if there is a call for it to run.
Disabled: End device is not allowed to run even if there is a call for it to run.
No Action: The diagnostic has no affect on the end device.
Table M-D-2. Tracer ZN520 Diagnostics
Diagnostic Fan Other Outputs (Note 1)
Condensate overflow Off Valves closed, fresh air damper closed, electric heat off, baseboard heat off
Low temperature detection Off Valves open, fresh air damper closed, electric heat off, baseboard heat off
Low air flow - fan failure Of Valves closed, fresh air damper closed, electric heat off, baseboard heat off
Space temperature failure Of Valves closed, fresh air damper closed, electric heat off, baseboard heat off
Entering water temp failure On Valves enabled (Note 2), fresh air damper enabled (Note 2), electric heat enabled (Note 2), baseboard heat off
Discharge air temp low limit Off Valves open, fresh air damper closed, electric heat off, baseboard heat off
Discharge air temp failure Off Valves closed, fresh air damper closed, electric heat off, baseboard heat off,
fresh air temp failure On Valves enabled, fresh air damper minimum position3, electric heat enabled, baseboard heat enabled
Relative humidity failure On Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled
Generic 4-20ma failure On Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled
CO2 Input failure On Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled
Maintenance required On Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled
Local fan mode failure On Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled
Local setpoint failure On Valves enabled, fresh air damper enabled, electric heat enabled, baseboard heat enabled
Invalid unit configuration Off Valves Disabled, fresh air damper disabled, electric heat disabled, baseboard heat disabled
Normal – power up On Valves enabled, fresh air damper enabled, electric heat enabled
Note 1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.
Note 2: When the entering water temperature is required but not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller
automatically clears the diagnostic once a valid entering water temperature value is present (non-latching diagnostic). When the entering water temperature sensor fails, the controller
prohibits all hydronic cooling operation, but allows the delivery of heat when heating is required. In the Cool mode, all cooling is locked-out, but normal fan and outdoor air damper
operation is permitted.
Note 3: When the outdoor air temperature sensor has failed or is not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The controller
automatically clears the diagnostic once a valid outdoor air temperature value is present (non-latching diagnostic). When the outdoor air temperature sensor fails or is not present, the
controller prohibits economizer operation.
52 BCXC-SVX01A-EN
Maintenance
Common Diagnostics
Power-up control wait When power-up control wait is enabled (non-zero time), the controller remains
off until one of two conditions occurs:
1. The controller exits power-up control wait once it receives communicated
information.
2. The controller exits power-up control wait once the power-up control wait
time expires.
Cycling fan operation When the fan mode switch is in the auto postion, the unit fan cycles off when
there is no call for heating or cooling. The heating/cooling sources cycle on or
off periodically with the unit fan to match the capacity according to pulse
width modulation (PWM) logic.
Unoccupied operation The fan cycles with capacity when the unit is in unoccupied mode. This
occurs even if the unit is in continuous fan operation. While unoccupied, the
fan cycles on or off with heating/cooling to provide varying amounts of
heating or cooling to the space. to match the capacity diagnostics
according to pulse-width-modulation (PWM) logic.
Fan mode off When using the local fan mode switch to determine the fan operation, the off
position controls the unit fan to off.
Requested mode: off It is possible to communicate the operating mode (such as off, heat, and
cool) to the controller. When “off” is communicated to the controller, the unit
controls the fan to off. The unit is not capable of heating or cooling when the
controller is in this mode.
Diagnostic present A specific list of diagnostics effects fan operation. For more information, see
the “Diagnostics” section.
No power to the If the controller does not have power, the unit fan does not operate. For
controller the Tracer ZN controller to operate normally, it must have an input voltage of
24 VAC. When the green LED is off continuously, the controller does not have
sufficient power or has failed.
Unit configuration The controller must be properly configured based on the actual installed end
devices and application. When the unit configuration does not match the
actual end devices, the valves may not work correctly.
Manual output test The controller includes a manual output test sequence to verify binary output
operation and the associated wiring. However, based on the current step in
the test sequence, the unit fan may not be powered on. Refer to the “Manual
Output Test” section .
Unit wiring The wiring between the controller outputs and the fan relays and contacts
must be present and correct for normal fan operation. Refer to the specific
unit wiring diagrams on the unit.
BCXC-SVX01A-EN 53
Maintenance Diagnostics
Requested mode: off It is possible to communicate the operating mode (such as off, heat, and
cool) to the controller. When off is communicated to the controller, the unit
controls the fan to off. The unit is not capable of heating or cooling when the
controller is in this mode.
Valve override The controller can communicate a valve override request.This request
affects the valve operation.
Manual output test The controller includes a manual output test sequence to verify analog and
binary output operation and the associated wiring. However, based on the
current step in the test sequence, the valves may not be open. Refer to the
“Manual Output Test” section.
Diagnostic present A specific list of diagnostics affects valve operation. For more information,
see the “Diagnostics” section.
Sampling logic The controller includes entering water temperature sampling logic that
automatically invokes during 2-pipe or 4-pipe changeover. It determines
when the entering water temperature is either too cool or too hot for the
desired heating or cooling mode. Refer to the “Entering Water Temperature
Sampling” section.
Unit configuration The controller must be properly configured based on the actual installed end
devices and application. When the unit configuration does not match the
actual end device, the valves may not work correctly.
No power to the If the controller does not have power, the unit fan does not operate. For
controllerthe Tracer® ZN010,510 controller to operate normally, it must have
an input voltage of 24 VAC. When the green LED is off continuously, the
controller does not have sufficient power or has failed.
Unit wiring The wiring between the controller outputs and the valve(s) must be present
and correct for normal valve operation. Refer to the unit unit wiring diagram
on the unit.
Valve override The controller can communicate a valve override request to affect the valve
operation.
Manual output test The controller includes a manual output test sequence that verifies analog
and binary output operation and the associated wiring. However, based on
the current step in the test sequence, the valves may be open. Refer to the
“Manual Output Test” section.
Diagnostic present A specific list of diagnostics affects valve operation. For more information,
see the “Diagnostics” section.
Sampling logic The controller includes entering water temperature sampling logic that
automatically invokes during 2-pipe or 4-pipe changeover to determine if the
entering water temperature is correct for the unit operating mode. Refer to
the “Entering Water Temperature Sampling” section.
Unit configuration The controller must be properly configured based on the actual installed end
devices and application. When the unit configuration does not match the
actual end device, the valves may not work correctly.
Unit wiring The wiring between the controller outputs and the valve(s) must be present
and correct for normal valve operation. Refer to the unit wiring diagram on
54 BCXC-SVX01A-EN
Maintenance Diagnostics
Requested mode: off It is possible to communicate the operating mode (such as off, heat, cool)
to the controller. When off is communicated to the controller, the units shuts
off the electric heat.
Communicated disable Numerous communicated requests may disable electric heat, including an
auxiliary heat enable input and the heat/cool mode input. Depending on the
state of the communicated request, the unit may disable electric heat.
Manual output test The controller includes a manual output test sequence that verifies analog
and binary output operation and associated output wiring. However, based
on the current step in the test sequence, the electric heat may not be on.
Refer to the “Manual Output Test” section.
Diagnostic present A specific list of diagnostics affects electric heat operation. For more informa-
tion, see the “Diagnostics” section.
Unit configuration The controller must be properly configured based on the actual installed end
devices and application. When the unit configuration does not match the
actual end device, the electric heat may not work properly.
No power to the If the controller does not have power, the unit fan does not operate. For
controller the Tracer® ZN010,510 controller to operate normally, it must have an input
voltage of 24 VAC. When the green LED is off continuously, the controller
does not have sufficient power or has failed.
Unit Wiring The wiring between the controller outputs and the electric heat contacts
must be present and correct for normal electric heat operation. Refer to the
unit wiring diagrams on the unit.
Requested mode: off It is possible to communicate the operating mode (such as off, heat, cool) to
the controller. When off is communicated to the controller, the unit closes the
fresh air damper.
Manual output test The controller includes a manual output test sequence that verifies analog
and binary output operation and associated output wiring. However, based
on the current step in the test sequence, the fresh air damper may not be
open. Refer to the “Manual Output Test” section .
Diagnostic present A specific list of diagnostics effects fresh air damper operation. For more
information, see the “Diagnostics” section.
Unit configuration The controller must be properly configured based on the actual installed end
devices and application. When the unit configuration does not match the
actual end device, the damper may not work correctly.
No power to the If the controller does not have power, the unit fan does not operate. For
controller the Tracer® ZN010,510 controller to operate normally, it must have an
input voltage of 24 VAC. When the green LED is off continuously, the
controller does not have sufficient power or has failed.
Unit wiring The wiring between the controller outputs and the fresh air damper must be
present and correct for normal damper operation. Refer to thelunit wiring
diagrams on the unit.
BCXC-SVX01A-EN 55
Maintenance Diagnostics
Manual Output Test The controller includes a manual output test sequence that verifies analog
and binary output operation and associated wiring. However, based on the
current step in the test sequence, the fresh air damper may be open. Refer
to the“Manual Output Test” section.
Unit Configuration The controller must be properly configured based on the actual installed end
devices and application. When the unit configuration does not match the actual
end device, the damper may not work correctly.
Unit Wiring The wiring between the controller outputs and the fresh air damper must be
present and correct for normal damper operation. Refer to the unit wiring
diagrams on the unit.
Normal operation The controller opens and closes the fresh air damper based on the
controller’s occupancy mode and fan status. Normally, the fresh air damper
is open during occupied mode when the fan is running and closed during
unoccupied mode.
Power up control wait When power up control wait is enabled (non-zero time), the controller
remains off until one of two conditions occurs:The controller exits power up
control wait once it receives communicated information.The controller exits
power up control wait once the power up control wait time expires.
Manual output test The controller includes a manual output test sequence you can use to verify
output operation and associated output wiring. However, based on the
current step in the test sequence, the valve(s) may not be open. Refer to the
Manual Output Test section.
Fan mode off When a local fan mode switch (provided on the Trane zone sensor)
determines the fan operation, the off position controls the unit off and
valves to close.
Sampling logic The controller includes entering water temperature sampling logic which is
automatically invoked during 2-pipe and 4-pipe changeover when the
entering water temperature is either too cool or too hot for the desired
heating orcooling.Refer to the Entering Water Temperature Sampling
section.
Diagnostic present A specific list of diagnostic affects valve operation. For more information, see
the Diagnostics section.
Unit configuration The controller must be properly configured based on the actual installed end
devices and application. When the unit configuration does not match the
actual end devices, the valves may not work correctly. Example: A 2-pipe
heat/cool changeover unit will not cool if the entering water temperature is
too warm for cooling or if the entering water sensor is not present. The unit
will not heat if the entering water temperature is too cool for heating.
Unit wiring The wiring between the controller outputs and the valve(s) must be
present and correct for normal valve operation.
Random start observed After power up, the controller always observes a random start from 0 to 25
seconds. The controller remains off until the random start time expires.
56 BCXC-SVX01A-EN
Maintenance Diagnostics
Unit configuration The controller must be properly configured based on the actual installed end
devices and application. When the unit configurationdoes not match the actual
end devices, the unit may not work correctly.
Diagnostic present A specific list of diagnostic affects valve operation. For more information, see
the Diagnostics section.
Manual output test The controller includes a manual output test sequence you can use to verify
output operation and associated output wiring. However, based on the
current step in the test sequence, the valve(s) may not be open. Refer to the
Manual Output Test section.
Freeze avoidance When the fan is off with no demand for capacity (0%) and the outdoor air
temperature is below is below the freeze avoidance setpoint, the controller
disables compressors and electric heat outputs. This includes unoccupied
mode when there is no call for capacity or any other time the fan is off.
Normal operation The controller energizes the outputs only as needed to meet the unit capacity
requirements.
BCXC-SVX01A-EN 57
Typical Wiring
Maintenance Diagram
58 BCXC-SVX01A-EN
Typical Wiring
Maintenance Diagram
BCXC-SVX01A-EN 59
Typical Wiring
Maintenance Diagram
60 BCXC-SVX01A-EN
Typical Wiring
Maintenance Diagram
BCXC-SVX01A-EN 61
Typical Wiring
Maintenance Diagram
62 BCXC-SVX01A-EN
Typical Wiring
Maintenance Diagram
BCXC-SVX01A-EN 63
Typical Wiring
Maintenance Diagram
64 BCXC-SVX01A-EN
Typical Wiring
Maintenance Diagram
BCXC-SVX01A-EN 65
Typical Wiring
Maintenance Diagram
66 BCXC-SVX01A-EN
Typical Wiring
Maintenance Diagram
BCXC-SVX01A-EN 67
Typical Wiring
Maintenance Diagram
2 DASHED LINES INDICATE RECOMMENDED FIELD WIRING 2 SUPPLY FAN AND COIL SECTION 1CB1 TRANSFORMER CIRCUIT BREAKER 16
2 BY OTHERS. DASHED LINE ENCLOSURES AND/OR DASHED 3 1K1 SUPPLY FAN CONTACTOR 20
DEVICE OUTLINES INDICATE COMPONENTS PROVIDED 4 MIXING BOX SECTION 1K3 DX RELAY 24
BY THE FIELD. SOLID LINES INDICATE WIRING BY
TRANE CO. 5 EXTERNAL PIPING
3
7S6
7S6 7S6 6 ELECTRIC HEAT CONTROL BOX 1T1 CONTROL POWER TRANSFORMER 16
3 ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE 7 FIELD INSTALLED DEVICE 1TB1-L1,-L2 CONTROL TERMINAL BLOCK
NATIONAL ELECTRIC CODE (NEC), STATE AND LOCAL
4 REQUIREMENTS. 1U1 ZN CONTROLLER 18
4 NUMBERS ALONG THE RIGHT SIDE OF THE SCHEMATIC 2B1 SUPPLY FAN MOTOR 11
5 DESIGNATE THE LOCATION OF CONTACTS BY LINE NUMBER.
5 FIELD SUPPLIED CONTROL RELAYS, POWERED BY THIS UNIT, 2S2 CONDENSATE OVERFLOW SWITCH 32
MUST BE PILOT DUTY RATED, 24VAC COIL, 6VA MAX.
6
2S5 FAN STATUS SWITCH 36
6 WIRING TO ZONE SENSOR MUST BE 16-22 AWG, CU TWISTED ELECTRIC HEAT
2S7 ELECTRIC HT LOCKOUT SWITCH 23
PAIR SHIELDED CABLE AND NO MORE THAN 1000 FT LG. CONTROL BOX
7 SHIELD MUST BE GROUNDED AT UCM END(END CHASSIS) AND 2S8 EVAP DEFROST FROSTAT 24
TAPED AT THE OTHER END. IF INSTALLED IN CONDUIT, DO 1S1
4U4 MIXING BOX DAMPER ACTUATOR 27
NOT INSTALL WIRES IN CONDUIT THAT CONTAINS WIRES 24VAC
8 OR HIGH VOLTAGE POWER WIRES.
15
1CB1 1T1
W(BLK) BLU YEL 1TB1-L2 B(BLK)
16 24V
75VA 11
E 1TB1-L2 D(WHT)
17
11 1U1
1TB1-L1 C,K (BLK) D
18 TB1-1 24V POWER GND TB1-2
10
19
6
7U6
1K1 J1
W,X E (BLK) 17A(BLK) 1K1-10,12
20 1 HIGH SPEED ZONE TB3-1 1 ZONE
1TB1-L1 10 1P1-1
7K5 5
1TB1-L1 14A(YEL)
21 2 EXHAUST GND TB3-2 2 COM
10 1P1-2
1K2
22 SET TB3-3 3 CSP
5 1P1-3
1K3
1TB1-L1 K 1P2-1 5P3-1 5P4-1 G 5P4-2 5P3-2 1P2-2
23 DX COOLING FAN TB3-4 4 FAN SWITCH
10 1J2-1 2J3-1 5J4-1 2 4 5J4-2 2J3-2 1J2-2
1P1-5
8 1K3
1P2-1 J 1P2-3 5P3-3 5P4-3 G,J 5P4-3 38A 5P3-3
2S8 19B 1P2-2
1P2-3 C
24 5 ON/OFF TB2-6 6 COMM LOW(-) 1K3-23
1J2-1 1J2-3 2J3-3 5J4-3 1 35J4-3 2J3-3 1J2-3 -
1J2-2 1P1-6
1P1-5
CLG COMM
1TB1-L1 X 2S7 1P5-1
BRN 5P6-1 5P7-1 ORG 5P7-2 5P6-2 1P5-2
15C(ORG)
25 COMMON STAGE 1 9 STAGE 1 TB2-5 5 COMM HI(+)
10 1J5-1 2J6-1 5J7-1 5J7-2 2J6-2 1J5-2 1P1-9 +
8 ELECTRIC
1P5-3 HEAT5P6-3 5P7-3 5P7-3 5P6-3 1P5-3 LO(-)
CONTROL BOX PUR 16C(PUR)
26 STAGE 2 10 STAGE 2 TB2-4
1J5-3 2J6-3 5J7-3 5J7-3 2J6-3 1J5-3 1P1-10 - TRACER
4U4 COMM COMM OUT
E(WHT) 1P8-3 4P9-3 C 2J9-1 B 1J8-1 12A(PNK) HI(+)
27 TR1 CCW CCW 11 OPEN TB2-3
1J8-3 V X TR1 1P1-11
2J9-3 4P9-1 1P8-1 + SPLICE AND
OAD
B(BLK) 1P8-4 4P9-4 C 2J9-2 B 1J8-2 13A(BRN) INSULATE SHIELDS
28 TR CW CW 12 CLOSE TB2-2
1J8-4 V R TR 1P1-12 - LO(-)
2J9-4 4P9-2 1P8-2 TRACER
COMM 7
COMM IN
29 TB4-1 BOP TB2-1
+ HI(+)
9 GENERIC BOP GENERIC
2S3
30 TB4-2 24V
5RT2 1P11-1
31
5P10-1 2J10-1 1J11-1
1P11-2 2S2
23A(PUR) 2P13-1 B 2J13-2
32 J2-3
5P10-2 2J10-2 1J11-2 2J13-1 B 2P13-2
BI-2
2RT1 SPLICE
7RT1 GREEN PLUG
SPLICE CONDENSATE 24A(PUR)
33 J3-3 J2-4
2P12-1 2J12-1
AI-2 DAT
34 J3-4 J2-5
2P12-2 2J12-2 OR FIELD RECONFIGURED
7RT3 BI-3 OCC/UNOCC
SPLICE SPLICE AS GENERIC
35 J3-5 J2-6
AI-3-OAT
25A(YEL) 2S5
36 J3-6 J2-7
BI-4 Pd
FAN-STAT 26A(YEL)
37 J2-8
38
39
40
41
42
68 BCXC-SVX01A-EN
43
44
Typical Wiring
Maintenance Diagram
NOTES:
1 UNLESS OTHERWISE NOTED, ALL SWITCHES ARE SHOWN DEVICE PREFIX LOCATION CODE LEGEND
AT 25˚
25 C (77˚
(77 F), AT ATMOSPHERIC PRESSURE, AT 460/60/3
50% RELATIVE HUMIDITY, WITH ALL UTILITIES TURNED L1 L2 L3 AREA LOCATION DEVICE LINE
1 DESCRIPTION
OFF, AND AFTER A NORMAL SHUTDOWN HAS OCCURED. 1 MAIN CONTROL PANEL DESIGNATION NUMBER
2 DASHED LINES INDICATE RECOMMENDED FIELD WIRING 2 SUPPLY FAN AND COIL SECTION 1CB1 TRANSFORMER CIRCUIT BREAKER 16
2 BY OTHERS. DASHED LINE ENCLOSURES AND/OR DASHED 3 1K1 SUPPLY FAN CONTACTOR 20
DEVICE OUTLINES INDICATE COMPONENTS PROVIDED 4 MIXING BOX SECTION 1K3 DX RELAY 24
BY THE FIELD. SOLID LINES INDICATE WIRING BY
TRANE CO. 5 EXTERNAL PIPING 1S1 MANUAL DISCONNECT SWITCH 7
3
7S6
7S6 7S6 6 1T1 CONTROL POWER TRANSFORMER 16
3 ALL FIELD WIRING MUST BE IN ACCORDANCE WITH THE 7 FIELD INSTALLED DEVICE 1TB1-L1,-L2 CONTROL TERMINAL BLOCK
NATIONAL ELECTRIC CODE (NEC), STATE AND LOCAL
4 REQUIREMENTS. 1U1 ZN CONTROLLER 18
4 NUMBERS ALONG THE RIGHT SIDE OF THE SCHEMATIC 2B1 SUPPLY FAN MOTOR 11
5 DESIGNATE THE LOCATION OF CONTACTS BY LINE NUMBER. 2RT1 DISCHARGE AIR TEMP SENSOR 33
SPLICE
SPLICE
SPLICE
SPLICE
5 FIELD SUPPLIED CONTROL RELAYS, POWERED BY THIS UNIT, 2S2 CONDENSATE OVERFLOW SWITCH 32
MUST BE PILOT DUTY RATED, 24VAC COIL, 6VA MAX. 2S3 FREEZE-STAT 30
6
6 WIRING TO ZONE SENSOR MUST BE 16-22 AWG, CU TWISTED GRN BLK BLK BLK
PAIR SHIELDED CABLE AND NO MORE THAN 1000 FT LG.
7 SHIELD MUST BE GROUNDED AT UCM END(END CHASSIS) AND 2S8 EVAP DEFROST FROSTAT 24
TAPED AT THE OTHER END. IF INSTALLED IN CONDUIT, DO 1S1
NOT INSTALL WIRES IN CONDUIT THAT CONTAINS WIRES 24VAC EQUIPMENT
8 OR HIGH VOLTAGE POWER WIRES. GROUND
15
1CB1 1T1
W(BLK) BLU YEL 1TB1-L2 B(BLK)
16 24V
75VA 11
E 1TB1-L2 D(WHT)
17
11 1U1
1TB1-L1 C,K,M (BLK) D
18 TB1-1 24V POWER GND TB1-2
10
19
6
7U6
1K1 J1
W E (BLK) 17A(BLK) 1K1-10,12
20 1 HIGH SPEED ZONE TB3-1 1 ZONE
1TB1-L1 10 1P1-1
7K5 5
1TB1-L1 14A(YEL)
21 2 EXHAUST GND TB3-2 2 COM
10 1P1-2
1K2
22 SET TB3-3 3 CSP
5 1P1-3
1K3
1TB1-L1 K 1P2-1 5P3-1 5P4-1 G 5P4-2 5P3-2 1P2-2
23 DX COOLING FAN TB3-4 4 FAN SWITCH
10 1J2-1 2J3-1 5J4-1 2 4 5J4-2 2J3-2 1J2-2 1P1-5
8 1K3
1P2-1 J 1P2-3 5P3-3 5P4-3 G,J 5P4-3 38A 5P3-3
19B 1P2-2
1P2-3
2S8 C
24 5 ON/OFF TB2-6 6 COMM LOW(-) 1K3-23
1J2-1 1J2-3 2J3-3 5J4-3 1 35J4-3 2J3-3 1J2-3 -
1J2-2 1P1-6
1P1-5
7B3 (7VA MAX) CLG COMM
1TB1-L1 M2S7 1P5-1 L 5P6-1 5P7-1 5P7-2 15A 5P6-2 B 1P5-2 C
25 M 9 ON/OFF TB2-5 5 COMM HI(+)
10 1J5-1 2J6-1 D 5J7-1 5J7-2 2J6-2 1J5-2 1P1-9 +
8 HTG
1P5-3 5P6-3 5P7-3 5P7-3 5P6-3 1P5-3 LO(-)
26 TB2-4
1J5-3 2J6-3 5J7-3 5J7-3 2J6-3 1J5-3 1P1-10 - TRACER
7U4 COMM COMM OUT
E(WHT) 1P8-3 4P9-3
SPLICE 2J9-1
SPLICE 1J8-1 12A(PNK) HI(+)
27 TR1 CCW 11 OPEN TB2-3
1J8-3 2J9-3 4P9-1 1P8-1 1P1-11 + SPLICE AND
OAD
B(BLK) 1P8-4 4P9-4
SPLICE 2J9-2
SPLICE 1J8-2 13A(BRN) INSULATE SHIELDS
28 TR CW 12 CLOSE TB2-2
1J8-4 2J9-4 4P9-2 1P8-2 1P1-12 - LO(-)
COMM TRACER
7
COMM IN
29 TB4-1 BOP TB2-1
+ HI(+)
9 GENERIC BOP GENERIC
21A(GRA) 2S3
30 TB4-2 24V J2-1
BI-1
5RT2 1P11-1 FRZ-STAT 22A(GRA)
31 J2-2
5P10-1 2J10-1 1J11-1
1P11-2 2S2
23A(PUR) 2P13-1 B 2J13-2
32 J2-3
5P10-2 2J10-2 1J11-2 2J13-1 B 2P13-2
BI-2
2RT1
7RT1 GREEN PLUG
B 34A(BRN) CONDENSATE 24A(PUR)
33 J3-3 J2-4
2P12-1 2J12-1
AI-2 DAT
B 35A(BRN)
34 J3-4 J2-5
2P12-2 2J12-2 OR FIELD RECONFIGURED
7RT3 BI-3 OCC/UNOCC
SPLICE SPLICE AS GENERIC
35 J3-5 J2-6
AI-3-OAT
2S5
36 J3-6
37
38
39
40
41
BCXC-SVX01A-EN
42
69
43
Index
70 BCXC-SVX01A-EN
Index
BCXC-SVX01A-EN 71
US