Communication failure
R2 CB (main communication failure)
R2-02 CB (dedo)
AT-01,ST-02.ST-03
According to above history description the Feeder line R2 clearly has a problem related to line Voltage
unbalance and bad power factor when compared to Feeder lines R3 and R1 (i.e. they still have good
power factor which is around 0.99). R1 and R3 have balanced and accepted voltage values (around
14.6KV for each Line to Line Voltage). But measured values obtained from scada must be compared to
the values that are measured in the field during maintenance operation since some times the scada
system can log values that do not represent what is in the actual field.
The above type of power abnormality can also have effect on scada communication devices and this
may me be the main reason for communication abnormity that has been seen on Feeder line R2 since
the power abnormality was present.
REFERENCES
DATE 23/12/2022 12:10
R2 VOLTAGE Vab AND Vbc DROPPED FROM 13.839 TO 10.377KV AND 4,493KV
VOLTAGE (Vab) DROPPED TO 10.377KV
VOLTAGE (Vbc) DROPPED TO 4.493KV
PEAK LOAD = 4.33 MW
REACTIVE POWER= 1.506 KVAR
POWER FACTOR = 0.944