General instructions
IG-296-EN, version 01, 12/03/2020
LIB
CAUTION!
When medium-voltage equipment is operating, certain components are live, other parts may be in movement and some may
reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental
recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on
the following criteria:
• Elimination of hazards wherever possible.
• Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are
incorporated in the equipment.
• Communication about remaining risks to facilitate the design of operating procedures which prevent such risks,
training for the personnel in charge of the equipment, and the use of suitable personal protective equipment.
• Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with the
environmental restrictions established by the competent authorities.
Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of Standard
IEC 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in accordance with the
requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on activities in or near
electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other
recommendations of a more general nature which are applicable to the situation according to current legislation[1].
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also
on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:
• The equipment must be handled and transported appropriately from the factory to the place of installation.
• All intermediate storage should occur in conditions which do not alter or damage the characteristics of the equipment
or its essential components.
• Service conditions must be compatible with the equipment rating.
• The equipment must be operated strictly in accordance with the instructions given in the manual, and the applicable
operating and safety principles must be clearly understood.
• Maintenance should be performed properly, taking into account the actual service and environmental conditions in
the place of installation.
The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any
jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Warranty
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the
event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this
equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual
belongs to Ormazabal.
[1]
For example, in Spain the “Regulation on technical conditions and guarantees for safety in high-voltage electrical installations” – Royal Decree
337/2014 is obligatory.
In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject
to change without prior notice. These characteristics, as well as the availability of components, are subject to confirmation by
Ormazabal.
General instructions Contents
cgmcosmos: Medium voltage cubicles with full insulation
in SF6 gas up to 24 kV in accordance with IEC Standard
Contents
1. General description
Ormazabal's cgmcosmos system, designed in accordance models, with full insulation in SF6 gas, thus allowing
with the requirements set out in regulations of the different secondary electrical distribution schematics to be
International Electrotechnical Committee (IEC), is formed configured in medium voltage up to 24 kV[2].
by different unifunctional and multifunctional switchgear
1.1. Models
Standard Description
IEC 62271-1 Common specifications for high voltage switchgear standards
IEC 62271-100 High voltage alternating current circuit-breakers
IEC 62271-102 Alternating current earthing switches and disconnectors
IEC 62271-103 High voltage switches for rated voltages above 1 kV and below 52 kV
IEC 62271-105 Alternating current switch-fuse combinations
IEC 62271-200 A.C. metal-enclosed switchgear and controlgear for rated voltages above 1 kV and up to and including 52 kV
IEC 62271-206/IEC 61243-5 Voltage presence indicating systems
IEC 60529 Degrees of protection provided by enclosures (IP Code)
IEC 60282-1 Current-limiting fuses
[2]
Further information at www.ormazabal.com
1 Gas tank
1.1 Side connection female bushings
2 Driving mechanism area
2.1 Actuating shafts (see mimic diagram of each model)
2.2 LRM-VDS system according to NBN EN 61243-5
3 Base
3.1 Cable compartment access cover
3.2 Medium voltage cable fixing support
3.3 Gas relief compartment
3.4 Earth collector
3.5 Front cable connection bushings
* Optional elements.
This is the compartment in which the switch-disconnector diagram includes all the position indicators for the driving
or the circuit-breaker is actuated, depending on the type of elements.
function.
The cgmcosmos system has, in line with the cubicle model,
The mimic diagram for the main medium voltage circuit the following types of driving mechanism:
is displayed on the cover of this compartment. The mimic
B Tilting l
BM Motorised tilting l
AR Accumulation of energy with latch p
ARM Accumulation of energy with motorised latch p
RAV Circuit-breaker with reclosing option v
RAMV Circuit-breaker with motorised reclosing option v
These elements are operated independently, i.e., their The B, BM, AR and ARM driving mechanisms can be replaced
actuation speed does not depend on the speed of the by upgrading in any of the three positions (closed - open -
manual operation. earth). Whilst the driving mechanism is withdrawn, these
positions of the switch can be blocked using a coupling
device, whether in service or not.
1.3.3. Base
Located in the lower front section of the cubicle and has Ormazabal's cgmcosmos system is designed and
a cover interlocked with the earthing switch, thus allowing constructed to withstand at least the thermal and dynamic
front access to the medium voltage cables. effects of an arc of 16 kA for 1 seconds should a defect
result in an internal arc in the gas compartment. The system
As standard, designed to contain up to: conducts the gases generated in a fully controlled manner
to avoid any possible injury to people in the equipment
1. Two shielded screw-in terminals (reduced) per phase
operation area.
or one terminal (reduced) plus surge arrester (reduced)
with space for the corresponding incoming power
Optionally, a gas expansion relief duct can be
cables.
positioned in the rear of the cubicle to redirect the
2. Cable ties for the power cables. gases to the top section. Please check with Ormazabal.
3. Earthing bars.
As an option:
Name plate
N° Cubicle serial number*
Type Ormazabal switchgear system.
Designation Cubicle model
Standard Standards applied to the equipment
Name Equipment name
Ur Equipment rated voltage (kV)
Up Lightning impulse withstand voltage (kV)
Ud Power frequency withstand voltage (kV)
fr Equipment rated frequency (Hz)
Ir Equipment rated current (A)
Instructions Manual General Instructions Manual (IG) for the system
Class Driving mechanism class according to IEC 62271-103
N Number of mainly active load breaking operations
Ik/Ip Short-time withstand current/Short-time withstand peak value
tk Short-time withstand current time
Pre Gas pressure inside the gas tank (MPa)
Pme Minimum operating gas pressure (MPa)
SF6 Weight of insulating fluid (g)
CO2e Equivalent CO2 fluid mass (t)
Year Year of manufacture
TC Minimum working temperature
IAC Internal arc classification
* In the event of incident, this number should be reported to Ormazabal.
The values set out in this table are general for the
cgmcosmos system and are only valid when confirmed
by Ormazabal. Some cubicle models can withstand
partial values. For more detailed information, contact
Ormazabal.
Height (h) Width (a) Depth (f) Bushings height (g) Weight
Module
[mm] [mm] [mm] [mm] [kg]
1300 725 90
-l[2] [3] [4] 365 735
1740 1165 100
1300 410 140
-p 470 735
1740 850 150
-v (RAV) 1740 480 845 695 240
Feeder Fuse protection
1300 290
-2lp[2] [3] 1190 735 725 410
1740 1165 850 310
The weight refers to the enclosure, with no metering transformer inside.
[2]
In the case of dual symmetric terminal, the depth of the switchgear increases by 200 mm and the weight by 5 kg, per feeder function.
[3]
In the case of symmetric terminal plus symmetric surge arrester, the depth of the switchgear increases by 200 mm and the weight by 5 kg, per feeder
function.
[4]
For exterior cable test device, please check with Ormazabal.
Installation Indoor
Maximum ambient temperature + 40°C
Minimum ambient temperature - 5°C/- 30°C(a)
Maximum mean ambient temperature, measured over a 24-hour period + 35°C
Maximum mean relative humidity, measured over a 24-hour period < 95%
Maximum mean relative humidity, measured over a 1-month period < 90%
Maximum mean vapour pressure, measured over a 24-hour period 2.2 kPa
Maximum mean vapour pressure, measured over a 1-month period 1.8 kPa
Maximum height above sea level 2000 m
Solar radiation Negligible
Pollution due to corrosive and/or flammable gases Insignificant
Vibrations due to systemic movements or caused by causes external to the switchgear Negligible
(a)
Storage: - 40°C
[3]
Position the rear of the cubicle facing the driver, to avoid damaging the front.
3. Storage
If it needs to be stored, the equipment must be placed on After prolonged storage, clean all the insulating parts
dry ground or on top of damp-proof insulating material, still carefully before commissioning the equipment. The
in its original packaging. enclosure should be cleaned with a clean, dry lint-free cloth.
Storage must always be INDOORS, with the following b. The mean water vapour pressure value, measured in
conditions recommended: a period of 24 hours, must not exceed 2.2 kPa.
c. The mean relative humidity value, measured over a
1. Ambient air temperature should not exceed 40°C
period of one month, must not exceed 90%.
and its mean value, measured in a period of 24 hours,
should not exceed 35°C. d. The mean water vapour pressure value, measured
in a period of one month, must not exceed 1.8 kPa.
2. The ambient air temperature should not drop below
- 5°C. There are also cubicles with storage temperature 7. During transport, vibrations caused by external factors
up to -40°C. or seismic movements must be insignificant.
3. The switchgear must be protected from direct solar
Any other conditions must be notified beforehand,
radiation. since the equipment must be factory-adjusted to
4. Altitude, both in transport and in storage, must not the environmental pressure at the final destination
exceed 2000 m. or during transport. Otherwise, the pressure gauge
5. The environmental air must not have any significant needle may indicate an incorrect value, even if the
equipment's internal gas pressure is correct.
contamination from dust, smoke, corrosive and/or
inflammable gases, vapours or salt.
6. The switchgear must be protected from the rain, and
the humidity conditions should be as follows:
a. The mean relative humidity value, measured over a
period of 24 hours, must not exceed 95%.
4. Installation
The cgmcosmos system switchgear is supplied as standard 5. Remove the pallet, handling the cubicle as indicated in
protected by plastic packaging. section 2.1.
6. Unpack the accessories box in the front section or on
On receiving the equipment, check that the goods supplied
the top of the cubicle.
correspond to the order and associated documentation. If
this is not the case, contact Ormazabal immediately. 7. Remove the self-adhesive protective plastic from the
cable compartment cover.
The disassembly process for the equipment is as follows:
The self-adhesive plastic must be removed from the
1. Using a blade, cutter or similar tool, cut the cellophane cable compartment cover so that the equipment
the cubicle is wrapped in.[4] enclosure's earth connection may have the proper
2. Completely remove the cellophane. electrical continuity.
3. Detach the white polystyrene corner pieces.
8. Dispose of any waste in an environmentally-friendly
4. Unscrew the fixings between the base and the pallet. manner.
[4]
It is advisable to cut the cellophane at the rear of the cubicle or at the corner to avoid scratching the surface.
The minimum distances to the walls and ceiling which must Minimum distances [mm]
be maintained in the installation are as follows: Side wall (a) 100
1740 mm high 560
Roof (b)
1300 mm high 700
Front clearance (c) 800
cgmcosmos-v 50
Rear wall (d)
Other functions 100
Table 4.1. Minimum installation distances
[5]
For any doubts, please ask Ormazabal.
[6]
In each case, bear in mind which cable is to be used in the particular installation.
Feeder function
Dimensions in mm.
[7]
Tests carried out with a test current of 21 kA.
Dimensions in mm.
Front and rear cable input or output with straight terminal (D1/D2).
Side cable input or output with straight terminal (D3/D4).
Dimensions in mm.
Front and rear cable input or output with straight terminal (D2).
Side cable input or output (D4).
Figure 4.6. Dimensions [mm] of the cable trench for cgmcosmos-v with
RAV driving mechanism
Trench necessary for the circuit-breaker with RAV driving mechanism function
Approximate Minimum depth
Cable Cable
radius of
Cable insulation Cable type section diameter
curvature* D2 D4
[mm2] [mm]
[mm]
< 150 38 500 300 350
185 42 600
400 450
Single-core 240 42 600
Height 1740 mm Dry insulation 300 48 750
600
400 48 750
550
< 150 85 750
Three-core 550
185 85 750
* Check against the data of the manufacturer of the cable used.
Table 4.4. Trench necessary for the circuit-breaker with RAV driving mechanism function
a M10 x 25 bolt
b 66x65 mm profile
c Anchoring support
[8]
See section “5. Recommended sequence of operations” on page 35.
Anchoring dimensions
f
b c d
Module Internal arc
[mm] [mm] [mm]
1s
-l* 325 - - 631.5
-p 430 - - 631.5
-v (RAV) 430 - - 631.5
-2lp 317 - - 631.5
Table 4.5. Anchoring dimensions
Figure 4.12. Anchoring diagram cgmcosmos-l double cable Figure 4.14. Anchoring diagram cgmcosmos-2lp 1300 mm high
1740 mm high
Figure 4.13. Anchoring diagram cgmcosmos-v with RAV driving Figure 4.15. Anchoring diagram cgmcosmos-2lp 1740 mm high
mechanism 1740 mm high
The cubicles must be joined as indicated in the Spare parts Ormazabal's RA-146 spares and accessories document,
and accessories instructions which is supplied with the materials kit for connecting
cubicles.
When connecting the general earth collector, follow the 1. Bolt the earth strip between every 2 medium voltage
figure below. cubicles, in the rear of the cable compartment, using 2
hexagonal M8 x 20 bolts. Apply a torque of 15 Nm.
Tools:
- 13 mm open-ended wrench.
- Torque wrench with 13 mm adapter.
The medium voltage incoming and outgoing feeders are Never touch live connectors, not even screened
linked to the transformer or, occasionally, other cubicles connectors. Screening does not constitute a protection
via cables. These cables and the corresponding bushings against direct contact.
on the cgmcosmos system cubicles can be connected with When the equipment is in service and a reserve cubicle
simple (plug-in) or reinforced (screw-in) connecting points, is left with voltage in the upper busbar and without the
either IEC type or IEEE-386 compliant. cables in the lower bushings, insulating plugs must be
placed in the bushings (EUROMOLD type) or close the
The cable compartment contains the connecting cable earthing switch and lock that position with a padlock.
bushings for the incoming and outgoing feeders, as well as
for the outgoing feeders to the transformer. The recommended terminations are described below.
The size of the cable compartment allows the use of both
insulated and partially insulated terminals.[9]
Rated 12 kV 24 kV
current Manufacturer Connector Connector Section Connector Section
[A] type [mm2] type [mm2]
Angled 158LR 16 - 150 K-158LR 16 – 150
EUROMOLD(*) Screened
Straight 152SR 16 - 120 K-152SR 25 - 120
3M Screened Angled 93-EE-8XX-2 25 - 95 93-EE-8XX-2 25-95
F&G Screened Angled ASW 10/250 25 - 120 ASW 20/250 25 – 120
Angled SEHDW11 25 - 150 SEHDW21 25 – 250
KABEL-DRAHT Screened
250 Straight SEHDG11 25 - 150 SEHDW21 25 - 150
PFISTERER Screened Angled CAW 20/250 35 - 70 CAW 20/250 35 - 70
Angled PMA-1-250/25 25 - 95 PMA-1-250/25 25 – 95
PIRELLI Screened
Straight PMR-1-250/25 25 - 95 PMR-1-250/25 25 – 95
Angled RSES 16 – 120 RSES 16 – 120
RAYCHEM Screened
Straight RSSS 16 - 95 RSSS 16 – 95
3M Unscreened 93-EE-8XX-2 25 - 95 93-EE-8XX-2 25 - 95
400LR 70 - 300 K-400LR 25 - 300
EUROMOLD(*) Screened
400TE 70 - 300 K-400TE 25 – 300
AST 10/400 25 - 240 AST 20/400 25 - 240
Screened ASW 10/400 25 – 240 ASW 20/400 25 - 240
ASTS 10/630 120 - 240 ASTS 20/630 25 - 240
F&G AGL 10/630 120 - 240 - -
AGLS 10/630 120 - 240 - -
Unscreened
AWK 10/630 25 – 240 ASGS 10/630 25 – 240
AWKS 10/630 25 – 240 AWKS 20/630 25 – 240
400
KABELDON Unscreened KAP 300 10 - 300 - -
SEHDW12 35 – 185 SEHDW22 25 – 250
Screened SEHDT12 35 – 150 SEHDT22 35 – 150
KABEL-DRAHT
SEHDW12 35 – 185 SEHDW22 25 - 250
Unscreened - 25 - 150 SEHDG23 185 - 240
PMA-2-400/24 25 – 95 PMA-2-400/24 25 - 95
PIRELLI Screened PMR-2-400/24 50 – 300 PMR-2-400/24 50 – 300
PMA-3-400/24 25 - 240 PMA-3-400/24 25 - 240
UHGK+RICS 120 – 300 UHGK+RICS 95 – 240
RAYCHEM Unscreened
IXSU+RICS 16 – 800 IXSU+RICS 16 – 800
Continues on the next page
[9]
It is advisable to use fully insulated connectors for voltages of 24 and 17.5 kV, according to HD 629.
Continuation
Rated 12 kV 24 kV
current Manufacturer Connector Connector Section Connector Section
[A] type [mm2] type [mm2]
450SR 70 – 300 K450SR 35 – 300
Screened 400LB 25 – 300 K-400LB 25 – 300
EUROMOLD(*)
400TB 35 – 300 K-400TB 35 – 300
Unscreened 15TS 35 – 630 UC412L 35 – 630
F&G Screened AST 10/630 25 – 240 AST 20/630 25 – 240
630
Screened SEHDT13 185 – 240 SEHDT23 185 – 240
KABEL-DRAHT
Unscreened SEHDG12 35 – 185 SEHDG22 35 – 185
PFISTERER Screened - - CAT 20/630 95 – 240
UHGK+RICS 120 – 300 UHGK+RICS 95 – 240
RAYCHEM Unscreened
IXSU+RICS 16 – 800 IXSU+RICS 16 – 800
1250 EUROMOLD(*) Screened 440TB 185 – 630 K440TB 185 – 630
* Connectors tested in cgmcosmos cubicles.
Rated 12 kV 24 kV
current Manufacturer Connector Connector Section Connector Section
[A] type [mm2] type [mm2]
AGM
- - 25 – 150
20/400+GKV20
F&G Unscreened
AWM AWM
25 – 240 25 – 150
10/400+SKV10 20/400+GKV20
KABELDON Unscreened KAP 300 U 10 – 300 - -
400 PMA-3-400/24+CPI 25 – 240 PMA3-CPI 25 – 240
PMA-2-400/24+CPI 25 – 95 PMA-2-400/24+CPI 25 – 95
PIRELLI Screened
PMR-2-400/24
50 – 300 PMR-2-400/24 + CPI 50 – 300
+ CPI
UHGK+RICS 12 – 300 UHGK+RICS 95 – 240
RAYCHEM Unscreened
IXSU+RICS 16 – 800 IXSU+RICS 16 – 800
EUROMOLD(*) Screened K-400TB-MIND 25 – 240 K-400TB-MIND 25 – 240
630 UHGK+RICS 120 – 300 UHGK+RICS 95 – 240
RAYCHEM Unscreened
IXSU+RICS 16 – 800 IXSU+RICS 16 – 800
* Connectors tested in cgmcosmos cubicles.
Main characteristics:
• Two normally open (NO) voltage-free contacts calibrated
at the same level.
• Accuracy class: + 20 °C - 1 %
- 30 °C to 60 °C - 2.5 %
• Temperature range: - 30 °C to + 60 °C
1. Move the grey slider to the left (this releases the lever
access so the switch-disconnector can be closed).
2. Connection operation:
a. Manual operation (B driving mechanism). Insert
the lever in the switch access (red area), move the
actuating arm to the end and turn clockwise 90°.
b. Motorised operation (BM driving mechanism).
Activate the corresponding operation command.
These driving mechanisms allow the operation 2. Open the bottom cover to access the cable
of going from earthing switch closed to switch- compartment.
disconnector open, even when the cable compartment 3. Follow the steps in section “5.2.3. Opening operation
cover is open. Thus, the switch-disconnector cannot from the earthing position”.
be changed to the closed position until this cover has
been put back. 4. Carry out the cable test.
The cable test can only be carried out in cgmcosmos-l 5. To return to earthing position, follow the steps in
feeder functions which include B/BM driving section “5.2.3. Opening operation from the earthing
mechanisms with this characteristic. Please check with position”.
Ormazabal. 6. Close the bottom cover to access the cable
compartment.
1. Follow the steps in section “5.2.6. Earthing operation
7. Follow the steps in section “5.2.6. Earthing operation
from isolating position”.
from isolating position”.
a Switch-disconnector operation.
b Earthing switch operation.
c Switch-disconnector status indicator.
d Earthing switch status indicator.
e Earthing switch locking with a padlock.
f Padlock locking of switch closing and spring charge operations.
g LRM-VDS system according to NBN EN 61243-5
h Manual trip operation.
Fuse status indicator:
i GREEN: Voltage.
RED: Striker tripped.
j Pressure gauge viewing window.
k Spring charge indicator.
Figure 5.13. Type-1 lever detail (anti-reflex) Figure 5.14. Type-2 lever detail (anti-reflex)
5.3.4. Spring charge operation and closing of the switch from isolating position
Start with the switch (5) and the earthing switch (6) in open
positions. Operate the lever in the direction indicated in
Figure 5.16.
Start with the switch (7) in closed position and the earthing
switch (8) in open position. Press the push-button (9) and
check the springs are uncharged (10).
Start with the switch (3) and the earthing switch (4) in open
positions. Operate the lever in the indicated direction until
the final situation indicated in Figure 5.18 is achieved.
Make sure that the end with the striker of the new fuse
faces forward (carriage insulator end).
It is advisable to change all three fuses, even if they do
not appear to be damaged.
11. To close the cover, first ensure that the clip is properly
engaged and that the fuse holder is in the correct
position. Fit the fuse and cable compartment access
cover by pulling it upwards until it is removed from its
position.
The fuses recommended for use in the fuse protection The following table shows the recommended fuse ratings
functional units are defined according to the tests carried according to the Ur/Ptransf. ratio:
out. The next
1. Fuses recommended: SIBA brand with medium type 7. For overload conditions in the transformer or use of
striker, conforming to IEC 60282-1 (Low loss fuses). other brands of fuse, please consult Ormazabal.
2. The values for combined fuses, in accordance with IEC
62271-105 are greyed. For the auxiliary services function, the recommended
3. The fuse-switch assembly has been temperature-rise fuse is "Back up" type 10/24 kV, 442 mm, calibre 2 A.
tested under normal service conditions according to
IEC 62271-1. Transfer current according to IEC 62271-105:
4. A fuse-holder carriage adapted for 292 mm 6/12 kV
fuses is available. Ur fuse Ur cubicle Itransfer
5. For ratings not marked in bold the measurement is 442 [kV] [kV] [A]
mm. 12 12 2300
24 24 1600
6. If any of the fuses blows, we recommend changing all
three. Table 5.2. Transfer current
The actuating levers to be used to operate the switch- The spring charge lever is used to manually charge the
disconnector with B or BM driving mechanisms is: springs of the circuit-breaker mechanism.
Figure 5.30. Mechanisms lever for B and BM actuation Figure 5.31. Spring charge lever RAV
Undervoltage coil
6. Safety elements
6.1. Interlocks
The switchgear is provided with safety locks, which ensure 2. The cubicles have a safety lock which prevents access
the following conditions: to the medium voltage cable compartment while the
earthing switch is not closed. In normal operation,
1. The switch-disconnector and the earthing switch this earthing switch cannot be opened if the cable
cannot both be closed at the same time. compartment cover is not in place.
Cubicles of the cgmcosmos system with B/BM driving Sequence to remove the interlock lock
mechanisms are designed to optionally incorporate lock
assemblies in the earthing switch and switch-disconnector 1. Move the slide (yellow for the earthing switch actuating
actuating shafts, both in the open and closed positions. shaft or grey for the switch-disconnector actuating
Examples of locking with interlocks (optional): shaft) until it completely covers access to the lever in the
actuating shaft. Until the position indicator is situated
• Example 1: Earthing interlocked in open position. This
on the instructed position the interlock is disabled.
avoids setting the switch to the "earthing" position until
the key for the low voltage disconnector lock has been 2. Insert the interlock key and turn it in the direction
recovered. indicated on the mimic diagram of the cubicle until it
reaches the stop piece.
• Example 2: Earthing interlocked in closed position
(ALWAYS INTERLOCK for work without voltage). It It is now that the position indicator is locked until the
prevents anyone from accidentally opening the earthing sequence to remove the interlock is carried out
switch by removing the earth from the cable. 3. Remove the key from the corresponding interlock.
7. Maintenance
For safety reasons, maintenance operations performed These mechanisms must be inspected when used under
directly on the driving mechanism must be performed extreme conditions (dust, salt, pollution). It is advisable to
WITHOUT any actuating levers inserted. carry out at least one operation during the inspections.
7.1. Preventive maintenance of the cgmcosmos-v cubicle with RAV driving mechanism
The actuating mechanisms and other elements outside Maintenance should be carried out every 5 years or 2000
the gas tank may require preventive maintenance; the operating cycles, unless, based on the conditions of use, the
frequency of this maintenance depends on the existing user, together with Ormazabal, considers otherwise.
environmental conditions (harsh environments, dust,
extreme temperatures, etc.) and must be established in line The recommended preventive maintenance sequence
with the experience and responsibility of the installer. is described in Ormazabal's MO-080 Operations
Manual.
Although the cubicles have been designed for a service life If any of the stated auxiliary components need to be
in accordance with IEC 62271-200, certain components can changed, the corresponding spare parts kit must be
be replaced and installed for various reasons. ordered, and the instructions given in the corresponding
documentation must be followed.
Certain spares and accessories must be installed in the
cubicle by specialised personnel. Please check with
Ormazabal.
Equipment -l -p -v (RAV)
Switch-disconnector/Disconnector X X X
Circuit-breaker - - X
Earthing switch X X X
Side connection female bushings X X X
Fuse holder compartment - X -
Front connection bushings X X X
Side connection bushings O O O
Pressure switch X X X
Gas density monitor[15] O O O
Driving mechanisms -l -p -v (AV/RAV)
B X O X
BM O O O
AR - O -
ARM - O -
RAV - - X (RAV)
RAMV - - O
Manual driving mechanisms -l -p -v (AV/RAV)
Group of auxiliary contacts 2 NO + 2 NC switch O O O
Group of auxiliary contacts 1 NO + 1 NC Earth connection O O O
Group of auxiliary contacts 2 NO + 2 NC Earth connection O O -
Group of auxiliary contacts 2NO + 2 NC circuit -breaker - - X
Group of auxiliary contacts 9NO + 9 NC circuit -breaker - - O
Opening coil - O O
Bistable - O O
Actuating lever X X X
Motorised driving mechanisms -l -p -v (AMV/RAMV)
Group of auxiliary contacts 9 NO + 9 NC circuit-breaker - - X
2nd opening coil - - O
Auxiliary undervoltage coil - - O
Closing coil - - O
Continued on next page
[10]
Pressure gauge with temperature compensation and one normally open contact for external indicating or pressure monitoring of SF6.
Continuation
9. Environmental information
cgmcosmos cubicles are defined as a pressure-sealed being released into the atmosphere. Extracting and
hermetic system, according to IEC 62271-1, which contains handling of SF6 must be carried out by qualified personnel,
sulphur hexafluoride (SF6)[11]. using a sealed piercing system.
SF6 is included in the Kyoto Protocol list of greenhouse For the usage and handling of the SF6, the indications listed
gases. SF6 has a GWP (Global Warming Potential) of 22,200. in IEC 62271-303 must be followed.
(TAR, IPCC 2001).
Management and treatment of the rest of materials must
At the end of the product's life, the contents of the SF6 must be carried out in accordance with the country’s current
be recovered for processing and recycling, preventing it legislation.
[11]
This information is given on a label on the equipment itself.
www.ormazabal.com