Professional Documents
Culture Documents
3 system
Medium-voltage switchgear with
integrated insulation in SF6 gas up to
40.5 kV in accordance with IEC Standard
with rated current up to 630 A
General instructions
IG-136-EN, version 11, 10/01/2019
LIB
CAUTION!
When medium-voltage equipment is operating, certain components are live, other parts may be in movement and some may
reach high temperatures. Therefore, the use of this equipment poses electrical, mechanical and thermal risks.
In order to ensure an acceptable level of protection for people and property, and in compliance with applicable environmental
recommendations, Ormazabal designs and manufactures its products according to the principle of integrated safety, based on
the following criteria:
• Elimination of hazards wherever possible.
• Where elimination of hazards is neither technically nor economically feasible, appropriate protection functions are
incorporated in the equipment.
• Communication about remaining risks to facilitate the design of operating procedures which prevent such risks,
training for the personnel in charge of the equipment, and the use of suitable personal protective equipment.
• Use of recyclable materials and establishment of procedures for the disposal of equipment and components so
that once the end of their service lives is reached, they are duly processed in accordance, as far as possible, with the
environmental restrictions established by the competent authorities.
Consequently, the equipment to which the present manual refers complies with the requirements of section 11.2 of Standard
IEC 62271-1. It must therefore only be operated by appropriately qualified and supervised personnel, in accordance with the
requirements of standard EN 50110-1 on the safety of electrical installations and standard EN 50110-2 on activities in or near
electrical installations. Personnel must be fully familiar with the instructions and warnings contained in this manual and in other
recommendations of a more general nature which are applicable to the situation according to current legislation[1].
The above must be carefully observed, as the correct and safe operation of this equipment depends not only on its design but also
on general circumstances which are in general beyond the control and responsibility of the manufacturer. More specifically:
• The equipment must be handled and transported appropriately from the factory to the place of installation.
• All intermediate storage should occur in conditions which do not alter or damage the characteristics of the equipment
or its essential components.
• Service conditions must be compatible with the equipment rating.
• The equipment must be operated strictly in accordance with the instructions given in the manual, and the applicable
operating and safety principles must be clearly understood.
• Maintenance should be performed properly, taking into account the actual service and environmental conditions in
the place of installation.
The manufacturer declines all liability for any significant indirect damages resulting from violation of the guarantee, under any
jurisdiction, including loss of income, stoppages and costs resulting from repair or replacement of parts.
Warranty
The manufacturer guarantees this product against any defect in materials and operation during the contractual period. In the
event that defects are detected, the manufacturer may opt either to repair or replace the equipment. Improper handling of this
equipment and its repair by the user shall constitute a violation of the guarantee.
Registered Trademarks and Copyrights
All registered trademarks cited in this document are the property of their respective owners. The intellectual property of this manual
belongs to Ormazabal.
[1]
For example, in Spain the “Regulation on technical conditions and guarantees for safety in high-voltage electrical installations” – Royal Decree
337/2014 is obligatory.
In view of the constant evolution in standards and design, the characteristics of the elements contained in this manual are subject
to change without prior notice. These characteristics, as well as the availability of components, are subject to confirmation by
Ormazabal.
General instructions Table of contents
cgm.3 system: Medium-voltage switchgear with integrated
insulation in SF6 gas up to 40.5 kV in accordance with
IEC Standard with rated current up to 630 A
Table of contents
6. Safety elements.........................................................74
7. Maintenance..............................................................76
9. Environmental information.....................................81
1. General description
Ormazabal's cgm.3 system, designed following the with full SF6 gas insulation, which can be used to configure
requirements set out in the standards of the International different secondary distribution configurations in medium
Electrotechnical Commission (IEC), is made up of different voltage up to 40.5 kV.[2]
unifunctional and multifunctional switchgear models,
1.1. Models
Unifunctional Multifunctional
Function Functions
switchgear switchgear
cgm.3-l Feeder cgm.3-2lp 2 feeder functions and 1 fuse protection
cgm.3-s Busbar switch 2 feeder functions and 1 vacuum circuit-
cgm.3-2lv
breaker
Busbar switch with earth connection on the right
cgm.3-s-pt
(-ptd) or on the left (-pti) Table 1.2. Multifunctional switchgear
cgm.3-p Fuse protection
cgm.3-v Vacuum circuit-breaker
cgm.3-rb Busbar rise
cgm.3-rb-pt Busbar rise with earth connection
cgm.3-rc/-r2c Cable/double cable rise
cgm.3-m Metering
Standard Description
IEC 62271-1 Common specifications for high voltage switchgear standards.
IEC 62271-100 High-voltage alternating current circuit-breakers.
IEC 62271-102 Alternating current disconnectors and earthing switches.
IEC 62271-103 High-voltage switches for rated voltages above 1 kV up to and including 52 kV.
IEC 62271-105 Alternating current fuse-switch combinations.
IEC 62271-200 Alternating current metal-enclosed switchgear for rated voltages above 1 kV and up to and including 52 kV.
IEC 62271-206/IEC 61243-5 Voltage presence indicating systems.
IEC 60529 IP ratings for enclosures.
IEC 60282-1 Current-limiting fuses.
1 Gas tank
1.1 Side connection female bushings
2 Driving mechanisms area
2.1 Name plate
2.2 Operating sequence plate
2.3 Actuating shafts (see mimic diagram for each model).
2.4 ekor.vpis/ekor.ivds voltage presence detection unit*
2.5 ekor.sas acoustic earthing prevention alarm unit*
3 Base
3.1 Cable compartment access cover
3.2 Medium voltage cable fixing bracket
3.3 Gas relief compartment
3.4 Earth collector
3.5 Front cable connection bushings
* Optional elements.
This is the compartment in which the switch-disconnector, The mimic diagram includes all the position indicators for
earthing switch or circuit-breaker is driven, depending on the driving elements.
the type of function.
The cgm.3 system has, in line with the cubicle model, the
The mimic diagram for the main medium voltage circuit is following types of driving mechanism:
displayed on the cover of this compartment.
Table 1.4. Types of driving mechanisms can be replaced by upgrading in any of the three possible
These elements are operated independently, i.e., their positions (closed-opened-earthed). Whilst the driving
actuation speed does not depend on the speed of the mechanism is withdrawn, these positions of the switch can
manual operation. be blocked using a coupling device, whether in service or
not.
B, BM, B2M, BR-A, BR‑AM and BR‑A2M driving mechanisms
1.3.3. Base
Made up of the cable compartment and the gas relief Gas relief compartment
compartment:
Ormazabal's cgm.3 is designed and constructed to
Cable compartment withstand at least the thermal and dynamic effects of an arc
of 16 kA for 0.5 seconds should a defect result in an internal
arc in the gas compartment. The system conducts the gases
This is located in the bottom front section of the cubicle
generated in a fully controlled manner to avoid any possible
and has a cover interlocked with the earthing switch, thus
injury to people in the equipment operation area.
allowing front access to the medium voltage cables.
As standard, it is designed to contain up to: Optionally, a flue can be positioned in the rear of the
cubicle to redirect the gases to the top. Please check
• Two shielded screw-in terminals (reduced) per phase with Ormazabal.
or one terminal (reduced) plus surge arrester (reduced)
with space for the corresponding incoming power
cables.
• Ties for the power cables.
• Earthing flatbars.
As an option:
Name plate
N° Cubicle serial number*
Type Ormazabal cubicle system
Designation Cubicle model
Standard Standards applied to the equipment
Name Equipment name
Ur Equipment rated voltage (kV)
Up Lightning impulse withstand voltage (kV)
Ud Power frequency withstand voltage (kV)
fr Equipment rated frequency (Hz)
Ir Equipment rated current (A)
Instructions Manual General Instructions Manual (IG) for the system
Class Driving mechanism class according to IEC 62271-103
N Number of mainly active load breaking operations
Ik/Ip Short-time withstand current/Short-time withstand peak value
tk Short-time withstand current time
Pre Gas pressure inside the gas tank (MPa)
Pme Minimum operating gas pressure (MPa)
SF6 Insulating fluid mass (kg)
CO2e Equivalent CO2 fluid mass (t)
Year Year of manufacture
TC Minimum working temperature
IAC Classification of internal arc
Table 1.6. Characteristics
The values set out in this table are general for the
cgm.3 system and are only valid when confirmed by
Ormazabal. Some cubicle models can withstand
partial values. For more detailed information, check
the table for each cubicle model in Ormazabal's
CA-112 catalogue.
Width (a) Depth (f) Height (h) Bushings height (g) Cable fastening height (i) Weight
Cubicle
[mm] [mm] [mm] [mm] [mm] [kg]
Installation Indoor
Maximum ambient temperature + 40 °C
Minimum ambient temperature - 5 °C / - 30 °C(b)
Maximum mean ambient temperature, measured over a 24-hour period + 35 °C
Maximum mean relative humidity, measured over a 24-hour period < 95 %
Maximum mean relative humidity, measured over a 1-month period < 90 %
Maximum mean vapour pressure, measured over a 24-hour period 2.2 kPa
Maximum mean vapour pressure, measured over a 1-month period 1.8 kPa
Maximum height above sea level 2000 m
Solar radiation Negligible
Ambient air pollution (dust, smoke, corrosive and/or flammable gases, vapours or salt) Insignificant
Vibrations caused by causes external to the switchgear or by seismic movements Insignificant
(b)
Storage: - 40 °C
The switchgear must always be kept upright, directly on the To handle assemblies of up to 4 cgm.3 functional units, one
ground or on a pallet depending on the type of handling of the following methods must be used:
involved.
Position the rear of the cubicle facing the driver, to avoid damaging the front.
[3]
3. Storage
If it needs to be stored, the equipment must be placed on After prolonged storage, clean all the insulating parts
dry ground or on top of damp-proof insulating material, still carefully before commissioning the equipment. The
in its original packaging. enclosure should be cleaned with a clean, dry lint-free cloth.
Storage must always be INDOORS, with the following 6. The switchgear must be protected from the rain, and
conditions recommended: the humidity conditions should be as follows:
a. the mean relative humidity value, measured over a
1. Ambient air temperature should not exceed 40 ºC
period of 24 hours, must not exceed 95 %.
and its mean value, measured in a period of 24 hours,
should not exceed 35 ºC. b. the mean water steam pressure value, measured in
a period of 24 hours, must not exceed 2.2 kPa.
2. The ambient air temperature should not drop below
- 5 °C. There are also cubicles with storage temperature c. the mean relative humidity value, measured over a
up to - 40 °C. period of one month, must not exceed 90 %.
3. The switchgear must be protected from direct solar d. The mean water steam pressure value, measured
radiation. over a period of one month, must not exceed
1.8 kPa.
4. Altitude, both in transport and in storage, must not
exceed 2000 m. 7. During transport, vibrations caused by external factors
or seismic movements must be insignificant.
5. The environmental air must not have any significant
contamination from dust, smoke, corrosive and/or
Any other conditions must be notified beforehand,
inflammable gases, vapours or salt. since the equipment must be factory-adjusted to the
atmospheric pressure.
Otherwise, the pressure gauge needle may indicate
an incorrect value, even if the equipment's internal
pressure is correct.
4. Installation
The cgm.3 system switchgear is supplied as standard 6. Unpack the accessory box located at the rear or on top
protected by plastic packaging. of the cubicle.
7. Remove the self-adhesive protective plastic from the
On receiving the equipment, check that the goods supplied
cable compartment cover.
correspond to the order and associated documentation. If
this is not the case, contact Ormazabal immediately.
The self-adhesive plastic must be removed from the
The disassembly process for the equipment is as follows: cable compartment cover so that the equipment
enclosure's earth connection may have the proper
1. Using a blade, cutter or similar tool, cut the cellophane electrical continuity.
the cubicle is wrapped in[4].
8. Dispose of any waste in an environmentally-friendly
2. Completely remove the cellophane. manner.
3. Detach the white polystyrene corner pieces.
It is advisable to make a visual inspection of the equipment
4. Unscrew the fixings between the base and the pallet.
to check whether it has suffered any damage in transit. If
5. Remove the pallet, handling the cubicle as indicated in damaged, contact Ormazabal immediately.
section 2.1.
It is advisable to cut the cellophane at the rear of the cubicle or at the corner to avoid scratching the surface.
[4]
The minimum distances to the walls and ceiling which must Minimum distances [mm]
be maintained in the installation are as follows: Side wall (a) 100
Height
600
1400 mm
Roof (b)
Height
550
1745 mm
Front clearance (c) 500*
Function Rear wall (d)**
cgm.3-l/-s/-v/-2lv/-rb/-rc 100/160***
cgm.3-p/-2lp 0
cgm.3-m without IAC
0
classification
cgm.3-m with IAC
100/150****
classification
* An operating clearance of 1000 mm is recommended.
(**) Cubicles with classification IAC AFLR: d = 800 mm.
*** Configurations with p and 2lp cubicles.
**** for classification IAC 21 kA-1 s.
Minimum recommended dimensions based on the trench IEC 62271-200. These dimensions may vary in accordance
dimensions used in the tests in accordance with Standard with the radius of curvature of the cables used[6].
Trench necessary for the feeder, busbar rise and cable rise function
Cable data Approximate Minimum depth
Cable Cable radius of
Cable curvature* D1 D2
Cable type section diameter
insulation [mm] [mm] [mm]
[mm2] [mm]
< 150 41 555 200 500
185 43 590
Single-core 200 550
240 45.2 640
Dry insulation 18/30 kV
300 47.5 685
300 660
400 48 745
3-core 18/30 kV < 150 92.7 805 650 650
* Check against the data of the manufacturer of the cable used.
Table 4.2. Trench necessary for the feeder, busbar rise and cable rise
function
In each case, bear in mind which cable is to be used in the particular installation.
[6]
Figure 4.6. Dimensions [mm] of the cable trench for cgm.3-v with AV/RAV
driving mechanism.
Trench necessary for the circuit-breaker with AV/RAV driving mechanism function
Cable data Approximate Minimum depth
Cable Cable radius of
Cable curvature* D1 D2
Cable type section diameter
insulation [mm] [mm] [mm]
[mm2] [mm]
<150** 41 555 400 400
185 43 590
Single-core 400 500
240 45.2 640
Dry insulation 18/30 kV
300 47.5 685
500 600
400 48 745
3-core 18/30 kV < 150 92.7 805 850 850
* Check against the data of the manufacturer of the cable used.
** 150 mm2 cable valid up to 21 kA.
Trench necessary for the feeder, busbar rise and cable rise function
Cable data Approximate Minimum depth
Cable Cable radius of
curvature* D1 D2
Cable insulation Cable type section diameter
[mm] [mm] [mm]
[mm2] [mm]
< 150** 41 555 500 800
1400 mm***
185 43 590
Single-core 550 900
Height
Table 4.5. Trench necessary for the feeder, busbar rise and cable rise
function
900 900
Dry insulation 18/30 kV 95 38 500
150 41 555 950 950
3-core 18/30 kV < 95 86 735 1400 1400
< 50 35 430 500 500
1745 mm
550 550
Dry insulation 18/30 kV 95 38 500
150 41 555 600 600
3-core 18/30 kV < 95 86 735 1050 1050
* Check against the data of the manufacturer of the cable used.
Figure 4.9. Dimensions [mm] of the cable trench for cgm.3-v with AV/RAV
driving mechanism.
Trench necessary for the circuit-breaker with AV/RAV driving mechanism function
Cable data Approximate Minimum depth
Cable Cable radius of
curvature* D1 D2
Cable insulation Cable type section diameter
[mm] [mm] [mm]
[mm2] [mm]
< 150** 41 555 750 750
1400 mm***
185 43 590
Single-core 800 800
Height
Metering function
Before assembling the cubicles, the floor must be carefully The cubicles can be fastened to the floor in two ways:
levelled to prevent any deformation which may make it
difficult to connect the cubicles to one another.
a M10 x 25 bolt
b 65 x 65 x 4 mm profile
c Anchoring bracket
If the floor of the installation is level enough, it is advisable The sequence for anchoring the cubicles to the floor is as
to install the medium voltage cubicle anchored directly to follows:
the floor.
1. The cubicle's switch must be in the earthing position[9].
Figure 4.13. Detail of anchor points in cgm.3 -l, -s, -s-pt, -p,-v, -rb, -rb-pt Figure 4.14. Detail of anchor points in cgm.3 -l, -p, -v cubicles measuring
cubicles measuring 1745 mm high 1400 mm high
Figure 4.15. Detail of anchor points in cgm.3 -l, -s, -s-pt, -p, -v, -rb,-rb-pt
Figure 4.18. Anchoring points in cgm.3-m cubicles
double cable cubicles measuring 1745 mm high
Figure 4.21. Detail of anchor points in cgm.3-2lp cubicles measuring Figure 4.22. Anchoring points in cgm.3-2lv cubicles
1400 mm high
Earthquake equipment
The cgm.3 system has earthquake resistant equipment
as an option.
The earthquake resistance of this type of switchgear
does not only depend on the equipment construction
and design, but also on the installation.
In order to anchor this type of cubicles properly, use
the six points indicated in the figure below.
For further information, please ask Ormazabal.
The cubicles must be joined as indicated in Ormazabal's with the materials kit for connecting cubicles.
RA-163 spares and accessories document, which is supplied
When connecting the general earth collector, follow the 1. Bolt the earthing flatbar between every two medium
figure below. voltage cubicles, in the rear section, using 2 hexagonal
M8 x 20 bolts. Apply a torque of 15 Nm.
Tools:
13 mm Open-ended wrench
Torque wrench with 13 mm adapter.
The medium voltage incoming and outgoing feeders are Never touch live connectors, not even screened
linked to the transformer or, occasionally, other cubicles connectors. Screening does not constitute a protection
via cables. These cables and the corresponding bushings in against direct contact.
the cgm.3 system cubicles can be connected with simple When the equipment is in service and a reserve cubicle
(plug-in) or reinforced (screw-in) connecting points, either is left with voltage in the top busbar and without the
IEC type or IEEE-386 compliant[10]. cables in the bottom bushings, insulating plugs must
be placed in the bushings (EUROMOLD type) or close
The cable compartment contains the connecting cable the earthing switch and lock that position with a
bushings for the incoming and outgoing feeders, as well as padlock.
for the outgoing feeders to the transformer.
The terminals recommended for networks with Ur = 36 kV
The size of the cable compartment allows the use of both are detailed below.
insulated and partially insulated terminals[11].
36 kV
Cable Type Rated current [A] Manufacturer Connector
Connector type Section [mm2]
400 M400LR 35-240
Dry insulation 630 EUROMOLD(*) Screened M400TB 35-240
630 M400TB 18-630
* Connectors recommended for Ormazabal’s cgm.3 system.
Apart from the list above, CENELEC terminals are also valid.
For other values, check with Ormazabal.
In accordance with figure 13 of Standard IEEE 386: “600 A dead-break interface No. 1, 21.1 kV”
[10]
It is advisable to use fully insulated connectors for voltages of 36 and 40.5 kV, according to HD 629.
[11]
The medium voltage and current transformers are housed For further information on the installation and
in tracks installed in the cgm.3-m metering modular cubicle connection of cgm.3-m metering transformers by
by Ormazabal. Ormazabal, check Operations manual MO-082
"Installation of transformers and busbars in metering
The layout and connection of these transformers (maximum cubicles”.
three voltage transformers and three current transformers
per metering cubicle) will correspond to the order
configuration and the type of transformers to be installed.
Ormazabal has two voltage presence indicator options: The purpose of the test points for the three phases and
earth is to make it easier to check the phase balance[12]
• ekor.vpis unit for detecting voltage, designed in between cubicles. Ormazabal's specific phase comparator
accordance with Standard IEC 62271-206. The “voltage ekor.spc can be used to do this.
presence” indicator is therefore displayed when the
phase-earth voltage is equal to or greater than 45 %
With the ekor.vpis, if the indicators do not light up, use
of the rated voltage and is not visible when the phase-
other means to check that there is no voltage.
earth voltage is less than 10 % of the rated voltage.
• ekor.ivds unit for detecting voltage, designed in
accordance with Standard IEC 61243-5. Therefore, the
“voltage presence” detection is displayed when the
phase-earth voltage is between 45 % and 120 % of the
rated voltage and is not visible when the phase-earth
voltage is less than 10 % of the rated voltage.
Figure 5.5. There is NO indication in the comparator. Figure 5.6. There IS indication in the comparator
Optionally, other comparison devices which comply with Standard IEC 62271-206 may be used.
[13]
See section "5.2. Voltage presence indicator" of these general instructions manual.
[14]
2. Disconnecting operation:
a. Manual operation. Insert the lever in the earthing
switch actuating shaft, move the driving arm to the
end and turn anti-clockwise 90º.
b. Motorised operation (BM/B2M driving mechanism).
Activate the corresponding operation command.
2. Connecting operation:
a. Manual operation (B driving mechanism). Insert
the lever in the switch access (grey area), move the
actuating arm to the end and turn clockwise 90º.
b. Motorised operation (BM/B2M driving mechanisms).
Activate the corresponding operation command.
2. Disconnecting operation:
a. Manual operation (B driving mechanisms). Insert
the lever in the switch access (grey area), move the
actuating arm to the end and turn anti-clockwise
90º.
b. Motorised operation (BM/B2M driving mechanisms).
Activate the corresponding operation command.
2. Connecting operation:
a. Manual operation. Insert the lever in the earthing
switch actuating shaft, move the driving arm to the
end and turn clockwise 90º.
b. Motorised operation (BM/B2M driving mechanism).
Activate the corresponding operation command.
These driving mechanisms allow the operation 3. Open the bottom cover to access the cable
of going from earthing switch closed to switch- compartment.
disconnector open, even when the cable compartment 4. With the lever in the earthing switch access, follow
cover is open. Thus, the switch-disconnector cannot the steps in section "5.4.3. Opening operation from
be changed to the closed position until this cover has earthing position".
been put back.
5. Carry out the cable test.
The cable test can only be carried out in cgm.3
feeder functions which include B/BM/B2M driving 6. To return to earthing position, follow the steps in
mechanisms with this characteristic. Please check with section "5.4.6. Earthing operation from open position".
Ormazabal. 7. Close the bottom cover to access the cable
1. Follow the steps in section "5.4.6. Earthing operation compartment.
from open position".
2. Leave the lever in the earthing switch access (yellow
area).
2. Connecting operation:
a. Manual operation (B driving mechanism). Insert
the lever in the switch access (grey area), move the
actuating arm to the end and turn clockwise 90º.
b. Motorised operation (BM driving mechanism).
Activate the corresponding operation command.
2. Disconnecting operation:
a. Manual operation (B driving mechanism). Insert
the lever in the switch access (grey area), move the
actuating arm to the end and turn anti-clockwise
90º.
b. Motorised operation (BM driving mechanism).
Activate the corresponding operation command.
2. Disconnecting operation:
a. Manual operation. Insert the lever in the earthing
switch actuating shaft, move the actuating arm to
the end and turn anti-clockwise 90º.
b. Motorised operation (BM/B2M driving mechanism).
Activate the corresponding operation command.
2. Connecting operation:
a. Manual operation. Insert the lever in the switch
access (grey area), move the actuating arm to the
end and turn clockwise 90º.
b. Motorised operation (BM/B2M driving mechanisms).
Activate the corresponding operation command.
2. Disconnecting operation:
a. Manual operation. Insert the lever in the switch
access (grey area), move the actuating arm to the
end and turn anti-clockwise 90º.
b. Motorised operation (BM/B2M driving mechanisms).
Activate the corresponding operation command.
2. Connecting operation:
a. Manual operation. Insert the lever in the earthing
switch actuating shaft, move the driving arm to the
end and turn clockwise 90º.
b. Motorised operation (BM/B2M driving mechanism).
Activate the corresponding operation command.
2. Disconnecting operation:
a. Manual operation (B driving mechanism). Insert
the lever in the earthing switch actuating shaft,
move the driving arm to the end and turn anti-
clockwise 90º.
b. Motorised operation (BM driving mechanism).
Activate the corresponding operation command.
2. Connecting operation:
a. Manual operation (B driving mechanism). Insert
the lever in the earthing switch actuating shaft,
move the driving arm to the end and turn clockwise
90º.
b. Motorised operation (BM driving mechanism).
Activate the corresponding operation command.
2. Disconnecting operation:
a. Manual operation
Insert the lever in the earthing switch actuating
shaft, move the drive arm to the end and press
inwards on the head of the lever with one hand, and
turn 90º anti-clockwise with the other hand.
b. Motorised operation (driving mechanism
BR-A2M). Activate the corresponding operation
command.
5.8.4. Spring charge operation and closing of the switch-disconnector from open position
2. Connecting operation:
a. Manual operation.
Insert the lever in the earthing switch actuating
shaft, move the drive arm to the end and press
inwards on the head of the lever with one hand, and
turn 90º clockwise with the other hand.
b. Motorised operation (driving mechanism
BR-A2M). Activate the corresponding operation
command.
Make sure that the side of the new fuse striker faces
the carriage insulator side. It is advisable to change
all three fuses, even if only one of them appears to be
damaged.
Close the cover and check that all the strikers have been
reset.
The fuses recommended for use in the fuse protection out by the manufacturers. The following table shows the
functional unit are defined according to tests carried recommended fuse ratings according to the Ur/Ptransf. ratio:
• Recommended fuses: SIBA 20/36 kV, type HHD, medium The transfer currents have been tested in accordance with
type striker, for functional units up to 36 kV and SIBA the following parameters:
HHD TB 40.5 kV, medium type striker, for functional units
up to 40.5 kV (conforming to IEC 60282-1). Ur Fuse Ur Cubicle Ir Fuse Itransfer
[kV] [kV] [A] [A]
• For other makes and overcharge protection, check with
36 36 Type SSK 80 820
Ormazabal.
40.5 40.5 Type HHD 63 700
Table 5.2. Transfer currents
6. Safety elements
The switchgear is provided with safety locks, which ensure 2. The cubicles have a safety lock which prevents access
the following conditions: to the medium voltage cable compartment unless
the earthing switch is closed. In normal operation,
1. The switch-disconnector and the earthing switch this earthing switch cannot be opened if the cable
cannot both be in closed position at the same time. compartment cover is not in place.
7. Maintenance
For safety reasons, maintenance operations performed extreme conditions (dust, salt, pollution). It is advisable to
directly on the driving mechanism must be performed carry out at least one operation during the inspections.
WITHOUT any actuating levers inserted.
Components manufactured from galvanised sheet steel
The live parts of the main circuit and switching equipment have been painted to ensure their resistance to rust. Any
do not require inspection or maintenance, as they are scratches, dents or similar on them must be repaired to
completely insulated in SF6, and therefore free from any prevent rust.
influence from external environment.
Facilities which operate under severe climate
The operating mechanism for the cgm.3 system cubicles conditions, in excess of those defined as normal
driving devices does not require lubrication for correct service conditions (IEC 62271-1), must carry out the
operation throughout its estimated lifetime, according to regular preventive maintenance tasks required. Check
the service conditions specified in IEC 62271-1. with Ormazabal for the environmental conditions of
the installation.
These mechanisms must be inspected when used under
2. ekor.sas connections.
The actuating mechanisms and other elements outside Maintenance should be carried out every 5 years or 2000
the gas tank may require preventive maintenance; the operating cycles, unless, based on the conditions of use, the
frequency of this maintenance depends on the existing user, together with Ormazabal, considers otherwise.
environmental conditions (harsh environments, dust,
extreme temperatures, etc.) and must be established in line The recommended preventive maintenance sequence
with the experience and responsibility of the installer. is described in Operations Manual MO-079 by
Ormazabal.
Although the cubicles have been designed for a service life ordered, and the instructions given in the corresponding
in accordance with IEC 62271-200, certain components can documentation must be followed.
be replaced and installed for various reasons.
Certain spares and accessories must be installed in the
If any of the stated auxiliary components need to be cubicle by specialised personnel. Please check with
changed, the corresponding spare parts kit must be Ormazabal.
-rb/ -rc/
Driving mechanisms -l -p -s -s-pt -v -m -2lp -2lv
-rb-pt -r2c
B X - X X X - O - X X
BM O - O O O - O - O O
B2M O - - O O - - - O O
BR-A - X[1] - - - - - - X -
BR-AM O O - - - - - - O -
BR-A2M O O - - - - - - O -
AV - - - - O - - - - X
RAV - - - - O - - - - X
Circuit breaker motorisation - - - - O - - - - O
4 NC + 4 NC circuit-breaker - - - - O - - - - O
Group of auxiliary contacts 2 NO + 2 NC switch
1 NO + 1 NC earth connection O - O O - - - - O O
Opening coil - - - - O - - - - O
Opening coil + 1 NOC switch + micro-switch - O - - O - - - O O
Bistable + 1 NOC switch + micro-switch - O - - - - - - O -
-rb/- -rc/-
Protection, metering and control -l -p -s -s-pt -v -m -2lp -2lv
rb-pt r2c
ekor.sas X O - O O - O - O X
ekor.vpis X X O X X O X O X X
ekor.ivds[1] O O O O O O O O O O
ekor.rpg/ekor.rpa [3] - - - - O - - - - O
ekor.rpt / ekor.rpa [3] - O - - - - - - O -
ekor.spc O - - - - - - - O O
ekor.rci O - O O - - O - O O
ekor.rtk O O - - O - - - O O
-rb/- -rc/-
Enclosure -l -p -s -s-pt -v -m -2lp -2lv
rb-pt r2c
Metering transformers and medium voltage cables - - - - - X - - - -
access cover
Gas relief compartment X X X X X - X - X X
Cable compartment access cover X X[2] - - X - X X X X
Special cable compartment access cover O - - - - - O - O -
Medium voltage cable fixing bracket X X - - X X X X X X
Earth collector X X X X X X X X X X
-rb/- -rc/-
Interlocks and locks -l -p -s -s-pt -v -m -2lp -2lv
rb-pt r2c
Earth connection OPEN O O - O O - O - O O
Earth connection CLOSED O O - O O - O - O O
Switch OPEN O O O O O - - - O O
Circuit-breaker CLOSED O - O O - - - - O O
Earth connection CLOSED + OPEN O O - O O - O - O O
Continues on the next page
Continuation
-rb/ -rc/
Others -l -p -s -s-pt -v -m -2lp -2lv
-rb-pt -r2c
Opening the access cover - - - - - O - O - -
Control box O O O O O O O - O -
Auxiliary profiles for fastening to the floor O O O O O O O O O O
Side incoming cable box O O O O O - O - O O
Medium-voltage connection bridges - - - - - X - - - -
Voltage transformer connection braids - - - - - X - - - -
Voltage transformers - - - - - O - - - -
Current transformers - - - - - O - - - -
Female bushing-bushlink bushing converter - - - - - - - O - -
Operating sequence plate X X X X X - X - X X
Name plate X X X X X X X X X X
O Optional equipment
X Basic equipment
- Not available
[1]
Components which can only be replaced by specially qualified Ormazabal personnel.
[2]
Cable compartment access cover and compartment.
[3]
In the case of self-powered protection units, the self-power sensors are supplied on their own, for assembly when installing the
cubicles in the medium voltage cables.
9. Environmental information
cgm.3 cubicles are defined as a pressure-sealed system, it being released into the atmosphere. Extracting and
according to IEC 62271-1, which contains hexafluoride handling of SF6 must be carried out by qualified personnel,
(SF6)[16]. using a sealed piercing system.
SF6 is included in the Kyoto Protocol list of greenhouse For the usage and handling of the SF6, the indications listed
gases. SF6 has a GWP (Global Warming Potential) of 22 200 in IEC 62271-303 must be followed.
units (TAR, IPCC 2001).
Management and treatment of the rest of materials must
At the end of the product's life, the SF6 contained in it be carried out in accordance with the country’s current
must be recovered for processing and recycling, to prevent legislation.
Notes
www.ormazabal.com