FSD-211 Combination Fire Smoke Damper


APPLICATION & DESIGN
Model FSD-211 is a combination fire smoke damper with 3V style blades. This model is designed for operation and dynamic closure in emergency fire
smoke situations. It is rated for airflow and leakage in either direction. The FSD-211 may be installed horizontally or vertically (with blades running
horizontally).

DAMPER RATINGS
UL 555 Fire Resistance Rating
Fire Rating: 1 1/2 hours
Dynamic Closure Rating: Actual ratings are size dependent
Velocity: Up to 2,000 ft/min
Pressure: 6 in. wg
Height
UL 555S Leakage Rating
Leakage Class: I
Operational Rating: Actual ratings are size dependent
Velocity: Up to 2,000 ft/min
Width
Pressure: Up to 6 in. wg
Damper 5 in.
Temperature: Up to 350 F depending on actuator Location
"A"
PRODUCT DETAILS Sleeve
Frame Type: Channel Length
Frame Thickness: 16 ga
• This drawing shows a general damper configuration and is not intended to depict the
Closure Device: RRL exact configuration of all dampers in this submittal.
Closure Temperature: 250 F • Width and height furnished approximately 0.250 in. undersize.
Blade Action: Parallel • Add sleeve thickness for overall sleeved damper dimension.
• If the actuator is contained, then it does not extend more than 1.500 in. above or below
Blade Seal: Silicone the damper sleeve.
Axle/Linkage Material: Steel • Dampers with more than one section wide will be furnished with a single OCI device
Axle Bearings: 316 SS per row when the blade indicator option is selected.
• Installation instructions available at www.greenheck.com.
Sizing: Nominal

ACTUATOR INFORMATION CODES APPROVED


Model FSD-211 meets the requirements for fire
Actuator Type: 230 VAC
dampers, smoke dampers and combination fire smoke
Operating Mode: Two Position
dampers established by:
Actuator Operation: Spring Return
National Fire Protection Association:
Fail Position: Closed
NFPA Standards 80, 90A, 92, 101, 105
Time Cycle: Standard
IBC (International Building Codes)
Operating Temperature: 250 F
CSFM (California State Fire Marshal)
Velocity: 2,000 ft/min
Fire Damper Listing (3225-0981:103)
Pressure: 4 in. wg
Leakage (Smoke) Damper Listing (3230-0981:104)
NEMA Enclosure: 1
Underwriters Laboratories:
UL Classified to U.S. and Canadian safety standards
OPTIONS & ACCESSORIES Standard 555 & 555S (Listing # R13317)