Job: DAMPERS, MAPFRE MIRAFLORES, 080722


Mark: VCD-20
Model: VCD-20

VCD-20 3V Blade Volume Control Damper


APPLICATION & DESIGN
The VCD-20 is a general purpose control damper for applications as an automatic control or manual balancing damper with low to medium pressure and
velocity systems. A wide range of electric actuators are available.

DAMPER RATINGS
Pressure: Up to 5 in. wg - pressure differential
Channel Frame
Velocity: Up to 3,000 ft/min
Temperature: Up to 250 F

PRODUCT DETAILS
Frame Type: Channel
Frame Thickness: 16 ga
Material: Galvanized
Blade Type: 3V
1.25 in.
Blade Action: Opposed Height max
Blade Seal Material: N/A (typical)
Axle/Linkage Material: Steel
Axle Bearings: Synthetic
Damper Temp. Rating: 180 F
Jackshafting: No Preference
Actuator Sizing: Default SqFt Width
Ext. Shaft Length: Standard (6 in.) 5 in.
Multi-Section Fastening: Standard
Sizing: Nominal
• This drawing shows a general damper configuration and is not intended to depict the
ACTUATOR INFORMATION exact configuration of all dampers in this submittal.
• Width and height furnished approximately 0.250 in. undersize.
Actuator Type: 230 VAC • Factory supplied actuators are sized for 1,500 fpm and a fully-closed differential
Actuator Mounting: External pressure of 2 in. wc. Contact factory for actuator sizing on applications exceeding those
levels.
Actuator Location: Left Side • Installation instructions available at www.greenheck.com.
Operating Mode: TwoPosition
Actuator Operation: Spring Return
Fail Position: Closed
CODES APPROVED
IECC (International Energy Conservation Code)
NEMA Enclosure: Least Cost
compliant
Auxiliary Switches: No
The AMCA Certified Ratings Seal applies to Air
Spring Return Time: Standard
Performance
OPTIONS & ACCESSORIES
Union Label: No Preference

SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Drive Arrangement:
Actuator Mfr: Actuator Model: Actuator Qty:
Drive-
Honeywell MS4609F1210 1
1-1 9 48.000 in. 48.000 in. CC-11-1FEL-0
Act. Orientation: Standoff:
Perp Down 1.500 in.
Drive Arrangement:
Actuator Mfr: Actuator Model: Actuator Qty:
Drive-
Honeywell MS4604F1210 1
1-2 1 59.000 in. 16.000 in. CC-21-1FEL-0
Act. Orientation: Standoff:
Perp Up 1.500 in.
Drive Arrangement:
Actuator Mfr: Actuator Model: Actuator Qty:
Drive-
Honeywell MS4604F1210 1
1-3 8 6.000 in. 6.000 in. CC-11-1FEL-0
Act. Orientation: Standoff:
Parallel 1.500 in.

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 1 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: VCD-20
Model: VCD-20
ID # TAG QTY Width Height CONFIGURATION
Drive Arrangement:
Actuator Mfr: Actuator Model: Actuator Qty:
Drive-
Honeywell MS4604F1210 1
1-4 8 12.000 in. 10.000 in. CC-11-1FEL-0
Act. Orientation: Standoff:
Parallel 1.500 in.
Drive Arrangement:
Actuator Mfr: Actuator Model: Actuator Qty:
Drive-
Honeywell MS4604F1210 1
1-5 1 14.000 in. 10.000 in. CC-11-1FEL-0
Act. Orientation: Standoff:
Parallel 1.500 in.
Drive Arrangement:
Actuator Mfr: Actuator Model: Actuator Qty:
Drive-
Honeywell MS4604F1210 1
1-6 1 18.000 in. 6.000 in. CC-11-1FEL-0
Act. Orientation: Standoff:
Parallel 1.500 in.
Drive Arrangement:
Actuator Mfr: Actuator Model: Actuator Qty:
Drive-
Honeywell MS4604F1210 1
1-7 6 20.000 in. 6.000 in. CC-11-1FEL-0
Act. Orientation: Standoff:
Parallel 1.500 in.

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 2 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: VCD-20
Model: VCD-20

AMCA

AMCA Licensed for Air Performance

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance
ratings only.

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 3 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: FSD-212
Model: FSD-212

FSD-212 Combination Fire Smoke Damper


APPLICATION & DESIGN
Model FSD-212 is a combination fire smoke damper with 3V style blades. This model is designed for operation and dynamic closure in emergency fire
smoke situations. It is rated for airflow and leakage in either direction. The FSD-212 may be installed horizontally or vertically (with blades running
horizontally).

DAMPER RATINGS
UL 555 Fire Resistance Rating
Fire Rating: 1 1/2 hours
Dynamic Closure Rating: Actual ratings are size dependent
Velocity: Up to 2,000 ft/min
Pressure: 6 in. wg
UL 555S Leakage Rating
Leakage Class: II
Operational Rating: Actual ratings are size dependent Height
Velocity: Up to 2,000 ft/min
Pressure: 6 in. wg
Temperature: Up to 350 F depending on actuator
Damper

PRODUCT DETAILS Width Location


"A" 5 in.
Frame Type: Channel Sideplate
Length
Frame Thickness: 16 ga
Closure Device: RRL • This drawing shows a general damper configuration and is not intended to depict the
Closure Temperature: 165 F exact configuration of all dampers in this submittal.
Blade Action: Parallel • Width and height furnished approximately 0.250 in. undersize.
• Dampers with more than one section wide will be furnished with a single OCI device
Blade Seal: Silicone per row when the blade indicator option is selected.
Axle/Linkage Material: Steel • Installation instructions available at www.greenheck.com.
Axle Bearings: 316 SS
Sizing: Nominal CODES APPROVED
Model FSD-212 meets the requirements for fire
ACTUATOR INFORMATION dampers, smoke dampers and combination fire smoke
Actuator Type: 230 VAC dampers established by:
Operating Mode: Two Position National Fire Protection Association:
Actuator Operation: Spring Return NFPA Standards 80, 90A, 92, 101, 105
Fail Position: Closed IBC (International Building Codes)
Time Cycle: Standard CSFM (California State Fire Marshal)
Operating Temperature: 250 F Fire Damper Listing (3225-0981:103)
Velocity: 2,000 ft/min Leakage (Smoke) Damper Listing (3230-0981:104)
Pressure: 4 in. wg Underwriters Laboratories:
NEMA Enclosure: 1 UL Classified to U.S. and Canadian safety standards
Standard 555 & 555S (Listing # R13317)
OPTIONS & ACCESSORIES
Union Label: No Preference

SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-1 10 36.000 in. 36.000 in.
Honeywell MS4609F1210 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-1
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-21-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-2 8 46.000 in. 48.000 in.
Honeywell MS4620F1203 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-46

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 4 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: FSD-212
Model: FSD-212
ID # TAG QTY Width Height CONFIGURATION
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-21-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-3 2 48.000 in. 48.000 in.
Honeywell MS4620F1203 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-46
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-4 6 12.000 in. 6.000 in.
Honeywell MS4604F1210 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-1
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-5 1 12.000 in. 8.000 in.
Belimo FSTF230-S 1 Perp Down
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-2
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-6 13 12.000 in. 12.000 in.
Belimo FSTF230-S 1 Parallel
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-3
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-7 1 16.000 in. 8.000 in.
Belimo FSTF230-S 1 Perp Down
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-2
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-8 1 22.000 in. 10.000 in.
Belimo FSTF230-S 1 Perp Down
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-2
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-9 2 12.000 in. 6.000 in.
Honeywell MS4604F1210 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-1

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 5 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: FSD-212
Model: FSD-212
ID # TAG QTY Width Height CONFIGURATION
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-10 7 32.000 in. 8.000 in.
Belimo FSTF230-S 1 Perp Down
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-2
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-11 1 32.000 in. 10.000 in.
Belimo FSTF230-S 1 Perp Down
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-2
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-12 1 32.000 in. 12.000 in.
Belimo FSTF230-S 1 Parallel
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
18.000 in. 12.000 in. Vertical
CL-3
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Right Side
No MLS-11-1FER-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
2-13 2 25.000 in. 25.000 in.
Honeywell MS4604F1210 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-1

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 6 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: FSD-212
Model: FSD-212

AMCA

AMCA Licensed for Air Performance.

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance
ratings only.

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 7 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: FSD-II HUMO
Model: SMD-202

SMD-202 Smoke Damper


APPLICATION & DESIGN
Model SMD-202 is a leakage rated modulating smoke damper with 3V style blades. The SMD-202 has been qualified to 2,000 ft/min and 6 in. wg for
operational closure in emergency smoke control situations. Model SMD-202 may be installed horizontally or vertically (with blades running horizontally)
and is rated for airflow and leakage in either direction.

DAMPER RATINGS
Ratings
LeakageClass: II
Operational Ratings
Velocity: Up to 2,000 ft/min
Pressure: 6 in. wg
Temperature: Up to 350 F
Height

PRODUCT DETAILS
Frame Type: Channel
Frame Thickness: 16 ga
Damper
Blade Action: Parallel Width Location
Blade Seal: Silicone "A" 5 in.
Sideplate
Blade Indicator: None Length
Axle/Linkage Material: Steel
Axle Bearings: 316 SS • This drawing shows a general damper configuration and is not intended to depict the
Sizing: Nominal exact configuration of all dampers in this submittal.
• Width and height furnished approximately 0.250 in. undersize.
• Installation instructions available at www.greenheck.com.
ACTUATOR INFORMATION
Actuator Type: 230 VAC CODES APPROVED
Operating Mode: Two Position Model SMD-202 meets the requirements for smoke
Actuator Operation: Spring Return dampers established by:
Fail Position: Closed National Fire Protection Association:
Time Cycle: Standard NFPA Standards 90A, 92, 101, 105
Operating Temperature: 250 F IBC (International Building Codes)
Velocity: 2,000 ft/min CSFM (California State Fire Marshal)
Pressure: 4 in. wg Leakage (Smoke) Damper Listing (3230-0981:104)
NEMA Enclosure: 1 Underwriters Laboratories:
UL Classified to U.S. and Canadian safety standards
OPTIONS & ACCESSORIES Standard 555S (Listing # R13317)
Union Label: No Preference

SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Left Side
No MLS-21-1FEL-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
3-1 2 40.000 in. 40.000 in.
Honeywell MS4620F1203 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-42
Compact Drive Arrangement:
Actuator Mounting: Actuator Location:
Configuration: Drive-
External Left Side
No MLS-21-1FEL-1
Actuator Mfr: Actuator Model: Actuator Qty: Act. Orientation:
3-2 2 42.000 in. 42.000 in.
Honeywell MS4620F1203 1 Perp Up
Component
Sideplate Length: Damper Location: Mounting:
Location Code:
12.000 in. 6.188 in. Vertical
CL-42

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 8 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: FSD-II HUMO
Model: SMD-202

AMCA

AMCA Licensed for Air Performance.

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Programs. The AMCA Certified Ratings Seal applies to air performance
ratings only.

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 9 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: BR-30
Model: BR-30

BR-30 No Flange Barometric Relief Damper


APPLICATION & DESIGN
The BR-30 is an eccentrically pivoted backdraft damper for low velocity systems. This model is a vertical mounted damper designed to allow horizontal
airflow and prevent reverse airflow.

DAMPER RATINGS
Max. Pressure: 2 in. wg
Max. Velocity: Up to 2,000 ft/min
Temperature: 180 F

PRODUCT DETAILS
Frame: Galvanized
Frame Thickness: 16
Blade: Aluminum
Blade Seal Material: TPE
Blade Thickness: 0.063 in.
Axle Material: Plated Steel
Axle Bearings: Galvanized Ball
Start Open Pressure: 0.05 in. wg
Linkage Material: Galvanized Steel
Jamb Seal Material: None
Operation: Counterbalanced
Sizing: Nominal

OPTIONS & ACCESSORIES


Clean Wrap: No
Union Label: No Preference • This drawing shows a general damper configuration and is not intended to depict the
exact configuration of all dampers in this submittal.
• Width and Height furnished approximately 0.25 in. under size.
• Installation instructions available at www.greenheck.com.
• Pressure drop data applies to units with minimum start open pressure. Higher start
open pressure will result in different performance.

SUMMARY
SECTIONS SECTIONS SHIP
ID # TAG QTY W (in.) H (in.)
WIDE HIGH SECTIONS
4-1 4 30.000 30.000 1 1 1

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 10 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: WD-300
Model: WD-300

WD-300 Backdraft Damper


APPLICATION & DESIGN
The WD-300 is a vertical mount backdraft damper for horizontal airflow. The dampers are opened by air pressure differential and closed by gravity.

DAMPER RATINGS
Max. Pressure: Up to 2 in. wg - pressure differential
Max. Velocity: Up to 2,500 ft/min
Temperature: 180 F

PRODUCT DETAILS
Frame: Galvanized Steel
Frame Thickness: 18 ga
Blade: Aluminum
Blade Seal Material: Vinyl
Blade Thickness: 0.025 in. - 0.032 in.
Axle Material: Steel
Axle Bearings: Synthetic
Linkage Material: Galvanized
Actuator Voltage: None
Sizing: Nominal

OPTIONS & ACCESSORIES


Clean Wrap: No
Union Label: No Preference
• This drawing shows a general damper configuration and is not intended to depict the
exact configuration of all dampers in this submittal.
• Width and Height furnished approximately 0.125 in. under size.
• Installation instructions available at www.greenheck.com.
• Pressure drop data applies to units with minimum start open pressure. Higher start
open pressure will result in different performance.

SUMMARY
SECTIONS SECTIONS SHIP
ID # TAG QTY W (in.) H (in.)
WIDE HIGH SECTIONS
5-1 15 6.000 6.000 1 1 1
5-2 1 6.000 10.000 1 1 1
5-3 8 12.000 10.000 1 1 1
5-4 1 14.000 6.000 1 1 1
5-5 1 18.000 6.000 1 1 1
5-6 6 20.000 6.000 1 1 1
5-7 1 6.000 8.000 1 1 1
5-8 2 6.000 6.000 1 1 1
5-9 1 8.000 6.000 1 1 1

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 11 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: DFD-150
Model: DFD-150

DFD-150 DFD-150: 1 1/2 hour dynamic rated fire damper


APPLICATION & DESIGN
Model DFD-150 is approved for use in walls, floors and partitions with fire resistance ratings less than 3 hours. UL 555 classifies dynamic rated fire
dampers for use in HVAC systems that are operational in the event of fire.
Damper
DAMPER RATINGS
Fire Rating: 1½ hours
Dynamic Closure Rating
Maximum Velocity: 4,000 ft/min vertical mount only,
up to 24 in. x 24 in.;
2,000 ft/min vertical or horizontal mount
on all sizes
MaximumPressure: 4 in. wg Height
PRODUCT DETAILS
Frame: Galvanized Steel
Frame Depth: 3.688
Blade: Galvanized Steel
Closure Device: Fusible Link
Closure Temp: 165 F Width
Velocity: 2,000 ft/min
Sizing: Nominal

OPTIONS & ACCESSORIES • This drawing shows a general damper configuration and is not intended to depict the exact
configuration of all dampers in this submittal.
Transition: A • Damper is furnished approximately 0.250 in. undersize.
Union Label: No Preference • Installation instructions available at www.greenheck.com.

CODES APPROVED
This model meets the requirements for fire dampers established by:
• UL Classfied (U.S. and Canada)
Standard UL 555 (Listing #R13317)
• National Fire Protection Association
NFPA Standard 80,90A & 101
• IBC: International Building Codes
• California State Fire Marshal: CSFM listing # 3225-981:102

SUMMARY
ID # TAG QTY Width Height CONFIGURATION
Sections Wide: Sections High: Blade Stack: Mounting:
6-1 1 6.000 in. 10.000 in.
1 1 1.530 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-2 1 10.000 in. 12.000 in.
1 1 1.700 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-3 2 14.000 in. 6.000 in.
1 1 1.020 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-4 1 16.000 in. 8.000 in.
1 1 1.360 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-5 1 20.000 in. 8.000 in.
1 1 1.360 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-6 1 22.000 in. 47.000 in.
1 2 3.230 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-7 2 25.000 in. 25.000 in.
1 1 3.400 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-8 1 36.000 in. 12.000 in.
1 1 1.700 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-9 2 40.000 in. 16.000 in.
2 1 2.210 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-10 1 10.000 in. 20.000 in.
1 1 2.720 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-11 1 20.000 in. 12.000 in.
1 1 1.700 in. Vertical

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 12 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722
Mark: DFD-150
Model: DFD-150
ID # TAG QTY Width Height CONFIGURATION
Sections Wide: Sections High: Blade Stack: Mounting:
6-12 2 24.000 in. 18.000 in.
1 1 2.550 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-13 3 40.000 in. 40.000 in.
2 2 2.720 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-14 3 79.000 in. 23.500 in.
3 1 3.230 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-15 4 75.000 in. 25.500 in.
3 1 3.570 in. Vertical
Sections Wide: Sections High: Blade Stack: Mounting:
6-16 3 32.000 in. 26.300 in.
1 1 3.570 in. Vertical

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 13 of 14
Printed Date: 07/11/2022
Job: DAMPERS, MAPFRE MIRAFLORES, 080722

Damper Drive Arrangements Job Summary -Start-

Drive Arrangement: Drive-CC-11-1FEL-0

Drive Arrangement: Drive-CC-21-1FEL-0

Drive Arrangement: Drive-MLS-11-1FER-1

Drive Arrangement: Drive-MLS-21-1FEL-1

Drive Arrangement: Drive-MLS-21-1FER-1

Damper Drive Arrangements Job Summary -End-

D:\DAMPERS, MAPFRE MIRAFLORES, 080722.gfcj


CAPS 4.38.1089 Generated by: eduhar@primelines-hvac.com Page 14 of 14
Model VCD-20
Control Damper 3V Blade
Application
The VCD-20 series is a general purpose control damper for applications as an automatic control or manual balancing
damper with low to medium pressure and velocity systems.
Damper Ratings
Pressure: Up to 5 in. wg (1.2 kPa) - pressure
differential
Velocity: Up to 3,000 fpm (15.2 m/s)
Temperature: -40°F to 250°F (-40°C to 121°C). Consult
factory for higher temperatures.

Size Limitations
Minimum Maximum Size
WxH
Size Single Section Multiple Section
Inches 6x6 48 x 74 Unlimited
mm 152 x 152 1219 x 1880 Unlimited

Flange Options
5 in. 5 in. 5 in.

*W & H dimension furnished approximately 1⁄4 in. (6mm) undersize.

Construction Standard Optional


Frame Material Galvanized Steel 304SS
Frame Thickness 16 ga. (1.5mm) 12 ga. (2.7mm)*
1 1/2 in. (Typical)
5 in. x 1 in. Single flange,
Frame Type (127mm x 25mm) reversed flange,
Channel double flange Single Flange Reversed Flange Double Flange
Blade Material Galvanized Steel 304SS * Shown with optional internally mounted actuator.
Blade Thickness 16 ga. (1.5mm) -
Blade Type 3V - Blade Operation
11/4 in.
Blade Operation Opposed Parallel max.
11/4 in.
max.
(typical) (typical)
Axle Material 1
⁄2 in. dia. Plated Steel 316SS
Axle Bearings Synthetic 316SS
Linkage Material Plated Steel 316SS
Baked Enamel,
Paint Finishes Mill Finish Hi Pro Polyester,
Industrial Epoxy
*When 12 ga. frame is selected and the damper height is less than 17
inches, low profile top and bottom frame members are utilized. These low
5 in. 5 in.
profile frame members will be made from 16 ga. material.
Parallel Blades Opposed Blades

Notes:
• Low profile head and sill are used on sizes less than 17 in. (432mm) high
• Linkage concealed in the frame
• Electric actuator and manual quadrant available. Factory supplied actuators are sized for 1500 fpm (7m/s) and fully
closed differential pressure of 2 in. wg (.5 kPa). contact factory for actuator sizing on applications exceeding those
limits.
• Blades must be horizontal for either horizontal or vertical mount. If you need vertical blades, see VCD-23V model.

Installation instructions available at www.greenheck.com.


Pressure Drop Data VCD-20
This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations
shown. All data has been corrected to represent standard air at a density of .075 lb/ft3(1.201 kg/m3).
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information along
with an analysis of other system influences should be used to estimate actual pressure losses for a damper installed in a
given HVAC system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test
configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the
damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop
than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of extremely
high entrance and exit losses due to the sudden changes of area in the system.

5D 6D

5D 6D

5D 6D
Figure 5.3
5D

D 4 (W) (H)
5D 3.14

5D
D 4 (W) (H)
3.14
D 4 (W) (H)
3.14

Figure 5.2

Figure 5.5
AMCA Certified Pressure Drop Data VCD-20
5D Greenheck
6D Fan Corporation certifies that the model VCD-
20 shown herein is licensed to bear the AMCA Seal. The
ratings shown are based on tests and procedures performed
in accordance with AMCA Publication 511 and comply with
the requirements of the AMCA Certified Ratings Programs.
The AMCA Certified Ratings Seal applies to Air Performance
ratings.
AMCA 5.2
5D

D 4 (W) (H)
3.14

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) Velocity (fpm) Velocity (fpm)
(in. wg) (in. wg) (in. wg)
500 0.01 500 0.01 500 0.01 500 0.01 500 0.01
1000 0.05 1000 0.03 1000 0.02 1000 0.04 1000 0.03
1500 0.11 1500 0.06 1500 0.05 1500 0.08 1500 0.07
2000 0.19 2000 0.10 2000 0.09 2000 0.15 2000 0.12
2500 0.29 2500 0.16 2500 0.14 2500 0.22 2500 0.18
3000 0.41 3000 0.23 3000 0.19 3000 0.32 3000 0.26
3500 0.55 3500 0.30 3500 0.27 3500 0.43 3500 0.36
4000 0.72 4000 0.40 4000 0.35 4000 0.56 4000 0.47

AMCA 5.3
5D 6D

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) Velocity (fpm) Velocity (fpm)
(in. wg) (in. wg) (in. wg)
5D
500 0.01 500 0.01 500 0.01 500 0.01 500 0.01
1000 0.03 1000 0.02 1000 0.02 1000 0.03 1000 0.03
1500 5D 0.08 6D 1500 0.04 D 41500
(W) (H) 0.03 1500 0.07 1500 0.06
2000 0.13 2000 0.07 3.14
2000 0.06 2000 0.12 2000 0.10
2500 0.20 2500 0.11 2500 0.09 2500 0.18 2500 0.16
3000 0.29 3000 0.16 3000 0.13 3000 0.26 3000 0.22
3500 0.40 3500 0.21 3500 0.19 3500 0.36 3500 0.30
4000 5D 0.51 4000 0.28 4000 0.25 4000 0.46 4000 0.39

D 4 (W) (H)
3.14

AMCA 5.5

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) Velocity (fpm) Velocity (fpm)
(in. wg) (in. wg) (in. wg)
500 0.03 500 0.03 500 0.03 500 0.03 500 0.03
1000 0.13 1000 0.12 1000 0.12 1000 0.12 1000 0.12
1500 0.30 1500 0.26 1500 0.28 1500 0.27 1500 0.28
2000 0.53 2000 0.47 2000 0.50 2000 0.47 2000 0.49
2500 0.82 2500 0.75 2500 0.78 2500 0.75 2500 0.77
3000 1.19 3000 1.04 3000 1.12 3000 1.07 3000 1.12
3500 1.62 3500 1.41 3500 1.53 3500 1.45 3500 1.53
4000 2.10 4000 1.90 4000 2.00 4000 1.91 4000 2.01
.4

St
.3

.2

Leakage Data VCD-20


1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 150

Leakage testing was conducted in accordance with AMCA Standard 500-D and is expressed as cfm/ft2 of damper face
area. All data has been corrected to represent standard air at a(cfm/ft
Air Leakage density
2) of 0.075 lb/ft3 (1.204 kg/m3).

VCD-20
15.0

10.0
9.0
8.0
7.0

Static Pressure Difference ( in. wg)


6.0
5.0

4.0

3.0

2.0

1.0
.9
.8
.7
.6
.5

.4

.3

.2

1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 100 150

Air Leakage (cfm/ft2 )

Velocity Limitations

74

60
Damper Height (in.)

48

3000 2500 2000


36 fpm fpm fpm

24

12

0
0 12 24 36 48
Damper Width (in.)
Space Envelopes VCD-20
Space Envelopes
On dampers less than 18 in. (457mm) high, actuators may also require clearances above and/or below the damper
frame. “B” and “T” dimensions are worst case clearance requirements for some dampers less than 18 in.
(457mm) high. All damper sizes under 18 in. (457mm) high do not require these worst case clearances. If space
availability above or below the damper is limited, each damper size should be individually evaluated.
D

T
Damper
frame

Optional
Jackshaft

Height T B D
Actuator Type/Model
Inches (mm) Inches (mm)
>6 to <10 0 123⁄4 6
AFBUP (-S) and FSNF Series, Belimo
>10 to <18 0 2 6
MSxx20 Series, Honeywell
>18 0 0 10
>6 to <10 0 31⁄2 6
FSLF, LF and TFB Series, Belimo
>10 0 0 6
>6 to <9 0 43⁄4 6
MSxx04 & MSxx09 Series, Honeywell
>9 0 0 6
>6 to <10 0 12 ⁄43
6
MS75xx Series, Honeywell >10 to <18 0 7 6
>18 0 0 6

This drawing depicts the worse case clearance requirements for an actuator with a jackshaft.
1 1/4 in. (32mm)
max.

Internal mount only


A B C
Actuator model
All except - EFB & 7 3⁄4 in 3 3⁄4 in 5 3⁄8 in A
EFCX Series (197 mm) (95 mm) (136.5 mm)
EFB & EFCX Series 8 1⁄2 in 6 in 8 1⁄2 in B
(216 mm) (152mm) (216 mm)

Actuator

Mounting
• External - includes extension pin (standoff bracket
optional) C

• External kit - actuator and all mounting hardware


5 in.
• Internal - blade lever (127mm)
Specifications

Multi-Section Assembly
Dampers larger than the maximum single section size, will be made up of a multiple of equal size sections. Multiple
section dampers can be jackshafted together so that all sections operate together as shown below.
NOTE: Dampers larger than 48 in. x 74 in.
(1219mm x 1880mm) are not intended to be structurally self supporting. Additional horizontal bracing is
recommended to support the weight of the damper and vertical bracing should be installed as required to hold
against system pressure.

Refer to IOM document 463384 for


structural support requirements on
multi-section assemblies.

Specifications
Control dampers meeting the following specifications shall be furnished and installed where shown on plans and/or as
described in schedules.
Damper blades shall be 16 ga. (1.5mm) galvanized steel 3V type with three longitudinal grooves for reinforcement.
Blades shall be completely symmetrical relative to their axle pivot point, presenting identical resistance to airflow and
operation in either direction through the damper (blades that are non-symmetrical relative to their axle pivot point or
utilize blade stops larger than 1⁄2 in. [13mm] are unacceptable). Linkage shall be blade-to-blade concealed in jamb (out of
the airstream) to protect linkage and reduce pressure drop and noise.
Damper frame shall be 16 ga. (1.5mm) galvanized steel formed into a structural hat channel shape with reinforced
corners to meet 11 ga. (3.1mm) criteria. Bearings shall be corrosion resistant, permanently lubricated, synthetic (acetal)
sleeve type, rotating in extruded holes in the damper frame for maximum service. Axles shall be square and positively
locked into the damper blade.
The Damper manufacturer’s submittal data shall certify all air performance pressure drop data is licensed in accordance
with the AMCA Certified Ratings Program for Test Figures 5.2, 5.3 and 5.5. Damper air performance data shall be
developed in accordance with the latest edition of AMCA Standard 500-D.
Basis of design is model VCD-20.

Copyright © 2021 Greenheck Fan Corporation


VCD-20 Rev. 21 May 2021
Drive Arrangement Definition
On multi-blade dampers (except vertical blade and Face & Bypass), they are given a drive arrangement code
that helps describe the construction of the damper. The following breaks down what each number and letter
represents.

22-2FEL- 2
1 2 3 4 5 6 7
1 Number of sections wide

2 Number of sections high


Jackshaft

Damper Height
3 Number of actuators or manual quadrants

4 Who supplies the actuators or manual quadrants


F - Factory
Actuator or
C - Customer Supplied (field mounted) Manual Quadrant
5 Actuator or manual quadrant mounting
E - External
I - Internal
B - Both internal and external

6 Actuator or manual quadrant location


L - Left hand drive
R - Right hand drive
B - Both right and left Damper Width

7 Number of jackshafts

Vertical blade and face & bypass dampers are given a configuration ID number that helps describe the
construction of the damper. See the following examples:

Model Drive Arrangement


Prefix
AMD-23, 33, 42 AMD
AMD-42V VB
DFD-210, 230; DFDAF-310;
MLS
DFDAF-330; SEDFD-210
FBH & FBV FB
FSD, OFSD, CFSD, SMD, SEFSD,
SSFSD, SESMD, SSSMD series MLS
(except vertical blade models)
FSD-311V, SMD-301V VB
GFSD series GFSD
ICD series CC
IMO series MLS
MBD-15 & VCD series (except CC
vertical blade models)
VCD-xxV (vertical blade models) VB
Jump-over Bracket
The function of the jump-over bracket is to attach multiple damper sections together.

Jump-over Jackshaft

ITEM QTY PART NO. DESCRIPTION


1 1 DAMPER
2 1 913119 BRACKET JUMP-OVER SS
3 4 415575 NUT,SPNLK 1/4-20 18-8
4 4 416103 CS,1/4-20x1.5 HH,316SS

C
1

2
4
Model FSD-212
Combination Fire Smoke Damper
Application
Steel 3V Blades
Model FSD-212 is a combination fire smoke damper with
3V style blades. This model is designed for operation UL 555S Leakage Class II
and dynamic closure in emergency fire smoke situations. UL 555 1 ⁄2 Hour Fire Resistance Rating
1
It is rated for airflow and leakage in either direction. The
FSD-212 may be installed vertically (with blades running
horizontal) or horizontally.

Ratings
UL 555 Fire Resistance Rating
Fire Rating: 11⁄2 hours
Dynamic Closure Rating: Actual ratings are size
dependent
Velocity: Up to 2,000 fpm (10.2 m/s)
Pressure: Up to 6 in. wg (1.5 kPa)
UL 555S Leakage Rating
Leakage Class: II
Operational Rating: Actual ratings are size
dependent
Velocity: Up to 2,000 fpm (10.2 m/s)
Pressure: Up to 6 in. wg (1.5 kPa)
Width and Height dimensions furnished approximately 1⁄4 in.
Temperature: Up to 350°F (177°C) - depending (6mm) undersize. Add sleeve thickness for overall sleeved
upon the actuator damper dimension.

Construction Standard Optional


Frame Material Galvanized steel -
Frame Material Model FSD-212 meets the requirements for fire
16 ga. (1.5mm) - dampers, smoke dampers and combination fire smoke
Thickness
dampers established by:
5 in. x 1in. National Fire Protection Association
Frame Type (127mm x 25mm) -
NFPA Standards 80, 90A, 92, 101 & 105
hat channel
IBC International Building Codes
Blade Material Galvanized steel -
CSFM California State Fire Marshal
Blade Material
16 ga. (1.5mm) - Fire Damper Listing (#3225-0981:103)
Thickness
Blade Type 3V - Leakage (Smoke) Damper Listing (#3230-0981:104)

Plated steel out of airstream,


Linkage -
concealed in jamb See complete marking on
Axle Bearings 316SS - product.
Axle Material Plated steel - UL 555 and UL 555S
Blade Seals Silicone - Classification R13317
Jamb Seals Stainless Steel -
Maximum Size
RRL/OCI, Minimum
Closure Device RRL TOR, WxH Single Multiple Section
Size
Fusible Link Section Horizontal Vertical
212°F (100°C), 4 in. wg (1 kPa) pressure
250°F (121°C), Inches 6x6 32 x 50 or 36 x 48 144 x 96 128 x 100
Closure Temperature 165°F (74°C)
286°F (141°C),
350°F (177°C) 813 x 1270 or
mm 152 x 152 3658 x 2438 3251 x 2540
914 x 1219
Features: 6 in. wg (1.5 kPa) pressure
• Frames are constructed with reinforced corners. Low Inches 6x6 36 x 48 144 x 96 128 x 96
profile head and sill are used on sizes less than 17 in. mm 152 x 152 914 x 1219 3658 x 2438 3251 x 2438
high (432mm).
Installation instructions available at www.greenheck.com.
Options FSD-212
• Factory mounted accessories • Sealed transitions and sleeves
- Quick connect breakaway connections • Security bars
- Access doors
• Smoke detectors
• Greenheck test switches (GTS-1, -2, -3, -4)
• Transitions: R, C, O
• Momentary test switch
• POC retaining angles
• RRL/OCI (Open closed indication switches)
• TOR (Temperature limited override)

Pressure Drop Data


This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations
shown. All data has been corrected to represent standard air at a density of .075 lb/ft3(1.201 kg/m3).
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information
along with an analysis of other system influences should be used to estimate actual pressure losses for a damper
installed in a given HVAC system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test
configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the
damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop
than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of
extremely high entrance and exit losses due to the sudden changes of area in the system.

5D 6D

5D 6D

Figure 5.3 5D 6D

5D

D 4 (W) (H)
5D 3.14

5D
D 4 (W) (H)
3.14
D 4 (W) (H)
3.14

Figure 5.2

Figure 5.5
Pressure Drop FSD-212
AMCA Figure 5.2 5D

D 4 (W) (H)
3.14

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.04 500 0.02 500 0.01 500 0.01 500 0.03
1000 0.14 1000 0.07 1000 0.04 1000 0.06 1000 0.10
1500 0.31 1500 0.16 1500 0.09 1500 0.13 1500 0.23
2000 0.55 2000 0.29 2000 0.16 2000 0.23 2000 0.41
2500 0.86 2500 0.45 2500 0.25 2500 0.36 2500 0.63
3000 1.24 3000 0.65 3000 0.36 3000 0.52 3000 0.91
3500 1.69 3500 0.89 3500 0.49 3500 0.70 3500 1.24
4000 2.20 4000 1.16 4000 0.64 4000 0.92 4000 1.62

AMCA Figure 5.3 5D 6D

5D 6D

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) 5D Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.02 500 0.01 500 0.01 500 0.01 500 0.02
1000 0.09 1000 0.04 1000 0.03 1000 0.04 1000 0.07
1500 0.20 1500 0.09 1500 0.06 D 1500 4 (W) (H)0.10 1500 0.16
2000 0.36 2000 0.16 5D 2000 0.11 2000 3.14 0.17 2000 0.29
2500 0.56 2500 0.25 2500 0.17 2500 0.27 2500 0.45
3000 0.81 3000 0.35 3000 0.24 3000 0.39 3000 0.64
3500 1.10 3500 0.48 3500 0.33 3500
4 (W) (H) 0.53 3500 0.88
4000 1.44 4000 0.63 4000 0.42
D 4000 0.70 4000 1.14
3.14

AMCA Figure 5.5

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.06 500 0.03 500 0.03 500 0.03 500 0.04
1000 0.22 1000 0.14 1000 0.12 1000 0.13 1000 0.17
1500 0.50 1500 0.31 1500 0.26 1500 0.30 1500 0.38
2000 0.89 2000 0.54 2000 0.46 2000 0.53 2000 0.67
2500 1.39 2500 0.85 2500 0.73 2500 0.83 2500 1.04
3000 2.00 3000 1.22 3000 1.05 3000 1.19 3000 1.50
3500 2.72 3500 1.66 3500 1.42 3500 1.62 3500 2.05
4000 3.55 4000 2.17 4000 1.86 4000 2.11 4000 2.67

Greenheck Fan Corporation certifies that the


model FSD-212 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to
air performance ratings only.
Sleeve Length

Application Data FSD-212


Actuators and Accessories T*

T*
Space Envelopes
S
Externally mounted actuators always require space
outside of the damper sleeve. The “S” dimension
illustrates the clearance required for various
available actuators.
On dampers less than 18 in. (457mm) high,
actuators may also require clearances above and/
or below the sleeve. “B” and “T” dimensions are
worst case clearance requirements for some
dampers less than 18 in. (457 mm) high. All
dampers 18 in. (457mm) or more in height, do
not require these worst case clearances. If space
availability above or below the damper sleeve is
limited, each damper size should be individually
evaluated. B*

B*

B* T* S
With With Piggyback
Actuator Type/Model
RRL, RRL/OCI, or RRL, RRL/OCI, or
No Yes
TOR TOR
120 Volt AC
FSLF120 (-S) Belimo 7 ⁄16 in (195mm)
11
0 6 in. (152mm) NA
FSNF120 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
FSTF120 (-S) Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
MS4104 Series Honeywell 1
⁄2 in. (13mm) 8 ⁄2 in (216mm)
1
6 in. (152mm) NA
MS4X09 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS4120 Series Honeywell 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229mm)
24 Volt AC
FSAF24 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) NA
FSTF24 (-S) Belimo 7 ⁄16 in (195mm)
11 1
⁄2 in. (13mm) 6 in. (152mm) NA
FSLF24-S Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
FSNF24 (-S) Belimo 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229mm)
MS8104 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS8120 Series Honeywell 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229m)
230 Volt AC
FSLF230-S Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
FSNF230-S Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
FSTF230-S Belimo 711⁄16 in (195mm) 1
⁄2 in. (13mm) 6 in. (152mm) NA
MS4604 Series Honeywell 1
⁄2 in. (13mm) 8 ⁄2 in (216mm)
1
6 in. (152mm) NA
MS4X09 Series Honeywell 1
⁄2 in. (13mm) 81⁄2 in (216mm) 6 in. (152mm) NA
MS4620 Series Honeywell 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229mm)
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in.
Application Data FSD-212
Damper Sleeve Dimensional Data
The drawings below and corresponding table show the position of the FSD-212 damper when mounted in a factory
sleeve. The standard mounting locations provide enough space for the mounting of actuators, controls and allow space
for installation of retaining angles and duct connections.
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be
positioned at other locations within a range of 6 in. (152mm) to 16 in. (406mm) for the "A" dimension.
Sleeve 1½ in. (38mm)
maximum blade
clearance "A" Dimension
in. (mm)
Sleeve Std Sleeve Max Sideplate
Sleeve
3¾ in.
(95mm)
All Dampers (RRL) 7 ⁄16 in. (183)
3
16 (406) 63⁄16 (157)
When Height is 11 in.
5³/8 in.
(279) or less with RRL, 12 (305) 16 (406) 12 (305)
(137mm) RRL/OCI, or TOR
Varies due to
height NOTE: Entire damper frame is not required to be installed within the wall. The damper
blades, when closed should be contained within the wall.
11/2 in. max.

Sideplate
5 in.
A (127mm)

Sleeve Length

3 3/4 in.

6 in.

Varies
5 3/8 in.

5 in.
A 5 in.
A
Sideplate
Length** Sleeve Length

Damper Sizing Information


Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal
size. The following figures show maximum damper section size and assembly configurations for multi-section dampers.

Double Section
Single Section

50 in.
(1270mm)
50 in. 50 in.
(1270mm) (1270mm)

32 in. (813mm)
64 in. (1626mm)
32 in. (813mm)
Transitioned Damper Dimensions FSD-212
When a combination fire smoke damper is being used in conjunction with round or oval ductwork, the FSD-212 can be
supplied in a factory sleeve with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the
duct dimensions. Drawings below show overall damper size.
D* + 2 in. (51mm) +T s
W* + 2 in. (51mm)+Ts
W* + 2 in. (51mm)+Ts

D* + 2 in. (51mm)+Ts
H* + 2 in. (51mm)+T s H* + 2 in. (51mm)+Ts
2 1/8 in. H*
2 1/8 in. H* (54mm)
2 1/8 in. (54mm)
(54mm)

W*
W*
16 in. D* 16 in. 16 in.
(406mm) (406mm) (406mm)
Minimum Minimum Minimum

TYPE R TYPE O TYPE C


*These dimensions are furnished approximately 1⁄4 in. (6mm)
undersize, except round and oval dimensions which are
approximately 1⁄8 in.(3mm) undersize.
Ts = (2)(Sleeve Thickness)

Specifications
Combination Fire Smoke Dampers meeting the following in the damper frame. Blade edge seals shall be silicone
specifications shall be furnished and installed where rubber designed to inflate and provide a tighter seal
shown on plans and/or as described in schedules. against leakage as pressure on either side of the damper
Dampers shall meet the requirements of NFPA 80, increases. Jamb seals shall be stainless steel compression
90A, 92, 101 & 105 and further shall be tested, rated type. Blades shall be symmetrical relative to their axle
and labeled in accordance with the latest edition of UL pivot point, presenting identical resistance to airflow in
Standards 555 and 555S. Dampers shall have a UL555 either direction or pressure on either side of the damper.
fire rating of 1½ hours and be of low leakage design The Damper Manufacturer's submittal data shall certify
qualified to UL 555S Leakage Class II. all air performance pressure drop data is licensed in
Each damper /actuator combination shall have a UL555S accordance with the AMCA Certified Ratings Program for
elevated temperature rating of 250°F (121°C) minimum Test Figures 5.2, 5.3, and 5.5. Damper air performance
and shall be operational and dynamic rated to operate data shall be developed in accordance with the latest
at maximum design air flow at its installed location. Each edition of AMCA Standard 500-D. Dampers shall be
damper shall be supplied with an appropriate actuator labeled with the AMCA Air Performance Seal.
installed by the damper manufacturer at the time of Damper must be rated for mounting vertically (with blades
damper fabrication. Damper actuator shall be (specifier running horizontal) or horizontally and be UL 555S rated
select one of the following) electric type for 120, 24, or for leakage and airflow in either direction through the
230 volt operation. damper. Each damper shall be supplied with a 165°F
Damper blades shall be 16 ga. (1.5mm) galvanized steel (74°C) RRL.
3V type with three longitudinal grooves for reinforcement. The basis of design is Model FSD-212.
Damper frame shall be galvanized steel formed into a
structural hat channel shape with reinforced corners.
Bearings shall be 316SS type rotating in extruded holes

Copyright © 2020 Greenheck Corporation


FSD-212 Rev. 18 October 2020
SMD-202
Smoke Dampers
Application Steel 3V Blades
Model SMD-202 is a leakage rated smoke damper with 3V style UL 555S Leakage Class II
blades. The SMD-202 has been qualified to 2,000 fpm (10.2 m/s)
and 6 in. wg (1.5 kPa) for operational closure in emergency smoke
control situations. Model SMD-202 may be installed vertically
(with blades running horizontally) or horizontally and is rated for
airflow and leakage in either direction.
Ratings
Leakage Class: II
Operational Rating
Maximum Velocity: 2,000 fpm (10.2 m/s)
Maximum Pressure: 6 in. wg (1.5 kPa)
Maximum Temperature: 350°F (177°C)

Construction Standard
Frame Material Galvanized steel
Frame Material Thickness 16 ga. (1.5mm) LH

5 in. x 1 in. (127mm x 25mm)


Frame Type
hat channel RH
Blade Material Galvanized steel
Blade Material Thickness 16 ga. (1.5mm)  &H dimensions furnished approximately 1⁄4 in. (6mm) undersize.
W
Blade Type 3V (Add sleeve thickness for overall sleeved damper dimension)
Actuator is shown mounted internal left.
Plated steel out of airstream,
Linkage
concealed in jamb
Axle Bearings 316SS Model SMD-202 meets the requirements for
Axle Material Plated steel smoke dampers established by:
Blade Seals Silicone National Fire Protection Association
Jamb Seals Stainless Steel NFPA Standards 90A, 92, 101 & 105
IBC International Building Codes
Size Limitations
CSFM California State Fire Marshal
Maximum Size
Leakage (Smoke) Damper Listing
WxH Minimum Size Single Multiple (#3230-0981:104)
Section Section
4 in. wg (1 kPa) pressure
32 x 50 or 144 x 100 or
Inches 6x6
36 x 48 288 x 50
813 x1270 or 3658 x 2540 or
mm 152 x 152
914 x 1219 7315 x 1270
See complete marking on
6 in. wg (1.5 kPa) pressure product.
Inches 6x6 36 x 48 144 x 48 UL 555S Classification
mm 152 x 152 914 x 1219 3658 x 1219 R13317

Features:
• Frames are constructed with reinforced corners. Low
profile head and sill are used on sizes less than 17 in.
high (432mm).
• Blades are reinforced with 3 longitudinal structurally
designed vee's.
• Actuators: Electric Installation instruction available at www.greenheck.com
Options & Pressure Drop Data SMD-202
Options for SMD-202:
• Factory mounted accessories • Sealed transitions and sleeves
- Quick connect breakaway connections
- Access doors • Security bars
• Test switches (GTS-3 & GTS-4) • Smoke detectors
• Momentary test switch • Transitions: R, C, O
• POC retaining angles
• OCI (Open closed indication switches)

Pressure Drop Data


This pressure drop testing was conducted in accordance with AMCA Standard 500-D using the three configurations
shown. All data has been corrected to represent standard air at a density of .075 lb/ft3 (1.201 kg/m3).
Actual pressure drop found in any HVAC system is a combination of many factors. This pressure drop information
along with an analysis of other system influences should be used to estimate actual pressure losses for a damper
installed in a given HVAC system.
AMCA Test Figures
Figure 5.3 Illustrates a fully ducted damper. This configuration has the lowest pressure drop of the three test
configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the
damper.
Figure 5.2 Illustrates a ducted damper exhausting air into an open area. This configuration has a lower pressure drop
than Figure 5.5 because entrance losses are minimized by a straight duct run upstream of the damper.
Figure 5.5 Illustrates a plenum mounted damper. This configuration has the highest pressure drop because of
extremely high entrance and exit losses due to the sudden changes of area in the system.

5D 6D

AMCA 5.3

5D

D 4 (W) (H)
3.14

AMCA 5.2

AMCA 5.5
Pressure Drop SMD-202
AMCA Figure 5.2 5D

D 4 (W) (H)
3.14

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.04 500 0.02 500 0.01 500 0.01 500 0.03
1000 0.14 1000 0.07 1000 0.04 1000 0.06 1000 0.10
1500 0.31 1500 0.16 1500 0.09 1500 0.13 1500 0.23
2000 0.55 2000 0.29 2000 0.16 2000 0.23 2000 0.41
2500 0.86 2500 0.45 2500 0.25 2500 0.36 2500 0.63
3000 1.24 3000 0.65 3000 0.36 3000 0.52 3000 0.91
3500 1.69 3500 0.89 3500 0.49 3500 0.70 3500 1.24
4000 2.20 4000 1.16 4000 0.64 4000 0.92 4000 1.62

AMCA Figure 5.3 5D 6D

5D 6D

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) 5D Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.02 500 0.01 500 0.01 500 0.01 500 0.02
1000 0.09 1000 0.04 1000 0.03 1000 0.04 1000 0.07
1500 0.20 1500 0.09 1500 0.06 D 1500 4 (W) (H)0.10 1500 0.16
5D
2000 0.36 2000 0.16 2000 0.11 2000 3.14 0.17 2000 0.29
2500 0.56 2500 0.25 2500 0.17 2500 0.27 2500 0.45
3000 0.81 3000 0.35 3000 0.24 3000 0.39 3000 0.64
3500 1.10 3500 0.48 3500 0.33 D 4 (W)
3500 (H) 0.53 3500 0.88
4000 1.44 4000 0.63 4000 0.42 3.14
4000 0.70 4000 1.14

AMCA Figure 5.5

12 in. x 12 in. (305mm x 305mm) 24 in. x 24 in. (610mm x 610mm) 36 in. x 36 in. (914mm x 914mm) 12 in. x 48 in. (305mm x 1219mm) 48 in. x 12 in. (1219mm x 305mm)
Pressure Drop Pressure Drop Pressure Drop Pressure Drop Pressure Drop
Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg) Velocity (fpm) (in. wg)
500 0.06 500 0.03 500 0.03 500 0.03 500 0.04
1000 0.22 1000 0.14 1000 0.12 1000 0.13 1000 0.17
1500 0.50 1500 0.31 1500 0.26 1500 0.30 1500 0.38
2000 0.89 2000 0.54 2000 0.46 2000 0.53 2000 0.67
2500 1.39 2500 0.85 2500 0.73 2500 0.83 2500 1.04
3000 2.00 3000 1.22 3000 1.05 3000 1.19 3000 1.50
3500 2.72 3500 1.66 3500 1.42 3500 1.62 3500 2.05
4000 3.55 4000 2.17 4000 1.86 4000 2.11 4000 2.67

Greenheck Fan Corporation certifies that the model


SMD-202 shown herein is licensed to bear the AMCA Seal.
The ratings shown are based on tests and procedures
performed in accordance with AMCA Publication 511
and comply with the requirements of the AMCA Certified
Ratings Programs. The AMCA Certified Ratings Seal
applies to air performance ratings only.
Application Data SMD-202
Actuators and Accessories
T*
Space Envelopes T*

S
Externally mounted actuators always require space
outside of the damper sleeve. The “S” dimension
illustrates the clearance required for various available
actuators.
On dampers less than 18 in. (457mm) high, actuators
may also require clearances above and/or below the
sleeve. “B” and “T” dimensions are worst case clearance
requirements for some dampers less than 18 in. (457mm)
high. All dampers 18 in. (457mm) or more in height,
do not require these worst case clearances. If space
availability above or below the damper sleeve is limited,
each damper size should be individually evaluated.
B*

B*
B* T* S
With With Piggyback
Actuator Type/Model
RRL, RRL/OCI, or RRL, RRL/OCI, or
No Yes
TOR TOR
120 Volt AC
FSLF120 (-S) Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
FSNF120 (-S) Belimo 1
⁄2 in. (13mm) 9 ⁄16 in (249mm)
13
6 in. (152mm) 9 in. (229mm)
FSTF120 (-S) Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
MS4X09 Series Honeywell 1
⁄2 in. (13mm) 8 ⁄2 in (216mm)
1
6 in. (152mm) NA
MS4120 Series Honeywell 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
24 Volt AC
FSAF24 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) NA
FSTF24 (-S) Belimo 711⁄16 in (195mm) 1
⁄2 in. (13mm) 6 in. (152mm) NA
FSLF24-S Belimo 7 ⁄16 in (195mm)
11
0 6 in. (152mm) NA
FSNF24 (-S) Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
MS8120 Series Honeywell 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
230 Volt AC
FSLF230-S Belimo 711⁄16 in (195mm) 0 6 in. (152mm) NA
FSNF230-S Belimo 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)
FSTF230-S Belimo 711⁄16 in (195mm) 1
⁄2 in. (13mm) 6 in. (152mm) NA
MS4X09 Series Honeywell 1
⁄2 in. (13mm) 8 ⁄2 in (216mm)
1
6 in. (152mm) NA
MS4620 Series Honeywell 1
⁄2 in. (13mm) 913⁄16 in (249mm) 6 in. (152mm) 9 in. (229mm)

* For dampers 18 in. (457mm) or more in height these dimensions are 0 in.
Application Data SMD-202
Sleeve 1½ in. (38mm)

Damper Sleeve Dimensional Data maximum blade


clearance

The drawings below and corresponding table show Sleeve


3¾ in.
the position of the SMD-202 damper when mounted (95mm)

in a factory sleeve. The standard mounting locations


provide enough space for the mounting of actuators,
controls and allow space for installation of retaining 5³/8 in.
(137mm)

angles and duct connections. Varies due to


height Sideplate
The standard location of a damper mounted in a
factory sleeve ("A" dimension) is shown below. The
damper can be positioned at other locations within a
range of 6 in. (152mm) to 16 in. (406mm) for the "A" A
5 in.
(127mm)
dimension.
Sleeve Length

"A" Dimension 6 in.

in. (mm) Sleeve Vari


Sideplate
Standard Maximum
All Dampers 7 3⁄16 in. (183) 16 (406) 63⁄16 (157) 5 in.

A
When Height is Sideplate
12 Length**

11 in. (279) or 12 (305) 16 (406)


(305)
less with OCI

NOTE: Entire damper frame is not required to be installed within the wall.

Damper Sizing Information


Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of
equal size. The following figures show maximum damper section size and assembly configurations for multi-section
dampers.

Double Section

Single Section

50 in.
(1270mm)
50 in. 50 in.
(1270mm) (1270mm)

32 in. (813mm)
64 in. (1626mm)
32 in. (813mm) 32 in. (813

100 in.
(2540mm)
Transitioned Damper Dimensions SMD-202
When a fire/smoke damper is being used in conjunction with round or oval ductwork, the SMD-202 can be supplied
in a factory sleeve with round or oval transitions on both ends of the sleeve. Dampers should be ordered to the duct
dimensions. Drawings below show overall damper size.

D* + 2 in. (51mm) +T s
W* + 2 in. (51mm)+Ts
W* + 2 in. (51mm)+Ts

D* + 2 in. (51mm)+Ts
H* + 2 in. (51mm)+T s H* + 2 in. (51mm)+Ts
2 1/8 in. H*
2 1/8 in. H* (54mm)
2 1/8 in. (54mm)
(54mm)

W*
W*
16 in. D* 16 in. 16 in.
(406mm) (406mm) (406mm)
Minimum Minimum Minimum

TYPE R TYPE O TYPE C

*These dimensions are furnished approximately 1/4 in. (6mm)


undersize, except round and oval dimensions which are
approximately 1/8 in. (3mm) undersize.

Ts = (2)(Sleeve Thickness)

Specifications
Smoke Dampers meeting the following specifications shall be stainless steel compression type. Blades shall be symmetrical relative
furnished and installed where shown on plans and/or as described in to their axle pivot point, presenting identical resistance to airflow in
schedules. Dampers shall meet the requirements of NFPA 92, 101 & either direction or pressure on either side of the damper.
105 and further shall be tested, rated and labeled in accordance with The Damper Manufacturer's submittal data shall certify all air
the latest edition of UL Standards 555S. Dampers shall have a low performance pressure drop data is licensed in accordance with the
leakage design qualified to UL555S Leakage Class II. AMCA Certified Ratings Program for Test Figures 5.2, 5.3, and 5.5.
Each damper /actuator combination shall have a UL555S elevated Damper air performance data shall be developed in accordance with
temperature rating of 250°F (121°C) minimum and shall be rated to the latest edition of AMCA Standard 500-D. Dampers shall be labeled
operate at maximum design air flow at its installed location. Each with the AMCA Air Performance Seal.
damper shall be supplied with an appropriate actuator installed by Damper must be rated for mounting vertically (with blades running
the damper manufacturer at the time of damper fabrication. Damper horizontal) or horizontally and be UL 555S rated for leakage and airflow
actuator shall be (specifier select one of the following) electric type for in either direction through the damper.
120 (24 or 230) Volt operation.
The basis of design is model SMD-202.
Damper blades shall be 16 ga. (1.5mm) galvanized steel 3V type with
three longitudinal grooves for reinforcement. Damper frame shall
be galvanized steel formed into a structural hat channel shape with
reinforced corners. Bearings shall be 316SS type rotating in extruded
holes in the damper frame. Blade edge seals shall be silicone rubber
designed to inflate and provide a tighter seal against leakage as
pressure on either side of the damper increases. Jamb seals shall be

Copyright ©2020 Greenheck Fan Corporation


SMD-202 Rev. 17 October 2020
Model BR-30 Series
Barometric Relief Dampers
Vertical Mount - Horizontal Airflow
Application
The BR-30 series is an eccentrically pivoted backdraft
damper for low velocity systems. BR-30 series is a vertical
mounted damper and designed to allow horizontal airflow
and prevent reverse airflow. The blade is formed aluminum
which increases sensitivity and reduces blade mounted
counterbalance weights. On-blade counterweights are
provided to fine tune start-to-open and full open blade
operation. Ball bearings minimize friction.
Recommended Applications
• Gravity hood intake and exhaust
• Stairwell pressurization
• Room pressurization
• Ductwork outlets
Poor Applications
• Propeller fan outlets (high velocity)
• Centrifugal fan outlets (high velocity)
• Building pressurization (sensitive to wind)
• Pressure relief exceeding 0.3 in. wg (0.075 kPa)
• W & H dimensions furnished approximately 1/4 in. (6mm) undersize.
Ratings
Back Pressure: 2.0 in. wg (0.5 kPa) 1.5 in. 1.5 in.
Start -to-Open Pressure: 0.05 in. wg (.01 kPa)
Velocity: 2000 fpm (10.2 m/s)
Temperature: 180°F (82°C)
Construction Standard Optional 4 3/8 in.
MAX
304SS,
Frame Material Galvanized Steel
Extruded Aluminum 1 in.
MAX
Frame Thickness
16 ga. - Airflow
(1.5mm)
No Flange -
(BR-30)
Flange on Discharge -
Frame Type
(BR-31)
Flange on Intake -
5 in.
(BR-32)
Blade Material Aluminum - BR-30 BR-31 BR-32
Blade Seal TPE None No Flange on Flange on
0.063 in. - Flange Discharge Intake
Blade Thickness
(1.6mm)
Size Limitations
Axle Plated Steel 316SS
Maximum Size
Axle Bearings Galvanized Ball Acetal w/SS Ball Minimum
WxH Single Multiple
Linkage Material Galvanized Steel - Size
Section Sections
Jamb Seal None EPDM
Inches 8x6 48 x 74 96 x 148
Blade mounted with - mm 203 x 152 1220 x 1880 2438 x 3759
Counterbalance
adjustable weights
Baked Enamel, Feature
Paint Finishes None Hi Pro Polyester,
Industrial Epoxy • Selectable start open from .05 to .30 in. wg
(0.012 kPa - 0.075 kPa).

Installation instructions available at www.greenheck.com.


Performance Data BR-30 Series
Performance data results from testing a 12 in. x 12 in. and 36 in. x 36 in. (305mm x 305mm and 914mm x 914mm) in
accordance with AMCA Standard 500-D using Figure 5.3 (fully ducted), 5.2 (ducted exhausting into an open area), and
5.5 (plenum mounted). All data has been corrected to represent standard air density at 0.075 lb/ft3 (1.201 kg/m3).
Pressure drop data shown is based on minimum start open pressure. Higher start open pressure will result in different
pressure drop.

Damper Size Damper Size


12 in. x 12 in. 36 in. x 36 in.
(305mm x 305mm) (914mm x 914mm)
2.0 2.0

5.5 5.5
1.0 1.0
.9 .9
.8 .8
5.2 5.2
.7 .7
.6 .6
.5 .5
5.3 5.3
Pressure Drop (in. wg)

Pressure Drop (in. wg)


.4 .4

.3 .3

.2 .2

.1 .1
.09 .09
.08 .08
.07 .07
.06 .06
.05 .05

.04 .04

.03 .03
100 200 300 400 500 600 800 1000 2000 3000 100 200 300 400 500 600 800 1000 2000 3000
700 900 700 900

Velocity Velocity
(fpm) (fpm)

Specifications
Barometric backdraft dampers meeting the following linkage with blade mounted counterbalance weights.
specifications shall be furnished and installed where shown Damper manufacturer’s printed application and
on plans and/or as described in schedules. performance data including pressure, velocity, and
Dampers shall consist of: 16 ga. (1.5mm) insert mount temperature limitations shall be submitted for approval
galvanized steel hat channel frame with 5 in. (127mm) showing damper suitable for pressures to 2 in. wg (0.5
depth; blades from 0.063 in. (1.6mm) thick formed kPa), velocities to 2000 fpm (10.2 m/s, and temperatures
aluminum, eccentrically pivoted; 3⁄8 in. (9.5mm) square to 180°F (82°C). Testing and ratings to be in accordance
plated steel axles with galvanized steel press-fit ball with AMCA Standard 500-D.
bearings; damper shall be equipped with pressure activated Basis of design is model BR-30.
TPE blade seals; and internal plated steel blade-to-blade

Copyright © 2020 Greenheck Corporation


BR-30 Series Rev. 9 August 2020
Model DFD-150
Dynamic Rated Fire Damper
1 ⁄2 Hour Fire Resistance Rating
1

Application
Model DFD-150 is approved for use in walls, floors, and partitions
with fire resistance ratings less than 3 hours. This model carries a
11⁄2 hour UL fire damper label. UL555 classifies dynamic rated fire
damper for use in HVAC systems that are operational in the event
of fire.

Ratings
UL 555 Fire Resistance
Fire Rating: 11⁄2 hours
Velocity
4000 fpm (20.3 m/s) vertical mount only, up to 24 in. x 24 in.
(610mm x 610mm);
2000 fpm (10.2 m/s) vertical or horizontal mount all sizes
Pressure
Maximum: 4 in. wg (1 kPa)

* W & H dimensions furnished approximately 1⁄4 in. (6mm) undersize.

See complete marking on


Construction product.
Construction Standard Optional UL 555S Classification
R13317
Frame Material Galvanized steel* -
Frame Depth 3 ⁄16 in. (94mm)
11
-
Blade Material Galvanized steel* -
Closure Spring Stainless steel -
Model DFD-150 meets the requirements for fire
212°F or 286°F dampers established by:
Fusible Link 165°F (74°C)
(100°C or 141°C)
• National Fire Protection Association
Mounting Vertical Horizontal
NFPA Standards, 80, 90A, and 101
* in gauges required by UL listing R13317
• International Building Codes (IBC)
• CSFM California State Fire Marshal
Fire Listing (#3225-0981:0102)

W*
W*
Stainless Steel Fusible Link (replaceable)
Closure Spring Stainless Steel Fusible Link (replaceable)
Closure Spring

H*
H*

“K” side
“K” side

Horizontal Mount
Horizontal Mount

3 11/16 in. Vertical Mount


(94mm) 3 11/16 in. Vertical Mount
(94mm)

DFD-150 January 2022


Options and Accessories
• Breakaway connections
• Clean wrap
• Closed indicator switch
• Flanges
• Grille tabs
• Retaining angles
• Security bars
• Sealed transitions and sleeve
• Transitions: B, B2, C, CO, CR, R

Document Links
Installation Instructions Life Safety Damper Catalog

Damper Product Selection Guide Specifications

Damper Warranty

DFD-150 January 2022


Factory Sleeve Option
All fire damper installations require the use of sleeves, angles and methods described in the installation instructions. Sleeves can be
field fabricated or factory furnished as a completed damper/sleeve assembly.
Sleeves are galvanized steel and are available in 20 through 10 ga. (1mm - 3.5mm) thicknesses and lengths up to 36 in. (914mm).
“K” dimension specifies location of damper within the sleeve. Minimum is 4 in. (102mm), maximum is “L” less 4 in. (102mm), which
allows for mounting angle installation, and duct connection at each end of the sleeve. If “K” dimension is not specified, it will be
provided as one half of “L” dimension (damper centered in sleeve).
Note: If using access doors, the door should be installed on the “K” side of the damper.

Sleeve

Damper
H*

K
Damper CL Damper Frame
Location W*
L
Overall Sleeve Length

Sealed Option
When sealed option is selected, B transition will need to be field sealed in the area where duct to sleeve connection is made.

Type B with sleeve

Seal this area.

DFD-150 January 2022


Type A, B, & B2
Dampers larger than maximum single section sizes are supplied in 2 or more sections of equal size. Multi-section dampers are factory
assembled ready for installation.

Size Limitations
Inches Type A Type B & B2 P
(mm) Minimum Maximum* Minimum Maximum*
Single H*
H *
4x4 36 x 36 4x3 36 x 31
Section
(102 x102) (914 x 914) (102 x 76) (914 x 787)
Vertical
VERTICAL MOUNT
72 x 48 72 x 45 HORZONTAL MOUNT
(1829 x 1219), (1829 x 1143),
Multi
60 x 60 60 x 56 1 1/2
Varies
1 1/2
Section** NA NA in.

3 in.
W* in.
W *
(1524 x 1524) or (1524 x 1422) or
Vertical
120 x 30 O* 120 x 26
H*
(3048 x 762) (3048 x 660) Type A

16 in.
10 in.
Single
4x4 30 x 30 4x3 30 x 26
Section
(102 x 102) (762 x 762) (102 x 76) (762 x 660)
Horizontal
Multi

3 in.
NA 48 x 36 48 x 33
Section** NA
W* (1219 x 914) (1219 x 838) Damper
Horizontal Location
K Dim.
Sleeve
* Sizes are based on 165°F closure temperature and 2000 fpm. Consult
Length
factory for maximum size for different temperatures and velocities. Varies
** Consult factory for number of sections. Type B2
Multi-Section Limitations - Type A
Maximum Single Section
Dimensions
Maximum damper height is 48 in. (1219mm) when combination width is
Maximum Single Section Dimensions 72 in. (1829mm) or less.

36 in. (914mm) max.


31 in.(787mm)
Max.
48 in. (1219mm)
max.

36 in.
(914mm)
36 in. (914mm) max. max.

Maximum
Type A Single Single
SectionSection
Dimensions 72 in.
(1829mm) max.

Multi Section Limitations - Type B/B2


Maximum damper height is 45 in. (1143mm) when combination
width is 72 in. (1829mm) or less.

31 in.(787mm)
Max.
Multi-Section Limitations
Maximum damper height is 48 in. (1219mm) when combination width is 48 in. (1219mm) or less.

45 in. (1143mm)
36 in. Max.
(914mm)
max.

Type B Single Section

48 in.
72 in.
(1219mm) (1829mm)
max. Max.

Multi Section Limitations - Type B/B2


DFD-150 January 2022
Maximum damper height is 45 in. (1143mm) when combination
width is 72 in. (1829mm) or less.
Type A, B, & B2
Type B & B2 Overall
Damper Dimensions
Vertical Mount

H* O* H* O*
3 (76) 5 (127) 30 (762) 34 (864)
O*
4 (102) 6 (152) 31 (787) 36 (914) H*

5 (127) 7 (178) 32 (813) 37 (940)


6 (152) 8 (203) 33 (838) 37 (940)
7 (178) 9 (229) 34 (864) 37 (940)
8 (203) 10 (254) 35 (889) 38 (965) W*

9 (229) 11 (279) 36 (914) 39 (991) Type B2


Type B
10 (254) 12 (305) 37 (940) 40 (1016)
11 (279) 13 (330) 38 (965) 41 (1041)
Horizontal Mount
12 (305) 14 (356) 39 (991) 42 (1067)
13 (330) 15 (381) 40 (1016) 43 (1092) H* O* H* O*
14 (356) 16 (406) 41 (1041) 44 (1118) 3 (76) 5 (127) 19 (483) 22 (559)
15 (381) 18 (457) 42 (1067) 45 (1143) 4 (102) 6 (152) 20 (508) 23 (584)
16 (406) 19 (483) 43 (1092) 46 (1168) 5 (127) 7 (178) 21 (533) 24 (610)
17 (432) 20 (508) 44 (1118) 47 (1194) 6 (152) 8 (203) 22 (559) 26 (660)
18 (457) 21 (533) 45 (1143) 48 (1219) 7 (178) 9 (229) 23 (584) 27 (686)
19 (483) 22 (559) 46 (1168) 50 (1270) 8 (203) 10 (254) 24 (610) 28 (711)
20 (508) 23 (584) 47 (1194) 51 (1295) 9 (229) 11 (279) 25 (635) 29 (737)
21 (533) 24 (610) 48 (1219) 52 (1321) 10 (254) 12 (305) 26 (660) 30 (762)
22 (559) 26 (660) 49 (1245) 53 (1346) 11 (279) 13 (330) 27 (686) 31 (787)
23 (584) 27 (686) 50 (1270) 54 (1372) 12 (305) 14 (356) 28 (711) 31 (787)
24 (610) 28 (711) 51 (1295) 55 (1397) 13 (330) 15 (381) 29 (737) 32 (813)
25 (635) 29 (737) 52 (1321) 56 (1422) 14 (356) 16 (406) 30 (762) 33 (838)
26 (660) 30 (762) 53 (1346) 57 (1448) 15 (381) 18 (457) 31 (787) 34 (864)
27 (686) 31 (787) 54 (1372) 58 (1473) 16 (406) 19 (483) 32 (813) 35 (889)
28 (711) 32 (813) 55 (1397) 59 (1499) 17 (432) 20 (508) 33 (838) 36 (914)
29 (737) 33 (838) 56 (1422) 60 (1524) 18 (457) 21 (533) -

* Dimension is inches (mm). These dimensions are furnished approximately 1⁄4 in. (6mm) undersize. All ‘H’ dimensions larger than single section height
are two sections high. Refer to size limitations chart. The top section is a Type B/B2 and the bottom section are Type A.

DFD-150 January 2022


Type C, CO, CR, & R
Dampers larger than maximum single section sizes are supplied in 2 or more sections of equal size. Note: All multiple section dampers
with transitions, will include a factory installed sleeve.
Type CR Type CO & C Type R+
Inches (mm)
Minimum Maximum* Minimum Maximum* Minimum Maximum*
Single Section
3 (76) 30 (762) 3 x 3 (76 x 76) 34 x 30 (864 x 762) 3 (76) 34 (864)
Vertical

70 x 44 (1778 x 1118),
Multi Section 55
NA NA 58 x 55 (1473 x 1397) or NA 58 (1473)
Vertical** (1397)
118 x 25 (2997 x 635)

Single Section
3 (76) 25 (635) 3 x 3 (76 x 76) 28 x 25 (711 x 635) 3 (76) 28 (711)
Horizontal
Multi Section
NA 32 (813) NA 46 x 32 (1163 x 787) NA 34 (864)
Horizontal**
+
With 2 in. (51mm) offset. Sizes adjust with an 1 in. (25mm) offset.
* Sizes are based on 165°F closure temperature and 2000 fpm. Consult factory for maximum size for different temperatures and velocities.
** Consult factory for number of sections.

Maximum Single Section Dimensions


Overall Damper Dimensions

Type C Type CO D*+2

Type CR

30in.
30 in. O*
(762mm)
max. (762mm)
max.

34 in. 34 in. D*
(864mm) (864mm)
max. max.
W*+2

Type CO
Type CR Type R O*

H*

W*
W*+2

34 in.
Type C
(889mm)
30 in. max.
(762mm) O*
max. Type R transition is centered on
damper frame. (Dimension are with H*
2 in. (51mm) offset.)

W*
C, CO, CR transitions are positioned 1 in. (25mm)
from bottom of sleeve.

DFD-150 January 2022


Type C, CO, CR & R
DFD-150
Dynamic Fire Damper

Vertical Mount Horizontal Mount

H* or D* O* H* or D* O* H* or D* O* H* or D* O* H* or D* O*
3 (76) 6 (152) 21 (533) 26 (660) 39 (991) 45 (1143) 3 (76) 6 (152) 18 (457) 22 (559)
4 (102) 7 (178) 22 (559) 27 (686) 40 (1016) 46 (1168) 4 (102) 7 (178) 19 (483) 23 (584)
5 (127) 8 (203) 23 (584) 28 (711) 41 (1041) 47 (1194) 5 (127) 8 (203) 20 (508) 24 (610)
6 (152) 9 (229) 24 (610) 29 (737) 42 (1067) 48 (1219) 6 (152) 9 (229) 21 (533) 26 (660)
7 (178) 10 (254) 25 (635) 30 (762) 43 (1092) 49 (1245) 7 (178) 10 (254) 22 (559) 27 (686)
8 (203) 11 (279) 26 (660) 31 (787) 44 (1118) 50 (1270) 8 (203) 11 (279) 23 (584) 28 (711)
9 (229) 12 (305) 27 (686) 32 (813) 45 (1143) 50 (1270) 9 (229) 12 (305) 24 (610) 29 (737)
10 (254) 13 (330) 28 (711) 33 (838) 46 (1168) 51 (1295) 10 (254) 13 (330) 25 (635) 30 (762)
11 (279) 14 (356) 29 (737) 34 (864) 47 (1194) 52 (1321) 11 (279) 14 (356) 26 (660) 31 (787)
12 (305) 15 (381) 30 (762) 36 (914) 48 (1219) 53 (1346) 12 (305) 15 (381) 27 (686) 31 (787)
13 (330) 16 (406) 31 (787) 37 (940) 49 (1245) 54 (1372) 13 (330) 16 (406) 28 (711) 32 (813)
14 (356) 18 (457) 32 (813) 37 (940) 50 (1270) 55 (1397) 14 (356) 18 (457) 29 (737) 33 (838)
15 (381) 19 (483) 33 (838) 39 (991) 51 (1295) 56 (1422) 15 (381) 19 (483) 30 (762) 34 (864)
16 (406) 20 (508) 34 (864) 40 (1016) 52 (1321) 57 (1448) 16 (406) 20 (508) 31 (787) 35 (889)
17 (432) 21 (533) 35 (889) 41 (1041) 53 (1346) 58 (1473) 17 (432) 21 (533) 32 (813) 36 (914)
18 (457) 22 (559) 36 (914) 42 (1067) 54 (1372) 59 (1499)
19 (483) 23 (584) 37 (940 43 (1092) 55 (1397) 60 (1524)
20 (508) 24 (610) 38 (965) 44 (1118) -

* Dimension is inches (mm). These dimensions are furnished approximately 1/4 in. (6mm) undersize. All ‘H’ dimensions larger than single section height
are two sections high. Refer to size limitations chart.

Copyright © 2022 Greenheck Fan Corporation


DFD-150, R26, January 2022
Greenheck Fan Corporation reserves the right to make
product changes without notice.