You are on page 1of 4

Submittal Ref.

#: SQP001392_1

Design Envelope Split-Coupled Vertical In-Line Pump


Model: Series Design Envelope Sensorless 4300 1013-200.0
Project name: DASMEP-22-06273 Representative: Omar Muqthar S
Location: Phone number:
Date submitted: 6/15/2022 12:29 PM e-mail: omuqthar@armstrongfluidtechnology.com
Engineer: Submitted by: Muqthar S, Omar
Application design data
Tag number: Secondary CWP Configuration: Single
Service: Suction pressure: 0 ft
Location: Fluid: Non-Potable Fluid - Water
Qty: 4 Operating temperature: 60 °F
Total system flow: 3192 USgpm Duty flow per pump: 3192 USgpm
System head: 5 bar Viscosity: 31 SSU
Environment: Indoors Specific gravity: 1.0000
Total dissolved solids: 0 ppm Safety factor % flow: 0%
Efficiency at Design: 88.76 % Safety factor % head: 0%
NPSHR: 0.9 bars Absorbed Power/BHP: 151.9 hp
Min. maintained system 2 bar Impeller diameter: 13.9 in
pressure*:
PEIvl: Not applicable ERvl: Not applicable
Standby qty: 0 Pump/motor run qty: 1
Outlet velocity: 12.98 ft/s

*If minimum maintained system pressure is not known, default is 40% of design head.

Materials of construction
Construction: Bronze Fitted Impeller: Bronze
Rating: ANSI-125 Pump shaft: 416 Stainless Steel
Connections: Inlet: 10in, Outlet: 10in Flush line: Braided Stainless Steel
Casing (volute): Cast Iron Casing gasket: Confined Non-Asbestos Fiber

Mechanical seal data


Seal type: Outside Balanced Rotating face: Resin Bonded Carbon
Manufacturer code: C-SSC AB2 Stationary seat: Sintered Silicon Carbide
Springs: Stainless Steel Secondary seal: Viton
Rotating hardware: Stainless Steel Maximum total dissolved 2000 PPM
solids (TDS)****:

Electrical data
Supplier: Factory Choice Insulation class: Class F Insulation
Size: 200 hp Motor type: Inverter Duty
Frame size: 447TC Efficiency: NEMA Premium 12.12
Enclosure: TEFC Power supply: 460/3/60
Operating speed @ 100% 1620 rpm Operating speed @ 50% 1140 rpm
flow: flow***:

***Based on minimum pressure setting of 40% of design head.

www.armstrongfluidtechnology.com 6/15/2022 12:29:51 PM, Ref. #SQP001392_1 Page 1 of 5


****Note: Please ensure proper seal is selected by inputting Total Dissolved Solids (TDS) in PPM in ADEPT if water quality is
poor at site. Also select Flush Line Filter or Cyclone Separator if there are other contaminants in the fluid

IVS controller data


Sensorless control: Yes - Quadratic press control Communication port: RS 485
Communication protocol (*): Default Field Reconfigurable Analog inputs: 2 (current or voltage)
Enclosure: UL Type 12/IP55 Analog outputs: 1 (current)
Fused disconnect switch: None Digital inputs: 4 (programmable)
Control orientation: L1 Digital outputs: 2 (programmable)
Expansion card: None Cooling: Fan cooled through back channel
Absorbed Power/BHP at 50% 83.55 hp Ambient temperature: 14°F to 113°F (up to 3280 ft
load/flow and 55% of elevation)
design head:
Meets ASHRAE 90.1: Yes EMI/RFI control: Integrated filter to meet
EN61800-3
Harmonic suppression: Integrated DC link reactor**
(*): If Default - Field reconfigurable is selected, Default from factory will be BACnet MS/TP and can be reconfigured in the field.
** The IVS control is a low harmonic control with a built-in DC link reactor equivalent in performance to a 5% AC line reactor. This
does not guarantee performance to any system wide harmonic specification or the costs to meet a system wide specification. If
supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system
harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

Performance curve

----Admin Data—-
Tag Num: Secondary CWP
Service:
Series 4300 Location:
DE IVS Sensorless
----Motor Data----
10x10x13 @ 1620 rpm
8 Motor Size: 200 hp
*PT-131-6-0
ANSI/HI 14.6 ----Design Duty Points---
Flow: 3192 USgpm
7
Head: 5 bar
Impeller: 13.9 in

6 ----Performance Data---
70 75 79
13.9 in 82 85  NPSHR: 0.9 bars
8788
89  Eff. @ Design: 88.76 %
89
Head (bars)

5 89  Absorbed Power/BHP @
88
87 Design: 151.9 hp
85  Mtr Capability @ Rated Spd:
82
4 79 178.29 hp
250 hp
75  BEP @ Design Imp: 89 % @
3076.78 USgpm
3 70200 hp  %maximp.range: 100.00%
 Outlet velocity: 12.98 ft/s
 Op. Speed: 1800 rpm
150 hp
2 10 in 125 hp
70
70 hp
100
70
1 System 75 hp
60 hp
40 hp
2530
hphp

0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000

Water, spgr=1.0000 Flow (USgpm)

www.armstrongfluidtechnology.com 6/15/2022 12:29:51 PM, Ref. #SQP001392_1 Page 2 of 5


--Control Data—

1. Hmax @ 54.3 Hz:


Series 4300 NPSHR: 0.9 bars
Intersection Pt: 3192 usgpm @ 5
DE IVS Sensorless bars
10x10x13 @ 1620 rpm bhp=151.9 hp, eff=88.76 %%,
8 75 80 *PT-131-6-0 %bepq=104 %%
63 Hz ANSI/HI 14.6
84
2. Control (QPC) @ 49.83 Hz:
7 87 NPSHR: 0.78 bars
89 Intersection Pt: 2793 USgpm @
4.3 bars
6 bhp=114.05 hp, eff=88.9%,
89 %bepq=99.1%
54.3 Hz
87 3. Control (QPC) @ 45.35 Hz:
Head (bars)

5
84 NPSHR: 0.66 bars
Intersection Pt: 2362.08 USgpm
80 @ 3.64 bars
4 75 bhp=82.22 hp, eff=88.41%,
%bepq=92.33%

3 4. Control (QPC) @ 40.87 Hz:


NPSHR: 0.51 bars
Intersection Pt: 1883.28 USgpm
@ 3.04 bars
2
31.9 Hz bhp=56.15 hp, eff=86.26%,
200 hp %bepq=81.95%

1 System
5. Control (QPC) @ 36.4 Hz:
NPSHR: 0.35 bars
18 Hz Intersection Pt: 1308.72 USgpm
NPSHr @ 2.5 bars
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 bhp=35.34 hp, eff=78.35%,
%bepq=63.86%
Water, spgr=1.0000 Flow (USgpm) 6. Hmin: 2 bars 31.92 Hz:
NPSHR: 0.13 bars
Intersection Pt: 0 USgpm @ 2
bars
(Head Q Min) Setting= 40% Hmax

Design envelope pumping unit capability


Operating point Flow Head Efficiency
Full capability at 100% design flow 3192 USgpm 6.47 bars 88.71%
Design point 3192 USgpm 5 bar 88.76 %
50% average flow (with default load profile) 1596 USgpm 2.75 bars 83.29 %

www.armstrongfluidtechnology.com 6/15/2022 12:29:51 PM, Ref. #SQP001392_1 Page 3 of 5


Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 200 °F

All Pump casings are hydrostatically tested to requirements of ANSI/HI 14.6 standard.

Options
Sensorless Bundle: Yes DEPC Parallel Sensorless: No
Energy Performance Bundle: No Protection Bundle: No
Dual Season Setup: No Zone Optimization Bundle: No

Cooling Heating
Q1: N/A Q2: N/A
H1: N/A H2: N/A
H1min: N/A H2min: N/A
Maximum Flow: N/A Minimum Flow: N/A

Optional Services
On-Site Pump Commissioning: Cost not Included Extended Warranty: No
Pump Manager: Yes Include Spare Parts Qty: 0

Dimensional data (not for construction)


Side view Top view

Inverter motor type: Inverter duty

www.armstrongfluidtechnology.com 6/15/2022 12:29:51 PM, Ref. #SQP001392_1 Page 4 of 5