Professional Documents
Culture Documents
B
(DISPONIBLE EN ESPAÑOL EN EWCCONTROLS.COM)
ewccontrols.com/acrobat/090375a0244.pdf
Leave this bulletin on the job site for future reference!
The BMPlus Zone Control System allows you to easily J1
CONTROL SYSTEM
upgrade an inefficient single zone HVAC system, into a 14
21
28 40
43
46 130
140
150 19
26
33
D10
D11
R36
R37
D12 R38
R41
R39
M6 OFF
42 34 52 5 47 SAS
system. The Superior Design, Intuitive Firmware, Simple M4 R1
STAGING
TIMER OAS
R2
LOW TEMP
LIMIT
R3
HIGH TEMP
LIMIT
2 ND STAGE HEAT
R4
DIFFERENTIAL
R42
SAS
C5 C7 C15
M2 R43
Setup Options, Easy to Understand wiring and Backwards M1
K1 R15
R16
C8
R14
U3
D21
R40
R82
OAS
OAS
MOTOR U1 U2 ZONE3
Contractors dream. Combined with EWC Motorized M6 K2
RESET
C10
R45
R46
T STAT
C
M4 U4
R52
G
M6 F1
D4
ZONE2
R53
M4 + + U5 T STAT
Y
expanded to 5 or 7 zones, using 1 or 2 R
OAS < STAGING> TIMER
OFF < 50% RULE > ON
OFF < SAS > ON U6
C9
R56
R57 R
GAS < FAN > HYDRONIC
G
Model XM2 Expansion Modules.
D5
R58
R19 Z1
C K5 R59
R20
R60
ZONE1
SYSTEM
LED1 STATUS R35
T STAT
R21 R61
C
Compatible Controls 2 & 3 stage conventional or dual G
Y2
D6 R22
K 6 R23
LED2
LED3
OAS
SAS
R62 W/E
U7
HVAC fuel heat pumps, without the need for dual Y1 R24
LED 4 ZONE 3 R71
R63 O/B
Y
O R25
R64
LED10 W1 B
R73
R72
R34 R77
D9 LED11 W2 EM R76 NORM
Compatible Compatible with any off the shelf EWC BMPlus3000 rev B SW 4
Figure 1
Thermostats H e a t P u m p T h e r m o s t a t
(2heat/1cool). You may also use any Box Contents * BMPlus 3000 Control Panel
regular Heat/Cool thermostat * Supply Air Sensor
(1heat/1cool). You may still use * Technical Bulletin TB228
regular Heat/Cool thermostats to * Mounting Hardware
control a Heat Pump system.
Thermal The BMPlus module has a Thermal
Automatic The BMPlus Zone system features Circuit circuit breaker that protects the
Heat/Cool automatic changeover from any Breaker module(s) from shorts in the damper
Changeover thermostat allowing for individual zone and thermostat field wiring. It will
comfort from the HVAC system. not protect against shorts in the
A green STATUS LED pulses as a steady HVAC system wiring.
Status LED
heart beat to indicate Micro- processor CAUTION: When the circuit breaker
activity and 24v power is present. is tripped it will get quite hot. To
Function specific colored LED’s illuminate reset the breaker: Shut off power to
System LEDs the panel. Find and repair the short.
to indicate the HVAC system mode of
operation and active zone identification. Restore the 24VAC power.
See page 10 for details. Indoor Fan Any zone can activate the indoor fan
Control and only the dampers in zones calling
Damper LEDs Green LEDs labeled Zone 1 thru Zone 7
for continuous fan operation will open.
indicate which dampers are energized to
Continuous fan operation will only
the open position.
occur when there are no active or
Operating INPUT VOLTAGE: 19-30VAC 60 Hz pending, heat or cool demands. A dip
Power Transformer 40-100VA MAX. NEC Class 2. switch is provided to enable automatic
CURRENT DRAW: Max 15VA @ 24VAC. fan operation in heat mode. Useful for
OVER-CURRENT PROTECTION: 4.0 amp straight electric heat or hydronic heat
Operating applications.
TEMPERATURE: -20° to 160°F (-29° to 71°C)
Conditions HUMIDITY: 0% - 95% RH Non-Condensing.
1
TB-228 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
P/N 090375A0228 REV. L 06.01.18 Copyright © 2007 EWC Controls All Rights Reserved
BMPlus 3000 FIRMWARE/HARDWARE FEATURES
The panel has seven built-in Delay Timers Cooling and Heating Limit Controls
*Built-In
that insure safe & reliable operation.
Timer
Settings The Adjustable Cooling Limit
* Start-up Delay Timer = 3 minutes-fixed 43
* Short Cycle Timer = 3 minutes-fixed 40 46 potentiometer sets the supply air
* Change Over Timer = 4 minutes-fixed 37 49
temperature at which the cooling is
* Opposing Call Timer = 20minutes-fixed cycled off and the fan continues to run,
34 52
* Staging Timer = OFF or 7-42 min. -Adj. LOW TEMP allowing the coil to warm up.
* Supply Air Limit Timer = 3minutes-fixed LIMIT
* Purge Delay Timer = 90 seconds-fixed
The Adjustable Heating Limit
130
140
150
potentiometer sets the 1st stage heat
*Startup The panel will not activate any
supply air temperature, at which the
Delay cooling or heating operation until 120 160
the startup delay has expired. This heating is cycled off and the fan
Timer 110 170
continues to run, allowing the heat
occurs after any initial power up or HIGH TEMP
power failure. Press the Reset LIMIT exchanger or coil to cool down.
button for 1 second to override.
The Adjustable 2nd stage heat
*Short Cycle When all zone demands are 19 26
33 differential potentiometer sets the 2nd
Timer satisfied, the panel will not resume stage heat supply air temperature, at
the same mode of operation for a 12 40 which the heating is cycled off and the
minimum of 3 minutes. 5 47 fan continues to run, allowing the heat
*Changeover A built-in timer prevents the system 2nd STAGE HEAT
DIFFERENTIAL
exchanger or coil to cool down.
Timer from rapidly switching between NOTE: Allows the supply air sensor to
heating and cooling modes. At the Example: be installed in the supply air plenum,
Hi Temp. Limit =130°F
end of a call, a 4 minute timer is regardless of the coil/heat exchanger
plus 2nd stg. DT= 40°F
started and the panel will not switch to New Limit = 170°F. configuration. Allows the installer to fine
the opposing mode until the timer has tune virtually any multi stage heating
expired. system!
A 20 minute delay must expire, or the
*Opposing active zone(s) must satisfy, before The separate reset buttons on the
Call the panel will honor a thermostat old BMP3000 have been replaced by
Delay Timer demand to changeover to the Reset
BUTTON a single button with dual functions.
opposite mode of system operation.
Momentarily pressing the RESET
Staging The STAGING TIMER sets the
button clears the built-in timers
Timer / OAS amount of continuous call time in 1st
controlling the Startup delay timer,
21
stage, before second stage heat or
14 28 RESET Short cycle timer, W2 timer, Supply air
cool is energized. NOTE: The
sensor timer and the Changeover
7 35 potentiometer also serves as the Always reset the CPU
anytime you make timer. This enables you to test the
42 Outside Air Changeover Setting.
OFF dip-switch changes to installation faster. Caution should be
STAGING The BMPlus 3000 can inhibit heat the BMP3000 panel!
Timer / OAS observed when using this button.
staging based on a Timer or DO NOT use a sharp
OFF, 7 to 42 Outside Air Temperature. object to press the
minutes or 7 NOTE: An Optional OAS Sensor is
button! Your finger tip Pressing the RESET button for 7
to 42 will work fine.
required to use the OAS feature. seconds will reset the CPU for
degrees F.
NOTE: 2nd stage cool delay defaults the entire zone system.
Any setting
below 7 is off! to 30 minutes, if OAS is chosen to
DO NOT set to off inhibit 2nd stage Heat. Emergency An On-Board Switch is provided that
if using OAS
Heat allows the Customer to set the system
The time delay of 3 minutes must Switch to the Emergency heat mode.
*Supply Air expire before the BMPlus 3000 will
Limit This switch is shown in the NORMAL
re-energize heat or cool mode. This
Delay Timer EM position.
delay occurs when the processor
detects the supply air temperature is This switch would be used for Heat
higher or lower than the High or Low Pump applications where the
temperature limit settings. Customer chooses to use Regular
NORM
*Purge Delay The last Damper(s) will be held Open Heat/Cool thermostats instead of
Timer for 90 seconds at the end of every call Heat Pump thermostats.
allowing a system purge into the last
2 zone that was calling.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
Selecting the Options Using the DIP Switches
***FS = Factory Settings
RECORD YOUR OWN DIP SWITCH
SETTINGS HERE ON
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com 3
INSTALLATION & WIRING INSTRUCTIONS
WARNING: THESE PANELS ARE DESIGNED FOR USE WITH 24VAC. DO NOT USE OTHER VOLTAGES! USE CAUTION TO AVOID ELECTRIC
SHOCK OR EQUIPMENT DAMAGE. ALL WORK SHOULD BE PERFORMED TO LOCAL AND NATIONAL CODES AND ORDINANCES. USE 18
Mount the panel housing in a suitable/convenient location. Mounting hardware is provided. Avoid locations that may become wet or
produce condensation. Hot attics are OK. Use the knockouts on the panel housing as wire entryways. Strain relief fittings can be used
if desired. Use care and do not damage the circuit board when removing the knockouts and making wire connections. NOTE: The
24vac power supply should be supplied by a separate transformer. DO NOT use the 24vac power supply from the HVAC system
unless there is no other alternative. 2 zones and 2 dampers is the limit when stealing voltage from the HVAC system.
R
EWT-855i “Wi-Fi” Thermostat
W/E W2 Y1
*
C Y2 RC RH G O B
LED ZONE ZONE
T'STAT
1 C
C
W/E
W/E
O/B
O/B
Y
Y
R
R
G G
DRY R
ONE
ZONE
* Field installed jumper.
Figure 2d. Model EWT-955WH Wireless Thermostat:
Figure 2b Typical “Wi-Fi” Thermostat Configured for Configured for 2 heat 1 cool heat pump.
1 heat & 1 cool. See thermostat See thermostat instructions for further
4 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
THERMOSTAT WIRING CONTINUED
Figure 3. Model EWT-955WH Wireless Thermostat: Figure 4 Typical “Wi-Fi” Thermostat Configured for
Configured for 1 heat 1 cool. 2 heat & 1 cool Heat Pump. See
See thermostat instructions for further thermostat instructions for further details.
Figure 5 Wiring a split circuit thermostat to operate a Figure 6 Wiring for a Radiant floor loop as the first
Radiant floor heating or Baseboard heating stage of heat via the isolation relay and 2nd
Hydronic system. The BMPlus 3000 controls the stage Forced Air heat is controlled through the
cooling only in this type of configuration. zone panel.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com 5
SYSTEM WIRING
Conventional or Dual Fuel 2 Heat / 1 Cool Heatpump
Single Typical gas or Electric Furnace with with O (Cool) Type Reversing Valve
Transformer A/C. Note the common “C” wire is Typical heat pump system wiring with electric resistance or
Gas or Electric connected to the SYSTEM terminal Gas backup heat (No Dual Fuel kit required). This diagram
Furnace & A/C block of the BMPlus 3000. applies to air cooled or geothermal / ground source
1 or 2 Stage Heat systems.
6 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
SYSTEM WIRING CONTINUED
Single Typical 2 stage gas furnace with 2 Conventional or Conventional or Dual Fuel Heat Pump wiring
Transformer stage A/C. Constant or variable Dual Fuel 3 Heat / with 3 Heat / 2 Cool with B (Heat) Type
Gas & A/C speed systems can be connected 2 Cool Heat Pump Reversing Valve. Electric or Gas Furnace
Backup (No dual fuel kit is required). This
2 stage heat and controlled. Choose Timer or with B (Heat) Type diagram applies to air cooled or geothermal /
2 stage cool Outside air to delay 2nd stage.
Reversing Valve ground source systems.
BMPlus 3000
2 STAGE
OUTDOOR 2 STAGE GAS
FURNACE SYSTEM BMPlus 3000
CONDENSING AIR HANDLER
UNIT OR 1 0R 2 STAGE
G G GAS FURNACE SYSTEM
Y2 Y2 Y2 HEAT PUMP
2 STAGE G G
Y1 Y1 Y1
R W1 O Y2 Y2 Y2
C W2 Y1 Y1 Y1
W1/B
R W2/E B B O
C RH X/W W1 W1/B
R W2 W2/E
RC
C C R RH
NOTE: If desired, you can connect a “C” Common C RC
RC/RH
wire back to the “System” terminal block. Use it as LINK C
a TEST point while troubleshooting.
NOTE: The “R” wire connection to the condensing RC/RH
LINK
unit may not be required on your system.
* OFF, 7 TO 42 MINUTE STAGING TIME DELAY SETTINGS *SECOND STAGE 50% ZONE RULE SAVES ENERGY
* 7 TO 42°F. OUTSIDE AIR CHANGEOVER * STATUS LED’s ARE INCLUDED ON ALL MODULES
* OPERATES WITH MULTI STAGE HEATPUMPS *1 ZONE MODE COMPLIES WITH CALIFORNIA TITLE 24
* ADJUSTABLE DIFFERENTIAL LIMIT CONTROL * SIMPLIFIED WIRING AND EASY SYSTEM SETUP
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
7
DAMPER WIRING AND CONFIGURATION
Note: All zone dampers default to the "OPEN"
position after a purge delay has occurred. All Models ESR Damper Wiring
Dampers also default “OPEN” during
changeover & short cycle delays, and when
all zone demands are satisfied, and no MA-ESR ZONE
signals are detected from the thermostats. MOTOR
Either one
REFERENCE THESE DIAGRAMS PRIOR TO Not both M6
INSTALLATION AND POWER WIRING. DOING SO WILL { M4
SAVE TIME AND LABOR LATER ON.
NC NO C M M M2
ZONE MODULE DAMPER M1
Auxilary
MOTOR TERMINAL BLOCK SPDT
End Switch
DESIGNATION & FUNCTION Dry Contacts
ZONE Rated for
24vac only
MOTOR
A Spring Open Damper is wired to M1 & M6
.
Terminal M6 24vac to Close a damper(s) M6 A Spring Close Damper is wired to M1 & M4
Terminal M4 24vac to Open a damper(s) M4
Figure 16
Terminal M2 Constant 24vac HOT M2
Terminal M1 Common 24vac M1 Multiple ND and/or URD
Damper Wiring on a Single Zone
ZONE
(2-4 Dampers)
MOTOR
PC 6 M6
Figure 13 .
PO 4 M4
COM 1 M2
All Models ND, URD and SID Damper Wiring M1
PC 6
ZONE
MOTOR PO 4
COM 1
PC 6 M6
PO 4 M4
COM 1 M2 PC 6
M1 PO 4
COM 1
Figure 14
NOTE: Do not connect more
than 4 motor actuators in a
PC 6 series configuration. That will
decrease the chances of poor
All Models RSD Damper Wiring PO 4 electrical connections and
voltage drop issues. If wiring
COM 1 more than 4 dampers see figure
18.
ZONE Figure 17
MOTOR
M6 On all these dampers and most older style
MA-RSD
A Spring Open Damper is wired to M1 & M6 Contact EWC Controls Technical Support when you
A Spring Close Damper is wired to M1 & M4 are on the job site for assistance with damper wiring.
Figure 15 Have a Multi-Meter, pocket screw driver and wire
snips on hand.
8 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
DAMPER WIRING CONTINUED
If you need to connect numerous dampers to a single zone, or you are using dampers of unknown current draw
such as Spring Types, Isolation relays and separate power supplies may be required. Parallel as many dampers
as you want as long the total current load of the motor actuators does not exceed the VA rating of the
transformer. Other factors should also be considered, such as the full load amp rating of the isolating relay
contacts, voltage drops from long wire runs and feeder conductor sizing to junction points.
NOTE: Some older style dampers and competitor’s dampers cannot be paralleled and must be isolated or wired
in tandem. Contact EWC Controls Technical Support for assistance.
ZONE
MOTOR
PC 6 PC 6 PC 6 PC 6 M6
PO 4 PO 4 PO 4 PO 4
M4
COM 1 COM 1 COM 1 COM 1
M2
M1
PC 6 PC 6 PC 6 PC 6
PO 4 PO 4 PO 4 PO 4
COM 1 COM 1 COM 1 COM 1
PC 6 PC 6 PC 6 PC 6
PO 4 PO 4 PO 4 PO 4
COM 1 COM 1 COM 1 COM 1
BMPlus BMPlus
3000 12 22 30 Maximum number of dampers 3000 3 5 7
BMPlus per ZONE is 12. BMPlus
5000 9 19 26 Use Class 2 UL Listed 1585 Inherently 5000 2 4 6
BMPlus current limiting transformers only! BMPlus
7000 5 15 23 7000 1 3 5
Non-inherently current limiting transformers must have field provided over-current protection on the secondary 24 vac output. The table values
provided pertain to genuine ULTRAZONE Dampers and Competitors typical 24vac Spring loaded dampers. Included in these VA load ratings are the
correct number of thermostats, the BMPlus Zone System, and a 5% field factor. Spring loaded dampers draw higher currents & require more power.
T E S T I N G D A M P E R MOTORS
ND / URD / SMD / BMD Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminal 4. Damper should
Open. Remove 24vac hot from terminal 4 and apply to terminal 6. Damper should Close.
RDN / SMDL / BMDL Dampers - Connect 24vac common to terminal 1 and 24vac hot to terminals 2 and 4. Damper
should Open. Remove 24vac hot from terminal 4. Damper should Close.
SR / ESR / RSD Power Close / Spring Open Dampers - Connect 24vac common & hot to the two motor (M) terminals.
Damper should Close. Remove 24 vac hot. Damper should Open.
SR / ESR / RSD Power Open / Spring Close Dampers - Connect 24vac common & hot to the two motor (M) terminals.
Damper should Open. Remove 24vac hot. Damper should Close.
9
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
LED’S
BMPlus 3000 The BMPlus is equipped with 11 function specific LED’s that indicate HVAC system operation
LED’s and zone damper status. Familiarize yourself with the LED functions and definitions, in order to
accurately determine the Zoned HVAC system status and mode of operation.
GREEN
STATUS The STATUS LED pulses as a steady heart beat to indicate proper Microprocessor system status.
RED
OAS The OAS LED illuminates solid to indicate that the Outdoor Temperature has fallen below the chosen
set point. The OAS LED will blink rapidly to indicate a shorted or open Outdoor Air Sensor circuit.
The SAS LED illuminates solid to indicate that the Supply Temperature has exceeded the chosen
RED
SAS set point on either the HIGH TEMP LIMIT or the LOW TEMP LIMIT. The SAS LED will blink rapidly
to indicate a shorted or open Supply Air Sensor circuit.
GREEN ZONE 3 The ZONE 3 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
GREEN ZONE 2 The ZONE 2 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
GREEN ZONE 1 The ZONE 1 LED will illuminate solid to indicate that damper(s) is energized open, and the Zone is active.
The FAN LED will illuminate solid to indicate a demand for fan operation, during COOLING, HEATING,
GREEN FAN PURGE, or CONTINUOUS FAN operations.
YELLOW
Y2 The Y2 LED illuminates solid to indicate the 2nd stage of DX COOLING or DX HEATING is energized.
YELLOW Y1 The Y1 LED illuminates solid to indicate the 1ST stage of DX COOLING or DX HEATING is energized.
RED
W1/B The W1/B LED illuminates solid to indicate 1st stage of HEATING is energized in Gas/Hydronic mode.
The W1/B LED illuminates solid to indicate ‘B’ reversing valve is energized in HEAT PUMP operation.
NOTE: In Heat Pump Operation, this LED will stay illuminated after the call for heat is completed.
The W2/E LED illuminates solid to indicate 2nd or 3rd stage of HEATING is energized in GAS/HYDRONIC
RED W2/E or HEAT PUMP mode.
The W2/E LED illuminates solid to indicate EMERGENCY HEAT is energized in HEAT PUMP mode.
NOTES:
10 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
BMPlus3000 User Friendly
Rugged 10 pin
Expansion Header 3 Zone Main Adjustable
Potentiometers
Protective
header cap not
shown for clarity
Module
J1 Supply Air
CONTROL SYSTEM Sensor
43 140
D10 R36 Connections
21 26 D11 R37
Rugged Damper 14 28 40 46 130 150 19 33
D12 R38
Motor Terminal ZONE3 49 120 160 12 D13
7 35 37 40 R39
Blocks MOTOR
110 170 R41
M6 OFF 42 34 52 5 47 SAS
STAGING LOW TEMP HIGH TEMP 2 ND STAGE HEAT R42
M4 R1
TIMER OAS
R2
LIMIT
R3
LIMIT
R4
DIFFERENTIAL SAS
C5 C7 C15
M2 R15 C8
R43
OAS Outdoor Air
Dual Function K1 U3 R40
Reset M1 R16 R14 D21 R82 OAS Sensor
Button Connections
R81
ZONE2 D1
R44
MOTOR U1 U2 ZONE3
R45
K2 T STAT
M6 C10
R46 C
RESET
M4 U4
C11
R47 W/E
M2 D2
R13
R48 O/B
Thermal Circuit M1 R49
Breaker
K3 C12 Y
R50
ZONE1 R51
R
U9 Rugged
MOTOR C13
C14
G
D3 Y1 R52 Thermostat
M6 F1
D4
Terminal
R53 ZONE2
M4 + + U5 T STAT Blocks
Easy Setup R79
8 switch Bank
M2 R78
C
M1 C1 C2
SW3 HP < SYSTEM> OTHER R54 W/E
DF < HP > CONV
24 VAC K4 HC < TSTATS> HP
R55 O/B
O < RV > B
T’FORMER OAS < STAGING> TIMER
R66
C9
R56 Y
OFF < 50% RULE > ON
Polarized R OFF < SAS > ON U6 R57 R
Power Input D5 GAS < FAN > HYDRONIC
G
R58
Terminals R19 Z1
C K5 R59
R20
R60
ZONE1
SYSTEM
LED1 STATUS R35
T STAT
R21
OAS
R61
C
G D6 LED2
Isolated HVAC R22 R62 W/E Multi
System Y2 K 6 R23 LED3 SAS U7 Functional
Terminal Y1 R24
R63 O/B Zone 1
Block
LED 4 ZONE 3 R71
Y
O R25
R64 Thermostat
D7 R26 LED 5 ZONE 2 R Terminal
W1 B R65
Block
K7
R27
LED 6 ZONE 1 R68 G
W2 E R28 ONE
Isolated Common R67
terminal. Useful
RH R29
LED7
FAN U8 ZONE
when HVAC RC R30
R69
D8 LED 8 Y2
troubleshooting C K8
R31 R70 EM
RC RH R32
LED 9 Y1 R73
LINK
On-Board
R33 LED10 W1 B R72
R34 R77
CUTTABLE D9 LED11 W2 EM
Rc/Rh Link R76 NORM
EWC
Figure 19
BMPlus3000 rev B SW 4
The BMPlus 3000 Zone Control System includes Module to Module Factory Wiring. We power up the Expansion Modules
for you. The XM2 Expansion module includes a Status LED and Damper Status LED’s.
See page 11 and 12 for drawing representations of a 5 and 7 zone system and appropriate dip switch settings.
All you have to do is:
1. Set the dip switches to your specific application.
2. Connect your thermostats, dampers and system wiring.
3. Power up the Main Module
4. Check System Operation.
5. Enjoy.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com 11
Setting the XM2
Expansion Panel BMPlus5000
DIP Switches
C1 STATUS U4
Each expansion U1
C11
R47 W/E
M2 D2
R13
R48 O/B
M1 R49
K3 C12 Y
R50
ZONE1 R51
R
U9
MOTOR
D3
C13
Y1 C14 R52
G
M6 F1
D4
R53 ZONE2
M4 + + U5 T STAT
R79
M2 R78
C
Provide Over-Current M1 C1 C2
SW3 HP < SYSTEM> OTHER
DF < HP > CONV
R54 W/E
Protection 24 VAC K4 HC < TSTATS> HP R55 O/B
O < RV > B
T’FORMER OAS < STAGING> TIMER
R66
R56 Y
To R OFF < 50% RULE > ON
C9
R
Line OFF < SAS > ON U6 R57
Voltage
D5 GAS < FAN > HYDRONIC R58 G
R19 Z1
C K5 R59
R20
R60
ZONE1
LED1 STATUS T STAT
24 vac transformer SYSTEM R21 R35
OAS
R61
C
G D6 LED2
R22 R62 W/E
Y2 K 6 R23 LED3 SAS U7
Y1 R24
R63 O/B
LED 4 ZONE 3 R71
Y
O R25
R64
D7 R26 LED 5 ZONE 2 R
W1 B R65
K7
R27
LED 6 ZONE 1 R68 G
W2 E R28 ONE
R67
RH R29
LED7
FAN U8 ZONE
RC R30
R69
D8 LED 8 Y2
C K8
R31 R70 EM
RC RH R32
LED 9 Y1 R73
LINK R33 LED10 W1 B R72
R34 R77
D9 LED11 W2 EM R76 NORM
EWC BMPlus3000 rev B SW 4
Figure 20
12 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
Setting the XM2 BMPlus7000
Expansion Panel
DIP Switches C1
U1
STATUS U4
R19 R21 C
T
Each expansion K1
+
R12 R14
W/E
S
D M6 R1 O/B T
panel has a 2 M R2
R11 R13
Y A
P M4 C3 R10 R15
T
position DIP switch. R M2 D3
R3 R40
R39
U3 D6 D7 R
Factory set to insure M1 R4
A 0< > 1 R36 R16
R37
G
A 0<> 2 R23
R22
the main module D K2 R5 R38
R20
C T
M6 U5
M Y1
U2
R30 R26
W/E S
recognizes each P M4 R6
R M2
R29 R25 O/B TA
expansion module in Z1
R28 R27 Y T DIP switch settings for
M1 D2 D4 D5
D1 R17
D8 R 2nd Expansion panel.
the proper sequence. R34
R35
R24
R18 G Zones 6 & 7
J1
EWC
C1 STATUS U4
U1
R19 R21 C
+ W/E T
K1 R12 R14 S
FACTORY D M6 R1
R11 R13
O/B T
M R2
Y A
SUPPLIED P M4 C3 R10 R15
T
M2 R40 D6 D7 R
POWER & DATA R D3
R3
R39
U3
G
M1 A 0< > 1 R36 R16
POLARIZED R4
A 0<> 2 R37
R22
R23
R M2
R29 R25 O/B TA
Protective
M1 D2 Z1
R28
D4
R27
D5
Y T DIP switch settings for
header caps not D1 R17
D8 R 1st Expansion panel.
R34 R24
shown for clarity R35
R18 G
J1
EWC Zones 4 & 5
DO NOT CONNECT
OR DISCONNECT
BUS CABLE
WHILE THE PANEL
J1
IS POWERED.
CONTROL SYSTEM D10 R36
21 43 140 26 D11 R37
14 28 40 46 130 150 19 33
D12 R38
ZONE3 7 35 37 49 120 160 12 40 D13 R39
MOTOR
110 170 R41
M6 OFF
42 34 52 5 47 SAS
STAGING LOW TEMP HIGH TEMP 2 ND STAGE HEAT R42
M4 R1
TIMER OAS
R2
LIMIT
R3
LIMIT
R4
DIFFERENTIAL SAS
C5 C7 C 15
M2 R15 C8
R43
OAS
K1 U3 R40
M1 R16 R14 D21 R82 OAS
R81
ZONE2 D1
R44
MOTOR U1 U2 ZONE3
R45
K2 T STAT
M6 C10
R46 C
RESET
M4 U4
C11
R47 W/E
M2 D2
R13
R48 O/B
M1 R49
K3 C12 Y
R50
ZONE1 R51
R
U9
MOTOR
D3
C13
Y1 C14 R52
G
M6 F1
D4
R53 ZONE2
M4 + + U5 T STAT
R79
M2 R78
C
Provide Over-Current M1 C1 C2
SW3 HP < SYSTEM> OTHER R54 W/E
DF < HP > CONV
Protection 24 VAC K4 HC < TSTATS> HP
R55 O/B
O < RV > B
T’FORMER OAS < STAGING> TIMER
R66
R56 Y
To OFF < 50% RULE > ON
C9
R OFF < SAS > ON R
Line GAS < FAN > HYDRONIC
U6 R57
Voltage
D5
R58 G
R19 Z1
C K5 R59
R20
R60
ZONE1
LED1 STATUS T STAT
24 vac transformer SYSTEM R21 R35
R61
C
G D6 LED2 OAS
R22 R62 W/E
Y2 K 6 R23 LED3 SAS U7
Y1 R24
R63 O/B
LED 4 ZONE 3 R71
Y
O R25
R64
D7 R26 LED 5 ZONE 2 R
W1 B R65
K7
R27
LED 6 ZONE 1 R68 G
W2 E R28 ONE
R67
RH R29
LED7
FAN U8 ZONE
RC R30
R69
D8 LED 8 Y2
C K8
R31 R70 EM
RC RH R32
LED 9 Y1 R73
LINK R33 LED10 W1 B R72
R34 R77
D9 LED11 W2 EM R76 NORM
EWC BMPlus3000 rev B SW 4
Figure 21
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
13
BMPlus 3000 Wiring Diagram
Dual Fuel Heat Pump
PC 6 Auxiliary Heat Activates via
PO 4 Outdoor air Temperature or
SUPPLY AIR SENSOR
Heat Pump Thermostat Emergency Input OUTDOOR AIR SENSOR
COM 1
J1
ND / URD DAMPERS CONTROL SYSTEM D10 R36
14
21
28 40
43
46 130
140
150 19
26
33 D11 R37 ZONE 3 THERMOSTAT
D12 R38
ZONE3 49 120 160 12
7 35 37 40 D13 R39
MOTOR
PC 6 M6 OFF 42 34 52
110 170
5 47 R41
HEAT 68
STAGING
SAS
LOW TEMP HIGH TEMP 2 ND STAGE HEAT
PO 4 M4 TIMER OAS LIMIT LIMIT DIFFERENTIAL
R42
SAS
R1 R2 R3 R4 C W Y R G
M2 C5 C7 C15
R43
OAS
COM 1 M1 K1 R15
R16
C8
R14
U3
D21
R40
R82 OAS
R81
ZONE2 D1 R44
MOTOR U1 U2 ZONE3
R45
K2 T STAT
M6 C10
M4 RESET U4
R46 C
M2 C11
R47 W/E
PC 6 D2
R13 R48
O/B
M1 K3 R49
PO 4 C12 Y
R50
R ZONE 2 THERMOSTAT
ZONE1 R51
COM 1 MOTOR
D3
U9
C13
C14
G
Y1
M6 F1
D4
R52 HEAT 72
ZONE2
M4 + + U5
R53
T STAT
R79
M2 R78
C C W Y R G
M1 C1 C2
SW3 HP < SYSTEM> OTHER R54 W/E
DF < HP > CONV
24 VAC K4 HC < TSTATS> HP R55 O/B
O < RV > B
T’FORMER OAS < STAGING> TIMER
R66
R56 Y
To Line Voltage. R OFF < 50% RULE > ON C9
R
OFF < SAS > ON U6 R57
Provide Over-Current D5 GAS < FAN > HYDRONIC
R58 G
Protection. C K5
R19 Z1
R59
R20
ZONE1
24 vac transformer SYSTEM
LED1 STATUS R60
T STAT
R21 R35
40va G D6 LED2 OAS
R61
C
R22
Y2
R62 W/E ZONE 1 THERMOSTAT
K6 R23 LED3 SAS U7
Y1 R24
R63 O/B
LED 4 ZONE 3 R71
Y
O R25
R64 HEAT 70
W1 B
D7 R26 LED 5 ZONE 2 R65
R
2 STAGE GAS W2 E K7
R27
LED 6 ZONE 1 R68 G C W Y R G
R28
R67 ONE
OUTDOOR FURNACE RH R29
LED7
FAN U8 ZONE
RC R30
R69
HEAT PUMP G D8 LED 8 Y2
C K8
R31 R70
EM
Y2 Y2 RC RH R32
LED 9 Y1 R73
LINK R33
Y1 Y1 LED10 W1 B R72
R34 R77
O/B O/B
D9 LED11 W2 EM
NORM
EWC
R76
X/W W1 BMPlus3000 rev B SW 4
R W2
C R All wiring should be done to local and
C national codes and ordinances. Use
WARNING: THESE PANELS ARE DESIGNED
FOR USE WITH 24VAC. DO NOT USE OTHER color-coded, multi-conductor wire. Wire
VOLTAGES! USE CAUTION TO AVOID number to number or letter to letter on
ELECTRIC SHOCK OR EQUIPMENT DAMAGE. each control.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
BMPlus 3000 Wiring Diagram
2 STAGE GAS HEAT WITH 2 STAGE A/C
PC 6 2nd Stage Heat & 2nd Stage Cool Activates via
The Adjustable Timer. SUPPLY AIR SENSOR
PO 4 ZONE 3 THERMOSTAT
COM 1 HEAT
J1 68
CONTROL SYSTEM D10 R36
ND / URD DAMPERS 21 43 140 26 D11 R37
C W Y R G
14 28 40 46 130 150 19 33
D12 R38
ZONE3 7 35 37 49 120 160 12 40 D13 R39
MOTOR
110 170 R41
PC 6 M6 OFF 42 34 52 5 47 SAS
STAGING LOW TEMP HIGH TEMP 2 ND STAGE HEAT R42
M4 TIMER OAS LIMIT LIMIT DIFFERENTIAL SAS
PO 4 R1 R2 C5 R3 C7
R4 C15
M2 R43
R15 C8 OAS
K1 U3 R40
COM 1 M1 R16 R14 D21 OAS
R82
R81
ZONE2 R44
D1 U2 ZONE3
MOTOR U1
R45
K2 T STAT
M6 C10
RESET R46 C
U4
M4 R47
ZONE 2 THERMOSTAT
PC 6 C11 W/E
M2 D2 R48
R13 O/B
M1 R49 HEAT 72
PO 4 K3 C12 Y
R50
COM 1 ZONE1 R51
R
U9 C W Y R G
MOTOR C13
C14
G
D3 Y1 R52
M6 D4
F1 R53 ZONE2
M4 U5 T STAT
+ + R79
M2 R78
C
M1 C1 C2 R54 W/E
SW3 HP < SYSTEM> OTHER
DF < HP > CONV R55
24 VAC K4 HC < TSTATS> HP O/B
O < RV > B R66
T’FORMER OAS < STAGING> TIMER R56 Y
C9
OFF < 50% RULE > ON
To Line Voltage. R OFF < SAS > ON U6 R57 R
D5 GAS < FAN > HYDRONIC
Provide Over-Current R58 G
R19 Z1
C K5 R59
Protection. R20 ZONE1
LED1 R60
SYSTEM
STATUS R35
T STAT
24 vac transformer R21 R61
LED2 OAS C ZONE 1 THERMOSTAT
G D6 R22
40 va R62 W/E
Y2 K 6 R23 LED3 SAS U7
R63 O/B HEAT 70
Y1 R24
LED 4 ZONE 3 R71
R25 Y
O R64
D7 R26 LED 5 ZONE 2 R C W Y R G
R65
W1 B R27
2 STAGE GAS K7 LED 6 ZONE 1 R68 G
W2 E R28 ONE
FURNACE R67
OUTDOOR LED7
RH R29 FAN U8 ZONE
CONDENSING R69
RC R30
D8 LED 8 Y2
UNIT G R31 R70
C K8
EM
LED 9 Y1
RC RH R32 R73
Y2 Y2 LINK R33 LED10 R72
W1 B
Y1 Y1 R34 R77
D9 LED11 EM
W2 R76
R W1 NORM
SW 4
C W2 EWC BMPlus3000 rev B
R
C All wiring should be done to local
WARNING: THESE PANELS ARE DESIGNED and national codes and ordinances.
FOR USE WITH 24VAC. DO NOT USE OTHER Use color-coded, multi-conductor
VOLTAGES! USE CAUTION TO AVOID ELECTRIC wire. Wire number to number or
SHOCK OR EQUIPMENT DAMAGE. letter to letter on each control.
EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com
T R O U B L E S H O O T I NG
SYMPTOM SOLUTIONS
LED’S are responding properly but Check HVAC system wiring for proper connections.
HVAC system is malfunctioning. Check HVAC system wiring for shorts/miswiring.
Check HVAC System.
Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.
LED’s are not responding properly Check HVAC system wiring for shorts/miswiring.
and HVAC system is malfunctioning. Check HVAC system wiring for proper connections.
Check HVAC thermostat for proper connections.
Refer to Technical Bulletin for correct Setup/Wiring/Dip Switch settings.
LED’s illuminate and HVAC system Check damper motor wiring for proper connections.
functions normally but dampers do Check damper motor 24vac transformer voltage/fuse/BMPlus circuit breaker.
not respond. Check damper motor wiring for shorts/miswiring.
Refer to Technical Bulletin for correct Setup/Wiring.
REFER TO THE DAMPER MOTOR TESTING PAGE 9
LED’s do not illuminate and HVAC Check HVAC & BMPlus system transformer supply voltage.
system does not respond. Check HVAC & BMPlus system 24vac transformer voltage, fuse & the BMPlusB
circuit breaker.
Check HVAC & BMPlus system wiring for shorts/miswiring.
ISOLATING 24vac SHORTS Disconnect the wire(s) from the ‘R’ terminals on the BMPlus 3000 thermostat
terminal blocks , and the “M2/M4/M6’’ terminals on the BMPlus 3000 damper
F1 circuit breaker protects the motor terminal blocks. Restore power. If the short is no longer present, Ohm
BMPlus 3000 and reacts to a short in out the thermostat and damper field wiring for shorts/misconnections. Replace
the damper motor or thermostat or repair wires as necessary. Restore power. Module(s) will resume operation.
component and field wiring.
TESTING THERMOSTATS
Check to make sure that the thermostat Rc and Rh terminals are connected together, unless your application requires
separation of these circuits.
Use the (C) Common terminal provided at each thermostat terminal block to wire up full 24 vac hard-wired thermostats.
You should reference the (C) Common terminal when troubleshooting incoming thermostat demand signals, even if no wire is
connected there.
Make sure that you wire and configure your thermostats for the correct application. Most thermostats built today can be field
configured to operate as regular Heat/ Cool type or as Heat Pump type. Remember that you can use regular Heat/Cool
thermostats on the BMPlus 3000 for Heat Pump applications.
TECHNICAL SUPPORT
EWC Controls provides superior toll free Troubleshooting Support for the BMPlus 3000 when you are on the job site!
Call 1-800-446-3110 Monday - Friday 8am to 5pm EST
Otherwise call 1-732-446-3110 for information on the BMPlus 3000 and other ULTRA-ZONE products..
When calling for Technical Support, please have a multi-meter, pocket screwdriver, and wire cutter/stripper handy.
16 EWC Controls Inc. 385 Highway 33 Englishtown, NJ 07726 800-446-3110 FAX 732-446-5362 E-Mail- info@ewccontrols.com