CLIENT:
SBM OPERATIONS
PROJECT:
ES45000 PECEELPF441003 A5
DOCUMENT TITLE:
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
This specification captures the scope of supply, the functional requirements and the detailed technical requirements of a package,
piece of equipment or services that forms part of a wider system.
o
Status/ Date N of
Written by Checked by Approved by Approved by
Revision (DD-MMM-YY) Pages
INFORMATION ON STATUS:
C For Comments and Approval
V Valid for Construction
A Approved for Construction
D Deleted
Copyright © 2019 SBM Offshore N.V. and/or one or more of its subsidiaries and/or affiliates, as the case may be. This document is the property of SBM Offshore N.V.
and/or one or more of its subsidiaries or affiliates. This document or any part thereof is confidential and may not be distributed, copied, multiplied, or used in any other way
without the express written permission of the copyright holder(s). All rights are reserved.
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
The below tags are indicated in the content of this document to identify the critical
technical requirements:
‘Health & Safety” identify a requirement for the mitigation of a hazard to personnel health
S
and safety, beyond ‘regulation’ requirements.
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
TABLE OF CONTENTS
1. PURPOSE ......................................................................................................................... 5
2. REFERENCES .................................................................................................................. 5
7. GENERAL REQUIREMENTS.......................................................................................... 21
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
1. PURPOSE
This specification, and associated documents, governs the minimum requirements for the
design, construction, testing and delivery of Power Transformers to be installed on Floating
Production Installations.
Power transformers above 5MVA are outside the scope of this specification and must be
considered on a case by case basis.
2. REFERENCES
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
May: indicates a course of actions that is permissible within the limit of the
standard (a permission).
Shall: indicates an absolute requirement which shall be followed strictly in
order to conform to the standard.
Should: indicates a recommendation. Alternative solutions having the same
functionality and quality are acceptable.
COMPANY: SBM Offshore or as indicated in the contract or purchase order.
3.3 ABBREVIATIONS
AF Air Forced (Ventilation)
AN Air Natural (Ventilation)
AN/AF Air Natural/Air Forced – (Ventilation with thermostatically controlled
fan(s))
BIL Basic Insulation Level
CoG Centre of Gravity
DETC De-Energized Tap-Changer
FAT Factory Acceptance Test
GRP Glass Reinforced Plastic
HV High Voltage (any voltage higher than 1000V AC)
KNAF Liquid cooling natural (convection) Air Forced Ventilation
KNAN Liquid cooling natural (convection) Air Natural Ventilation
LV Low Voltage (any voltage up to and including 1000V AC)
MODU Mobile Offshore Drilling Units
PCBs Poly-Chlorinated Biphenyls
PCTs Poly-Chlorinated Terphenyls
PE Protective Earth
SPL Sound Pressure Level
VPI Vacuum Pressure Impregnated
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
4. SCOPE OF SUPPLY
CONTRACTOR’s scope of supply shall include, but not necessarily be limited to, Power
Transformer comprising of the following:
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
5. FUNCTIONAL REQUIREMENTS
R Power transformers for MODU are to be constructed and installed in accordance with the
requirements of ABS doc. ref. [2].
S
Transformers subject to a fire hazard. Restricted flammability is required. The emission of toxic
substances and opaque smokes shall be minimised in accordance with IEC doc. ref. [3], Part-
11.
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
5.3 PERFORMANCE
Power transformers shall be suitable for continuous duty at the rated power and specified
ambient conditions on all taps without exceeding the temperature rise and without any
deleterious effect of any kind.
Transformer lightning impulse withstand voltage or basic insulation level (BIL), temperature
ratings, over-voltage operation, fault current capability and the losses, impedance, and ratios
shall be within the tolerances in accordance with IEC doc. ref. [3].
The transformers shall be designed, selected and erected in accordance with IEC doc. ref. [4]
Part-14; inspected and maintained in accordance with IEC doc. ref. [4] Part-17.
Note: Vendor shall submit training and competency records to demonstrate the personnel who are
installing Ex-certified equipment are qualified as per IEC60079 series requirement.
5.3.5.2 Indoors
IP23 unless otherwise specified in the datasheet.
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
CONTRACTOR shall submit a copy of a short circuit withstand test previously performed on a
"similar" transformer. Test method and definition of "similar" transformer shall be as per IEC
document ref. [3] part 5.
• Dry-type transformer (in accordance with IEC doc. ref. [3], Part-11):
120 °C
• Liquid-Immersed transformer (in accordance with IEC doc. ref. [3], Part-1):
75 °C.
5.3.10 Efficiency
CONTRACTOR shall specify the transformer efficiency at full load, p.f. = 0.8.
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
• Indoor: ≤ 85 dB(A) at 1m
• Outdoor: ≤ 85 dB(A) at 1m.
R Emergency service transformers shall be able to operate with 22.5 degree list and 10 degree
trim in accordance with ABS doc. ref. [1].
Transformers key components that require maintenance shall be easily accessible and shall
not require full disassembly.
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
6. TECHNICAL REQUIREMENTS
General discipline technical requirements section defined in the GTS document ref. [11] that
are applicable to CONTRACTOR package are listed in table format in below sections.
Specific discipline technical requirements that are applicable to CONTRACTOR package are
defined in below sections.
Mechanical Handling
SECTION REQUIREMENTS
Lifting appliance and devices Refer to GTS ref. [11]
6.3 MATERIAL
CONTRACTOR shall comply with the Material requirements section of GTS document ref.
[11], as defined in below table:
Material
SECTION REQUIREMENTS
Coating System selection Refer to GTS ref. [11] and section 6.3.1.1
Surface Preparation and Coating Application Refer to GTS ref. [11] and section 6.3.1.2
GTS document ref. [11] requirements related to marine atmosphere paint system shall be
applicable to Liquid-immersed Transformers.
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
6.4 ELECTRICAL
CONTRACTOR shall comply with the Electrical requirements section of GTS document ref.
[11] as listed in below table.
Electrical
SECTION REQUIREMENTS
Refer to GTS ref. [11] and 5.3.5 and
Ingress protection
partially 6.4.7
Hazardous area Refer to GTS ref. [11] and 5.3.3
Earthing and bonding Refer to GTS ref. [11] and 6.4.8
Cable runways Refer to GTS ref. [11]
Cable Installation Refer to GTS ref. [11]
LV/LV dry-type transformers shall be vacuum pressure impregnated (VPI) with an insulating
Class H. The temperature rise shall not exceed the Class F requirements as per IEC doc. ref.
[3] Part-11, paragraph 11.1, Table 2.
In case of an ambient air temperature above the standard conditions (refer to paragraph 5.3.4,
the temperature rise shall be reduced as per paragraph 11.2 of IEC doc. ref. [3] Part-11.
6.4.1.2 Accessories
Dry type transformers shall be provided with the following accessories unless otherwise
specified in project particular specification:
• Temperature indicator
• All transformers that are greater than 50kVA shall have embedded winding temperature
detectors for temperature (overload) monitoring, as follows:
• HV/LV dry-type transformers shall have thermal protection by means PT 100 resistance
type temperature detectors (minimum one active and one spare measurement per
phase) with alarm and trip relays by others
• LV/LV dry-type transformers shall have thermal protection by means of thermistors type
temperature detectors or PT100 (as specified in project documentation, minimum one
measurement per phase) with alarm and trip relays by others
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
• Air to water heat exchanger shall be equipped with water leak detector (applicable to
AF/WF transformers only)
S • Each transformer shall be provided with an anti-condensation heater to be connected to
a 230VAC, 1-ph, and 60Hz supply provided by PURCHASER.
For transformers installed in hazardous area, provision shall be made to prevent electrostatic
discharges in accordance with IEC doc. ref. [4], Part-14.
6.4.2.1 Insulation Class
The insulation shall be class A and temperature rise as follows:
The core laminations shall be accurately cut with alternative lap joints having minimum air gap
and rigidly clamped to result in an assembly with minimum core loss and noise generation.
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
The core shall preferably be of a boltless construction, i.e. the complete magnetic circuit free
from bolt holes. These structures shall also support windings and shall be provided with lifting
lugs suitable for the total transportation weight.
S The core assembly shall be earthed by a single removable test link, connected to the
transformer grounding terminal or bar.
6.4.4 Windings
R Each HV/LV transformer shall be provided with an earthed metallic screen between each
primary and secondary winding, for the purpose of protecting the LV windings from dangerous
voltage from the HV windings, as per ABS doc. ref. [1]. The metallic screen shall be sized to
withstand the HV winding earth fault current of the intensity and duration indicated in project
documentation.
Where aluminium windings are utilized for liquid-immersed transformer, the winding to terminal
pad connection should also be liquid-immersed.
Tap changer box for outdoor transformers shall be suitable for Zone 2, IIA, and T3 or better.
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
S The tap-changer driving rod shall be sealed against air or liquid leakage and the design shall
be such that it may be set only into the predefined positions where the winding is connected
(no intermediate position with winding disconnected).
S The tap positions shall be clearly marked and a padlocking facility shall be provided to lock the
tap-changer switch in the selected position.
• HV - as per ABS doc. ref. [1] 4.8.5 - 3.7.1(a) e.g. 120mm for 11kV nominal voltage
• LV (all voltages) - 25mm
• HV - as per ABS doc. ref. [1] 4.8.5 - 3.7.1 (d) table i) e.g. 150mm for 11kV nominal
voltage
• LV (all voltages) - 35mm.
The transformer enclosure shall be equipped with windows for infrared inspection of the cable
connections and coils interconnections bolting.
For liquid immersed transformers power cables shall be terminated inside terminal boxes
suitable for Zone 2, IIA and T3 or better, unless otherwise specify in the datasheet.
• To connect the specified number and size of cables including its HV termination
• To allow the conductors straight connection to the terminals without introducing
excessive cable bending within the enclosure/box, especially if multicore cables are
used
• To avoid applying stress to the bushings and terminations.
Cable entry shall be via cable glands. Multi Cable Transits may be used on indoor
transformers instead of cable glands, if specified in the datasheet.
R Non-magnetic gland plates shall be provided for mounting of cable glands for single core
cables in accordance with ABS doc. ref. [1].
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
6.4.6.1 HV connection
For each HV/LV Transformer the primary HV connection side shall be provided with:
• Liquid immersed transformers: Euromold (Elastimold) termination and connection kits for
each cable termination
• Dry type transformers: bolted lugs HV termination kit.
Kits shall be supplied based on cable information provided in the datasheet.
6.4.6.2 LV connection
The flags shall have insulated mechanical supports at both sides suitable for the short circuit
level at the secondary side. Measures against galvanic corrosion between aluminium windings
and copper flags shall be provided. (If aluminium windings are utilized, special precautions
should be taken at the terminations).
If connections to windings are specified by bus duct, the bus-duct and its flange shall be
supplied by others, however all connecting bus-bar, nuts and bolts and other accessories shall
be provided by CONTRACTOR.
In this case flexible bus-bar shall be used for the connection of bus duct.
For cable to the PT100 / PTC, junction box shall be provided with a cable support (flat bar) for
internal wiring. The temperature sensors for the windings shall be clearly marked and wires
shall be marked according to terminal number of terminal strip.
S
Each junction box shall have an earth bolt at the outside for bonding to the transformer
assembly. For GRP junction boxes, this bolt shall terminate at the inside to provide an earthing
means inside the junction box to the protective earth (PE) bar.
All indoor junction boxes shall have Ingress protection to IP44 and shall be suitable for marine
type installation.
Contractor shall supply cable glands for the cables in his scope of supply. For liquid filled
transformers for outdoors installation, cable glands shall be certified, nickel plated brass
material, Hawke or CMP manufactured compression or displacement seal type with ISO
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
metric threads.
For dry type transformers located indoors in non-hazardous areas, cable glands shall be
general industrial type.
All outdoor junction boxes shall be stainless steel 316L, Ex e, and IP66.
High quality stainless steel 316L fixings / hinges shall be used to connect the gland plates and
door to the enclosure chassis. Metal to metal contact shall be maintained throughout the
connection of all the independent components.
Terminal strips shall be mounted on a stainless steel 316L back plate or support rail. The
support rail shall be raised 30 mm from base of box chassis by means of stand-off pillars.
6.4.8 Earthing
S Each transformer shall be provided with 2 (two) off earthing bosses on the outside of each
transformer enclosure for fixed earthing and bonding purposes.
S Dedicated PE bar for termination of the single core earthing cable or cable armours (as
applicable).
S Internal earth cables shall be insulated, coloured green/yellow and have a minimum size
35mm2. The colour combination green and yellow shall be such that on any 15mm length of
the conductor where colour coding is applied, one of these colours at least 30% and not more
than 70% of the surface and the other covering the remainder of that surface.
S Each HV/LV transformer shall be provided with earthing bullets on the HV and LV side for
temporary safety earthing.
6.4.9 Wiring
Wiring of auxiliary equipment on the transformers shall be securely fixed to prevent damage by
vibration, excessive movement and other hazards. The fixing of wiring shall not make rigid any
equipment or connecting boxes which have been specially mounted on resilient fixings.
Cables and wires shall be identified by permanent marking such as ferrules in line with the
relevant wiring diagram.
Internal wiring shall be multi-stranded tinned copper, flame retardant, low smoke and halogen
S
free. Wiring shall have a cross-sectional area not less than 2.5mm2 for CT and PT’s. Control-
circuit cables shall be not less than 1.0mm2. Wire insulation colours shall comply with IEC doc.
ref. [6].
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
Where specified, forced air with water cooling (AF/WF) shall be provided.
Air to water heat exchanger shall be of the double tube type and shall be designed according
to the cooling water chemistry and operating conditions specified in project documentation.
Access plates shall be stiffened and internal wiring shall be properly supported.
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
of steel sheet. Front and rear covers shall be removable to provide access to a terminal
compartment. Covers shall be fixed by means of bolts. This enclosure shall be fixed to the
transformer frame and equipped with lifting lugs. The transformer assembly shall be mounted
on a base frame.
The tank material shall be hot-dip galvanized mild-steel and the radiators material shall be
stainless steel 316L.
The tank, cover, valves and all accessories shall be hermetically sealed against air, water and
insulating liquid.
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
7. GENERAL REQUIREMENTS
General activities and associated deliverables requirements defined in the GTS document ref.
[11] that are applicable to CONTRACTOR package are listed in table format in below sections.
7.3 ENGINEERING
CONTRACTOR shall comply with the Engineering requirements section of GTS documents
ref. [11] as defined in below table.
Engineering
CDR CODE DOCUMENT NAME REQUIREMENTS
NP Nameplate Detail / Rubbing Refer to GTS ref. [11] and 7.3.1
FA TAG Register Refer to GTS ref. [11]
CWT Classification Society Type Approval Letter Refer to GTS ref. [11] and 7.3.2
CW Classification Society Final Release Note Refer to GTS ref. [11]
AN As Built Weight / CoG Refer to GTS ref. [11]
AK Equipment Data Sheets Refer to GTS ref. [11]
AC General Arrangement Drawings Refer to GTS ref. [11]
AO Foundation Plan Refer to GTS ref. [11]
BC Cable Index Refer to GTS ref. [11]
BG Interconnection Diagrams / Internal Wiring Diagrams Refer to GTS ref. [11]
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
Engineering
CDR CODE DOCUMENT NAME REQUIREMENTS
BL Electrical Motor Data Sheets Refer to GTS ref. [11]
BN Hazardous Area Equipment List Refer to GTS ref. [11]
BM Hazardous Area Equipment Certificates Refer to GTS ref. [11]
7.4 FABRICATION
CONTRACTOR shall comply with the Fabrication requirements section of GTS document ref.
[11] as defined in below table.
Fabrication
CDR CODE DOCUMENT NAME REQUIREMENTS
DR Surface Coating Procedures Refer to GTS ref. [11]
DS Surface Coating Records Refer to GTS ref. [11]
7.5 TESTING
CONTRACTOR shall comply with the Testing requirements section of GTS document ref. [11]
as defined in below table.
Testing
CDR CODE DOCUMENT NAME REQUIREMENTS
CU Calibration Certificates Refer to GTS ref. [11]
HC Noise Test Records Refer to GTS ref. [11]
CS Factory Acceptance Test (FAT) Procedures Refer to GTS ref. [11] and 7.5.1
CT Factory Acceptance Test (FAT) Records Refer to GTS ref. [11] and 7.5.2
OFFICIAL COPY - ES45000 - PECEELPF441003A5 - - - PDF Generated on 23-Aug-2019 9:42AM
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
HV/LV three-phase transformers of 100kVA and above are to be tested in the presence of the
R ABS Surveyor in accordance with ABS doc. ref. [1].
ELECTRICAL
POWER TRANSFORMER
SPECIFICATION
Delivery Requirements
CDR CODE DOCUMENT NAME REQUIREMENTS
EE Preservation Procedure Refer to GTS ref. [11]
EA Packing / Shipping Arrangement Procedure Refer to GTS ref. [11]
EB Packing List Refer to GTS ref. [11]
EC Installation/Erection Field Handling Procedures Refer to GTS ref. [11]
7.7 COMMISSIONING
CONTRACTOR shall comply with the Commissioning requirements section of GTS document
ref. [11] as defined in below table.
Commissioning
CDR CODE DOCUMENT NAME REQUIREMENTS
CY Commissioning Procedures Refer to GTS ref. [11]
7.8 MAINTENANCE
CONTRACTOR shall comply with the Maintenance requirements section of GTS document
ref. [11] as defined in below table.
Maintenance
CDR CODE DOCUMENT NAME REQUIREMENTS
FC Maintenance Manual Refer to GTS ref. [11]
FI Maintenance Schedule Refer to GTS ref. [11]
FE List of Special Tools or Equipment Refer to GTS ref. [11]
FH SPIR Forms / Two Years' / Capital Spares Refer to GTS ref. [11]
FF Commissioning / Start up Spare Parts Refer to GTS ref. [11]
7.9 OPERATION
CONTRACTOR shall comply with the Operation requirements section of GTS document ref.
[11] as defined in below table.
Operation
CDR CODE DOCUMENT NAME REQUIREMENTS
FB Operating Manual Refer to GTS ref. [11]
IND Index Vendor Data Book Refer to GTS ref. [11]