FEDERAL ENERGY MANAGEMENT PROGRAM

Cooling Towers:
Understanding Key
Components of

Source: Paul Johnston-Knight


Cooling Towers and
How to Improve
Water Efficiency

Introduction Overview water is evaporated into the air passing


Federal laws and regulations require Cooling towers are an integral component through the tower. As the water evapo-
Federal agencies to reduce water use of many refrigeration systems, providing rates, the air absorbs heat, which lowers
and improve water efficiency. Namely, comfort or process cooling across a broad the temperature of the remaining water.
Executive Order 13514 Federal range of applications. They are the point This process provides significant cool-
Leadership in Environmental, Energy, in the system where heat is dissipated to ing to the remaining water stream that
and Economic Performance, requires an the atmosphere through the evaporative collects in the tower basin where it can be
annual two percent reduction of water use process, and are common in industries pumped back into the system to extract
intensity (water use per square foot of such as oil refining, chemical process- more process or building heat, thereby
building space) for agency potable water ing, power plants, steel mills, and many allowing much of the water to be used
consumption as well as a two percent different manufacturing processes where repeatedly to meet the cooling demand.
reduction of water use for industrial, process cooling is required. They are The amount of heat that can be rejected
landscaping, and agricultural applica- also commonly used to provide comfort from the water to the air is directly tied
tions. Cooling towers can be a significant cooling for large commercial buildings to the relative humidity of the air. Air
source of water use for both of these cat- including airports, office buildings, with a lower relative humidity has a
egories of water use at Federal facilities. conference centers, hospitals, and hotels. greater ability to absorb water through
To realize potential savings it is essential evaporation than air with a higher relative
Cooling tower structures vary greatly
for Federal agencies understand the key humidity, simply because there is less
in size and design, but they all function
components of cooling towers and how water in the air. As an example, consider
to provide the same thing: liberation of
to improve water efficiency of the system cooling towers in two different locations–
waste heat extracted from a process or
as a part of a comprehensive approach to one in Atlanta, Georgia, and another in
building system through evaporation of
water management. Albuquerque, New Mexico. The ambient
water. In technical terms, cooling towers
are engineered and designed based on air temperature at these two locations
a specified cooling load, expressed in may be similar, but the relative humidity
In this Fact Sheet: in Albuquerque on average will be much
refrigeration tons.(1) The cooling load
• Introduction
is determined by the amount of heat lower than that of Atlanta’s. Therefore,
• Overview that needs to be extracted from a given the cooling tower in Albuquerque will be
process or peak comfort cooling demand. able to extract more process or building
• Structure
The cooling tower must be adequately heat and will run at a cooler temperature
• Basic Cooling Tower Terms because the dry desert air has a greater
sized to reject this same amount of heat
• Types of Towers to the atmosphere. capacity to absorb the warm water.
• Important Properties of Water
Cooling towers are used to reject heat Cooling towers can be split into two
• System Calculations through the natural process of evapora- distinct categories: open circuit (direct
tion. Warm recirculating water is sent to contact) and closed circuit (indirect)
• Factors That Limit Cycles of Concentration
the cooling tower where a portion of the systems. In open circuit systems the recir-
• System Concerns culating water returns to the tower after
• Treatment Options (1) One ton of refrigeration is equal to 12,000 Btu/hour.

continued >
2 FEDERAL ENERGY MANAGEMENT PROGRAM

gathering heat and is distributed across different components of a cooling detail in the System Concerns section).
the tower where the water is in direct tower structure. Development of any of these problems
contact with the atmosphere as it recircu- greatly reduces the cooling efficiency
First, the water is distributed evenly
lates across the tower structure. Closed and in severe cases can collapse portions
across the top of the cooling tower
circuit systems differ in that the return of the tower fill or tower structure. To
structure. Tower distribution decks can
fluid (often water, or sometimes water avoid this, film fill should be inspected
be a series of spray nozzles oriented up
mixed with glycol) circulates through the routinely to ensure it is clean and free of
or down (like a landscaping sprinkler
tower structure in a coil, while cooling debris, scale, and biological activity.
system) to uniformly distribute the water
tower water recirculates only in the tower
over the tower structure. In some cases, To minimize losses due to drift and help
structure itself (see Figure 1). In this case,
the distribution deck may just be a series direct airflow into the tower, louvers and
the return fluid is not exposed directly to
of holes through which the water falls drift eliminators are commonly used.
the air.
onto the tower structure. Regardless Louvers are most often seen along the
the distribution deck must uniformly sides of the tower structure, while drift
apportion the recirculating water across eliminators reside in the top section of the
the tower structure. Broken nozzles or tower to capture entrained water droplets
plugged orifices will impede uniform that may otherwise leave through the
distribution across the tower structure, stack. Damaged or incorrectly oriented
negatively impacting the overall heat louvers along with damaged drift elimi-
exchange capacity of the system. nators will lead to excessive losses due to
drift from the tower structure. Therefore,
As the water falls from the distribution
louvers and drift eliminator sections
deck, the surface area is further expanded
should be routinely inspected and
in the fill section. Older tower systems
repaired to ensure optimal water usage.
may feature splash bars made of plastic,
fiberglass, or wood that serve to break the After the water passes through the fill
falling water into tiny droplets. In recent it cascades down to a collection basin
years, many different forms of labyrinth- at the base of the tower structure. From
Figure 1. Example of a Closed Circuit Cooling like packing or film fill have been the basin the cold water can be pumped
Tower. incorporated. The closely packed nature back into the system to extract process
of film fill causes the water to travel or comfort cooling needs and begin the
through this portion of the tower in thin cycle all over again.
Structure streams, improving thermal efficiency
Cooling towers are the primary com- By design, cooling towers consume large
and the evaporation rate, thereby increas-
ponent used to exhaust heat in open volumes of water through the evapora-
ing heat rejection (see Figure 3).
recirculating cooling systems. They tion process to maintain comfort cooling
are designed to maximize air and water or process cooling needs, although they
contact to provide as much evaporation use significantly less water than similar
as possible. This is accomplished by capacity once-through cooling systems.
maximizing the surface area of the water Because the evaporative loss is water
as it flows over and down through the containing little to no dissolved solids,
tower structure. Figure 2 illustrates the the water remaining in the cooling tower
becomes concentrated with dissolved
solids, which can lead to scaling and
corrosive conditions. To combat these
problems, water with high total dissolved
solid content must be drained from the
Figure 3. Relative Thermal Performance of system via “blowdown.” The associated
Different Types of Fill. losses caused by blowdown, evaporation,
drift, and system leaks must be accounted
There are several variations of film fill for by system make-up requirements.
geometries commercially available, Figure 4 illustrates these water system
and though they do greatly increase the flow locations in generic terms.
heat rejection rate over splash-type fills,
they are also much more susceptible to
fouling, scaling, and microbiological
growth (these are discussed in greater
Figure 2. Overview of Cooling Tower Structure
Components.
continued >
FEDERAL ENERGY MANAGEMENT PROGRAM 3

Cross-Flow Towers – Cross-flow cooling


towers are structured so that air flows
horizontally across the falling water
(see Figure 6). This design provides less
resistance for the air flow, thereby reduc-
ing the fan horsepower required to meet
the cooling demand. These towers usually
feature gravity-fed water distribution
decks that are either open and uncovered,
or that are covered to limit algae growth
and debris from getting into the distribu-
tion deck. Gravity-fed distribution decks
have evenly spaced openings that the
water drops through to be spread across
the tower fill.

Figure 4. Illustration of Water Flow Across a Cooling Tower.

Basic Cooling Tower Terms by fans located at the base of the tower
Blowdown – Water discharged to remove (referred to as forced draft), or pulled
high mineral content system water, through by fans located at the top
impurities, and sediment. of the tower (referred to as induced draft).
Induced draft towers tend to be larger
Cycles of Concentration – Technical than forced draft units.
term used to describe the mass flow rela-
tionship between the amount of system Natural Draft Towers – Natural draft Figure 6. Example Cross-flow Cooling Tower.
feed water and the amount of blowdown towers are designed to move air up
sent down the drain. Also referred to as through the structure naturally without Counter-flow Towers – Counter-flow
concentration ratio, cycles of concentra- the use of fans. They use the natural law cooling towers have upward air flow that
tion correlates to the effective use of of differing densities between the ambient directly opposes the downward flow of
water in your system to provide heating air and warm air in the tower. The warm the water providing very good thermal
or cooling needs. High cycles of concen- air will rise within the chimney structure efficiency because the coolest air contacts
tration are directly related to low levels of because of its lower density drawing cool the coolest water (in the bottom section
water loss from your system. ambient air in the bottom portion. Often of the tower structure).
times these towers are very tall to induce
Dissolved Solids – The amount of dis- adequate air flow, and have a unique
solved minerals present in the water. shape giving them the name “hyperbolic” Important Properties of Water
towers (see Figure 5). A primary consideration for the operation
Drift – Droplets of water entrained in the
of the cooling tower system is the water
air leaving the top of the tower, or blown
quality of the make-up source. Differing
from the side of the tower by crosswinds.
sources present differing challenges.
Make-up – Water supply needed to Surface water sources include lakes,
replace all losses due to evaporation, rivers, and streams, while groundwater
leaks, or discharge in cooling systems. sources consist of wells or aquifers.
Depending on the location, surface water
sources will have seasonal variations
Types of Towers
and can carry high levels of suspended
Cooling Towers – Cooling towers are silt and debris that cause fouling if
classified by the direction of air flow not removed by pre-filtration systems.
(counter-flow or cross-flow) and the Groundwater sources don’t have the
type of draft (mechanical or natural). seasonal variations that surface water
Mechanical Draft Towers – sources have, but depending on the
Mechanical draft towers have air geology of the region, they can have high
forced through the structure by a fan. Figure 5. Hyperbolic Cooling Towers levels of dissolved minerals that contrib-
The air flow can be pushed through (Source: Victor Vizu). ute to scale formation or corrosion in the

continued >
4 FEDERAL ENERGY MANAGEMENT PROGRAM

cooling system. Recently, water reuse (OH-). Additional alkaline components (5) Cycles of Concentration ×
has become popular and many cooling may include phosphate (PO4-3), Blowdown = Blowdown +
systems are being supplied reclaimed ammonia (NH3), and silica (SiO2), Evaporation
effluent or discharge water from other though contributions from these ions
Solving for blowdown:
processes. While water reuse is a wise are usually relatively small.
resource option, consideration should be (6) Blowdown = Evaporation ÷
Conductivity – Conductivity is a mea-
made regarding the quality of the water (Cycles of Concentration -1)
surement of the water’s ability to conduct
and how that will impact the efficient
electricity. It is a relative indication of Also, if the blowdown rate and cycles of
operation of the cooling system, and
the total dissolved mineral content of the concentration are known, the make-up
the system’s ability to meet the required
water as higher conductivity levels cor- rate can be determined by solving equa-
cooling demand.
relate to more dissolved salts in solution. tion 4, and then the evaporation rate can
Whether the source water is surface, Conversely, purified water has very little be determined by solving equation 6 for
ground, or reuse, in nature there are a few dissolved minerals present meaning the evaporation:
basic water quality considerations that conductivity will be very low.
(7) Evaporation = Blowdown ×
should be understood.
(Cycles of Concentration – 1)
pH – pH is a measurement of how acidic System Calculations
or how alkaline a substance is on a scale To properly operate and maintain a
of 0 to 14. A pH of 7.0 is neutral (the
Factors That Limit Cycles
cooling tower, there needs to be a basic
concentration of hydrogen ions is equal understanding of the system water’s use. of Concentration
to the concentration of hydroxide ions), Water use of the cooling tower is the Increasing cycles of concentration saves
while measurements below 7.0 indicate relationship between make-up, evapora- water because it essentially means that
acidic conditions, and measurements tion, and blowdown rates. There are a water is being recirculated longer through
above 7.0 indicate basic or alkaline couple simple mathematical relationships the system before being blown down. But
conditions. The pH scale is logarithmic between the blowdown rate, evaporation as levels of dissolved minerals elevate
(each incremental change corresponds rate, make-up rate, and cycles of concen- with higher cycles of concentration, scal-
to a ten-fold change in the concentration tration of a cooling tower that are very ing and corrosion potential also increase.
of hydrogen ions), so a pH of 4.0 is ten useful to understand the principal flow All dissolved minerals have a saturation
times more acidic than a pH of 5.0 and rates. The first relationship illustrates limit that, if exceeded, will lead to scale
one hundred times more acidic than a pH the overall mass balance consideration formation.(2) Additionally, high levels of
of 6.0. Similarly, a pH of 9.0 is ten times around a given cooling tower: dissolved minerals (high cycles of con-
more basic or alkaline than a pH of 8.0 centration) increases the water’s tendency
and one hundred times more alkaline than (1) Make-up = Blowdown+ Evaporation to be corrosive (corrosion is discussed
a pH of 7.0. In this case, the blowdown accounts for in greater detail below). Chemical and
all system losses including leaks and mechanical treatment programs allow
Hardness – Hardness refers to the pres-
drift, except for evaporation. the thresholds of scaling tendencies and
ence of dissolved calcium and magne-
corrosion to be pushed; however, limits
sium in the water. These two minerals are The second principal relationship defines still persist necessitating management of
particularly troublesome in heat exchange cycles of concentration in terms of make- dissolved minerals (conductivity) levels
applications because they are inversely up flow and blowdown flow: through elimination of high mineral
soluble – meaning they come out of solu-
(2) Cycles of Concentration = Make-up content water through blowdown. The
tion at elevated temperatures and remain
÷ Blowdown following section discusses these
soluble at cooler temperatures. For this
concerns in greater detail.
reason calcium and magnesium-related This equation can be rearranged to either
deposits will be evident in the warmest of the following to solve for the make-up
areas of any cooling system, such as the rate or blowdown rate: System Concerns
tubes or plates of heat exchangers, or in Cooling towers are dynamic systems
the warm top regions of the cooling tower (3) Blowdown = Make-up ÷ Cycles of because of the nature of their operation
fill where most of the evaporation occurs. Concentration and the environment they function within.
Alkalinity – Alkalinity is the presence (4) Make-up = Cycles of Concentration Tower systems sit outside, open to the
of acid neutralizing, or acid buffering × Blowdown elements, which makes them susceptible
minerals, in the water. Primary contribu- to dirt and debris carried by the wind.
If the evaporation rate and cycles of Their structure is also popular for birds
tors to alkalinity are carbonate (CO3-2), concentration are known, the blowdown
bicarbonate (HCO3-), and hydroxide and bugs to live in or around, because
rate can then be determined by substitut-
ing equation 4 into equation 1:

(2) Scaling will occur predominantly in the heat exchangers and in the fill-section of the tower structure, but may also occur in the piping or on the tower distribution deck.
continued >
FEDERAL ENERGY MANAGEMENT PROGRAM 5

of the warm, wet environment. These Scaling – Scaling is the precipitation of area, leading to lower thermal efficiency
factors present a wide range of opera- dissolved minerals components that have of the system.
tional concerns that must be understood become saturated in solution. Figure 9
Microbiological Activity –
and managed to ensure optimal thermal illustrates calcium carbonate scale
Microbiological activity is micro-
performance and asset reliability. Below collecting on a faucet head. Factors that
organisms that live and grow in the cool-
is a brief discussion on the four pri- contribute to scaling tendencies include
ing tower and cooling system. Cooling
mary cooling system treatment concerns water quality, pH, and temperature. Scale
towers present the perfect environment
encountered in most open-recirculating formation reduces the heat exchange abil-
for biological activity due to the warm,
cooling systems. ity of the system because of the insulating
moist environment. There are two distinct
properties of scale, making the entire
Corrosion – Corrosion is an electro- categories of biological activity in the
system work harder to meet the cooling
chemical or chemical process that leads tower system. The first being plank-
demand. An expanded discussion for
to the destruction of the system metal- tonic, which is bioactivity suspended, or
scaling is available at www.gewater.
lurgy. Figure 7 illustrates the nature of a floating in solution. The other is sessile
com/handbook/cooling_water_systems/
corrosion cell that may be encountered biogrowth, which is the category given
ch_25_deposit.jsp.
throughout the cooling system metal- to all biological activity, biofilms, or
lurgy. Metal is lost at the anode(3) and biofouling that stick to a surface in the
deposited at the cathode.(4) The process is cooling system. Biofilms are problematic
enhanced by elevated dissolved mineral for multiple reasons. They have strong
content in the water and the presence of insulating properties, they contribute
oxygen, both of which are typical of most to fouling and corrosion, and the bi-
cooling tower systems. products they create that contribute to
further micro-biological activity. They
can be found in and around the tower
structure, or they can be found in chiller
bundles, on heat exchangers surfaces,
(see Figure 10), and in the system piping.
Additionally, biofilms and algae mats are
problematic because they are difficult
to kill. Careful monitoring of biocide
treatments, along with routine measure-
Figure 7. Example of a Corrosion Cell.
ments of biological activity are important
to ensure bio-activity is controlled and
There are different types of corrosion
limited throughout the cooling system.(6)
encountered in cooling tower systems
Figure 9. Calcium Carbonate Scale
including pitting, galvanic, microbiologi-
(Source: Hustvedt).
cally influenced (Figure 8), and erosion
corrosion, among others (expanded
Fouling – Fouling occurs when sus-
discussion is available at www.gewater.
pended particles fall out of solution
com/handbook/cooling_water_systems/
forming deposits. Common foulants
ch_24_corrosion.jsp). Loss of system
include organic matter, process oils, and
metallurgy, if pervasive enough, can
silt (fine dirt particles that blow into the
result in failed heat exchangers, piping,
tower system, or enter in the make-up
or portions of the cooling tower itself.
water supply). Factors that lead to fouling
are low water velocities(5), corrosion, and
process leaks. Fouling deposits, similar to
scale deposits, impede the heat exchange
capabilities of the system by providing an
insulating barrier to the system metal-
lurgy. Fouling in the tower fill can plug Figure 10. Biofouled Heat Exchanger
Figure 8. Microbiologically Influenced Corrosion film fill reducing the evaporative surface (Source: Taprogge GmbH).
(Source: Taprogge GmbH).

(3) The anode in a corrosion cell is defined as the site where metal is lost from the system structure and goes into solution.
(4) The cathode in a corrosion cell is defined as the site where the metal lost at the anode is deposited.
(5) Low water velocities may occur in poorly designed or improperly operated heat exchangers, in the cooling system piping, or in locations across the tower fill where uniform distribution
is not maintained.
(6) Beyond the operational and mechanical problems bioactivity causes in cooling tower systems, there is a human health issue if the system develops a specific bacterium
known as Legionella. For more information regarding Legionella and Legionnaires’ disease go to www.cdc.gov/legionella/patient_facts.htm.
continued >
6 FEDERAL ENERGY MANAGEMENT PROGRAM

Treatment Options Examples of “green” chemistry programs blowdown control and the other showing
Traditional water treatment programs are include polysilicate corrosion inhibitors blowdown controlled with a conductivity
designed and implemented to account (used for many years in potable water controller. The charts illustrate the impact
for the system concerns outlined above. systems), polyaspartic acid dispersants, of implementing blowdown control-
This ensures the tower system operates and hydrogen peroxide for biocide appli- lers, revealing conductivity rates that
optimally and achieves the needed cool- cations. Another biocide that received the stay much closer to the ideal set point
ing requirement. These programs consist 1997 Environmental Protection Agency compared to manual control.
of chemical additives including corrosion (EPA) Green Chemistry Award is THPS
More robust automation platforms are
inhibitors, dispersants, scale inhibitors, – tetrakis (hydroymethyl) phosphonium
also available from several manufacturers
and biocides that function to protect the sulfate.(7)
that provide system-wide monitoring
cooling system and keep heat exchange Automation – Automation systems are and dosing. These platforms are scalable
surfaces clean and free of deposits or available providing a broad range of depending on the need, but offer
bio-films. When this is accomplished, capacities to control single or multiple conductivity/blowdown control, pH con-
maximum cycles of concentration can be parameters in the cooling system such as trol, real-time chemical monitoring and
achieved, and the cooling system can be conductivity and blowdown control, pH dosing, continuous corrosion monitoring,
operated at peak efficiency both in terms control, and real-time chemical monitor- web-enabled reporting, and alarm relays.
of water use and energy use. Beyond ing and dosing. The benefit of these systems is tightened
traditional water treatment programs control of the various control points of
there are options to build upon the current Blowdown controllers are available from
the water treatment program, not only
program, improve the current program, several different commercial suppliers
eliminating excessive water use and high
or replace the current program. and offer a range of control points from
cycle conditions, but also controlling
simple conductivity/blowdown control,
Water Modeling – Software platforms chemical residuals and treatment dosing
to timed or meter relay chemical dosing.
provide the ability to model the system’s based on real-time corrosion and scaling
Many of them incorporate water meter
scaling tendencies, corrosion characteris- indices. In trend terms, similar results to
inputs and alarm relays if threshold
tics, and view optimal chemical applica- the conductivity improvements shown
measurements are exceeded.
tion (also referred to as “dosing”). by Figures 11 and 12 can be achieved
This can be a powerful tool to better Blowdown controllers offer continuous on chemical treatment residuals, pH set
understand if the system is operating at monitoring and control of the blowdown point and acid feed, biocide dosing, and
the maximum cycles of concentration of the tower system. This ensures high corrosion monitoring. Figures 13 and 14
possible, to see problem points in the sys- conductivity is avoided, minimizing scal- illustrate the performance improvement
tem (low flow velocity, high temperature ing and corrosive conditions and mini- real-time dosing achieves on chemical
heat exchangers, for example), and to see mizes excessive blowdown which wastes residuals, ensuring the proper dosage of
impacts of varying water characteristics. water. Figures 11 and 12 provide two corrosion and scale inhibitors at all times
Additionally, these modeling platforms opposing trends – one showing manual and eliminating overfeed or underfeed of
allow a facility to review the potential
impact of integrating water reuse
resources, altering chemical treatment
programs, or variations to certain opera-
tional parameters such as pH set-point.
In some cases, local and regional water
treatment professionals may have the
capability to supply similar modeling
results as a part of your existing water
treatment program or for a consulting fee.
Green Chemistries – “Green” chemistry
programs exist primarily to replace tradi-
tional treatments that have been deemed
harmful for environmental reasons.
“Green” chemistries often don’t result in
improved thermal efficiency or reduced
water consumption, but provide environ-
mental compliance and reduced dis-
Figure 11. Conductivity Trend for Manual or Timed Blowdown Control.
charge of harmful or illegal substances.

(7) To view the details of the THPS Green Chemistry Award go to www.epa.gov/gcc/pubs/pgcc/winners/dgca97.html. The complete list of recipients for the EPA’s Green Chemistry Awards
is available at www.epa.gov/gcc/pubs/pgcc/past.html.
continued >
FEDERAL ENERGY MANAGEMENT PROGRAM 7

these products. These platforms offer


web-enabled reporting interfaces so
operators and maintenance staff can
view tower performance remotely.
Additionally, alarms for out-of-
compliance measurements can be sent
via email or text message alerting
maintenance or operations personnel
so corrective actions can be taken.
Filtration – Filter systems are nothing
new to industrial water systems, and
have been used as pre-treatment in many
different applications for many years.
In recent years, side-stream filtration
systems have become popular among
many water treatment professionals.
They function to remove suspended
Figure 12. Conductivity Trend for a System Using a Blowdown Controller.
solids, organics, and silt particles down
to 0.45 microns from a portion or all of
the system water on a continual basis,
thereby reducing fouling, scaling and
microbiological activity. This allows the
cooling system to work more efficiently
and often reduces the amount of water
blown down. However, the net impact on
water consumption must consider the fact
that these platforms require back-washing
to clean the filter system. The amount of
water used to regenerate the filter system
should be added to the water lost due to
evaporation and blowdown.
Softening – Softeners function to remove
hardness (calcium and magnesium) from
the make-up water, or can be incorpo-
rated as a side-stream system to soften a
portion of the water continuously. This Figure 13. Chemical Residuals Trend for Timed Feed.
effectively manages (or eliminates) the
amount of calcium and magnesium in
the tower bulk water, thereby reducing
the scaling potential of calcium and
magnesium related deposits. By reducing
or eliminating the scaling potential of
calcium and magnesium, higher attention
should be given to corrosion monitoring
and the corrosive characteristics of the
water. Calcium and magnesium function
naturally as corrosion inhibitors, so if
they are minimized or removed from
the water, the corrosive conditions will
increase putting more importance on
the corrosion management program and
tighter requirements on pH and alkalinity
control.
Figure 14. Chemical Residuals with Real-Time Dosing.

continued >
8 FEDERAL ENERGY MANAGEMENT PROGRAM

Chemical-free Platforms – In recent bioactivity by damaging cell walls of Water Reuse – Water reuse options vary
years many innovations have been made potential microbes that pass through the depending on the nature of water uses
in systems that provide chemical-free treatment zone. Corrosion is controlled from site to site along with a broad range
treatment replacements to traditional naturally by these systems as they allow of other considerations, including local
treatment platforms. These include the water to run at elevated pH levels, or and regional water reuse laws and the
systems that are singular in their target alkaline conditions. availability of an adequate reuse resource.
treatment, such as ozone(8) and ultraviolet The concept is relatively simple: take
Similarly, systems employing hydro-
biocide systems. These systems are discharge water from one application,
dynamic cavitation impact the water’s
very effective disrupting and eliminat- apply sufficient treatment to it if needed,
characteristics to control scaling, corro-
ing biological activity in the treatment and then use it as a make-up water
sion, and biological activity. Instead of
zone, are flexible across a broad pH resource for the cooling tower system.
imparting electromagnetic principles to
range, have low operating costs, and no Two examples of reuse are collecting the
accomplish these ends, hydrodynamic
undesirable byproducts. These systems condensation from air-handlers and then
cavitation impacts the water mechani-
treat an isolated point in the system, so pumping them back to the tower system
cally by rapid changes in pressure and
far-reaching parts of the cooling system make-up, or implementing a reverse
mechanical collision in the treatment
may have bioactivity due to extended osmosis system on the cooling tower
zone. Again, scaling is controlled through
distances from the treatment application blowdown. The condensed water that
the seeding mechanism of calcium
point. Additionally, sessile bioactivity in collects in air handlers is an excellent
carbonate (calcite) formation, which in
the system beyond the point treatment resource of high quality make-up water
turn collects any other dissolved minerals
may not be affected by the ozone and for the tower system. Because it is con-
nearing their respective saturation points
ultraviolet treatments. densation, by nature it will be relatively
and removes them through in-line filtra-
pure, and therefore will not require much
There are also other types of compre- tion. Low pressure zones strip the passing
additional treatment to make it sufficient
hensive chemical-free platforms and the water of CO2, maintaining naturally
for using as tower make-up water.(10)
market has evolved, offering many dif- alkaline conditions to control corrosion.
These systems are not difficult to engi-
ferent types of platforms, which currently Lastly, the cavitation process ruptures
neer, nor are they typically very capital
have varying degrees of success in the cell walls of microbes passing through
intensive.(11)
commercial marketplace. Several have the treatment zone, thereby managing
been available for many years, but the bioactivity in the cooling systems. Reverse osmosis (RO) systems (similar
evolution of the differing technologies to Figure 15) are common in many
These systems and many others like them
has allowed for many more platforms to
have case studies and testimonials posted
be developed.(9) The exact mechanisms
to demonstrate successful replacement of
used to alter the water’s characteristics
standard treatment options, including
vary from platform to platform, includ-
energy savings and water efficiency
ing electromagnetic and hydrodynamic
gains. They offer the advantage of
principles as point treatments to control
reduced or eliminated need for treatment
scaling and corrosion along with micro-
chemicals and have had many successful
biological activity. Systems that employ
installations with documented improve-
electromagnetic principles feature a treat-
ments. However, some installations have
ment zone where an electric field courses
had difficulty depending on the water
through the flow of the recirculating
quality, especially where the natural ten-
water creating a “seeding” mechanism for
dencies of the source water lean toward
dissolved minerals, principally calcium
corrosive conditions. Furthermore, point
carbonate (also known as calcite). The
treatments may have some difficulty with
seeding process creates a location for
systems that are extensive and have far
other dissolved minerals to agglomerate,
reaching-pipe runs or heat exchangers
or come out of solution, and then be
that are a substantial distance from the
removed via in-line filtration systems that
treatment system itself.
follow the treatment system. The pulses
of electricity also behave to counter Figure 15. Desalination Plant Using Reverse
Osmosis Technology (Source: James Grellier).

(8) Ozone is a reactive form of oxygen that has strong oxidizing characteristics making it very effective at controlling microbiological activity.
(9) This document features mechanisms of a few different available systems and is not intended to be a comprehensive overview of all commercially available chemical-free water treatment systems.
(10) The purity of the water will increase its natural abilities as a solvent and stagnant water systems are ideal for bioactivity. Care should be taken when considering the materials of construction
for the collection and distribution system and if needed a small amount of biocide may be needed to minimize bioactivity. Additionally, the corrosion program for the tower system will need to
reviewed or modeled to ensure proper corrosion control steps are taken to protect system metallurgy.
(11) For more information on condensate recovery systems a case study is available at www.femp.energy.gov/program/waterefficiency_csstudies.html.

continued >
FEDERAL ENERGY MANAGEMENT PROGRAM 9

applications including desalination, stream (the concentrate flow) that would


industrial pre-treatment platforms, and be discharged from the system. These Where to Get More Information
applications where the purity require- systems can be difficult to operate FEMP Water Efficiency:
ments for water are very high. In the case correctly, and are expensive to purchase www.femp.energy.gov/program/
of water reuse from a tower system, the and operate. However, locations where waterefficiency.html
blowdown water would be sent directly water resources are limited or discharge
into an RO system, which would purify permits prohibit excessive cooling tower Cooling Technology Institute:
a portion of the water (the permeate blowdown, RO platforms are a consider- www.cti.org/
flow) and concentrate the bulk of the ation to minimize the overall losses from American Society of Heating,
dissolved minerals into a smaller waste a cooling system. Refrigeration, and Air-Conditioning
Engineers:
www.ashrae.org/
American Society of Mechanical
Engineers:
www.asme.org/
If questions remain, contact:
Will Lintner
Federal Energy Management Program
(202) 586-3120
William.Lintner@ee.doe.gov
Brian Boyd
Pacific Northwest National Laboratory
(509) 371-6724
Brian.Boyd@pnl.gov

EERE Information Center


1-877-EERE-INFO (1-877-337-3463)
www.eere.energy.gov/informationcenter

DOE/PNNL-SA-75820 • February 2011


Prepared and produced by Pacific Northwest National Laboratory (PNNL) on behalf of the U.S. DOE-Federal Energy Management Program

Printed with a renewable-source ink on paper containing at least 50% wastepaper, including 10% post consumer waste.