You are on page 1of 11

-04_IndirectSea_p46_p50.

FH11 4/10/07 9:54 PM Page 1

Indirect Seawater Cooling


and Thermal Storage System
46 in Changi Naval Base

with its poorer energy efficiency, a water-


THE ENGINEERING cooled system consumes a huge amount of
CHALLENGE water. The marine environment is also known
to create corrosion problems for conventional
When DSTA was tasked to develop a new naval air conditioning systems. These problems
base in Changi, the main challenge was to would be further accentuated if decentralised
provide cost-effective engineering solutions cooling towers or air-cooled condensers were
that could meet current as well as future needs installed in every building. However, given the
of the Republic of Singapore Navy. The proximity of the naval base to the sea, the use
solutions were to allow new technologies and of seawater for cooling purposes was
innovations to be incorporated and integrated considered a viable option.
into the overall engineering design. The
development aimed to provide flexibility,
enhance operational efficiency, conserve water
SYSTEM INNOVATION
and energy, and optimise capital investment.
In addition, careful consideration was given The system innovation implemented for the
to the growth of the supporting infrastructure naval base is the unique integration of Indirect
and trends in the external environment that Seawater Cooling, Thermal Storage and an
would impact the future developmental needs, On-Demand condenser water distribution
such as the ongoing deregulation of power network. Refer to Figure 1.
supply in Singapore.
The objective is to provide air conditioning to
In the design of the air conditioning system the buildings in the naval base in an energy-
for the buildings in the new naval base, the efficient manner through the use of a water-
objective was to have an energy-efficient cooled system, without consuming potable
system that consumes minimal water. Various water. The use of an indirect seawater cooling
options, which included the conventional air- system gives higher energy efficiency in heat
cooled and water-cooled systems, were studied rejection without having to use expensive
and evaluated. While the conventional air- corrosion resistant chillers, pipe work and
cooled system did not fit the requirements associated equipment. Furthermore, an indirect

Figure 1. Basic Concept of Indirect Seawater Cooling and Thermal Storage System
-04_IndirectSeaWater_final.FH11 4/4/07 1:43 PM Page 4

seawater cooling system enables the corrosion


and bio-fouling problems associated with
seawater cooling to be localised. The
integration with thermal storage further
optimises the efficiency of the seawater
infrastructure by utilising its spare capacity
during off-peak hours. In addition, it favours
the demand-side energy management and is
ready to benefit from the increasing difference
between peak and off-peak electricity rates
brought about by the deregulation of power
supply. The on-demand condenser water
network is a fully variable flow system and
supplies water according to demand in cooling. Figure 2. Indirect Seawater Cooling System
This optimises the pumping energy required
for condenser water distribution.
INDIRECT SEAWATER
This system innovation was developed in COOLING SYSTEM
phases, starting from 2000. It was awarded the
Engineering Achievement Award by the An extensive literature research into the use
Institution of Engineers Singapore in 2000, the of seawater for cooling purposes was
Energy Efficient Building Award by the Building conducted. Study trips to existing facilities that
and Construction Authority in 2002 and the use seawater for cooling purposes, such as the
ASEAN Energy Award in 2002, in recognition Senoko Power Station, Marina Hotels and
of the outstanding engineering contributions Shopping Complex and Chek Lap Kok Airport
made in the design of the system based on in Hong Kong, were made to learn from their
applicability and originality. The next few experiences. Different design concepts were
sections will elaborate on the system design. studied, assessed and evaluated. The options

47
Figure 3. Indirect Seawater Cooling System in Changi Naval Base
-04_IndirectSeaWater_final.FH11 4/4/07 1:43 PM Page 5

48

Figure 4(a). Seawater Intake Chamber Figure 4(b). Titanium Plate Heat Exchanger

Figure 4(c). Condenser Water Pump Figure 4(d). Electro-Chlorinator

were narrowed down to the direct and indirect maintainability. Figure 4 shows the seawater
seawater cooling systems. cooling system installed in the naval base.

Figures 2 and 3 show the indirect seawater Challenges In Seawater Cooling


cooling system, which comprises mainly the
seawater intake chambers, a seawater cooling The major challenges encountered in
plant and a condenser water distribution implementing the seawater cooling system
network. The sea serves as a huge heat sink were seawater corrosion and marine growth.
with an unlimited cooling capacity, which The feedback gathered from visits to some
removes heat from the air conditioning plants. seawater cooling projects had suggested
Seawater is drawn in from the intake chamber unfavourable experiences encountered in the
and the seawater cooling plant facilitates the operation and maintenance of seawater plants.
heat transfer between the seawater and the To keep these problems to a minimum,
condenser water. The condenser water is then different design concepts were evaluated. In
distributed throughout the base to various addition, research studies were conducted in
buildings through the distribution network. the selection of corrosion resistant materials
and to determine the effective strategy to
The seawater cooling plant consists of plate- combat marine growth (Teo, Ng, Chang, Ng &
type heat exchangers, primary condenser water Ng, 2000). Furthermore, means to control
pumps, an electro-chlorinator and controls. A marine growth must be environmentally
plate-type heat exchanger is employed for friendly, as far as possible, to prevent any
indirect seawater cooling for better significant impact to the quality of the seawater
in the basin.
-04_IndirectSeaWater_final.FH11 4/4/07 1:43 PM Page 6

Indirect Seawater Cooling


and Thermal Storage System
in Changi Naval Base

Effective Corrosion Control


Scheme

a. Indirect Seawater Cooling Concept

The indirect seawater cooling system was


chosen for implementation. With a more
localised seawater circuit, corrosion control
can be focused and effectively managed
through the use of superior corrosion resistant
materials without inflating the cost significantly.
Although direct seawater cooling appears more
efficient in heat transfer and utilises less
Figure 5. Direct Vs Indirect Seawater Cooling System
equipment, its seawater circuit will be fairly
extensive. The air conditioning plant and all
the piping would then have to be seawater
resistant and maintained against corrosion and
Microbiological
fouling. Indirect seawater cooling, on the - Slime, Algae

other hand, has a localised seawater circuit 30 Macroinvertebrates


- Mussels, Barnacles
and uses fresh water in the condenser water
network. Hence, the air conditioning plant and
70
piping are similar to those used in a
conventional air conditioning system. Refer to
Figure 5.

b. Use of Corrosion Resistant Materials

To effectively manage seawater corrosion,


extensive studies were conducted and an
Figure 6. Typical Marine Fouling Organisms
evaluation of the array of corrosion resistant
materials available in the market was carried
out. The most effective materials were selected seawater environment is shown in Figure 6.
for implementation. Factors considered when We employed the use of mechanical and
selecting the materials included material chemical treatment to minimise bio-fouling.
compatibility, seawater condition, service life
a. Mechanical Treatment
span, environmental friendliness, maintenance
requirement and cost. Fibre Reinforced Plastic
The use of a screen filter at the seawater intake
piping, titanium plate heat exchangers, duplex
chamber helps to prevent foreign objects,
stainless steel pumps and copper nickel passive
including macro organisms, from entering the
filters were selected for the building of the
seawater cooling system. Travelling rotary
indirect seawater cooling system.
screens are conventionally used in other
seawater cooling systems. However, such a
Effective Marine Growth filter system tends to be labour intensive and
Control Scheme costly to maintain, given the high maintenance
and electrical power consumption. An
The main macro-fouling organisms around the alternative was sought and it was found that
49
Singapore coastline are green mussels, a passive screen filtration system would use
barnacles and tubeworms. A typical less moving parts, which enhances the system’s
classification of bio-fouling organisms in reliability, maintainability and safety.
-04_IndirectSea_p46_p50.FH11 4/10/07 9:54 PM Page 2

50

the intake of seawater, through the heat


exchanger, the outfall and back to the harbour.
For environmental friendliness, chlorine is
generated from the electrolysis of seawater
using electro-chlorinators and injected into
the seawater circuit at the seawater intake.

A study was conducted to determine the


FRP material with
optimal chlorine-dosing plan to prevent the
mussels
build-up of marine organisms in the seawater
circuit. A laboratory study was also carried out
to evaluate the biocidal efficacy of eight
commercial biocides. Environmental factors
Figure 7(a). Laboratory Set Up
were also taken into consideration for the
selection. The laboratory set up is as shown in
Figure 7. Laboratory analysis has determined
that a continuous chloride dosing, at a dosage
- Hypochloride of about 1.5ppm at the water intake region
- AWT-375
- Camtrol 1300/1301 - Hypochloride would minimise bio-fouling. The residual
- C-Treat 6 - Camtrol 1301/1300 concentration at the discharge is expected to
- Drewsperse 767 - Magna 1B Seacide
- Magna 1B Seacide - C-Treat 6 be lower (<0.9ppm) due to losses and chemical
- Mexel
- Oil Chem B62 degradations. The seawater in the vicinity
would further dilute the discharge. In the event
of breakdowns of the electro-chlorination unit,
- Hypochloride
- Camtrol 1301 biocides such as Clam Trol CT1301 can be used
as a substitute, at a dosage of about 25ppm.
Figure 7(b). Results from Laboratory Testing This biocide dosing is also used for
prolonged shutdowns.
In addition, this system is less labour intensive
and relatively easy to design and install. Bio- OPTIMISATION OF THE
fouling resistance materials such as 90/10
copper nickel iron alloy for the passive seawater
HYDRONIC SYSTEM
intake filter were used. To prevent the
attachment of clams and mussels, a minimum The varying cooling demand from each building
flow velocity of 1m/s in the pipeline is designed. and the phased development of the naval base
In addition, the avoidance of stagnant would require comprehensive studies to ensure
conditions and good maintenance during that the system performs optimally throughout
operations are essential to minimise the implementation. For the condenser water
bio-fouling problems. distribution network, a fully variable flow
system, otherwise known as the decoupler
b. Chemical Treatment concept, was adopted to conserve pumping
energy. A study was done to model the
A filter screen cannot prevent the microscopic seawater cooling system using hydronic
bacteria, fungi and larvae of mussels from computer simulation (Toh, Wong, Ng & Han,
entering the cooling systems. Chemical 2000) so as to further optimise the energy
treatment is therefore necessary to prevent efficiency of the system over several phases of
the establishment of a biofilm. The chemical the naval base development.
treatment programme is of great importance
in seawater cooling systems, beginning from
-04_IndirectSeaWater_final.FH11 4/4/07 1:43 PM Page 8

Indirect Seawater Cooling


and Thermal Storage System
in Changi Naval Base

The study included an analysis of the


temperature, flow and pressure losses in the
reticulation system and heat exchangers at
Make ICE Melt ICE
ultimate full load, full load at phased operation,
and off-design conditions. It established the
control concept for the seawater cooling system
and defined the optimum flow control
strategies for the condenser water piping
network. The study also established that the
flow rate in the seawater circuit should be 16
Exploit the use of cheaper
percent more than that of the condensing off-peak power for air
conditioning and reducing
water circuit for best results. The estimated the electricity bill Store ICE
overall improvement in system efficiency was

Figure 8. Thermal Ice Storage System

Figure 9(a).
Thermal Ice Storage
System

15 percent. Based on the study, the equipment


was appropriately sized and selected for
implementation.

THERMAL STORAGE
The thermal (ice) storage system produces ice
during the off-peak period (night time), which
can be stored and used to supplement part of
the air conditioning load during the peak
period (day time). See Figure 8. By carefully 51
sizing the thermal storage capacity, the peak-
cooling load in the day could be ”shaved” and
Figure 9(b). Partial Storage Load Levelling
“transferred” to the night. See Figure 9.
-04_IndirectSeaWater_final.FH11 4/4/07 1:43 PM Page 9

52

The “shaved” capacity was designed at


approximately 25 percent of the peak-cooling OTHER SPECIAL
load for the buildings in the naval base. This CONTRIBUTIONS AND
helped maximise the overall savings, taking BENEFITS
into consideration the tariff gap and the costs
of the thermal (ice) storage and indirect
This system innovation has contributed to the
seawater cooling systems.
conservation of energy and water, which are
both scarce resources in Singapore. In addition,
The creative combination of thermal (ice)
it opens up an avenue for owners to reduce
storage with seawater cooling has brought
their operating costs by shifting some of the
with it several advantages. In shifting part of
power requirements for air conditioning to
the cooling load into the night, the ice storage
the night and thus benefit from the lower cost
mechanism is able to fully exploit the night-
of off-peak electricity. The viability of indirect
time spare capacity of the seawater cooling
seawater cooling also offers another option
system to make and store ice. This spare
for other coastal developments to use seawater
capacity from the equipment would
for cooling applications. The studies on
otherwise be lying idle due to the reduced
corrosion control and combating marine
night-time load.
growth will provide useful data for application
in other developments.

It also sets an example in the use of thermal


storage for demand-side management, which
Commissioned
and operational
has gained significance with the gradual
since October deregulation of power supply market in
2000
Singapore. In this new competitive playing
field, power utility prices can be expected to
become more competitive. This innovation will
allow the customer to maintain flexibility and
react to the widening gap between peak and
off-peak power tariffs. In developed countries
such as Japan, the peak and off-peak
differentiation is about 80 percent.
Figure 10. Thermal Ice Storage Plant in
Changi Naval Base
Though now a niche application for Changi
In addition, by shaving off part of the peak Naval Base (CNB), this fledging technological
day cooling load and ”shifting” it to the night, innovation can be expected to gain further
the thermal (ice) storage helped reduce the acceptance and benefits in the new energy
day capacity needed from the seawater cooling market. The successful implementation of this
system, thus reducing the infrastructure innovation in Singapore will encourage
requirements. These include reduced pump developers from other countries to give due
sizes, piping and power supply infrastructure consideration to this option. There is strong
for the indirect seawater cooling system and potential to adapt this innovation in other
condenser water circuit, thus making it even coastal developments.
more cost-effective. Figure 10 shows the
thermal (ice) storage plant.
-04_IndirectSeaWater_final.FH11 4/4/07 1:43 PM Page 10

Indirect Seawater Cooling


and Thermal Storage System
in Changi Naval Base

The use of thermal (ice) storage, which


APPROACHES IN favoured demand-side energy management
MAKING A DIFFERENCE has allowed us to maintain flexibility and react
to the widening gap between peak and off-
DSTA was able to achieve this innovation peak power tariffs. The unique combination
through its comprehensive understanding of of the indirect seawater cooling, thermal (ice)
the technological trends and developments in storage systems and hydronic optimisation
the building industry and the creative makes this entire cooling system a cost-effective
application of the appropriate technologies. and viable solution for the requirements of
the CNB.
In developing this project, DSTA collaborated
with experts and researchers from our tertiary
REFERENCES
institutions and local research agencies. The
scope of collaboration included research in
Chua, H. K., Ng, Y. S., Tay, L. C., & Wong, Y. W.
corrosion and marine growth controls for the
(2001). Innovative Approach to Energy Efficient
seawater circuit (Teo, Ng, Chang, Ng & Ng,
Buildings. Presented at the Seminar on
2000), computer simulation study on the
Doorways to Energy Efficient Buildings in
performance of the proposed on-demand
October 2001.
district cooling system (condenser water
network) (Toh, Wong, Ng & Han, 2000) and
Tay, L. C. & Ng, Y. S. (2001, April). Seawater
performance study on thermal storage
Cooling and Thermal Storage in the New Naval
(Wijeysundera & Lee, 1997). Computerised
Base Development in Singapore. In IES Journal.
engineering and simulation tools were used
to evaluate the various design options before
Teo, E. H., Ng, L. C., Chang, K. W., Ng, W. F. &
deciding on the optimum implementation.
Ng, Y. S. (2000). Minimising Corrosion & Bio-
Leveraging external expertise has improved
fouling in Sea-water Systems.
the quality of the design and pushed the limits
of energy efficiency to a higher level.
Toh, K. C., Wong, Y. W., Ng, Y. S. &Han, F. (2000).
Performance Optimisation of the Central Sea-
CONCLUSION water Cooling System in Changi Naval Base.

Wijeysundera, N. E. & Lee, C. J. (1997). Design


In summary, the proximity of the CNB to the
& Simulation Aspects of Ice-based Thermal
sea presented the opportunity to use seawater
Energy Storage Systems.
optimally. Although it presented difficulties in
terms of corrosion and bio-fouling, the
challenges were overcome with careful
engineering and extensive studies with experts
and researchers from local universities and
research agencies. The CNB was able to benefit
from better energy efficiency through a water-
cooled system that does not consume fresh
water. The system continues to save a significant
amount of fresh water annually as compared
to a conventional water-cooled system.
53
-04_IndirectSeaWater_final.FH11 4/4/07 1:43 PM Page 11

54

BIOGRAPHY
Chua Hian Koon is Assistant Director (Protective Mechanical and Electrical
Systems). He oversees the strategic development and implementation of the
mechanical and electrical engineering and operational masterplans for critical
infrastructures. Hian Koon is a recipient of the Defence Technology Prize in
2006 for outstanding contributions to the Protective Technology Research
Team. A Public Service Commission scholar, Hian Koon obtained in 1988 his
Dip D'Ingenieur in electrical engineering (first class honours and Master)
from the Ecole Nationale Superieure D'Ingenieurs Electriciens de Grenoble,
and also a joint Master in engineering science from the Ecole Centrale de
Lyon. He is a registered Professional Engineer (Electrical) and a guest lecturer
for the Master of Engineering course in Protective Technology at Nanyang
Technological University (NTU).

Sim Jin Sing is Programme Manager (Protective Mechanical and Electrical


Systems). He leads a team to conduct engineering feasibility studies,
in addition to designing and implementing conventional and specialised
mechanical systems in the Ministry of Defence and the Singapore Armed
Forces to enhance the ministry’s defence capabilities. He was previously
involved in master planning of mechanical requirements in operational
facilities such as air bases and naval bases to enhance operational effectiveness
and efficiency. Jin Sing possesses good technical knowledge in seawater
cooling systems, thermal storage and radiant cooling systems. He holds a
Bachelor of Engineering (Mechanical) and a Master of Science (Mechanical
Engineering) from the National University of Singapore (NUS). He is a registered
Professional Engineer (Mechanical).

Ng Yew Soon is Project Manager (Protective Infrastructure). He currently


leads a team of engineers to develop the mechanical and electrical (M&E)
systems in a large-scale infrastructure developmental project. He is also
responsible for engineering master planning, detailed design and
implementation of the M&E systems for the operations and logistics facilities.
Yew Soon was a key project team member in the development and
implementation of the Indirect Seawater Cooling and Thermal Storage System.
He holds a Bachelor of Engineering (Mechanical) from NTU as well as double
Masters of Science in Defence Technology and Systems and Operations
Research from the Temasek Defence Systems Institute under the DSTA
Postgraduate Scholarship.
-04_IndirectSeaWater_final.FH11 4/4/07 1:43 PM Page 12

Indirect Seawater Cooling


and Thermal Storage System
in Changi Naval Base

Formerly from DSTA, Tay Leng Chua is Assistant Managing Director of United
PREMAS Limited. He is responsible for providing security consultancy and
total solutions to enhance safety and security. The scope of security consultancy
includes security audit, building vulnerability assessment, planning and design
for protection and security. Leng Chua was a key project team member in
the development and implementation of the Indirect Seawater Cooling and
Thermal Storage System. He has received numerous awards, including the
Public Administration Medal (Bronze) in 2004 and the Defence Technology
Prize in 1999 for the Explosive testing of Structural Components. Currently
the Vice President of the Institution of Engineers, Singapore, Leng Chua holds
a Bachelor of Engineering (Mechanical) from NTU and a Master of Science
(Industrial Engineering) from NUS. He is also a registered Professional
Engineer (Mechanical).

Ng Chor Boon is Project Lead (Protective Mechanical and Electrical Systems).


He is responsible for technology development in defence infrastructure,
numerical modelling and explosive testing. He is also involved in collaboration
projects on blast effects on structures, as well as in the design of blast doors.
Chor Boon was part of the team that received the DSTA Team Excellence
Award for the Passive Blast Attenuation System in 2004. He holds a Bachelor
of Engineering (Mechanical Engineering) from NUS under the Public Service
Commission (Local) Scholarship, and a Master of Engineering in
High Performance Computation for Engineered Systems from the
Singapore-MIT Alliance.

55

You might also like