Condensing Plant

Operating Documentation Condenser Level Protection


Functional Description

Process Engineering Function of Condenser densation process arrested due to rising level) that the con-
Level Protection denser level can never increase to such an extent during
coastdown of the steam turbine that water enters the steam
Turbine steam and/or bypass steam is for the most part
turbine.
condensed in the condenser. The level of the condensate is
determined by the balance of inlet and outlet flows. Any los- The condenser level is measured using 3 differential
ses in the water/steam cycle are compensated for by the in- pressure transmitters (10MAG10CL021, 10MAG10CL022,
jection of demineralized water into the condenser (see scope 10MAG10CL023).
of supply and description of the water/steam cycle). The condenser level protection is implemented in a 2-out-
If the condenser level rises unallowably in the event of a of-3 standard configuration. It is also implemented in failsafe
fault (e.g. failure of condensate pumps), various consequen- technology.
ces are possible:
Annunciations
• Impermissible pressure increase in the condenser
• Risk of damage to LP moving blades due to ingress of Before the trip initiation limit signal of the condenser level
water protection is reached, the warning alarm "Condenser level
• Flooding of condenser standpipe and/or direct drains HIGH" and the fault alarm "Condenser level TOO HIGH" are
(steam hammer when turbine drains open) output in the control room. Demineralized water injections are
terminated when the fault alarm is issued.
Condenser level protection is provided to avoid hazards
of this kind. This initiates trip of the steam turbine and bypass Different annunciations are issued by the condenser level
protection depending on the operating condition. Comments
Transmittal, reproduction, dissemination and/or editing of this document as well
as utilization of its contents and communication thereof to others without express
authorization are prohibited. Offenders will be held liable for payment of
damages. All rights created by patent grant or registration of a utility model or

station when the permitted condenser level is exceeded.


and any necessary action by the operating personnel are de-
For steam turbines installed on a turbine deck, steam tur-
scribed in the comments on annunciations.
bine tripping by the condenser low-vacuum trip is initiated at
such an early stage when the condenser level is high (con-
Copyright © Siemens Energy 2011 - All Rights Reserved
design patent are reserved.
Class: Restricted

Siemens Energy MAG &MFE020 2-1-MA5-373-M0003 / 1-1