au
Applications
& benefits
Applications Benefits
Purpose Laboratories, microelectronic For the Developer
Access floors through their infinite flexibility facilities Reduces risk of premature
provide the key element required for today's Where a non-magnetic and non-corrosive building obsolescence.
intelligent buildings and equipment rooms. work platform is required in medium or Reduces design time – services
The simplistic concept of access floors can heavy grade panels. The system combines reticulation can be deferred.
readily accommodate future changes die cast aluminum panels with wide range
whether they are organisational, Accelerates construction cycle.
of anti-static finishes and stainless steel or
technological or climatic in origin. aluminum understructure. Helps keep tenants for long term.
Overcomes many problems with
General office Information processing renovations of existing buildings.
A medium duty application requiring A heavy duty static and dynamic loading Maximises lettable area.
a system capable of withstanding both application. Functional, hard clean surface
static and dynamic loadings. Stability
and acoustics are important.
and quick access important. For the Tenant
Reduces initial fitout costs.
Telephone exchanges and
Dealing rooms switching centres Reduces costs of churn (rate of change
over time) for life of occupancy.
A heavy duty application requiring a system
capable of withstanding both static and A heavy duty static and dynamic loading Maximises flexibility of layout.
dynamic loadings. Stability and quick application. Functional hard clean surface
and quick access important. Some special Provides infinite capacity for
access important. services growth.
features often required.
Impact loads
These are typically accidental in nature
and generate extremely severe shocks
which can cause some access floors to fail
catastrophically. Impact loads most often
occur during the construction cycle, initial
fitout, move-in and during equipment and
furniture re-arrangement.
PAGE 4
Other performance criteria 3. Acoustics Tasman Access Floor systems have
Airborne sound (travelling from room been tested in accordance with
1. Earthing to room such as voices, telephone and AS4154 – 1993 Australian Standard
equipment noise) and footfall sounds – General Access Floors. Also meet
All metal components should have
(floor impact noise transmitted from requirements under PSA PF2 (UK)
continuity to Mains earth with a maximum
one source to other areas) are becoming and C.I.S.C.A. (USA) and EN 12825
resistance of one Ohm (AS 3000).
increasingly important criteria for (Europe) testing criteria.
Continuity is extremely important for
safety and the creation of an appropriate creating a productive office environment.
electrostatic discharge path. Acoustic attenuation of access floor systems
confirmed by certified tests should be
2. Flammability and thermal considered in office applications.
containment
Prior to the application of floor coverings,
access floor panels should provide a
minimum of heat transfer and maximum
fire retardation capabilities. Ignitability,
Spread of flame, Heat Evolved and Smoke
Developed should provide zero indices
(AS 1530-3) and the indices should remain
zero with cut panels.
No structural component of access floor
should have a melting point less than
600 degrees Celsius.
PAGE 5
Tascor ®
PAGE 6
Performance data
Tascor® performance specification guide
System type Static loads Rolling loads Impact
loads #
Concentrated Ultimate 75mm x 150mm x
25mm 200mm x 75mm 25mm
Panel Type Understructure System Load Load 50mm
25mm Square 25mm Square 10 passes 10,000 passes 2.25kN Square
TC750U Stringerless Unifix® (TC100) 3.0kN 9.0kN 2.7kN 2.7kN 40,000 Passes 45Kg
TC750F Stringerless Gravity held (TC102) 3.0kN 9.0kN 2.7kN 2.7kN 40,000 Passes 45Kg
TC750S Bolt-on Stringer Gravity held (TC104) 4.0kN 12.0kN 2.7kN 2.7kN 40,000 Passes 68Kg
TC1000U Stringerless Unifix (TC100)
®
4.5kN 13.5kN 4.4kN 3.3kN 250,000 Passes 45Kg
TC1000F Stringerless Gravity held (TC102) 4.5kN 13.5kN 4.4kN 3.3kN 250,000 Passes 45Kg
TC1000S Bolt-on Stringer Gravity held (TC104) 4.5kN 13.5kN 4.4kN 3.3kN 250,000 Passes 68Kg
TC1350U Stringerless Unifix (TC100)
®
6.0kN 18.0kN 5.5kN 4.4kN 500,000 Passes 68Kg
TC1350F Stringerless Gravity held (TC102) 6.0kN 18.0kN 5.5kN 4.4kN 500,000 Passes 68Kg
TC1350S Bolt-on Stringer Gravity held (TC104) 6.0kN 18.0kN 5.5kN 4.4kN 500,000 Passes 68Kg
1kN is equivalent to 102Kg
PAGE 7
Tascor ®
Understructure Systems
Unifix® Stringerless
Provides maximum underfloor accessibility, while
providing rigid membrane for high stability.
Standard finished floor height systems provide for
nominal finished floor heights from 150mm to 750mm
with ± 25mm minimum height adjustment (TC100).
Low finished floor height systems provide for nominal
TC100 finished floor heights from 75mm to 200mm with
± 10mm minimum height adjustment (TC101).
Unifix® Pedestal head design provides lateral stability and
rigidity, with positive location lugs, providing safety even
when the system is not locked.
Freelay Stringerless
Absolutely maximises underfloor accessibility, while
providing moderate stability.
Standard finished floor height systems provide for
nominal finished floor heights from 150mm to 300mm
TC100 TC101 with ± 25mm minimum height adjustment (TC102).
Low finished floor height systems provide for nominal
finished floor heights from 75mm to 200mm with
± 10mm minimum height adjustment (TC103).
Using the Unifix® Pedestal head with special clip on
gasket, the positive location lugs ensure system stability.
Note however, the recommended height limits.
TC102
1. 2.
PAGE 8
TC104 TC105
TC104
Pedestals Assemblies
3. 4. 1. Standard field pedestal Assembly for Applications above
150mm Finished Floor Height.
2. Standard Perimeter Pedestal Assembly above
150mm Finished Floor Height.
3. Low Field Pedestal Assembly for Applications from
75mm Finished Floor Height with Equipotential Bonding
Washer.
4. Low perimeter Pedestal Assembly for Applications from
75mm Finished Floor Height.
TC101 TC101 perimeter
PAGE 9
Tasman Woodcore
Features
Construction
Panels are made by sandwich method using a high density
particle board core, 38mm thick, clad with adhesion bonded
hot dipped galvanised steel sheets and finished with high
pressure laminate.
Understructure
A complete range of understructure including stringerless
and bolted stringer and low finish floor height pedestals
is available.
Adjustment
Pedestal assemblies provide a wide range of
total adjustment.
Size
Standard system module is 600mm x 600mm.
Non standard panel size available on request,
subject to type and quantity.
Finishes
The panel is finished in a standard high pressure laminate
(HPL) finish, in standard colours – Greystar and Summer Mist.
Non standard and bare finishes available on request, subject
to type and quantity.
Benefits
Durable
The structural composition of a high density particle board
core and steel bonded together creates a durable access floor
that can accommodate both static and dynamic loads.
Precision Sizing
Panels are completely interchangeable for easy relocation
of panels.
Meets Standards
System options are available, to comply with Australian
Standard AS2834 – 1995 Computer Accommodation and
AS4154 – 1993 Australian Standard – General Access
Floors (Elevated Floors).
Fire Safety
The panels are tested in accordance with Australian Standard
Finishes AS1530 Part 3 – 1989. Indices achieved are Ignitability 0,
Spread of Flame 0, Heat Evolved 0, Smoke Developed 3.
E-Trimmed Laminate (C type)
Quiet
Panels are constructed with a PVC trim strongly bonded to the
panel edge and set flush with the high pressure laminate top The high grade Woodcore has excellent sound attenuation.
surface. This clearly delineates the edges of installed panels. Stringer or pedestal gaskets further dampen sound.
Panels can be finished with a range of special surface finishes
Electrostatic Resistance
and colours. Some finishes may not be suitable – please
consult with your local Tasman representative. Minimum 5 x 105 Ohms
Maximum 2 x 1010 Ohms
PAGE 10
Technical Data
This chart provides an easy means of selecting a Tasman Woodcore System to match the static and dynamic performance required for your
specific needs. Other panel types/grades are available on request. Please consult with your local Tasman representative.
Corner Support Gravity held (FC103) 4.0kN 11.0kN 3.3kN 2.7kN 45Kg
C38
Standard Stringer Gravity held (FC100) 4.5kN 13.5kN 4.0kN 3.3kN 45Kg
1kN is equivalent to 102Kg
Understructure Systems
Bolted Stringer System Stringerless System (FC 103)
(FC 100)
Low finished floor height systems
The stringers are heavy duty provide for nominal finished floor
25mm x 25mm welded tube heights form 75mm to 150mm.
sections. Standard finished floor height
Provides maximum rigidity under systems provide for nominal
the most demanding static or finished floor heights from 150mm
seismic conditions. Additional to 750mm.
rigidity may be achieved using Provides maximum accessibility
double length stringers (1200mm). to underfloor void.
Provides reference grid grounding Pedestal and Gasket
capability. design provides lateral stability
Understructure resistance to earth without bolted or fixed obstructions
maximum 1 ohm over to under floor void.
16 metre radius.
FC 100 FC 103
Pedestals
Standard finished floor Low finished floor height assembly
height assembly
For LFFH applications from
For FFH applications from 75mm to 150mm.
150mm to 750mm. Provides for ± 10mm minimum
Provides for ± 25mm minimum height adjustment at 75mm FFH.
height adjustment. Recommended for use with
Features fully adjustable tab lock stringerless systems.
adjusting nut, hot-dipped Features fully adjustable threaded
galvanised steel components. head assembly with anti rotation
Accepts 22.5kN axial load without gasket, hot-dipped galvanised
failure or loss of function. steel components.
Accepts 22.5kN axial load without
failure or loss of function.
PAGE 11
Tasman
Aluminium Access Floor System
Benefits
Precise size for easily interchangeable.
Non magnetic.
Die cast aluminum panels meet AS standard 4154.
Light weight for ease of handling.
Excellent rolling and concentrated load performance.
Bare coating finish.
Can be hosed cleaned.
Available in a wide range of anti-static finishes.
Call Tasman
to discuss your
project today!
PAGE 12
‘Premium’ range of access floor finishes
Sample of Tasman’s ‘Premium’ range – stone finishes Sample of Tasman’s ‘Premium’ range – timber finishes
A mix of Tasman’s ‘Premium’ finishes – stone and carpet finishes A mix of Tasman’s ‘Premium’ finishes – carpet and timber finishes
PAGE 13
Tasman
Tasman OnGrid® 60cm Modular Carpet Tile System
Benefits
Retained flexibility of an access floor with a carpet finish.
Compatible with Underfloor Air Distribution Systems.
Carpet tiles are securely attached to the access floor
panels so they will not move during normal use, but can
be detached easily if required.
Moving the carpet tile and panel combination is easy for
re-locating power/data outlets, air diffusers which are
installed in the panels.
Extensive range of carpet finished available from leading
modular carpet tile manufacturers, Ontera and Interface.
PAGE 14
Underfloor Air Distribution
Benefits
How does it work in General Designed to provide better health,
Office Environments? productivity and contentment of staff
within the office environment.
Improved ventilation is achieved as a
Access floors can deliver unlimited ability to house and clean, fresh and healthy air supply from
reticulate data and electrical services on demand and floor to ceiling stratifies the air and
enhances natural convection.
includes underfloor air distribution.
Personalised local comfort control.
Many green and high-performance sustainable buildings worldwide are now
incorporating underfloor air distribution. Whether using chilled beams, conditioned air Faster churn capabilities.
to the floor void, or just using the floor void to distribute fresh air, access floors
combine to assist in reducing energy costs, improving indoor air quality, and Facilitates energy savings with improved
enhancing personal comfort and productivity. fresh or conditioned air distribution.
The access floor plenum is simply filled with fresh or conditioned air at a slight
positive pressure, which is delivered into the occupied space through swirl diffusers or
fan air terminals. The air is delivered into the office space in a controlled manner to
create the ideal comfort for the working environment.
To enhance the effectiveness of the underfloor air distribution Tasman has locally
designed an underfloor plenum divider system for breaking underfloor areas into
different zones. This allows greater flexibility when cooling internal or perimeter zones.
Computer Room Tasman Stringered Gravity Held, Heavy Grade Access Floor System.
Panel surface is factory finished in anti-static High Pressure Laminate.
Code: TC1000SXH panel & TC104 Understructure System.
Information Processing Tasman Stringered Gravity Held, Heavy Grade Access Floor System.
Panel surface is factory finished in anti-static High Pressure Laminate.
Code: TC1000SXH panel & TC104 Understructure System.
If very heavy loadings then Extra Heavy Grade should be considered.
Code: TC1350SXH panel & TC104 Understructure System.
Telephone Exchange Tasman Stringered Gravity Held, Heavy Grade Access Floor System.
Panel surface is factory finished in anti-static High Pressure laminate.
Code: TC1000SXH panel TC104 Understructure System.
If very heavy loadings then Extra Heavy Grade should be considered.
Code: TC1350SXH panel & TC104 Understructure System.
PAGE 16
Woodcore Application Selection
Generally Tasman General Office Generally not recommended. Tascor® Systems should be used. Alternatively
Woodcore products are
a Woodcore System can be supplied on request.
suitable for smaller
or short term facilities
plus projects with special Dealing room Not suitable. Tascor® System should be used.
requirements or
configurations. Typically Call Centre Not Suitable. Tascor® System should be used.
installed at fit-out stage
of construction cycle.
Casino Not Suitable. Tascor® System should be used.
Computer room Tasman Stringered Gravity Held, Heavy Grade Access Floor System.
Panel surface is factory finished in anti-static High Pressure Laminate.
Code: C38EH panel & FC100 Understructure System.
Information Processing Tasman Stringered Gravity Held, Heavy Grade Access Floor System.
Panel surface is factory finished in anti-static High Pressure Laminate.
Code: C38EH panel & FC100 Understructure System.
If very heavy loadings then Tascor® Extra Heavy Grade should be considered.
Code: TC1350SXH on TC104 Understructure System.
Telephone Exchange Tasman Stringered Gravity Held, Heavy Grade Access Floor System.
Panel surface is factory finished in anti-static High Pressure laminate.
Code: C38EH panel & FC100 Understructure System.
If very heavy loadings then Tascor® Extra Heavy Grade should be considered.
Code: TC1350SXH on TC104 Understructure System.
PAGE 17
Accessories
General Accessories 5. Perforated panels
As an alternative to Air Grilles Tasman can
1. Grommets provide structurally rated perforated panels
Tasman can provide grommets in a with an anti-static high pressure laminate
range of sizes to provide flexible, easy surface. These perforated panels can be
to install access to underfloor outlets for provided with or without sliding damper.
power, data, telecom, vacuum and other
mechanical services. 6. Ramps, steps, fascias
and nosing
2. Floor Services Outlet Boxes (FSO) As part of the installation process Tasman
Tasman can provide a broad variety of are able to provide high quality, long life
shapes, sizes and capacities in Electrical ramps, steps, fascias and nosing. These
Outlet Boxes. These boxes normally allow items are robustly constructed and made on
for simple plug connections to power, site to match exactly the access floor and
data and voice in many configurations. the concrete slab transition. Ramps and
steps are usually finished with studded
3. Panel lifting devices rubber and thresholds (including step
Tasman panel lifters are designed for thresholds) are finished with an aluminum
use on all panels including bare and nosing and a rubberised insert. Thresholds
high pressure laminate panel surfaces. to fascias are also finished in the same
Tasman’s standard panel lifter has a nosing and insert system. This ensures that
certified rating 30kg and heavy panel when you purchase a Tasman Access Floor
lifter has a certified rating 80kg. you get a complete and finished job.
4. Air grilles
Product Data Sheets
Tasman can provide as a standard range,
Air Grilles suitable for installation in Detailed data sheets are available on all
Computer Rooms and EDP Centres with of the above accessories and naturally
or without opposed blade dampers. advice in relation to their uses and
applications are available when you Grommet
These come in a range of sizes to provide
appropriate air flow in such high heat contact Tasman Access Floors on
load areas. 1800 700 718 and for more detailed
information visit our website
www.tasmanaccessfloors.com.au
The above list defines the common items
required in access floor systems however
there are always new and different
requirements. It is likely that Tasman Access
Floors can provide such accessory needs.
PAGE 18
Tasman
Access Floors
Tasman Access Floors has successfully undertaken significant projects throughout Australia, New Zealand,
Middle East and South East Asia using Steel Concrete Composite and Woodcore Access Floors during a
period exceeding 25 years.
PAGE 19
TASMAN ACCESS FLOORS PTY LTD
– A Fletcher Building Company