You are on page 1of 1

NOTES:

1. All elevations are calculated/offset from EL. = 0, EL. = 0 at bottom of Tank/ Vessel
2. The height "H" and Upper Process Pressure don’t effect to Calib. Range, due to it effects to both sides of LT so that they kill themself.
3. If d(LT-H) and d(LT-L) are equal then elevation of transmitter EL(LT) is for reference only and not affected to
calculation results of calibration range (Ex.: in case the capillary tubes were used for transmitter).
4. If transmitter installs directly to Lower Nozzle then EL(LN) = EL(LT).
5. If upper process (vapour) is air then assumed d(U) = 0.
6. If Low Pressure Side of LT don’t connect to Higher Nozzle and keep at Atmospheric then assumed d(LT-L )= 0.
SG to Density Conversation (at same T, P Condition)
Tag No. TBA (Density for Silicone, Normally used: 960Kg/m3)
INPUT DATA Symb. Unit Description
dU 0.806 <> 806 Kg/m3
0 Kg/m3 Operating Density of upper process fluid (vapour).
820 dL Kg/m3 Operating Density of lower process fluid (liquid). SG Density

960 dLT-H Kg/m3 Operating Density in the HP leg of the transmitter (process fluid).
0 dLT-L Kg/m3 Operating Density in the LP leg of the transmitter (process fluid).
20000 ELUN mm Centre elevation of upper nozzle.
19200 EL100% mm Elevation of maximum level measurement (liquid level).
400 EL0% mm Elevation of minimum level measurement (liquid level).
300 ELLN mm Centre elevation of lower nozzle.
300 ELLT mm Centre elevation of Level Transmitter.
Apply
when use 1000 ELSP mm ELEVATION OF SETPOINT (liquid level).
setpoint

CALCULATION

--> Calibration Range of DP LT: 82.00 to 15498.00 mmH2O SPAN: 15416.00


OR 8.04 to 1519.83 mbarg OR 1511.79

Setpoint: mmH2O mbarg Percent (%)


588.00 57.66 3.28