RS-WS-*-2D-LCD
Industrial wall-mounted
LCD
Temperature and
Humidity Transmitter
User Manual
(Analog type)
contents
1. product description ............................................................................................................................................. 4
1.1 product description ...................................................................................................................................4
1.2 Features .....................................................................................................................................................4
1.3 Main Specifications ..................................................................................................................................4
1.4Equipment size .......................................................................................................................................... 5
1.5 product model ...........................................................................................................................................5
2. Equipment installation instructions ....................................................................................................................6
2.1 Inspection before equipment installation ................................................................................................. 6
2.2Installation method .................................................................................................................................... 6
2.3 wiring ........................................................................................................................................................8
2.3.1: Power wiring ................................................................................................................................ 8
2.3.2: Output interface wiring ................................................................................................................ 8
2.4Specific wiring .......................................................................................................................................... 9
2.5 Wiring example ........................................................................................................................................ 9
2.6Panel display description .........................................................................................................................10
3. Calculation method ...........................................................................................................................................10
3.1Current output signal conversion calculation ......................................................................................... 10
3.2Voltage output signal conversion calculation ......................................................................................... 10
4.Key operation instructions ................................................................................................................................ 10
5. Common problems and solutions .....................................................................................................................12
6. Contact information ..........................................................................................................................................13
1. product description
1.1 product description
The transmitter is an industrial wall-mounted high-protection grade enclosure, with a protection grade of IP65,
rain and snow proof and good air permeability. The circuit adopts American imported industrial-grade
microprocessor chips and imported high-precision temperature and humidity sensors to ensure excellent product
reliability, high precision and interchangeability. It adopts standard industrial interface 4~20mA/0~10V/0~5V
analog signal output, which can be connected to field digital display meter, PLC, frequency converter, industrial
control host and other equipment. It is safe and reliable, beautiful in appearance, and easy to install.
1.2 Features
1. Using high-precision temperature and humidity measurement unit, long-term stability and small drift
2. Adopt dedicated analog quantity circuit, wide application range
3.10~30V wide voltage range power supply
4. Easy to install, can be wall-mounted or rail-mounted
5. High anti-dust protection level (IP65)
6. LCD liquid crystal display, beautiful and generous
7. Buttons can set parameters, easy to operate
1.3 Main Specifications
DC power supply (default) DC 10~30V
Maximum power Current output 1.2W
consumption Voltage output 1.2W
1.4Equipment size
2.3 wiring
2.3.1: Power wiring
Wide voltage 10~30V DC power input. For 0-10V output devices, only 24V power supply can be used.
2.3.2: Output interface wiring
The standard equipment is equipped with 2 independent analog output.
2.4Specific wiring
TH Temperature V+
Output RH Humidity V+
(The device does not provide a communication line by default, the color of the line is for reference only)
3. Calculation method
3.1Current output signal conversion calculation
For example, the range is -40~+80 degrees Celsius, 4~20mA output, when the output signal is 12mA,
calculate the current temperature value. The span of this temperature range is 120 degrees, expressed by a 16mA
current signal, 120 degrees/16mA=7.5 degrees/mA, that is, the current 1mA represents a temperature change of 7.5
degrees. The measured value is 12mA-4mA=8mA.8mA*7.5 degrees/mA= 60 degrees. 60+(-40)=20 degrees, the
current temperature is 20 degrees.
3.2Voltage output signal conversion calculation
For example, the range is -40~+80 degrees Celsius, 0-10V output, when the output signal is 5V, calculate the
current temperature value. The span of this temperature range is 120 degrees, expressed by a 10V voltage signal,
120 degrees/10V=12 degrees/V, that is, a voltage of 1V represents a temperature change of 12 degrees. The
measured value is 5V-0V=5V.5V*12 degrees/V= 60 degrees. 60+(-40)=20 degrees, the current temperature is 20
degrees.
4.Key operation instructions
1 ) short press key , Enter the password input interface interface , short press 、 、
Password input (default password is 888), long press again after input keyEnter the main interface
of settings, the password error prompts ERR.
2 ) After entering the setting main menu , short press or Page forward and backward , short
3)short press 、 、 Parameters can be modified, after the parameter modification is completed
4)During the setting process, press Can abandon this setting,Press again Back to the main interface。
The specific parameter interface is as follows:
6. Contact information
Shandong Renke Control Technology Co., Ltd.
Address: 2nd Floor, East Block, Building 8, Shuntai Plaza, High-tech Zone, Jinan City, Shandong Province
Zip code: 250101
Phone: 400-085-5807
Fax: (86)0531-67805165
Website: www.renkeer.com
Cloud platform address: www.0531yun.cn