(Revision history)
Issued on: Jan. 01, 2007
Amended on: Jan.01, 2013
Amended on: Dec.01, 2013
3 DEFINITIONS ....................................................................................................................................... 5
5 REQUIREMENTS ................................................................................................................................. 7
6 TESTS ................................................................................................................................................... 15
8 MARKING ........................................................................................................................................... 17
12 WARRANTY ........................................................................................................................................ 20
1.1 Scope
This specification covers the 11/0.4kV oil-immersed ground mounted three (3) phase
conservator type distribution transformers for the distribution station of underground
GECOL distribution network.
2 Normative references
The distribution transformers shall confirm to the latest edition of following
international standards:
(a) IEC 60076: Power transformers
(b) IEC 60137: Insulated bushings for alternating voltages above 1,000 V
(c) IEC 60228: Conductors of insulated cables
(d) IEC 60296: Specification for unused mineral insulating oil for transformers and
switchgear
(e) IEC 60354: Loading guide for oil-immersed power transformers
3 Definitions
4.1 Kinds
Rated power of transformer shall be determined according to the Table 1 of this
specification.
Table 1 – Kinds of transformers
Specification No. Rated Power (kVA)
2221028 300
2221030 500
2221031 630
2221032 750
2221034 1000
2221036 1500
2221038 2000
4.2 Rating
(a) The normal rated power specified in Table 1 shall be the continuous rating under the
worst temperature conditions encountered in Libya.
(b) The nominal primary voltage shall be 11kV, 50Hz and the highest voltage for
equipment shall be 12kV.
(c) The nominal secondary voltage shall be 400/230V, 50Hz. The neutral point shall be
earthed.
(d) The primary winding connection shall be ∆ connection (3-phase 3-wire) and the
secondary winding connection shall be Y (3-phase 4-wire) connection. Vector group
shall be Dyn11.
(e) The normal voltage ratio of the transformers at principal tapping shall be 11000/400
Volts.
5 Requirements
5.1.1 Type
The transformers shall be conservator type.
5.1.3 Cooling
Cooling system of the transformers shall be natural circulation of oil and air (ONAN).
5.1.4 Core
The core shall be constructed of the best quality low loss, cold-rolled grain oriented steel
laminations confirming with the latest edition of IEC 60404. Laminations shall be
insulated with mineral oxide or better; the method of cutting and stacking will be "step lap",
so as to optimize the level of no-load losses. The core shall be assembled in a manner
which reduces vibration and minimize inherent noise. Both sides of individual stampings
shall be coated with the insulating material which shall be resistant against oil and
temperature. The complete core shall be effectively earthed.
The flux density in any part of the core shall not exceed 1.65 Tesla at nominal voltage
and frequency. The bidder shall provide saturation curve of the core material, proposed to
be used. Thickness of a lamination shall not exceed 0.3mm (M5). Laminations of
different grade(s) and different thickness(s) are not allowed to be used in any manner or
under any circumstances.
The core plates shall be insulated from one another to minimize the core loss and the
core shall be held together by bolts and clamping plates all of which shall be adequately
insulated. The completed core and winding assembly shall be provided with lifting eyes to
facilitate its removal from the transformer tank and shall be adequately braced and
supported to prevent movement during transit or service.
5.1.5 Windings
The windings shall be made of best soft drawn copper having high conductivity and
complying with the requirements of the latest edition of IEC 60228. The windings shall be
designed to meet the three fundamental requirements: mechanical, thermal and electrical.
The windings shall be capable of sustaining short circuit forces on the transformer as
required in clause 5.2.3 of this specification.
All windings shall be fully insulated according to IEC 60076 for standard insulation
level and for a system highest voltage of 12kV. And windings shall be wound with
adequate bracing and securing tapes in order to achieve a strong, self supporting structure.
Adequate cooling ducts shall be provided to ensure that temperature rise is within the
permissible limits at normal operating conditions.
The HV and LV windings shall be separated without difficulty for replacing each
winding.
5.1.7 LV bushings
LV bushings including neutral bushing shall be outdoor porcelain type conforming to
IEC 60137. They shall be mounted on tank side or on the top and sealed by cable box.
Bushing palms shall be made of brass be suitable for the bolting of conductor compression
lugs of termination for indoor use. The minimum phase to phase clearance shall not be less
than those stated in Table 5 of IEC 60076-3.
The porcelain shall not engage directly with the hard metal and gaskets shall be
interposed between them and the surface in contact with the gasket shall be unglazed. They
shall be installed in a manner to prevent ingress of moisture and to facilitate easy removal.
Note: Low voltage mono-block terminal bushings are accepted if the manufacturer
provided evidences of quality and performance for the mono-block bushings better than the
porcelain bushings.
750 kVA 7 2 1
No. of Cables No. of Cables Cross Sectional
Rated Power No. of Glands
by Phase for Neutral Area of a Cable
1000 kVA 14 4 2
Single Core
1500 kVA 14 4 2
XLPE 400mm2
2000 kVA 21 6 3
The cable boxes on the transformer shall be suitable for the above arrangement and shall
be complete with all necessary fittings, suitable cable lugs, glands, armour clamp, etc. The
cable boxes shall be suitable for approved type of heat shrinkable and pre-molded
terminations.
5.1.9 Glands
The glands shall be electrically separated from cable box, and the dielectric
characteristics of the insulation between gland and cable box shall meet the requirements
listed below.
(a) Power frequency withstand voltage: 2 kV at least
(b) Impulse withstand voltage: 6 kV at least
5.1.11 Fittings
The transformer shall be completely assembled with all its fittings and supplied with
first fill of oil. All bolts, nuts and all metal portions exposed to atmosphere continuously
shall be treated suitably to withstand the weather conditions in Libya.
Followings shall be considered as the minimum requirements.
(a) Off load tap changer
(b) Conservator vessel with oil filling hole and cap
(c) Breather with silica gel
(d) Oil level gauge
5.1.13 Tank
The transformer shall not leak of oil. Tank shall be fabricated of excellent quality mild
steel. The tank shall be designed so that the completed transformer can be lifted and
transported without deformation or oil leakage. The tank shall withstand pressures
developed during normal and abnormal operation of the transformer without permanent
deformation. The tank shall be electrically welded and tested for leaks.
The cooling radiators shall be of pressed steel, electrically welded, and independently
pressure tested. Radiators shall be welded to the main tank.
The top cover of tank and radiator shall be designed in such a way that water does not
accumulate. The transformer undercarriage shall be provided with bi-directional rollers to
allow longitudinal and transverse movement on flat surfaces.
5.1.15 Gaskets
All the gaskets used for sealing the tanks and connected external parts shall be made of
NBR (Nitrile (Acrylonitrile) Butadiene Rubber) or better that totally prevents the leakage
The guaranteed short circuit impedance shall be stated by the supplier. The tolerance
shall be ±10.0% of the declared value at principal tapping and ±15.0% of the declared
value at other tappings.
5.2.4 Insulation
The insulation of the bushings, terminations and windings shall be suitable as to meet
the requirements of the appropriate insulation class as specified in IEC 60076-1. The
insulation of HV side shall be designed to withstand 28kV rms for power frequency test
voltage and 75kV peak for impulse test voltage. And LV side shall be designed to
withstand 3kV rms for power frequency test voltage.
5.2.8 Efficiency
The minimum efficiency shall be equal or exceed the values in Table 7 of this
specification. All values shall be measured at 1.0 power factor, 100% load and adjusted to
75°C.
Table 7 – Minimum efficiency
Rated Power Minimum Efficiency
300 kVA 98.2%
500 kVA 98.4%
630 kVA 98.5%
750 kVA 98.5%
1000 kVA 98.6%
1500 kVA 98.8%
2000 kVA 98.9%
5.2.9 Bushing
The electrical characteristics of bushings shall meet the requirements of IEC 60137 and
IEC 60507.
6 Tests
Routine tests shall be repeated in the presence of GECOL representatives on 10% of the
quantity offered for inspection, chosen at random, subject to a minimum of 2 Nos. of each
type of transformer.
GECOL inspectors can test distribution transformers by using their own testing
instruments at manufacturer’s premises. During the witnessing of testing of transformer at
the supplier’s works Torrent power will also connect company’s meters and supplier has to
agree for the same.
GECOL may carry out routine tests in its laboratory on random basis on 20% of each
batch delivered to GECOL stores. If one transformer fails, GECOL can decide to reject the
batch, if pass GECOL can decide to test any number of transformers of the same batch and
the supplier shall replace any failed transformer.
GECOL may, at its option, open a transformer supplied to the stores, in supplier
presence at site or at departmental stores. If any of the technical particulars are seen to be
at variance than the guaranteed technical particulars, the whole lot of transformers will be
rejected and risk purchase resorted to.
In addition to the above, GECOL may pickup any transformer and decides to get it type
tested from competent and authorized body at GECOL’s cost. The supplier will be invited
to witness packing of the transformer at GECOL’s stores, and the type tests. If the
transformer fails to meet the requirement at type tests, the quantity of the transformer
ordered on them will be forthwith rejected.
7 Rating plates
The transformer shall be provided with a rating plate of weatherproof material, fitted in
a visible position and clearly readable at safety distance when cables are connected,
showing the appropriate items indicated below but not limited. The characters shall be
English roman letters and Arabic numeral characters.
Symbols and text shall be indelibly molded, stamped or engraved in a plate material and
they shall be at least 4.0mm high. If not contrasting in colour, they shall be grooved at least
0.5mm high.
(a) Kind of transformer
(b) Applicable international standard
8 Marking
Following markings shall be easily visible when the transformer is in service and the
entries shall be indelibly marked. The characters shall be English capital roman letters and
Arabic numeral characters.
(a) Rated power: Rated power and its unit shall be of salient character on middle
position of tank wall on HV side. Size of character shall be enough large to read it
from safety distance when the transformer is connected with cables. The salient part
shall be painted with red color indelible paint.
(b) Terminal symbol: HV terminal symbol shall be 1U, 1V and 1W from left side. LV
terminal symbol shall be 2N, 2U, 2V and 2W from right side and indelibly marked in
front of terminal bushings.
(c) Earthing terminal marking shall be marked adjacent to earthing terminal.
The outer packing must be clearly marked on at least four (4) sides as follows;
(a) Name of the procuring department
(b) Name of the supplier
(c) Contract description and number
(d) Final destination
(e) Gross weight
(f) Any special lifting instructions
(g) Any special handling instructions
(h) Any relevant pollution or environment classifications
10 Spare parts
Following spare parts shall be supplied with the transformers
11.3 Documentation
All documents supplied under this specification shall be documented to the extent that
the end user can easily understand its theory of operation, performance, installation and
maintenance for the product. All documents shall be submitted being filed in order to
approve of GECOL and reorder later.
Language in all documents and drawings shall be written in English and dimensions
shall be used in metric SI-units.
12 Warranty
The supplier shall provide a full three-year limited warranty on all equipment supplied.
The warranty shall cover all parts and all costs, which are directly attributable to the
supplier. Warranty coverage shall begin
on the date that the equipment is
received. Dia 44.5±0.2
Dia 32.5±0.2
Dia 30.9±0.2
48-0.2
0
10± 1
Dia 48.5±0.2
1 Manufacturer’s name
2 Applicable international standards
3 Conservator or sealed type
4 Rated power (kVA)
5 Rated voltage (kV)
6 System highest voltage (kV)
7 Rated voltage ratio at principal tapping (kV/V)
8 Method of cooling
9 Vector Group
10 Off circuit tapping range
11 Core
a) Maximum flux density at nominal voltage and frequency (Tesla)
b) Thickness of lamination (mm)
c) Iron loss per kg. weight of core (W)
12 Winding
a) Material of HV winding
b) Material of LV winding
13 Resistance of windings per phase at 75°C
a) HV winding (Ω)
b) LV winding (Ω)
14 Cross sectional area of winding
a) HV winding (mm2)
b) LV winding (mm2)
15 Cable box
a) Number of gland(s) and adaptable cable size at HV terminal
b) Number of gland(s) and adaptable cable size at LV terminal
16 Short circuit impedance
a) At principal tapping & rated frequency (%)
b) At highest tapping & rated frequency (%)
c) At lowest tapping & rated frequency (%)
Signature :
Signature :
27 Tank finish
a) Type of paint applied internally
b) Type of paint applied externally
c) Color of tank
d) Thickness of coating (µm)
28 Gasket
a) Material
b) Thickness (mm)
29 Insulation oil
a) Total oil required (Liters)
b) Mass of oil (kg)
c) Oil grade and standard specification adopted
30 Mass
a) Core and winding (kg)
b) Complete transformer excluding oil (kg)
c) Transformer arranged for shipment (kg)
31 Overall dimensions (Height (mm) × Length (mm) × Width (mm))
32 List of attached fittings
33 List and numbers of spare parts
Signature :
Designation :
Name of Tenderer :
Date :