THREE MONTHS BILL AVERAGE 12000 unit

DAILY UNIT 100 unit


SOLAR CAPACITY REQUIRED 25 KWp
CAPACITY OF INVERTER REQUIRED 25 KW

Total no of modules required 54 55.55556


Max no of modules in a series 18 17.31161
No of strings 3 3
DC capacity at opt temp 23.99624 KW
DC loading on Inverter 95.98497 %

Site temp condition


Cell temp min -5 deg cen
Cell temp max 60 deg cen
Present opt temp 30 deg cen
Vmp @ STC 698.7 V 739.8
Voc @ STC 834.7 V 883.8
Imp@STC 10.96 A
Ioc@STC 11.6 A
Vmp@-5 deg cen 799.7238 V
Vmp@60deg cen 669.8889 V
Voc@-5deg cen 955.3878 V

Vmp at opt temp 729.8127


PV MODULE MAKE : CANADIAN SOLAR
MODULE CAPACITY 450 Wp
Opt operating current Imp 10.96 A
Opt operating voltage Vmp 41.1 V
Open circuit voltage Voc 49.1 V
Short circuit current Isc 11.6 A

Temp coefficient Voc -0.27 %/Deg Cen


Temp coefficient Isc 0.05 %/Deg Cen

INVERTER MAKE FRANIUS


CAPACITY 25 KW
MPPT VOLTAGE RANGE 580-850 V
FEED IN START VOLTAGE 650 V
SYSTEM VOLTAGE 1000 V
No of MPPT 3 nos
No of string 3 nos

Vmp at -5 deg cen


Operating temp -5 deg cen
Temp dev from STP 30 -30
Change in voltage /module 3.3291 V -0.11097
Actual voltage/module 44.4291 V
Total string voltage at operating time 799.7238 V

Vmp at 60 deg cen


Operating temp 60 deg cen
Temp dev from STP 35 35
Change in voltage /module -3.88395 -3.88395
Actual voltage/module 37.21605
Total string voltage at operating time 669.8889

Voc at -5 deg cen


Operating temp -5 deg cen
Temp dev from STP 30 -30
Change in voltage /module 3.9771 V -3.9771
Actual voltage/module 53.0771 V
Total string voltage at operating time 955.3878 V
Vmp at opt deg cen
Operating temp 30 deg cen
Temp dev from STP 5 5
Change in voltage /module -0.55485 -0.55485
Actual voltage/module 40.54515
Total string voltage at operating time 729.8127