Professional Documents
Culture Documents
Three Transforemer Connection
Three Transforemer Connection
The connection of the primary and secondary winding of a three-phase transformer can
be designed in different ways according to the desired application and available
terminals.
Mostly, transformer winding is placed on one core that provides an economic connection
between the iron core and copper windings.
Table of content
1. Delta-Delta (Δ-Δ)
2. Star-Star (Y-Y)
3. Delta-Star (Δ-Δ)
4. Star-Delta (Y-Δ)
There are two three-phase windings in a three-phase transformer; primary winding and
secondary winding.
The connection of primary winding and secondary winding can be a star or delta
connection. According to the application of a transformer, the primary winding and
secondary winding can be connected in four possible configurations as follows:
• Delta-Delta (Δ-Δ)
• Star-Star (Y-Y)
• Delta-Star (Δ-Δ)
• Star-Delta (Y-Δ)
This connection is generally used even if the load is unbalanced and for large, low-
voltage transformers. The number of required phases/turns is relatively greater than that
for star-star connection.
The ratio of line voltages on the primary and secondary sides is equal to the
transformation ratio of the transformers.
Besides that, this connection is that even if one transformer is disabled, the system can
continue to operate in an open delta connection but with reduced available capacity.
The main advantage of this system is that if one phase fails to operate, the transformer
will run on the other two phases. This system is known as an open delta connection or V-
V connection.
This connection can be used for both balanced and unbalanced loading conditions.
The third harmonic is present in this system, but it circulates in the close path and does
not appear in the output voltage.
The disadvantage of the delta-delta connection is that the neutral point is not available in
the system. Therefore, a delta-delta connection is useful when primary or secondary
winding does not require a neutral terminal.
Star-Star (Y-Y) Connection
In this connection, the primary winding and secondary winding are connected in a star
connection. The connection diagram of the star-star connection is shown in the figure
below.
This connection is generally used only if the connected load is balanced for small, high-
voltage transformers. Because of the star connection, the number of required turns/phase
is reduced (as phase voltage in star connection is 1/√3 times of line voltage only).
Therefore, the amount of insulation required is also reduced.
The ratio of line voltages on the primary side and the secondary side is equal to the
transformation ratio of the transformers.
Line voltages on both the primary side and the secondary side are in phase with each
other.
Delta-Star (Δ-Y) Connection
The primary winding is connected in the delta and the secondary winding is connected in
the star with neutral ground. Therefore, it can be used to provide a 3-phase 4-wire
service.
The ratio of secondary to primary line voltage is √3 times the transformation ratio.
There is a 30° shift between the primary and secondary line voltages.
The secondary winding is delta connected and the primary winding is star star (Y)
connected with grounded neutral.
This star-delta connection is mainly used in step-down transformers at the substation end
of the transmission line.
The ratio of secondary to primary line voltage is 1/√3 times the transformation ratio.
There is a 30° shift between the secondary and primary line voltages.